Sorrento & Flamevector Fireplace Boilers

Similar documents
DANESMOOR FRONT SERVICE (FS) 12-18, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE


Installation and Maintenance Instructions XPG170 Electric Fires

DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

USER GUIDE LOGIC HEAT H

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Imperial Electric Fires

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Logic+ Combi

16 Ultiflame Inset Electric Fire

Installation and Maintenance Instructions XPG144/145/146 Electric Fires

USERS GUIDE. LOGIC+ Combi 24, 30, 35

Model 1174 Electric Heater User instructions for LED effect 2kw Inset Heater

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00

(manual control) (ezi-slide control) INSET COAL EFFECT GAS CONVECTOR FIRE V1/100/B INSTALLATION & USER INSTRUCTIONS

POWER SHOWERS Models 4500M 5002M 4500T 5002T

System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER

Installation & Maintenance Manual

16 XD Mk2 Inset Electric Fire

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HE 130/180 HE 190/220 OIL FIRED CENTRAL HEATING BOILER FOR BALANCED AND CONVENTIONAL FLUE

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

Imperial Electric Fires

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

INSTALLATION & USER INSTRUCTIONS

INSTALLER AND OWNER GUIDE

Installation and Operating Manual Drying Cabinet

User Instructions for Remote Controlled 2kW Rotisserie Effect Fan Heater Model 1276

Osprey 2 CFL

USER GUIDE VOGUE MAX SYSTEM

Baxi Maxflow Combi FS

Dovre 700CBW Cast Iron Wood Stove INSTALLATION INSTRUCTIONS 700G/1095

Oil TRIANCO. EuroStar Range BURNER DETAILS TRIANCO - OIL BURNER. To be retained by householder

INSTALLATION & USER INSTRUCTIONS

iheat 25c iheat 30c iheat 35c

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

Installation & Maintenance Manual

THE SEVERN. Installation Instructions for Freestanding Severn Stove with Boiler PERFORMANCE RATING

Dovre 250 Cast Iron Gas Stove

1. GENERAL SAFETY RULES

USERS GUIDE 24, 30. For installation guide see reverse of book

Light oil - kerosene burner

Domestic Gas Cookers & Ranges

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

OWNER S GUIDE ETERNITY. MODEL 540C (GC No ) INSET BALANCED FLUE GAS FIRE

Installation Instructions & Operating Manual IMPORTANT

Baxi Maxflow Combi WM

BENSON LINEAR RADIANT TUBE

GB IE INSTALLATION & USER INSTRUCTIONS. Model Number: V1/300/B (ez-slide control) HIGH EFFICIENCY INSET COAL EFFECT GAS CONVECTOR FIRE

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

2.8KW ELECTRIC FAN HEATER

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

EMBERGLOW CLASSIC RADIANT CONVECTOR GAS FIRE. Installation and Maintenance Instructions

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

Corn Flame Energy Corn Stove Model 3000

User's Instructions. Alpha CB50

Light oil burners. One stage operation

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25

BOSCH CONDENS 5000W ZSB18-2A

ST 40 Oil Burner. Installation & Maintenance Manual

Installation & Service Instructions

Performa 24. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

15 20 kw kw kw

FLUEBOOST. flueboost 350 gas fire model

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

5KW ELECTRIC FAN HEATER

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

15KW ELECTRIC FAN HEATER

GE Monogram. Installation. Instructions. Professional Gas Cooktops 48" Natural Gas Models ZGU48N4GWSS ZGU48N6RWSS ZGU48N6DWSS

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

Model 801 With Adorn, Icon, Visage, Elegant or Ultimate Fireslide fronts & Model 802 Ultimate, Cosyflame, Fyrside, Nebula & Pizzazz versions

Operating instructions for the DA 8-2 Extractor

User s Information Manual

Light oil / kerosene burner

INSTALLATION AND MANINTENANCE INSTRUCTIONS

BAXI BOSTON ALL MODELS FLOOR STANDING OPEN FLUE (OF) CENTRAL HEATING BOILERS INSTALLATION AND SERVICING INSTRUCTIONS. GAS TYPE G20 (Natural Gas)

