BIO-SELECT BIO-SELECT PLUS INSTALLATION, USER AND MAINTENANCE MANUAL

Similar documents
INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

LISEO Insert. European Standard Certification UNE EN inserts. LISEO s.r.o. Folknářská 1246/21 Děčín 2 Nové Město

Pellet Boilers. Instructions for Use and Maintenance

LISEO STOVES. European Standard Certification UNE EN stoves. LISEO s.r.o. Folknářská 1246/21 Děčín 2 Nové Město

HEAT RECOVERY AIR HANDLING UNIT

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

WHE 2.24 / WHE 2.24 FF

USERS MANUAL FOR GAS BOILERS

USER MANUAL 9kW LILLY PELLET STOVE

Trumatic E. Trumatic E 2400 (Australia) Operating instructions Page 4 Installation instructions Page 7. To be kept in the vehicle!

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

DH-Direct Fired Poultry Farm Diesel Heater

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

Corn Flame Energy Corn Stove Model 3000

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

Installation & Manual. Model T-25

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

Page 1. Cube Ref:

High Performance Electronic Modulation Automatic Cleaning Easy Installation 4 Power Levels: 9,15,25,42kW. Pellet Boilers. Future of Ecological Heating

So old fashioned... As the combustion chamber is completely room sealed, it does not release any smells and does not dirty.

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

Cooker Hood LA-72-CAN.

OPERATING INSTRUCTIONS with safety features

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

INSTRUCTIONS FOR INSTALLATION AND MANUAL Solid fuel stove for central heating THERMO IN

AZN ATEX INSTALLATION AND MAINTENANCE

TECHNICAL AND OPERATIONAL DOCUMENTATION

1 VICTRIX ZEUS Superior kw I features

Easyfire Standalone biomass pellet boiler

USER S INFORMATION MANUAL

CentroPelet ZV14 TECHNICAL INSTRUCTIONS HEATING TECHNIQUE. for regulation, use and maintenance of pellet stove

2.1 BOILER ROOM BOILER ROOM DIMENSIONS 2.3 CONNECTING UP SYSTEM 2.4 CONNECTING UP FLUE 2.5 ELECTRICAL CONNECTION

WHU WATER HEATING UNITS. GENERAL MANUAL MODEL KEY. June 2007 WHU WATER HEATING UNITS

Section 1 - Safety Information Section 2 - Installation: Wall Mount Hoods Section 3 - Installation: Island Mount Hoods

DTG Eco / V130

INSTRUCTIONS FOR INSTALLATION, SETTING AND USE

Installation Manual. Instrucciones de instalación y manual de usuario 1

USER S INFORMATION MANUAL

BIX B-One 100 kw INSTALLATION GUIDE

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

PELLETS BURNER 15-60kW MOC

Light oil / kerosene burner

1. The structure and its description

Forced draught gas burner

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

CINCINNATI, OH USA

E-COMBI EVO E-SYSTEM EVO

KKKKKKKCOOKER HOOD INSTRUCTION MANUAL

TECHNICAL MANUAL BIOTEC 25 AND BIOTEC 40

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

Installation, operation and care. Pellmax UB. Burner not included Replaces:

COMBY 4000 & 9000 STEAM CLEANER OPERATOR MANUAL

Problem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4.

INSTALLATION AND OPERATING INSTRUCTIONS. Ariterm 60+

Solid fuel hot water boiler TKH KW INSTRUCTIONS MANUAL for usage and maintenance

Operating instructions

Cookshack, Inc. Model FEC100 Fast Eddy Oven. Version /1/10

PELLET BURNER PV 350

STORAGE WATER HEATERS

Importance of a Draught Regulator

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

Installation instructions for the T 9820 Gas Dryer

INSTALLATION AND OPERATION GUIDE FOR HARGROVE GAS LOGS

FIREPLACE SIZES FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VACINITY OF THIS OR ANY OTHER APPLIANCE.

HEAT RECOVERY VENTILATOR

Eco Angus Wood Pellet Boilers

GFT-060/40/H2. Designed and built According AD-2000 regulation Homologation and branded CE According to the European Directive CE

WALL MOUNT RANGE HOOD. This manual is made with 100 % recycled paper. Electronic version of this manual is available at:

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only.

