Technical Specification

Similar documents
Technical Specification

Technical Specification

Technical Specification

Technical Specification

Technical Specification

Metropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

SAMPLE SPECIFICATIONS

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

BOILER HOUSE PRODUCTS GMS

MX RANGE PACKAGED STEAM BOILERS

FT14 and FT14HC. SG Iron Ball Float Steam Traps (1" HC, 1¼", 1½" and 2")

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

EXPRESSION OF INTEREST (EOI) FOR. Fire Fighting System (FFS)

Rental Boiler Specifications (Nebraska Boiler)

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

University of Delaware

Zeeco, Inc. Doc. No Tulsa, Ok Cover Page GLSF-14 Free-Jet and RWSF-4 Radiant Wall Burners. Range Fuels Soperton Plant, LLC

DIVISION FINNED WATER-TUBE WATER HEATERS

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

MULTIPLEX SELF RECUPERATIVE gas burner

FEEDWATER TANK WITH DEAERATOR DATASHEET. Capacity 1000 to lt Operating Pressure 0,5 bar

BuildingName The Description of the Project P DOCUMENTS

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

WATER-TUBE POOL HEATERS

Heating system service plans that provide total peace of mind.

Ball Float Steam Trap with Integral Spiratec Sensor and Flanged Connections

SECTION HEATING BOILERS

CHAPTER 2: PROPERTIES OF STEAM AND STEAM POWER

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

SECTION PLUMBING EQUIPMENT

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

FUEL-FIRED VERTICAL TUBELESS BOILERS

WATER-TUBE POOL HEATERS

DIVISION FINNED WATER-TUBE BOILERS

Assessment Schedule - TS.6

OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "VIHS"

Design and Construction Standards SECTION PLUMBING EQUIPMENT

FT14 Ball Float Steam Trap (Screwed)

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

Direct Fired Heater Model AD Specification

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

GFT-060/40/H2. Designed and built According AD-2000 regulation Homologation and branded CE According to the European Directive CE

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

Module 3: Liquid Fossil Fuel (Petroleum) Lecture 25: Refinery Equipments

Drum Level Instrumentation and

Flash Condensing De-aerator Heads Installation and Maintenance Instructions

BETTER HOME COMFORT AND PEACE OF MIND STARTS WITH THE BEST SERVICE PLANS.

HAWK GAS STOVE. Installation and Servicing Instructions

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

THW-I NTE. Description THW-I NTE. Industrial Hot Water Boiler THW-I NTE for Oil or Gasfiring. Industrial Hot Water Boiler

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

12711 TOWNEPARK WAY / LOUISVILLE, KY / / FAX

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

Steam Fundamentals. (in heating & processing applications)

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

Waste/Multi Oil Boilers from Flexiheat

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

Drum Level Instrumentation and. The ASME Boiler Code Requirements. Presented by: Jim Kolbus. Topics

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

Inverted Bucket Steam Traps

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

DIVISION FINNED WATER-TUBE BOILERS

C. B. Trading Corporation

LOW SURFACE TEMPERATURE RADIATORS

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

INDITHERM. Low temperature gas burners

Bringing a Steam Boiler On-Line from Cold.

Fuel-Fired Vertical Tubeless Boilers

Condensate Boiler Feed Water Make-Up

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

Condensate Return Feedwater Systems For Low and High Pressure Steam Boilers

APT and APT14 Automatic Pump Traps. for effective condensate drainage and removal

OPX INDUSTRIAL RANGE THERMAL OIL

WD7664 / WD7663 Maxon Burner Ellis Whisper Dryer Installation & Start UP

MFP14 Automatic pumps for condensate and other industrial fluids

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

DIVISION FINNED WATER-TUBE WATER HEATERS

.2 Section Waste Management and Disposal..5 Section Performance Verification of Mechanical Piping Systems.