Statesman 45/50L, 50/70L, 70/90L, 90/110L, Utility 50/70L, 70/90L, 90/110L, 110/130L, 130/150L

Installation and Maintenance Instructions XPG170e Electric Fires

AGA 13 AMP RETRO-FIT WITH AIMS

INSTALLATION & USER INSTRUCTIONS

Linea HE. High efficiency combi boiler. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Riva F40 Cube. Multi-Fuel Free Standing Stove. Installation Instructions. Models: RVF40C. For use in Great Britain and Eire IMPORTANT


PROPANE GAS HEATER MODEL NO: DEVIL 4000 OPERATION & MAINTENANCE INSTRUCTIONS PART NO: ORIGINAL INSTRUCTIONS GC ISS 4

Part No. DOC 16 Rev. 09 December USER and INSTALLATION INSTRUCTIONS OUTDOOR MODULES 50/70, 70/90, 90/120 & 110/140

Baxi Bermuda GF3/LFE5 Super

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

VH60SS 60CM VISOR HOOD STAINLESS STEEL

WORCESTER BOSCH 50/70, 70/90, 90/110 FLOOR STANDING OIL-FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS

Installation & Operating Instructions. Models: York Midi & Serrano Electric Stoves

MAINTENANCE AND SERVICE GUIDE

TRIANCO FLOOR STANDING OIL FIRED CENTRAL HEATING BOILERS FOR EXTERNAL INSTALLATION ONLY USER, INSTALLATION COMMISSIONING & SERVICING INSTRUCTIONS

Transcription:

orrento & Flamevector Fireplace Boilers ection 10. Fitting Instructions 10.1 Positioning the Boiler 10.2 Ventilation 10.3 lectrical 10.4 Combustion Air (Conventional Flue Models) 10.5 Water Connections 10.6 Air Inlet Diverter Box 10.7 Fuel 10.8 Baffles 10.9 Lock ut Button 10.10 imple Fault Finding 10.1 Positioning the Boiler nsure that the site provides sufficient access for installation and maintenance. As the heat exchanger is a totally water enclosed fabrication there is always a waterway beneath the boiler body which ensures that the water temperature is below 100ºC and a constructional hearth is not, therefore, required. orrento should be installed on a non-combustionable base AD CA HULD B AK U HA H HA XCHAG I PIID DAD C AD H AM LVL BA A H FACIA AMBLY. he heat exchanger measures 385mm wide x 515mm high x 300mm deep and sufficient additional space around the heat exchanger will be needed to allow access for pipe and flue connections and general installation. orrento can be introduced into a standard 16 x 22 fireplace opening. nsure that an opening not less than 16 x 22 remains for access of fascia assembly, for commissioning and taking flue gas samples. With conventional flue models, especially if located in a confined space, ensure that adequate ventilation is provided for efficient combustion. efer to manufacturer for balanced flue room-sealed options. nce installed it is not necessary to provide access form the top of the boiler as all routine servicing and maintenance can be conducted from the front of the appliance. It is advisable to leave a space for ventilation around the unit and to gain access to the flue for cleaning if necessary. It is also for the checking of flue gas temperatures etc, when serviced and commissioned. nsure that you comply with the Building egulations and Codes of Good Practice in the installation of the orrento appliance, e.g., flue terminals should not be discharged within 1 metre of an opening window or door. It is also advisable to seek permission from your local Building Inspector before installation of balanced flue models. It is unlikely that any difficulties will be presented. You are advised to install according to.f...c. recommendations. 47 Fig 78