BIOPLEX MCL-BIO INSTALLATION AND SERVICE MANUAL

BIOMASS BOILER ATTACK PELLET 30 AUTOMATIC PLUS

HOT WASHER MODEL NO: KING150

Kyung Dong Oil Boiler. Contents. 1. General Warnings Safety Warnings

Boiler Technical Specifications (2013)

Model RGAC/SGAC Self Contained Cooling/Gas Heat MODELS RGAC & SGAC - R22 USER'S INFORMATION, MAINTENANCE AND SERVICE MANUAL

PER-EKO type KSW & KSW PLUS Instruction Manual

DIGITAL MODULATING BOILERS

USER MANUAL. 60cm, 3 burners, Hob AKC 630

Instruction manual. Remote control electric IR HEATER

Pellet boiler Electronic Modulation Automatic Cleaning Grinder system Easy Installation 4 power levels: 10, 16, 25, 43 kw

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

Light oil - kerosene burner

Owner s Manual. A flame to light up your palate! Table of Contents. Warranty card inside

Operating Manual PELLEMATIC PES CMP06 TO_VA6.39 Pelletronic TOUCH ENGLISH. PE 1491 EN_TO 1.0 Europe s specialist in pellet heating

Operating Instructions

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

INSTRUCTIONS MANUAL FOR USE AND MAINTENANCE

Light oil burners. One stage operation

CENTRIFUGAL FANS user's manual. model VENTS VK.

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

USER S MANUAL NKP. Duct heater for supply air pre-heating with external control

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

CARE & INSTRUCTION MANUAL

PEGASUS F2 N 2S. CAST IRON GAS BOILER for heating with electronic ignition and flame control INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE

Use and maintenance Manual Longitudinal profile welding Model: LRW-130

USER MANUAL. 80 cm 2 burners, glass hob AKC 820C/BLM

Transcription:

STEEL BOILER FOR HEATING BIOMASS SOLID FUEL BIO-SELECT BIO-SELECT PLUS INSTALLATION, USER AND MAINTENANCE MANUAL COD. 57605EN.02

THANK YOU FOR PURCHASING THIS PRODUCT! On behalf of LASIAN Tecnología del Calor (Heat Technology) S. L. thank you for trusting us, and you choose the Bioselect / Bioselect Plus LASIAN boiler. Now you have a biomass boiler exclusively for home. Please read the advice and warnings in this manual, as it will furnish important information regarding the safe installation, use and maintenance carefully. The installation of the boiler Bioselect and Bioselect Plus must be performed by qualified personnel, following the manufacturer's instructions and in accordance with current standards. Improper installation may cause damage, hence the importance of this document is an integral part of the product. The manufacturer is not responsible for the misuse of it. 1

INDEX INTRODUCTION. 4 TECHNICAL SPECIFICATIONS.. 5 DESCRIPTION...... 7 Iron body 7 Burner and fuel feeder.. 7 Boiler regulation and control elements.. 10 SAFETY WARNINGS... 11 LOCATION. 12 ASSEMBLY 13 Boiler/Enclosures.... 13 OPERATING INSTRUCTIONS.... 20 Power regulation 20 Combustion air regulation.... 20 Ignition / Shutdown 21 MAINTENANCE. 21 Regular inspections.. 21 Boiler cleaning.... 22 MODEL REPLACEMENTS AND COMPONENTS.. 23 WARRANTY.....29 DECLARATION OF CONFORMITY.....30 2

INTRODUCTION Automatic biomass boilers from Lasian BIO-SELECT and BIO-SELECT PLUS Series have been designed for the production of hot water for heating through the use of solid fuel as pellets, almond shell and olive pulp and pits. In order to use other solid fuels, please get in touch with our technical department. They are available in three models with outputs of 35, 50 and 65 kw. They meet the requirements of the standard: UNE EN 303/5. Heating boilers. Part 5. Heating boilers for solid fuels, manually and automatically stoked, nominal heat output of up to 500 kw. Maximum operating pressure of the boilers BIO-SELECT Series is 3 bar. They consist of the following components: - Steel boiler body. - Fuel tank and auger feeder. - Burner and fan. - Igniter (only BIO -SELECT PLUS) - Electronic control panel. Their main features are: Automatic operation boiler. Electronic panel for heating systems control. Boiler body made of sheet steel. Adaptable to any fuel tank and with the possibility of placing it on either side of the boiler. Easy operation and minimal maintenance. The internal design of the boiler body ensures a large capacity of exchange between combustion gases and water. High performance with energy efficiency over 85%. Low emissions, minimal environmental impact. Combustion ashes are deposited in the lower part of the boiler where they are collected in a high capacity tray. 3

