FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings - Excluding Sleeping Accommodation)

Similar documents
FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

PREMISES FIRE SAFETY HANDBOOK

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

EMERGENCY EVACUATION PLAN

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

EMERGENCY EVACUATION PLAN

Fire detection and alarm

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Project Briefing Document. Section 3 Electrical Services design guide and specifications

SMOKE DETECTION - CHANGES DURING CONSTRUCTION OR OTHER WORKS TO PREVENT UNWANTED ALARMS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

3.1 Introduction. 3.1 Introduction

Policy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London

CALL FOR A FREE SURVEY

BUILDING FIRE STRATEGY

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL

RELIGIOUS, FESTIVAL & OTHER DECORATIONS - FIRE SAFETY GUIDANCE

A Guide To BS Understanding the selection, spacing and siting of detectors

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

2004 AUSTRALIAN STANDARDS UPDATE

BUILDING FIRE STRATEGY

Consultant Specification AGILE Wireless Fire Detection System

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

University Design Standard Fire Alarm Systems

Design Guidelines Fire Safety in New and Refurbished Buildings

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Control Panel User Guide

The EN54 Part 2 & 4 Fire System

Open-area Smoke Imaging Detector. Engineering Specification

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY

FIRE & LIFE SAFTEY STANDARD

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Fire Alarm Control Panel. System Maintenance and Log Book

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT

(Fire) Emergency Evacuation Plan

Smoke Vent Control Panel PCB4 V4 Installation Manual

Charlotte Building, 17 Gresse Street, London W1T 1QL

Analogue addressable devices

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

Fire Procedures. April 2016

Fire Systems Design Pocket Guide BS 5839 Part 1:2017 and CoP 0001 for Visual Alarm Devices. Fire Installers Mate. A guide to fire system design

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Addressable Loop Powered Visual Alarm Devices

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS

ALL YOU NEED TO KNOW ABOUT THE NEW STANDARDS IN ONE HANDY POCKET GUIDE. Updated for 2016 to include IA1501. Brought to you by: In association with:

four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT

MINERVA MZX125 Digital Addressable Fire Detection System

EVACUATION POLICY 1. General

Fire. This policy applies to all members of our school community, including those within the EYFS setting.

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

ZP3 Operator & Maintenance Manual Version 1

Loss Prevention Standard

Intelligent Security & Fire Ltd

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

Technical reference Reference & design

BUILDING FIRE STRATEGY

Policy for Safe Evacuation of Persons with Disabilities

scorpion SMOKE TESTING FOR ASD SYSTEMS AND HARD-TO-ACCESS POINT DETECTORS IN ACADEMIA APPLICATIONS RESTRICTED AREA AUTHORISED ENTRY ONLY

Intelligent Security & Fire Ltd

SOUTH AFRICAN NATIONAL STANDARD

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

CONVENTIONAL AUDIBLE VISUAL

Evolution Analogue Addressable Fire System

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Health and Safety Services. Safety Guide 5. Fire drills

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

BS 5839: Part THE CHANGES

Allianz Engineering Inspection Services Ltd. Electrical Services. Product Information

Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices. Approved to EN54-3/EN54-23

Intelligent Security & Fire Ltd

Managing Fire Safety To Ensure Legislative Compliance

USER MANUAL & MAINTENANCE GUIDE OG OO

The EN54 Part 2 and 4 Fire System

PERSONAL EMERGENCY EVACUATION PLANS (PEEP s)

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

Transcription:

Fire Safety Technical Guide FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings - Excluding Sleeping Accommodation) UCL Fire Alarm Standards & Specific Employers Requirements (ERs) for Projects - what you need to know: Mandatory Standard - all fire alarm systems in UCL premises shall be designed, installed and maintained to comply with the latest edition of BS 5839-1 & BS5839 series. Protocol - UCL fire alarm systems and devices shall use OPEN APOLLO protocol only, (unless the existing system is not compatible) with standard equipment to ensure communality of systems, efficiency of maintenance and control of software access. No other fire alarm panels or systems will be acceptable unless written permission. The Client - UCL as the Client strives to improve its standards and requires only fire alarm system designers, installers and maintenance companies that can demonstrate BAFE SP203 or LPC1014 with ISO9001 Quality Management System compliance or equivalent to undertake works on UCL fire alarm systems. Unwanted Fire Alarms - designers of fire alarm systems shall take considerable care to ensure that their fire alarm design reduces unwanted fire alarms through thoughtful understanding of room/space function, where the detection is provided, to avoid unwanted activation as far a reasonably practicable. Prohibited - the introduction by design or use of closed or managed fire alarm systems in premises under the control of UCL. Prohibited Acceptable Loop Capacity - as a general rule designers shall to ensure the numbers of devices provided on loops gives approx. 20% spare capacity (e.g. 126 devices - 20% = 105 devices) allowing for future changes or alterations to the system. Design - the raising of the alarm and warning to occupants in case of fire is a legal requirement. The addition of Automatic Fire Detection (AFD) is very often desirable to assist in early detection, property protection and in some instances an offset to extended Means of Escape (MoE) conditions; Life Category L2 or L1 Coverage - additional AFD to Life Category L2 or L1 standard shall be provided for specific areas such as high risk or high value (i.e. equipment or facilities in excess 0.5 million insurance value) or, where part of a fire engineered solution. Contingency Funds - Project Managers / Consultants / Principal Contractors shall ensure that contingency funds from the project are available at precontract, to provide & install addition sounders at commissioning, should the sound pressure coverage fall below acceptable levels any particular area. UCL Fire Safety Manager should be consulted with any design query in the first instance who will consult further, as required. Date Last Amended: Nov 16 1.

Contents 1.0. Fire Alarm Panels... 2 2.0. Smoke Detection - General Requirements... 2 3.0. Manual Call Points... 4 4.0. Sound Pressure Requirements & Visual Alarms Devices... 4 5.0. Disabled Refuges/Alarms & Hearing Impaired People Facilities... 6 6.0. Electrical Supplies & Batteries... 7 7.0. Fire Resistant Cabling... 7 8.0. Marking and Indicating of Fire Alarm Devices... 8 9.0. Ceilings, Ducts & Voids... 8 10.0. Door Hold Open, Fire Dampers & Other Automatically Released Equipment... 9 11.0. Access Control Devices Connected To Fire Alarm Systems... 9 12.0. Provision of Audible & Visual Warning at Internal Building Boundaries... 9 13.0. Mechanical & Electrical, Air Handling & Smoke Control Equipment Interfaces... 9 14.0. Specialist Biological Service Units... 9 15.0. Cause & Effect Matrix Fire Alarm System... 10 16.0. Fire Brigade Communications... 10 17.0. System Commissioning Requirements... 10 18.0. Quick Overview... 12 1.0. Fire Alarm Panels 1.1. UCL fire alarm panels must be capable and compatible of using and switching between all modes of Apollo Discovery detection heads, using alarm confirmation facilities. 1.2. In addition, have peer-to-peer networking and IP gateway facilities. 1.3. UCL Fire Alarm Panel Provision - the following manufactures only, shall be used: Advanced Electronic Ltd (see: www.advancedco.com); Kentec Ltd Taktis (see: www.kentec.co.uk); Morley IAS ZX series (see: www.morley-ias.co.uk); 2.0. Smoke Detection - General Requirements 2.1. All new and refurbished fire alarm systems are to designed and installed to meet BS 5839-1: Life Risk 4 or 3 1 (L4/L3) provision AFD (see below). 1 Note 1: Category L4/3 - the minimum standard of L4 provides AFD to all escape routes; this is to be supplemented by risk assessing all rooms off escape stairs and corridors for the provision of additional AFD to bring the system up to L3 standard. For example: all corridors and rooms off a Date Last Amended: Nov 16 2.

2.2. Detectors - in areas where there is an obvious risk of false alarms including persistent dusty, dirty and release of steam conditions, then the following detector heads should be considered: Rate of Rise heat detectors (kitchens - see guidance in UCL Fire Safety Technical Note TN105); Fixed heat at 55 C, 75 C or 90 C to be used where there is likely to be high ambient temperatures (boiler rooms or steam producing apparatus); 2.2. Multi-Sensing (Apollo Discovery) Heads - to be provided: (c). (d). in all laboratories; at Tea points and adjacent areas (see guidance in TN105); in other suitable locations; multi-sensing heads have five settings (guidance only check the latest specification by Apollo for accuracy before instructing): Mode 1 - multi-sensing using both heat / smoke monitoring & reacting at around 1% obscuration of the optical head & any temperature changes of more than 15 C; Mode 2 - optical sensing setting only (no heat sensing), reacting at around 2% obscuration of the optical head; Mode 3 - multi-sensing using both heat/smoke monitoring & reacting at around 2% obscuration of the optical head & any temperature changes of more than 21 C; Mode 4 - least sensitive setting using both heat & smoke monitoring and reacting at around 4% obscuration of the optical head and any temperature changes of more than 15 C - use this setting in all laboratories (unless specific requirements identified), tea points & peripheral areas outside kitchens or tea points etc. Mode 5 - heat sensing setting only; 2.3. Beam Detectors - where there is a requirement for covering large open spaces then Open Area Smoke Imaging Detection (OSID) by Xtralis Ltd beam detectors shall be considered: These beam detectors use two wavelengths to distinguish between particle size and solid intruding objects, thus helping to reduce unwanted alarms. Moreover, one unit because of its design covers much more area with multipoint viewing from a single beam detector head, thus reducing the staircase and high risk rooms such as laboratories, plant rooms, storage may require detection, but office accommodation (unless in single escape condition will probably not require additional detection). Risk analysis is to be completed as part of the design of the system. Note 2: each new system will need to be approved on a project-by-project basis to ensure that the correct cover of fire detection has been provided. Where AFD is provided in existing refurbished areas then generally, the devices should remain unless effected by wall or ceiling changes, which interfere with the existing device positions. Date Last Amended: Nov 16 3.

