Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

Similar documents
PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

Ventilation BCBC & Richard Kadulski Architect

Ventilation BCBC 9.32 & Richard Kadulski Architect

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (6)

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (2)

Mechanical Ventilation Checklists

PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015)

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Outside Air Requirements... SOLVED!

Heat Recovery Ventilation

State of MN Energy Code Ventilation Review for 2017 Energy Design Conference. By 1. Mike D. Wilson Dakota Supply Group

Put the V back in HVAC

C O D E S & A M M E N D M E N T S

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Pipe Sizing Table. Hydraulic Load Served (fixture units)

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

2015 MECHANICAL CODE REQUIREMENTS

Ventilation for New Low-Rise Residential Buildings July 20, 2015

InspirAIR Compact Heat and Energy Recovery. Multi-Family HRV/ERV

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Commissioning Worksheets (Part A-General) (W 1)

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

Building Regulations Approved Document F1 Means of Ventilation April 2006

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Ventilation Techniques. Topic 5 - Audio 53

BUILDING CODE COMMISSION

BPI 1200 and ASHRAE Standards

The 2018 Ventilation Extravaganza. Rick Karg Residential Energy Dynamics 2018

TECHNICAL SPECIFICATIONS

INSTALLATION AND SERVICE MANUAL

Short Term Accommodations Fire Code Requirements

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

Winnipeg Fire Department Fire Prevention Branch

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR)

An Introduction to Energy Efficient and Effective Whole-House Ventilation

Inspection Checklist Residential Mechanical Rough In July 2016

Indoor Environmental Quality

NEW HOME CERTIFICATION PROGRAM 2018 PROGRAM GUIDE

HS Series Installation & Operating Instructions RadonAway

INSTALLATION AND SERVICE MANUAL

SER Series. fantech. Installation Manual. Energy Recovery Ventilators. ser 1504 ser 1504n ser 2004 ser 2004n ser 3204d ser 3204n

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

SH, VH & SE Series. Installation, Operation and Maintenance Manual. Heat & Energy Recovery Ventilators SH 704 VH 704 SE 704

Building Codes, Ventilation Rates, and Certified Performance. Ventilation Track Comfortech 2007 St Louis, MO September 27, 2007

HRV/ERV Performance Issues

Contents. How to choose Recovery Ventilation type?...3. How do HRV, ERV and TRV Systems work?...4. Types of installations...5. VUT 200 H mini...

HEPA Filtration. HEPA Series. Air Filtration System IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

INFORMATION BULLETIN

ENERGY STAR Qualified Homes

COMcheck Software Version Mechanical Compliance Certificate

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

Uniform Dwelling Code 2017 Updates SPS 323

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI)

ASX7-4-IOM-6 J

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Electrical Tech Note 107

Effects of Kitchen Ventilation on Residential Dwellings

Residential and Commercial HRVs & ERVs. Heat Recovery Ventilators & Energy Recovery Ventilators

Spray Polyurethane Foam and Open-Combustion Appliances

Inspection Checklist Mechanical Rough in

SER Series. Installation Manual. Energy Recovery Ventilators SER 1504 SER 2004 SER 3204D

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)

Building Department Informational Handout

WHHR Midi & Midi Lite

EXHAUST FAN SCHEDULE

Installation Instructions

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

Ventilation Products AirCycler g2/g2-k Installation & User s Guide

Installation Instructions

DIVISION C ADMINISTRATIVE PROVISIONS

Limited Lifetime core warranty. 5-year warranty on balance of unit.

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

INSTALLATION DO S AND DON TS

Featuring Vent Lights and Premium Grilles

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Ventilation Products AirCycler g2/g2-k Installation & User s Guide

Chapter FUEL GAS CODE*

2012 International Fuel Gas Code Design, Installation and Inspection Principles

INTERNATIONAL MECHANICAL CODE

EARTH ADVANTAGE HVAC REQUIREMENTS

Supplement A- Improving Forced Air Heating Systems

BUILDING CODE COMMISSION

BROAN ERVS100 Part no. ERVS100S CFM (0.4 in. w.g.)