TECHNICAL SPECIFICATIONS Model series BIO -SELECT and BIO-SELECT PLUS can be used with solid fuels such as pellets, almond shell and olive pulp or pits. The use of different fuels results in different power. The experience of each user, depending on the characteristics of the fuel used, its moisture and hot water requirements, will determine the most appropriate adjustment of the boiler. The following tables show the main characteristics of each model of boiler: BIO-SELECT 35 BIO-SELECT 50 BIO-SELECT 65 kw 35 50 65 Nominal power kcal / h 30,100 43,000 55,900 kw 10 13 16 Minimum useful power kcal / h 8,600 11,180 13,760 Fuel consumption kg / (l.h.v. 4,100 kcal/kg moisture 10%) h 2.9 9.1 3.4 13.1 4.2 17 Efficiency % 87 87 87 Minimum useful power in standby kw 1.5 Fuel consumption in standby kg / h 0.37 Gases temperature C 140 230 140 230 140 230 Weight kg 285 320 370 Water volume in body l 91 106 121 Flue duct diameter mm 150 180 180 l 725 Fuel tank capacity kg 470 Autonomy with pellets, olive pits or similar h 51-160 36-138 27 111 Dimensions: width x height x depth mm 550X1612X1360 700X1640X1450 780X1700X1660 Maximum working pressure bar 4 Proof pressure bar 6 Minimum return water temperature C 55 Maximum working temperature C 90 Chimney draught mbar 0.15 0.25 0.20 0.30 0.20 0.30 Fumes flow: - at useful nominal power kg / s 0.024 0.034 0.045 - at minimum useful power kg / s 0.007 0.009 0.012 Connection - Impulse 1 H 1-½ H 1-½ H - Return 1 H 1-½ H 1-½ H Power ~ 230 V 50 Hz +T Nominal power used, heating mode W 330 330 330 Maximum power used, ignition mode 1330 1330 1930 Insulation of electric box IP 65 Fuels must have these characteristics: Particle size: max. 40 mm Calorific value: min. 3.100 kcal/kg Moisture: max. 25% 4

BOILER DIMENSIONS MODEL A B C D E F G H I J K L M BIOSELECT-35 550 610 1600 730 85 1280 1430 600 200 620 1"H 1"H Ø150 BIOSELECT-50 700 700 1800 820 225 1400 1550 600 200 720 1-1/2"H 1-1/2"H Ø180 BIOSELECT-65 780 780 1860 900 225 1465 1610 600 200 810 1-1/2"H 1-1/2"H Ø180 K heating return L heating one-way M chimney 5

DESCRIPTION IRON BODY Boiler body made of steel with vertical fumes passages and automatic cleaning system of these passages. In the ducts used for the passage of combustion gases, there are some retainers that favour the exchange of the heat contained in these gases. The impulse and water return intakes (G 1½ ) are in the back of the boiler. The front of the boiler has a large door for access to the combustion chamber and the ash pan for the purpose of cleaning the shoot and removal of ash. There is also an inspection lid placed on the door for the shoot cleaning of the fumes passages. The body is finished with a heat resistant coating to prevent thermal radiations and with the exterior finish of the enclosure sheets to give it cleanliness, pleasant visual aesthetics and protection against burns. BURNER AND FUEL FEEDER The burner has a longitudinal concave shape which receives the fuel to burn from an auger which is fed, in turn and with a hose, by another auger connected to the fuel hopper. There is a ceramic or stainless steel piece (depending on the models) installed over the burner. The air supply is provided by a fan coupled to the burner and supplied with a control for the inflow. The operation of these components is programmed by the electronic control of the boiler. The burner arrangement prevents material from the accumulation of burned material and the risk of a build-up of the burned material. This material is continuously replaced by new one. Burned material does not adhere to the walls of the combustion chamber but is stored in the tray provided for this purpose. Combustion is therefore safe and more notably, due to the characteristics of the material transport lines, heat transfer to the fuel tank becomes impossible. 6

MANUAL IGNITION BURNER (15010) 2 17 14 1 7 11 8 12 13 16 9 4 3 6 5 12 18 10 15 Mark Units Cod DESCRIPTION 1 1 54749 Manual ignition burner 35/50 kw 1 54750 Manual ignition burner 65 kw 2 1 57817 Burner stainless baffler Bioselect 35/50 1 57818 Burner stainless baffler Bioselect 65 3 1 54767 Burner auger 4 1 57674 6x6x70 flat key 5 1 54755 Motor-reducer set 6 1 57669 Special reducer flange 7 1 56186 Fan 8 1 56187 Fan seal 9 1 56491 Burner joint Bioselect 35/50 1 57771 Burner joint Bioselect 65 10 4 51052 DIN 934 M-8 6 Zn nut 11 4 51020 DIN 933 M-6x15 6.8 Zn screw 12 5 51050 DIN 933 M-8x25 6.8 Zn screw 13 4 50503 DIN 933 M-10x30 8.8 Zn screw 14 8 51027 DIN 125A Ø6 Zn flat washer 15 8 51028 DIN 125A Ø8 Zn flat washer 16 4 51053 DIN 125A Ø10 Zn flat washer 17 4 51025 DIN 934 M-6 6 Zn nut 18 1 50236 DIN 9021 Ø8 Zn flat washer 7