need for point detection. www.xtralis.com UCL Fire Technical Note - TN054 Further information can be found at Where access to maintain point detection may be difficult; Where possible temperature inversions influence the effectiveness of point detection. 2.4. Very Early Warning Smoke Detection (VESDA) / Aspirated Detection - where there is a requirement for air sampling detection and a solution to specific problem including access, Hypoxic atmospheres (Oxyreduct) then Xtralis VESDA / Aspire systems should be considered. Further information can be found at www.xtralis.com 2.5 Specialist Detection in Hard to Access Locations specialist detection solution such as Scorpion (www.scorpion-tester.com) should be considered to test smoke detection located for example in Containment Laboratories (CL) Containment Levels 2/3 to reduce maintenance staff exposure and lift shafts etc. 3.0. Manual Call Points 3.1. Anti-Tamper security covers - in student halls, circulation spaces, common rooms, bars of UCL Student s Union occupancy and MCP located in close proximity to magnetic door release units then Anti-Tamper security covers shall be fitted to each call point: I.e. Apollo - transparent hinged Cover (Apollo Ref: 26729-152); 4.0. Sound Pressure Requirements & Visual Alarms Devices 4.1. General Note on Sound Pressure Levels - UCL requires a higher standard of audibility than BS5839-1 for sounder coverage, therefore the average sounder level throughout the building should as far as reasonably practicable meet (or exceed) 75 db(a) in all areas. (Commentary - experience shown during fire alarm activations that higher sounder levels are required to engage over headphones etc. and motivate some students / staff to evacuate the building). 4.2. Sound Pressure Recording - a sound pressure check MUST be carried out with sound levels being recorded on a log sheet or plan. The log is to be submitted with the Commissioning Certificate short fall are to be increased by the addition of extra sounders to the area. 4.3. Voice Sounders (Preferred Option where Possible) - the following voice sounders conforming to BS5839 can be used combination voice and tone sounders shall be used in all areas where the public or large numbers of Date Last Amended: Nov 16 4.

students' use the space, where phased evacuation or the need to differentiate buildings is to be considered. Vimpex Ltd - 'Fire Cryer' (see: www.vimpex.co.uk) standard with the following voice messages: (1). Use Ref: (AK) Fire emergency - please remain calm and evacuate the building immediately (Female Voice); (2). Use Ref: (AC) This is a fire alarm test - No action required - No action required (Female Voice); (3). Use Ref: (AE) Fire alarm test now complete (Female Voice). Apollo Discovery Voice system - may be used but messages to be agreed with UCL Fire Safety Manager; 4.4. Visual Alarm Devices (VAD) - meeting BSEN54-23 shall be provided (visual flashing red lights) in the following locations: (c). Noisy environments - such as workshops / plant rooms / roof plant areas (in addition to audible sounders); Quite Environments - where audible alarms are not acceptable (control rooms / sound or anechoic booths etc.); To find the FA Panel - to identify and locate the main fire alarm panel particularly in property with identical frontage, or where the panel location is not obvious or in the normal location of the main entrance area; 4.5. Specialist Alarms - there may be projects that require more specialist equipment (e.g. external) to be specified, in which case Klaxon units should be considered. Further information can be found at www.klaxonsignals.com. 4.6. Visual Alarms Devices - visual alarms shall be provided where disabled or hearing-impaired persons may use facilities: Disabled Refuges - to allow clearer communications with others; Seminar / Lecture theatres / common rooms / WCs etc. Note - UCL will not accept blanket coverage of a building with supplementary VADs, provision need to be to be specific. Note Design teams and Principal Contractors to ensure that contingency funds from the project are available for additional sounders to be installed at commissioning, should the sound pressure coverage fall below acceptable levels any particular area. Where sound levels fall below this standard, additional sounders MUST be installed to raise the sound levels. Date Last Amended: Nov 16 5.