orrento & Flamevector Fireplace Boilers orrento Flamevector implest xample of Installing orrento Make sure hearth is suitably level throughout and level with the position where the fascia assembly will eventually stand. Place the heat exchanger dead centre, as far back as possible and connect water pipework and flue as previously detailed. Fig 79 It is advisable to supply suitable insulation around the heat exchanger once installed. Use kerosene (28 sec. Viscosity) oil not gas oil (35 sec. Viscosity) as burner operation is quieter using this fuel. emove fascia assembly panel and check the burner control box for lockout. If reset button on the control is illuminated - press to restart. If the burner does not fire and again goes to lock out, wait for 3 to 4 minutes and press reset button again. Where electric fan unit is fitted to orrento simply remove to gain access to reset button. 48 Fit burner into the burner port making sure that it is in the UPID DW attitude. Push up tightly against the gasket on the heat exchanger to avoid the escape of flue gases which could cause pollution. ighten securing nuts. he surround should be positioned and fixed prior to sliding in the fascia assembly. Plug burner control socket to the appropriate connection on the electrical control box situated on the right hand, inside of the fascia assembly. he sockets are deliberately different from each other to ensure that no plug can be mistakenly inserted into the wrong socket. Additional Information for Flamevector & Variations he thermostatic knob, amber operating light and red high limit warning light are mounted top left hand side externally. A 3 core cable is fitted for connection to programmer/time clock. he pre-wired plug and socket to connect the burner are situated behind the front panel. o remove front panel from the Flamevector, remove 4 screws form base and lift forward and upwards. he control box/lock out button is remotely situated at the middle bottom front of the Flamevector. It must be fitted to the purpose built bracket by the installer. A separate lead and 13 amp plug fitted with a 5 amp fuse is factory fitted for the operation of the living fire flame effect. wo switches and controls are on the right hand side externally and adjust brightness of coal effect and output of fan convector. he water connections to the fan convector are situated at the bottom right hand side of the Flamevector. Ball or fix type valves with suitable flexible connections to the flow and return pipes of the central heating system are recommended so that simple access is available for service and maintenance of burner/heat exchanger. he 10mm flow and return pipes may be trimmed back on the Flamevector to conceal flexible pipework and valves if required. A Flamevector has keyhole slots on the rear plate for securing to the fireplace.

10.2 Ventilation Fitting Instructions orrento & Flamevector Fireplace Boilers A grille should be provided at high level in the room with a free inlet area the same as that shown in the table for combustion air. Conventional Flue Models a. he flue should be arranged to sweep vertically, if possible, free from right angle bends and horizontal runs. b. he flue should have a cross sectional area not less than that of the boiler flue outlet. If the flue height is in excess of 25 feet the flue diameter should be increased by 25mm (1 inch) to avoid back pressure on start-up. c. If the connection is to be made to an existing chimney, it may be necessary for a flexible flue line to be fitted for the whole length of the chimney. d. Condensation may occur if the chimney is inadequately constructed. Provision should be made for draining if condensation is likely. orrento is highly efficient, more than 90% and a first class insulated flue should be installed if condensation is to be avoided. e. It is necessary to provide access for cleaning should this be necessary. f. If an external flue is used it should be of the twin insulated type. With such high efficiency boilers as orrento it is essential to fit insulated flues to avoid condensation. g. Flue should be sealed into the boiler socket with flue cement or a suitable sealant to ensure safety and the prevention of pollution to the burner. Balanced Flue ystems he boiler range can be supplied for room-sealed applications where the air for combustion is taken from the outside. Further details are available from the manufacturer. However, it is important that care is taken in choosing the location which should comply with the relevant Building egulations. With low level flues a copy of Building egulations should be obtained from the Local Authority. 49 Fig 80

10.3 lectrical Fitting Instructions orrento & Flamevector Fireplace Boilers All electrical connections and wiring should be performed by a qualified electrician in accordance with current lectrical an I egulations. Disconnect main supply before attempting any electrical connections. he electrical supply must be 220 volts A/C single phase 50Hz protected by a 5 amp fuse. Fig 81 50 Fig 82 he boiler is provided with a pre-wired plug and socket to connect the burner to the fascia assembly. A plug and socket are provided to bring the mains supply to the panel. Please note that a constant live supply has to be made to the orrento boiler to ensure that the illuminated coal flame arrangement may be operated even when the boiler is switched off. An auxiliary line feed which is clearly marked constant live is fitted for this purpose.