ELECTRONIC IGNITION BURNER (15011) 2 18 14 1 7 11 8 23 20 21 22 16 12 13 17 9 25 15 19 4 3 10 6 5 12 24 10 15 Mark Units Cod DESCRIPTION 1 1 54752 Automatic ignition burner 35/50 kw 1 54753 Automatic ignition burner 65 kw 2 1 57817 Burner stainless baffler Bioselect 35/50 1 57818 Burner stainless baffler Bioselect 65 3 1 54767 Burner auger 4 1 57674 6x6x70 flat key 5 1 54755 Motor-reducer set 6 1 57669 Special reducer flange 7 1 56186 Fan 8 1 56187 Fan seal 9 1 56491 Burner joint Bioselect 35/50 1 57771 Burner joint Bioselect 65 10 6 51052 DIN 934 M-8 6 Zn nut 11 8 51020 DIN 933 M-6x15 6.8 Zn screw 12 5 51050 DIN 933 M-8x25 6.8 Zn screw 13 4 50503 DIN 933 M-10x30 8.8 Zn screw 14 16 51027 DIN 125A Ø6 Zn flat washer 15 10 51028 DIN 125A Ø8 Zn flat washer 16 1 25131 Bluing DIN 975 M-8 8.8 threaded rod 17 4 51053 DIN 125A Ø10 Zn flat washer 8

18 8 51025 DIN 934 M-6 6 Zn nut 19 1 mt. 58132 Ø40 mm interior flexible transparent tube for air 20 1 56798 M8x30 Isophonic clamp Ø40 tube holding 21 1 57119 Heat gun ignition 1 57131 Heat gun ignition cable 22 1 57142 Air adapter 23 1 58131 Igniter air refrigeration intake coil 24 1 50236 DIN 9021 Ø8 Zn flat washer 25 2 58133 32-50 de 8 mm auger washer BOILER REGULATION AND CONTROL ELEMENTS ELECTRONIC REGULATOR It will assume automatic control on the basis of the inserted parameters, permanently taking into account the data from the temperature sensors. It is possible to operate all its elements for maintenance manually and to adjust the parameters of mode as to achieve the best performance in terms of the fuel used. SAFETY THERMOSTAT Pre-installed in the control panel. It is calibrated at 110 ºC in order to prevent any manoeuvre above this temperature. In case of overheating, it will be activated, and the warning light will be illuminate on in the control panel. It is necessary to wait until the temperature returns to normal to proceed with its rearmament. This is done manually by pressing the button protected by a cap-nut. In the event that the safety thermostat goes off repeatedly, it is imperative to disconnect the boiler and fix the existing fault. PRESSURE GAUGE It measures the pressure of the water in the circuit. FAN It is connected to the outside of the burner. The air intake is controlled by a flap installed in the air entrance of the same. ATTENTION To control it appropriately, consult the electronic regulation manual included with the boiler. ANTI-BACKFIRE FLAME THERMOSTAT It is installed in the feeding tube of the burner and its function is to prevent the backfire of the flame in the burner feeder. THERMOSTATIC FLOOD VALVE It is installed at the top of the auger of the fuel tank and it serves to extinguish the fire by water flooding in case of backfire of the flame in the boiler. 9