Silhouette. Feedwater Heater. Boiler Feedwater

STR-Series Indirect-Fired Air Turnover Units

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

BAXI BOSTON ALL MODELS FLOOR STANDING OPEN FLUE (OF) CENTRAL HEATING BOILERS INSTALLATION AND SERVICING INSTRUCTIONS. GAS TYPE G20 (Natural Gas)

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

MFP14 Automatic pumps. for condensate and other industrial fluids

Boiler Product Range

Water Fuel + Air for combustion Blowdown

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Transcription:

Cochran Ltd Newbie Works, Annan, Dumfries & Galloway, Scotland, UK DG12 5QU Telephone: +44 (0)1461 202111 Fax: +44 (0)1461 205511 Email: info@cochran.co.uk www.cochran.co.uk Three Pass Wet back THERMAX TWIN FURNACE Package Steam Boiler Technical Specification A Cochran Group Ltd Company Registered Office: Newbie Works, Annan, Dumfries & Galloway DG12 5QU Company Number: SC379382 Registered in Scotland TFTH- Jan 2017 Page 1 of 11

COCHRAN THERMAX TWIN FURNACE STEAM BOILER SPECIFICATION The COCHRAN THERMAX TWIN FURNACE PACKAGE STEAM BOILER is of horizontal three pass wet back design and constructed in accordance with BS EN 12953. It complies with the requirements of the Factories Act (1961) and Arrangement 1 of Guidance on Safe Operation of Boilers Ref: BG01 developed by the Safety Assessment Federation (SAFED) and the Combustion Engineering Association (CEA), the latter being the acceptance criteria for compliance with HSE and UK Inspection Authority requirements. Additionally, the Boiler is CE Marked to meet the requirements of: Pressure Equipment Directive Low Voltage Directive Electro-Magnetic Compliance Directive Machinery Safety Directive Throughout the manufacturing process, the BOILER is subject to inspection by a leading Independent Insurance Company. In addition, COCHRAN apply their own quality procedures that comply with the requirements of ISO 9001:2008. The attached schedules detail the specification of the Boiler proposed in the tender enclosed. Schedule Number Description Page Number 1 Boiler - Pressure Parts 3 2 Boiler Mounted Fabrications 5 3 Steam and Water Mountings 6 4 Feed Pump & Water Level Controls 7 5 Combustion Equipment / Control Panel / Wiring 8 6 Painting 9 7 Terminal Points 10 8 Tools / Documents 11 We reserve the right to amend or alter this Specification during the tender validity period or the manufacturing stage of any subsequent order to comply with any alteration or amendment to applicable Standards, Safety Codes, Guidance Notes or Revisions in Manufacturing Techniques. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 2 of 11

Schedule 1: Boiler Pressure Part GENERAL All plate used in the construction of the boiler is cut and profiled by computer controlled equipment. The shell, furnace and reversal chamber plates are then rolled, assembled, machine welded and subjected to NDT (either radiographic or ultrasonic) to ensure compliance with the latest construction standard requirements. Tube plates are drilled by computer controlled equipment to ensure the correct ligament is maintained and a satisfactory tube hole finish is achieved. BOILER SHELL Furnace and Reversal Chamber The two furnace tubes incorporate sections with 'bowling hoop' joints to provide sufficient stiffness and to allow for adequate expansion to take place. These are located between the front boiler tube plate and front tube plate of the totally submerged reversal chamber. The reversal chamber rear tube plate is stayed to the rear boiler tube plate with the required number of stay bars. Convection Tubes Two separate passes of convection tubes are fitted. One pass between the boiler front tube plate and the reversal chamber tube plate with another pass between the boiler front and rear tubeplates. All plain tubes are expanded into position with the inlet to the first pass tubes in the reversal chamber being expanded and welded. Stay tubes and stay bars are fitted to ensure that stressing of tube plates and tube nests are within construction code limits. Access and Inspection For inspection purposes, openings are provided to gain access to the steam/water side of the boiler. One 420 320mm elliptical manway opening is provided on the top of the boiler. Two 320 220mm elliptical headhole openings are provided in the lower quadrants toward the rear of the boiler, one provided on each side. One 125 90mm elliptical handhole opening is provided in the rear tubeplate. To permit observation and access into boiler furnace tube, a rear access door complete with a flame viewing sight port is provided. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 3 of 11