orrento & Flamevector Fireplace Boilers 10.4 Combustion Air (Conventional Flue Models) insulation may be added as appropriate. o provide fresh air for combustion a low level unobstructed inlet should be made approximately 3mm from the ground adjacent to the boiler. ecommended minimum free inlet area for air: Model q cm q Inches 12/15H 162 25 15/18H 220 34 18/21H 290 45 An adequate air supply must be delivered to the room in which orrento is sited in accordance with B5410 part 1 section 23. An air brick may have to be installed to permit sufficient ingress of air combustion. Minimising oise Level Whilst orrento is exceptionally quiet, by modern oil boiler standards, it still has an operational noise level. he site conditions and method of flueing can influence this noise level considerably. he following points are made to assist with the reduction of the noise level. 1. Most noise emission from the burner, if applicable, will escape from the front of the appliance through the air intake grille beneath the front fascia assembly. However, the front air intake grille has built in silencing materials. With inset models it is not acceptable, for the purpose of minimising noise to install the appliance in and open hearth allowing the excessive escape of burner noise. Instead you are strongly advised to make up the fire place around the fascia assembly leaving only sufficient space to permit the fascia assembly to be pulled forward and away from the burner for routine servicing. he general intention is to contain and seal in as much noise as possible. loppy workmanship and gaps left around the boiler fascia assembly will only allow noise to escape. 2. If it is possible to use balanced flue arrangement then, likewise, the front fascia assembly can be sealed to the fire-surround thus containing more of the noise. 3. Proper commissioning and regular servicing will ensure the smoothest and efficient operation of the burner thereby minimising sound. 4. ealant tape is factory fitted between the front fascia sections. nsure that this sealant is not damaged or removed during installation or servicing. Additional acoustic 51 Fig 83 10.5 Water Connections British tandard Codes of Practice must be used to provide correct water connections. For single flow and return systems, diagonally opposite sockets should be used, or if preferred top and bottom socket same side. All spare sockets should be blanked before filling the system.

orrento & Flamevector Fireplace Boilers 10.6 Air Inlet Diverter Box A filter must be fitted to the oil supply line which, if omitted, could cause failure to the burner or damage to the nozzle, the responsibility for which will not be accepted by Heating World Ltd. It is essential that a fire valve is fitted in the oil line to the burner so that, in the unlikely event of fire the oil supply is isolated. 10.8 Baffles Fig 86 Fig 84 10.9 Lock ut Button emove front panel of fascia assembly door by pulling forwards to release from latches. he lock out button, if illuminated, is visible and accessible and may be pressed if necessary. eplace the panel ensuring that it is properly resealed. Allow 3 to 4 minutes before each attempt at pressing lockout button to allow the control box to complete its full sequence of operation. Failure to allow adequate delay could cause further component failure. 10.10 imple Fault Finding Fig 85 10.7 Fuel he recommended fuel for your orrento is Class 2 (B 2869-7) known as Kerosene which has a viscosity of 28 seconds (edwood umber 1). ach burner is accordingly electronically set-up at the factory to ensure maximum efficiency. A test badge is affixed to the electrical control box inside the fascia assembly giving details of correct nozzle size and appropriate oil pump pressure. 52 In the event of the boiler failing to fire the following checks should be made before calling a ervice ngineer. 1. Check for failure of the electricity supply and/or that it is switched. 2. Check that there is sufficient oil in the tank and that the valve is open (turned fully counter-clockwise). 3. Check that the programmer or boiler operating switch is set to call for heat. 4. Check boiler thermostat is set to required temperature. 5. Check the fuse on the mains supply to the programmer of boiler operating switch.