SAFETY PRECAUTIONS Please pay attention to the following instructions before the installation and start-up of the boiler. Do not operate the boiler without a proper installation of the chimney. The chimney is very important for the optimum performance of the boiler and must provide the minimum draught in the table of features according to the model of boiler. This must be made of stainless material, thermally insulated and authorised. The boiler must always work on depression. ATTENTION If fumes are produced during the operation of the boiler, ventilate the room and check the tightness of both boiler and chimney elements. Once verified, if the problem persists, contact the T.A.S. for a solution. Installation must be carried out in accordance with the existing laws and regulations for this type of boilers and always taking care and observing the some minimum safety requirements for the people and buildings where they are placed. Existing regulations on fire protection in buildings will be especially considered. Regulations on ventilation, lighting level, electrical safety, minimum dimensions of the room, distance between machines must be complied to facilitate the maintenance as well as protection against external moisture and the provision of an efficient drainage system. The boiler should be installed in a well-ventilated room with a sufficient air entrance. No boiler will be installed in rooms or areas where flammable or explosive products can be stored. Do not install the boiler in spaces or areas of continuous use of people, rooms, living rooms, halls, etc. The boiler must be installed to ensure that the hydraulic circuit incorporates the security measures for an increase of temperature and water pressure, by including an open expansion tank at the highest point of the house or a closed expansion tank with safety valve calibrated to a pressure of 3 bar. Ensure that the water circulating pump in the installation is continuously running, unless it is controlled by a thermostat of minimum temperature of the water of the boiler. Any deficiency in the electrical installation must be repaired. Monitor and regularly maintain the water in the boiler and installation. ATTENTION Do not take water out of the installation or empty the water from the boiler except in extreme cases of maintenance or repair. Under no circumstances should the water from the boiler be for domestic use. Do not fill the body of the boiler with cold water during operation or when the body is hot, it would cause cracks due to thermal contrast cold-hot. The quality of the water is very important. The recommended water hardness is: 1-3 mol/m3= 5.6º d), PH: 8-9.5 10

LOCATION The boiler should be installed to allow easy access for the purpose of cleaning, maintenance and inspections, repairs, etc. It is advisable to support it on a base or a levelled, firm and fire resistant plinth. For a proper combustion, the fuel must be dry. It is recommended to appropriately store it, which will need to be at a safe distance from the boiler (at least 1 m) or in a different room. In no event should it be stored behind the boiler. It will have drainage and sewer connected to the network. The room where the boiler is stored should have continuous and sufficient air inlet. The approximate air consumption of each model of boiler is: BIOSELECT 35 BIOSELECT 50 BIOSELECT 65 120 m 3 /h 160 m 3 /h 208 m 3 /h ATTENTION A drain cock should be installed in the heating circuit, placed in the lowest point and as close to the boiler as possible. The provision of free space around the boiler must be as shown in the below diagram: 11

ASSEMBLY The boiler is supplied in two blocks or packages: the boiler and the burner and, in separate box, the auger feeder, fuel hopper components, enclosures and rest of accessories. BOILER 1. Remove the body boiler from the transport pallet and place it in its final location on the plinth described earlier. 2. Assemble the enclosures (See enclosures parts): 1-2 mm. Clearance of 1-2 mm to place the sheets Fit the right (2) and left (3) enclosures on the screws previously placed. Tighten the rear part screw to fasten each side: 12

Over the flat bar support, fit the screws (10), nuts (12) and washers (14) sides reinforcement (1) and fix it to the sides with screws (9): Fix the front door/s (7) to the clips in the riveted sides: 13

Fix the rear enclosure (4) to the side holes: Fix screws (9) in the front part of the sides, also leaving 1-2 mm. without screws. Fix the control panel to the screws of the sides into the rear tore holes in the casing: Leaving the control panel at the top and passing the boiler probes and pressure tap behind the reinforcement (1) we fix in the boiler: 14

Pass towards the rear the rest of the cables and through all the locations prepared with grommets: Fix the casing with two screws M4x7 (8): 15

Close the control panel with the front piece: Pass through the Ø30 grommet locations in the rear enclosure the rest of the wiring (labelled): 1. Backfire probe, ash collection cable. 2. Rest of the wiring. 3. Network cable. 16

1 3 2 Fix the ceiling enclosure (5) inserting the riveted centering tool in the tore locations of the sides: 17

Final state: 3. Install the burner with the studs (13) in the location of the rear part of the boiler: 18

Over the burner the ceramic or stainless steel piece (2) that is found in the box: 4. Connect the flue duct to the chimney. The diameter of the chimney must be at least equal to the boiler flue duct and will have the necessary draught as specified in the technical specifications. The mounted chimney will allow its cleaning and/or replacement of a section without having to move the boiler from its position. The exhaust gases from the boiler cannot under any circumstances support the weight of the chimney pipe. The chimney pipe shall be attached to other elements, never to the boiler. 5. Then proceed to complete the rest of the hydraulic installation: - Connect the return pipes with tap to the boiler outlet. - Placement of the fill cock connecting it to the lower pipe (water return). A flap valve must be placed to prevent communication between boiler water and water from the supply when the network pressure drops and the filling valve opens. - Installation of air-traps and safety valve. - Installation of water expansion vessel. - Conduct the safety valve and the discharge pipe to the drainage. - Installation of any other component, in addition to those above, that it is necessary to comply with the existing regulations for this type of installations. TANK / AUGER ATTENTION To place the tank and auger selected, read the biomass transports manual, supplied with the boiler. 19