5.0. Disabled Refuges/Alarms & Hearing Impaired People Facilities 5.1. UCL has a specific policy and procedures for accommodating people with disabilities - please discus with UCL Fire Safety Manager prior to design. 5.2. Disabled Refuge Communications - disabled refuges require a means of communicating so ensure that persons using the disabled refuge can communicate their presence and location in an emergency. Generally, there are two methods of providing this communications: (a) Telephone (preferred option) - provide a standard UCL internal data telephone connection within the disabled refuge, and install a BT Big Button 100 or Doro Phone Easy 311c handsets which are wall mounted hand set. UCL fire Safety provides information in a clip frame adjacent to the handset with UCL internal 24/7 full (for mobile use) & extensions contact numbers and exact location to assist user. Disabled Refuge Communication System - unless specifically agreed with UCL Fire Safety Manager do not use systems complying with BS5839-9, as UCL has found systems to problematical, because: (1). ongoing maintenance costs and reliability; (2). no one at the reception point to communicate with refuge occupants - causing stress to users; (3). Often abused and interfered causing alarms and faults on system. (c). Other Considerations - do not provide sounders close to or within refuge so that occupants can communicate without background alarm - see item 3.5 above. 5.3. Deaf Messaging Service (DMS) - UCL uses a DMS system connected to the fire alarm for hearing impaired persons through Fireco Ltd / www.alarmscom.co.uk - further details please see www.ucl.ac.uk/fire - UCL Fire Safety Technical Note TN007. 5.4. Disabled WC Alarms - disabled toilet alarms should be Timeguard Emergency Assist Alarms with a connection through the Gallagher Security system to signal back 24/7 to the UCL Security Control Room. See further detail from UCL Access Systems Manager: www.timeguard.com/products/safety/emergency-assist-alarms Date Last Amended: Nov 16 6.

6.0. Electrical Supplies & Batteries UCL Fire Technical Note - TN054 6.1. Main Electrical SUPPLY to Fire Alarm Panels - require a dedicated 240v supply using fire resistant cable and terminated into a double pole, isolating spur with key switch as defined in BS 5839-1. 6.2. Main Electrical ISOLATION to Fire Alarm Panels - means should be provided for double pole isolation of the mains supply to all parts of the system. 6.3. UCL requires a Fire Safety Isolator Switch (available from www.firesafe.co.uk) to be provided which is a secure method for safely isolating the mains voltage supply to fire systems in accordance with BS 5839-1. To be suitably sited, near the equipment served without the need for access to remote parts of the building; The 'Fire Safety Isolation' switch can only be isolated by an authorised person, by means of a key lock switch - the key is removable in both ON / OFF positions; The fuse cannot be removed without taking the cover off & when in the off position the FUSE is disconnected from the supply; A neon indicator is provided to indicate mains present at the switched output; Technical Specification: o Working Voltage: 250AV o Switch Contact Rating: Double Pole - 250V AC 4Amp o FUSE Rating: Max - 6A Fast (20mm) supplied o Switch Surge Rating: 80Amp o Key Number: 901 6.4. 24 Volt Equipment - UCL requires all auxiliary equipment interfaced with the fire alarm system such as door hold open magnets, Fire Alarm Do Not Enter (FADE) Signs etc. to be 24v volt. 7.0. Fire Resistant Cabling 7.1. All cables shall be coloured Red, unless there is overriding aesthetic reasons for White to be used. 7.2. Special attention is to be paid to the terminating of cables to ensure that earth faults are eliminated. Date Last Amended: Nov 16 7.