HS Series Installation & Operating Instructions RadonAway

BUILDING CODE COMMISSION

CHIMNEYS AND VENTS CHAPTER 8

SPECIFICATION casing manufactured from aludip steel in white low energy DC external motor aluminium plate heat exchanger

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

(A) ft 3. cfm. cfm (Q

Transcription:

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-09-32-03 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION

Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: 2-CC-B-09-32-03 Ontario CODE REFERENCE: Div. B, 9.32.3.5.(9) Div. B, 9.32.3.7.(3) Div. B, 9.32.3.7.(4) Div. B, 9.32.3.7.(5) Div. B, 9.32.3.8.(2) Div. B, 9.32.3.9.(4) Div. B, 9.32.3.11. Div. B, 9.32.3.12.(9) Div. B, 9.32.3.13.(1) DESCRIPTION OF THE PROPOSED AMENDMENT The proposed change will allow the use of energy recovery ventilators where a heat recovery ventilator is required or used. EXISTING 2012 BUILDING CODE PROVISION(S) Section 9.32. Ventilation 9.32.3. Mechanical Ventilation (See Appendix A.) 9.32.3.5. Supplemental Exhaust (9) Supplemental exhaust required in this Article may be provided by means of a heat recovery ventilator installed in accordance with Article 9.32.3.11. 9.32.3.7. Ventilation Systems Not Coupled With Forced Air Heating Systems (3) The mechanical system in this Article shall include a heat recovery ventilator installed in accordance with Article 9.32.3.11. (4) Outdoor air shall be distributed by a ductwork system from the heat recovery ventilator required in Sentence (3) to each bedroom, to any storey without a bedroom and, if there is no storey without a bedroom, to the principal living area. Building and Development Branch Page 1 of 6

(5) A supply duct from the outdoors to the heat recovery ventilator required in Sentence (3) and a main distribution trunk duct shall be provided and shall be sized according to Part 6, except that the supply duct and the main distribution trunk duct may be sized according to Table 9.32.3.7.A. where, (a) the total duct length from the outdoor hood to any supply register does not exceed 21 m, and (b) the total number of fittings does not exceed 8. Number of Bedrooms in Dwelling Unit Table 9.32.3.7.A. Minimum Outdoor Air Supply and Main Trunk Duct Sizes Forming Part of Sentence 9.32.3.7.(5) Minimum Outdoor Air Supply and Main Distribution Trunk Duct Diameter, mm 1 150 2 150 3 175 4 175 5 175 More than 5 System must comply with Sentence 6.2.1.1.(1) Column 1 2 9.32.3.8. Protection Against Depressurization (2) Where a solid fuel-fired combustion appliance is installed, the ventilation system shall include a heat recovery ventilator that is designed to operate so that the flow of exhaust air does not exceed the flow of intake air in any operating mode, and that complies with the requirements of Article 9.32.3.11. 9.32.3.9. Fan Ratings (4) Except for heat recovery ventilators, exhaust fans required to make up any part of the total ventilation capacity required by Article 9.32.3.3. shall have a sound rating not greater than that specified in Table 9.32.3.9. Table 9.32.3.9. Fan Sound Rating Forming Part of Sentence 9.32.3.9.(4) Fan Application Maximum Sound Rating, sones Rated according to CAN/CSA-C260-M Rated according to HVI 915 Principal exhaust fan 2.0 2.5 Supplemental exhaust fans installed in bathrooms and water closet rooms and their make-up air fans 2.5 3.5 Supplemental exhaust fans installed in kitchens and their make-up air fans no rating required no rating required Column 1 2 3 Building and Development Branch Page 2 of 6