OPERATING INSTRUCTIONS ATTENTION To control it appropriately, please consult the electronic regulation manual included with the boiler. REGULATION OF THE POWER OPERATING PARAMETERS VALUES The regulation of the power obtained from the boiler is made with the run time parameters and the stop time of the fuel feed. Changing the values of these parameters will result in different fuel consumption. The power must be selected depending on the demand of the installation, thus, once the temperature reaches the selected level, the burner will automatically shut off until such time that the water in the boiler drops below that level. REGULATION OF THE COMBUSTION AIR The combustion air can be regulated by a fan flap. The required flow will mainly vary depending on the power required, i.e., depending on the amount of fuel that is burning; but the specific characteristics of the fuel used (moisture, density, impurities, ) will also have an influence. As a guide, it can be stated that, with a chimney that provides the right draught, the degree of opening of the flap should be: - For maximum power: between 75% and 90%. - For minimum power: between 10% and 20%. Due to major differences that may exist between different fuels, to obtain an optimum air flow it is necessary to verify the correct combustion in the boiler and the gases temperature in the chimney that cannot exceed the values indicated in this manual. 20

IGNITION AND SHUTDOWN Proceed as indicated in the "CONTROL PANEL DIGITAL CONTROL". Before the ignition of the boiler check that the following elements are working properly and are in good condition: Sealing gaskets of the boiler, including front doors, burner plate and connections of the flue duct/chimney. Electronic control and rest of boiler regulation and control elements. Electricity and fuel facilities. Hydraulic installation. Check the operation of the circulator and check that the taps to the output of the boiler are open. Security systems according to the Existing Regulations. Level of water in the boiler. Check that the pressure is of at least 1.5 bar. Then, proceed to the ignition of the boiler: 1. If necessary, clean the combustion chamber, burner and ash collection tray. 2. Fill the fuel tank. 3. Close the doors and allow the fuel in the burner to start to burn (3 5 min.). 4. Once on, switch to automatic mode and the electronic control will start with the operation cycles according to the scheduled times. ATTENTION In the automatic ignition always keep the boiler doors closed to avoid any gas flue or possible deflagration. MAINTENANCE REGULAR INSPECTIONS These inspections may uncover irregularities that could lead to losses in efficiency and/or possible failures in the equipment. Below are examples of operations to be performed during regular inspections: Cleaning of the boiler heat transfer surfaces. Check the values entered into the control programming. Control of burner settings using a combustion analyzer. Check the good condition of the thermal insulation. Verify the absence of: o Fumes (smells), especially toxic. o Leakage of combustible gases (soot deposits/marks). o Noise (excessive or unusual). o Vibration (excessive or unusual). o Water leaks. 21

CLEANING OF THE BOILER Cleaning and maintenance of the boiler and its installation are essential for a proper, clean, economical and safe operation. The combustion chamber and fuel gases passages must be cleaned to remove ash deposits that can damage and reduce the rate of energy combustion transmission to the water. A loss of performance may occur due to an increase in the temperature of the exhaust gases from the boiler. A temperature increase in the gas duct of 100ºC is indicative that it is producing a 5% reduction in boiler efficiency. The user should follow the below recommendations for maintenance and cleaning of the boiler: 1.) To empty the ash tray without turning off the boiler, we need to put the controller in manual mode and take out the tray with protective gloves (thermal). Ashes will be temporarily gathered in a non-combustible container until they are completely off. This container will need to be far away from any combustible material. 2.) It is recommended to empty the tray at least once a week, regardless of the fuel used. 3.) The air intake both from the fan and the auger motors will need to be kept clean. To clean them it is necessary to electrically turn off the boiler. Only employ a DRY brush. It is not recommended the use of any chemicals. 4.) To clean the fumes passage, turn 360º the control located in the upper side of the boiler. You will hear a bang. Repeat this operation several times. It is recommended to do the fumes cleaning at least twice a week. 5.) Once finished any cleaning it is necessary to review all elements of the boiler (hoses, lids and doors seals, connections, connections, etc ) before starting the boiler again. 6.) There is no need to grease the augers, only to clean the motors air inlet. 22

MODEL REPLACEMENTS AND COMPONENTS BODY OF THE BOILER. Cods. 57610 Insulation support 23