7.3. The following cables should be used in all instances: UCL Fire Technical Note - TN054 FP 200 Gold, equal or approved; MICC cabling is required where routes provide mission critical signals or pass through a high risk or vulnerable areas (as per BS 5839-1); 7.4. Fixing - all fire alarm cabling is to be fixed to the structure, cable trays or cable management system using metal ties. No other fixing is acceptable. 8.0. Marking and Indicating of Fire Alarm Devices 8.1. Labelling - all fire alarm devices are to be permanently marked or by using suitable adhesive labels, to indicate the device Zone and Address number. 8.2. Identification - where remote or hidden detectors / devices are placed in voids, ducts or above ceilings then a suitable LED repeater indicator is to be provided in a logical and adjacent location. All LED indicators are to be clearly marked specifying type of device, address number and remote device location. 9.0. Ceilings, Ducts & Voids 9.1. Ceiling Voids - generally, where a void of 800 mm or greater than 10% of the room height: Variations - considered as 'low risk' (e.g. simple light units only within it, or if fire spread beyond the void / room of origin etc is unlikely) - then it is reasonable not to provide AFD in these spaces. This should be recorded as a variation on the relevant system certificate. Higher Risk - where there is an obvious risk such as significant electrical equipment (other than light units) or air handling units / chillers / void passes over other rooms or compartments, then the void should be provided with appropriate automatic fire detection as any electrical / equipment fire may not be detected at it initial stages. Clarification may be sought for the UCL Fire Safety Manger. 9.2. Detectors in Voids & Ducts - any void where detection is provided MUST be fully accessible and not obstructed for maintenance purposes. This means that ceiling tiles or access panels must be available directly below the detector to allow maintenance and a testing pole to be used, which requires a clear vertical path from below to be maintained. 9.3. Identification of Hidden Devices - see Para 8 above. Date Last Amended: Nov 16 8.

10.0. Door Hold Open, Fire Dampers & Other Automatically Released Equipment 10.1. These items should adhere to the terms of latest edition of BS 5839-3. It should be noted that 'door holders' are generally not acceptable on any fire door that leads directly onto a protected stair (to be discussed with the UCL Fire Safety Manager). 10.2. Door Release Switches - electromagnetic door release switches are to be positioned in a clear and accessible location, to prevent damage to fixings by doors being pulled close against the magnetic holders. 10.3. Auxiliary Equipment - interfaced with UCL fire alarm systems shall be 24 Volt equipment. 11.0. Access Control Devices Connected To Fire Alarm Systems 11.1. Where security Access Control Systems are to be installed in a building, it will be necessary to interface with the fire alarm system to meet UCL, local fire and District surveyor requirements. See UCL Fire Safety Technical Note TN001 & TN005 for specific requirements. 12.0. Provision of Audible & Visual Warning at Internal Building Boundaries Connected to the Fire Alarm System 12.1. Where the Means of Escape (MoE) routes access and egress passes through a building boundary, it is necessary to provide Visual and Audible Warning signs connected to the fire alarm systems and it will be necessary to interface with the fire alarm system to meet UCL, local fire, and District Surveyor Authority requirements. See UCL Fire Safety Technical Note TN058. 13.0. Mechanical & Electrical, Air Handling & Smoke Control Equipment Interfaces 13.1. Where mechanical & electrical systems and smoke control measures are provided and connected to the fire alarm system, please see UCL Fire Safety Technical Notes TN 038 & TN039 for general requirements. 14.0. Specialist Biological Service Units 14.1. Designers working on fire alarm within BSUs are to reference UCL Fire Safety Technical Note TN059#, available form the UCL Fire Safety Manager. Date Last Amended: Nov 16 9.

15.0. Cause & Effect Matrix Fire Alarm System UCL Fire Technical Note - TN054 15.1. Designers are to provide a cause and effect chart for all new systems - see UCL Fire Safety Technical Note TN063. 16.0. Fire Brigade Communications 16.1. UCL fire alarm panels shall alert the fire brigade via the UCL Security Control Room (24/7) using the Gallagher Security System via UCL Data system network wherever possible, by providing: a Fire Signal generated at the fire panel; a Fault signal generated at the fire panel; 16.2. Monitoring Centre - the signals are to terminate at the UCL Security Control Room on the Gower Street Campus, which acts as a 24-hour monitoring service for the UCL estate. The UCL Security Control Room Manager can be contacted on 020 7679 3333 and should be consulted on all signals required to be monitored by the Security Control Room, including security / lift / plant as well as fire alarm signals. Data connections can be arranged through the UCL ISD Network Group. 16.3. Alarm Receiving Company (ARC) - in some locations, a specialist ARC may be required, which should be arranged through our fire alarm maintenance provider and Southern Monitoring Services Ltd. A BT Redcare line and Digital Communications (Digicom) device will also be required. Requirements and procedures will need to be discussed with the UCL Fire Safety Manager at the outset of the project. 17.0. System Commissioning Requirements 17.1. Fire Alarm System Commissioning Engineers in all cases the UCL Fire Alarm Maintenance provider (Fisk Fire Protection Ltd) shall be employed to commission / test all UCL fire alarm system changes whether new, alterations or modification projects. Design, Installation Commissioning and UCL Acceptance Certificates: 17.2. The provision of the appropriate design, installation and commissioning certificates containing information based on the Model Certificates provided in BS 5839-1: Annex H, is to be provided by the appropriate parties. Copies of the certificates are to be issued as following: Date Last Amended: Nov 16 10.