9.32.3.11. Heat Recovery Ventilators (1) Where a heat recovery ventilator is installed to provide all or part of the requirements of this Subsection, this Article shall apply. (2) Heat recovery ventilators shall be designed to provide a minimum 55% sensible heat recovery efficiency when tested to the low temperature thermal and ventilation performance test method set out in CAN/CSA-C439, Rating the Performance of Heat/Energy-Recovery Ventilators, at a Station 1 test temperature of 25 C at an air flow not less than 30 L/s. (3) Where a heat recovery ventilator is connected to a forced air heating system, the supply side of the ventilator shall be directly connected to the return air side of the forced air heating system. (4) Two or more heat recovery ventilators shall not be connected in parallel air flow to a common air supply duct unless specifically recommended by the manufacturer. (5) Two or more heat recovery ventilators shall not be connected in parallel air flow to a common downstream exhaust duct. (6) Heat recovery ventilators installed in unheated spaces shall be installed so as to avoid condensation of moisture on fans and motors in exhaust air, in accordance with the manufacturer's instructions. (7) All start-up procedures recommended by the manufacturer including air balancing and air-flow determination shall be followed. (8) Free flow of condensate shall be provided in accordance with the manufacturer's recommendations or, in their absence, a condensate drain of minimum ½ inch nominal pipe size pitched in the direction of flow and complete with a trap or condensate pump with sufficient capacity shall be installed. (9) The heat recovery ventilator and all condensate lines shall be installed in a space where the ambient temperature will not adversely affect the operation of the system. (10) When operating at the rate required in Article 9.32.3.4., the supply and exhaust airflow rates of the heat recovery ventilator shall be balanced so that the value of the lesser flow shall be at least 90% of the value of the greater flow, unless otherwise recommended by the manufacturer. 9.32.3.12. Outdoor Intake and Exhaust Openings (9) Except for exhaust outlets serving heat recovery ventilators, exhaust outlets shall incorporate backdraft dampers. 9.32.3.13. Installation (1) Installation of fans and heat recovery ventilators shall be in accordance with manufacturer s instructions for minimizing noise and vibration transmission and achieving the required sound rating. Building and Development Branch Page 3 of 6

PROPOSED CODE CHANGE Section 9.32. Ventilation 9.32.3. Mechanical Ventilation (See Appendix A.) 9.32.3.5. Supplemental Exhaust (9) Supplemental exhaust required in this Article may be provided by means of a heat or energy recovery ventilator installed in accordance with Article 9.32.3.11. 9.32.3.7. Ventilation Systems Not Coupled With Forced Air Heating Systems (3) The mechanical system in this Article shall include a heat or energy recovery ventilator installed in accordance with Article 9.32.3.11. (4) Outdoor air shall be distributed by a ductwork system from the heat or energy recovery ventilator required in Sentence (3) to each bedroom, to any storey without a bedroom and, if there is no storey without a bedroom, to the principal living area. (5) A supply duct from the outdoors to the heat or energy recovery ventilator required in Sentence (3) and a main distribution trunk duct shall be provided and shall be sized according to Part 6, except that the supply duct and the main distribution trunk duct may be sized according to Table 9.32.3.7.A. where, (a) the total duct length from the outdoor hood to any supply register does not exceed 21 m, and (b) the total number of fittings does not exceed 8. Table 9.32.3.7.A. Minimum Outdoor Air Supply and Main Trunk Duct Sizes Forming Part of Sentence 9.32.3.7.(5) Number of Bedrooms in Dwelling Unit Minimum Outdoor Air Supply and Main Distribution Trunk Duct Diameter, mm 1 150 2 150 3 175 4 175 5 175 More than 5 System must comply with Sentence 6.2.1.1.(1) Column 1 2 9.32.3.8. Protection Against Depressurization (2) Where a solid fuel-fired combustion appliance is installed, the ventilation system shall include a heat or energy recovery ventilator that is designed to operate so that the flow of exhaust air does not exceed the flow of intake air in any operating mode, and that complies with the requirements of Article 9.32.3.11. Building and Development Branch Page 4 of 6