Mark Code Designation Qty. BSELCT-35 BSELCT-50 BSELCT-65 57610 Body of the boiler BIOSELECT-35 (Q.F.) 1 - - 1 57705 Body of the boiler BIOSELECT-50 (Q.F.) - 1-57710 Body of the boiler BIOSELECT-65 (Q.F.) - - 1 2 51412 1/2" 4 bulbs sheaths 1 3 50271 Flat spring bulbs sheath 1 4 51095 Bulbs fixing clip 1 5 51730 1/4" Pressure tap connection 1 6 52540 1-1/4" MD/MK peephole 1 7A - - - - Glass fiber insulation 7B - - - 24

MODEL REPLACEMENTS AND COMPONENTS BOILER ENCLOSURES 25

Mark Code Qty. Designation BSELCT-35 BSELCT-50 BSELCT-65 BSELCT-35 BSELCT-50 BSELCT-65 1 57650.1 57765.1 57715.1 Right side enclosure 1 2 57651.1 57766.1 57716.1 Left side enclosure 1 3 57652 57767 57717 Rear sheet enclosure 1 4 57653 57768 57618 Upper ceiling enclosure 1 5 57700 - - Lower enclosure front door 1-6 57701 57702 57703 Upper enclosure front door 1 7 50430 M4x7 screw 18 14 14 8 50431 M5x9 screw 6 8 8 9 51081 M-5 nut 6 4 4 10 50470 ST d3,2x6 rivet 12 8 8 11 50471 ST d3,2x16 rivet 2 12 52641 Riveted centering clip 6 4 4 13 51140 Riveted centering clip 6 4 4 14 50514 Centering cone 2 15 52840 Grummets 3 26

MODEL REPLACEMENTS AND COMPONENTS FUMES AUTOMATIC CLEANING CODE Mark Designation Qty. 1 57761 Arm support reaction 1 2 54755 0,12 Kw Motor-reducer set 1 3 57758 Reaction arm 1 4 57759 Motor-reducer axis adaptor 1 5 54758 Key 1 6 57775 Automatic cleaning system protection 1 7 57677 M-8x12 stud 2 8 51050 M-8x25 screw 1 9 51049 M-10 nut 2 10 50236 D8 flat washer 6 11 51053 D10 flat washer 2 27

MODEL REPLACEMENTS AND COMPONENTS ACCESSORIES CODE Mark Designation Qty. - 54773 Manoeuvre handle (cleaning) 1-56294 Cleaning brush 1-54733 1/8 x100 sheath(fumes probe Mods. PLUS) 1 28