(c). (d). UCL Fire Technical Note - TN054 All original certificate(s) to be placed in the Operational & Maintenance (O&M) Manuals; a copy of each certificate to be issued to the Fire Alarm Maintenance Contract Manager (UCL EM&I); a copy of each certificate to be issued the UCL Fire Safety Manager for building s fire certificate and fire strategy documents; any additional copies required by an authorised person; 17.3. Design Certificate - is to be provided in all cases by the Design Consultant on completion of the design stage of the fire alarm. 17.4. Installation Certificate - is to be provided in all cases by the Contractor installing the fire alarm system, on completion of the installation stage. 17.5. Commissioning Certificate - is to be provided in all cases by Commissioning Engineers (generally UCL Fire Alarm Maintenance provider) on completion of the testing & commissioning stage of the fire alarm. 17.6. Acceptance Certificate (UCL) - this is to be completed and issued the by Project / Design Consultant; and witnessed by a Nominated UCL Person on behalf of the Director of UCL Estates. 17.7. Only on completion of the Acceptance Certificate witnessed by a UCL Nominated Person may: a new system, become the primary Warning in Case of Fire for the building. where the fire alarm system has been replaced / upgraded etc may the old system be switched off and decommissioned. The new system may then become the primary Warning in Case of Fire for the building. 17.8. Addressing of Fire Device Locations - the programming of the device address must be carefully considered to ensure that its location matches the local, generic or room numbers to prevent confusion by staff, contractors or the Fire Brigade in locating the device. 17.9. Drawing and Zone Chart - zone chart information is to be supplied as part of the commissioning of the fire alarm system as follows: Clear fire alarm zone information in A4 Word format, is to be provided in a suitable clip frame position adjacent to the fire alarm panel. This is to provide quick reference to incident location. As Installed Drawings are to be provided on hard copy A1 sheets and in electronic AutoCAD 2007+ Version format scale of 1:50, 1:100 or 1:200 as appropriate. Date Last Amended: Nov 16 11.

18.0. Quick Overview 18.1. General equipment overview required by UCL for new and existing fire alarm systems on upgrading refurbishment etc (where practical): Items / Devices Details Protocols & Remarks Fire Panels Advance / Morley IAS ZX / Kentec Open Protocol / Apollo / Addressable Manual Call Points Apollo Open Protocol / Apollo / Addressable Smoke Detectors Apollo Range - Type to Suite Open Protocol / Apollo / Addressable Heat Detectors Apollo Range - Type to Suite Open Protocol / Apollo / Addressable Multi-Sensing Detectors Apollo Discovery Range Open Protocol / Apollo / Addressable Bells 8 / 10 To Suite Open Protocol / Addressable Sounders Apollo - Type to Suite Open Protocol / Addressable Voice Sounders Vimpex Firecryer Open Protocol / Addressable Beam Detectors Building Interface Cables Special / Bespoke Flame Proof / Explosive Proof (E) Visual Alarm Devices (VAD) Deaf & Hearing Impaired Warning Systems End Disabled WC Alarms Open Area Smoke Imaging Detection (OSID) by xtralis Philip Payne 2784 Range FP 200 Gold (or equivalent) MIC (where required by BS5839-1) Klaxon Ltd (www.klaxonsignals.com) Do not blanket cover for DDA - separate arrangements at UCL Deaf Message Service (DMS) or Hearing Fire Alert System (HFAS) (See UCL Fire Safety Tech Note TN007) Timeguard Emergency Assist Alarms Open Protocol / Addressable (www.xtralis.com) Fire Alarm Activated Do not Enter illuminated signs Red unless aesthetic consideration required One off external fittings etc BS EN 60079-10 - Explosion Proof (E) & External Fittings Red LED indicators fitted to sounder units Alarmscom Ltd www.alarmscom.co.uk Discuss with UCL Fire Safety Manager Apollo & CooperMEDC Ltd (www.coopersafety.com/brands/medc) www.timeguard.com/products/safety/emergencyassist-alarms Discuss with UCL Access Systems Manager Date Last Amended: Nov 16 12.