9.32.3.9. Fan Ratings (4) Except for heat or energy recovery ventilators, exhaust fans required to make up any part of the total ventilation capacity required by Article 9.32.3.3. shall have a sound rating not greater than that specified in Table 9.32.3.9. Table 9.32.3.9. Fan Sound Rating Forming Part of Sentence 9.32.3.9.(4) Fan Application Maximum Sound Rating, sones Rated according to CAN/CSA-C260-M Rated according to HVI 915 Principal exhaust fan 2.0 2.5 Supplemental exhaust fans installed in bathrooms and water closet rooms and their make-up air fans 2.5 3.5 Supplemental exhaust fans installed in kitchens and their make-up air fans no rating required no rating required Column 1 2 3 9.32.3.11. Heat Recovery Ventilators (1) Where a heat or energy recovery ventilator is installed to provide all or part of the requirements of this Subsection, this Article shall apply. (2) Heat or energy recovery ventilators shall be designed to provide a minimum 55% sensible heat recovery efficiency when tested to the low temperature thermal and ventilation performance test method set out in CAN/CSA-C439, Rating the Performance of Heat/Energy-Recovery Ventilators, at a Station 1 test temperature of 25 C at an air flow not less than 30 L/s. (3) Where a heat or energy recovery ventilator is connected to a forced air heating system, the supply side of the ventilator shall be directly connected to the return air side of the forced air heating system. (4) Two or more heat or energy recovery ventilators shall not be connected in parallel air flow to a common air supply duct unless specifically recommended by the manufacturer. (5) Two or more heat or energy recovery ventilators shall not be connected in parallel air flow to a common downstream exhaust duct. (6) Heat r energy recovery ventilators installed in unheated spaces shall be installed so as to avoid condensation of moisture on fans and motors in exhaust air, in accordance with the manufacturer's instructions. (7) All start-up procedures recommended by the manufacturer including air balancing and air-flow determination shall be followed. (8) Free flow of condensate shall be provided in accordance with the manufacturer's recommendations or, in their absence, a condensate drain of minimum ½ inch nominal pipe size pitched in the direction of flow and complete with a trap or condensate pump with sufficient capacity shall be installed. (9) The heat or energy recovery ventilator and all condensate lines shall be installed in a space where the ambient temperature will not adversely affect the operation of the system. Building and Development Branch Page 5 of 6

(10) When operating at the rate required in Article 9.32.3.4., the supply and exhaust airflow rates of the heat or energy recovery ventilator shall be balanced so that the value of the lesser flow shall be at least 90% of the value of the greater flow, unless otherwise recommended by the manufacturer. 9.32.3.12. Outdoor Intake and Exhaust Openings (9) Except for exhaust outlets serving heat or energy recovery ventilators, exhaust outlets shall incorporate backdraft dampers. 9.32.3.13. Installation (1) Installation of fans and heat or energy recovery ventilators shall be in accordance with manufacturer s instructions for minimizing noise and vibration transmission and achieving the required sound rating. RATIONALE FOR CHANGE Problem/General Background Currently, various provisions of Part 9 make reference to a heat recovery ventilator. Energy recovery ventilators provide similar benefits as they facilitate recovery of latent energy and moisture. Justification/Explanation The editorial change will clarify that the energy recovery ventilators that meet the same requirements as heat recovery ventilators can be used the meet the Code requirements. Cost/Benefit Implications No additional cost as the proposed change would provide another option. The change would increase design flexibility. Enforcement Implications None expected. Who is Affected Designers (including licensed architects and professional engineers), builders, contractors and installers, product manufacturers and enforcement officials are affected. Objective Based Analysis Not applicable. OTHER SUPPORTING MATERIALS None. Building and Development Branch Page 6 of 6