HOT WATER BOILER FOR HEATING MANUFACTURER WARRANTY COD. 51630.4 Manufacturer: LASIAN Tecnología del Calor, S.L. This complementary sheet is completed by the installer and user Nº 51612.6 IMPORTANT Read the content of this warranty sheet carefully. Should you have any doubt of interpretation consult your installer, seller or T.A.S. in your area. Fill in all required information on the warranty card and always retain this sheet, as it will be necessary to show it to our T.A.S. so any repair or inspection can be performed under warranty. The completion of the data in the manufacturing warranty card, assumes that the user acknowledges and accepts the terms and conditions of this Warranty Certificate. VALIDITY 1- The warranty comes into force from the date of start-up. This start-up is included in the price of the boiler but not the displacement caused for such start-up. The warranty duration is three years for the boiler body. The first two years include the material and labour and displacement costs and the third year only covers the material. 2- For the other components, it is established a two-year warranty on parts, labour and displacement, as long as a review or maintenance has been made by a T.A.S. or an entity authorized by LASIAN Tecnología del Calor, S.L This period of warranty coverage is valid for domestic use of the product. For any other use, the components will have a one-year warranty coverage, including labour and displacement. 3- To validate the warranty it is essential that a copy of the accompanying warranty card is sent to LASIAN Tecnología del Calor, S.L., and is received by our After Sales Department within 30 days from the installation of the equipment. Just a proof of purchase will not be accepted as a document to validate the warranty. COVERAGE 1- The manufacturer warrants their product exclusively against anomalies caused by manufacturing defects, consisting of repair or replacement, "in situ" or in the service facility, of the defective parts. 2- The warranty does NOT cover:. Parts that require change due to wear and tear, even if it occurs before the end of the warranty s validity term.. FAULTS CAUSED AS A RESULT OF IMPROPER INSTALLATION, NEGLIGENCE IN THE USE OF THE BOILER, LACK OF MAINTENANCE AND CLEANING, HANDLING BY UNQUALIFIED STAFF, IMPROPER OPERATION CONDITIONS, OR DAMAGE CAUSED IN TRANSPORTATION, HANDLING AND STORAGE OF THE BOILERS IN HOUSING OR PROPERTY DURING ITS INSTALLATION.. Breakdown of electrical components or product performance failures that may have occurred by external agents: storms, lightning, power surges or failure in the power supply, lack of earth connection, eddy currents, electromagnetic waves, etc.. Interventions that may be required due to poor water or fuel quality: - Water with high limescale index or chloride concentration greater than 300 mg/l. - Warranty does not cover damage to body boilers that may arise from operation of the burner with an airlock or low-pressure circuit, by filling a circuit while warm, freezing of the water contained in the boiler, calcareous obstructions or dirt, etc. Only will be covered perforations in the form of pores caused by possible defects in the conformation of the material. - Insufficient air inlet grilles for the combustion. - THERMAL GROUPS OR LIQUID FUEL BOILERS - Contaminated heating oil or water concentration greater than 250 mg/kg. - BIOMASS BOILERS OR SOLID FUELS - Fuels with a moisture content above 20%.. - Splinter size bigger than what specified in the G50 type. - Ensure unrestricted water recirculation for boiler as specified in the corresponding manual. - Ensure unrestricted chimney draft or section as specified in the corresponding manual.. THE WARRANTY DOES NOT COVER ANY FAULT THAT MAY ARISE DUE TO IMPROPER INSTALLATION OF THE SAME.. The warranty does not cover the review or maintenance service made one year after the start-up of the boiler. WARRANTY CONDITIONS 1- Warranty will be voided if the start-up of the appliance is not done by the Technical Assistance Service or by a person professionally accredited and authorized by the manufacturer. 2- If during the start-up of the boiler the T.A.S. detects any anomaly or defect in the installation, deficiency in the location (space, room ventilation, gas exhaust, etc..), the T.A.S. will not be forced to perform the start-up until the defect has been corrected and, if deemed appropriate, charge displacement expenses. 3- After the start-up, the T.A.S. (or authorized person or entity if applicable) will sign and stamp the warranty validating it. This "user" warranty sheet will be held by the same and will always be available when intervention in the boiler is required under the warranty concept. 4- Under no circumstances should the complete set of the boiler or burner be changed without the manufacturer authorization. 5- The manufacturer reserves the right to make product changes without notice, always maintaining the technical and essential service characteristics to fulfil the purpose for which the boiler is intended. 6- The manufacturer assumes no responsibility for damages caused to persons or property arising from accidents that are not exclusively from the boiler itself as an individual unit and for manufacturing defects. 7- In case of dispute, the customer waives their own jurisdiction and agrees to submit to the courts of Zaragoza or the designated by the manufacturer. USEFUL TIPS Do not handle the inside of the boiler. If you are unsure of its correct performance, please read carefully the instruction manual included with each appliance or consult your local Technical Service. To maintain optimal operation of the boiler or heating unit LASIAN, we recommend an annual review of the same by a member of our T.A.S. or an entity authorized by LASIAN Tecnología del Calor S.L., which for convenience we recommend you to perform it at the end of the heating season. LASIAN Tecnología del Calor S.L. 29

DECLARATION OF CONFORMITY In compliance with the requirements of the COUNCIL OF THE EUROPEAN UNION The Company LASIAN Tecnología del Calor, S.L. with C.I.F. B50141894, and registered address at: Políg. Ind. Las Norias, parcela nº 7-50450 MUEL (Zaragoza) - SPAIN Manufacturer of boilers for heating and S.H.W., brand: LASIAN In its different models: BIOSELECT / BIOSELECT PLUS 35 BIOSELECT / BIOSELECT PLUS 50 BIOSELECT / BIOSELECT PLUS 65 WE HEREBY DECLARE, under our sole responsibility, that the above mentioned products are manufactured in accordance with the following directives: Machinery Directive (98/37/CE) Low Voltage Directive (2006/95/CE) Electromagnetic Compatibility Directive (89/336/CEE) Regulations on Thermal Installations in Buildings (RITE), Adopted by Royal Decree 1027/2007. Complying in all cases with all the specifications of these, applying in all the models the provisions of the heating boilers standard: UNE EN 303-5 Heating boilers. Part 5. Heating boilers for solid fuels, manually and automatically stoked, nominal heat output of up to 500 kw. Muel, 8 th November 2013 The characteristics and manufacture date on each unit are indicated in the technical documentation that accompanies each boiler. 30

NOTES The manufacturer assumes no responsibility for damages caused to persons or property from accidents that are not exclusively from the boiler itself as an individual unit NOTE: The manufacturer reserves the right to make product changes without notice, always maintaining the essential characteristics to fulfil the purpose for which the boiler is intended. Technical Service: 31