Schedule 1: Boiler Pressure Part Cont. Seatings Mountings and controls are fitted to pads, standpipes and bosses welded to boiler shell. Materials Specification Shell and Shell Attachments: Shell, Furnace, Reversal Chamber and Tube Plates: Furnace Access Tube: Stay Bars: Plain and Stay Tubes: Mandoor Head Holes Muddoor Lifting Lug: Pads (Valves): Standpipes: BS EN 10025-2 P265 GH ASTM A106 GR B BS EN 10273 P235 GH BS EN 10216-1-TR2 BS EN 10216-2 BS EN 10217-1-TR2 BS EN 10217-2 BS EN 10025-2 P265 GH BS EN 10025-2 P265 GH ASTM A106 GR B Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 4 of 11

Schedule 2: Boiler Mounted Fabrications Casings; Insulation & Supports Front and Rear Casings Boiler front and rear casings are fabricated from mild steel plate fully welded to the Boiler tubeplates and shell. Front casing is insulated internally to reduce radiation loss to a minimum and incorporates hinged doors with screen plates which allow access to boiler tubeplates and tubes to facilitate tube cleaning, tube removal and inspection. Rear casing is provided with flanged outlet for chimney connection. Hinged doors allow access to tubeplate and tube nest and are also fitted with screen plates. Insulation and Sheeting Exposed areas of boiler shell and tubeplates are insulated with 100 mm thick high density insulation to reduce radiation loss to a minimum and is retained in position with bands. 20G (0.812mm thick) "Stucco" aluminium sheeting to BS1470 SICH.H. is applied to shell. Tubeplates, pads and standpipe penetrations are finished with aluminium collars. To aid access for inspection purposes inspection doors and valves are not provided with insulation, this is available on request as an added option. Pipework is provided uninsulated as the client may find it easier to insulate on site with other connecting pipework between the package and the system. Supports Boiler supports are fabricated as an all-welded structure fabricated from suitably sized hollow sections, incorporating outriggers which are welded or bolted as appropriate for the boiler feed pump and control panel. Jacking points are provided on the support structure to assist in offloading, positioning and manoeuvring the boiler. Ladders and Platform (OPTIONAL EXTRA) Access ladder and platform is fitted to allow access to top of boiler and safety valve. The ladder incorporates safety hoops beginning at a level of 2515 mm from floor level of the Boiler baseframe terminating above the level of the platform safety railing. The platform is provided on three sides with safety handrailing to a height of 950 mm, the fourth side left open for access to the boiler valves. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 5 of 11

Schedule 3: Steam & Water Mountings STEAM AND WATER MOUNTINGS General As standard, the valves and gauges we offer comply with BS EN 12953 and are fitted to the boiler standpipes with suitable joints and flanges drilled to BS EN 1092. Flange fixing is by metric studs and nuts or bolts. Standard valves and fitting are tabulated below: Qty Description Manufacturer Material 1 Steam Stop Valve, Angle pattern type Ari Armaturen Cast steel 1 Single Spring High Lift Safety Valve sized to provide Spirax Sarco SG Iron 100% discharge capacity 1 Feed water isolation, Angle pattern type Ari Armaturen Cast steel 1 Feed water, wafer pattern non-return Gestra Flowserve Stainless steel 1 Multi stage, fixed speed, centrifugal feed pump Grundfos Stainless steel 1 Water strainer, Y Type (supplied loose) ISIS Fluid Control Cast Iron 1 Manual Blowdown Valve, ball type RTK Control Carbon steel 2 Reflex type water gauge assembly with steam & water Klinger Carbon steel cocks fitted to a plate type column 1 Standard integrity Probe type Modulating controls. Flowserve - 1 Bourdon type, Direct mounted Pressure Gauge Stewart Buchanan Aluminium 1 Air vent valve David Auld Valves Bronze 1 DN25 Blanked connection for TDS Control or Chemical injection - - Drain pipework from the water gauge drain cocks and safety valve drain are extended in suitably sized pipework terminating individually at boiler centre line. NOTES: Valve materials are provided for the rating, pressure and temperature requirements. For multi-boiler installations an additional steam non-return valve will be required to comply with the requirements of Guidance Notes BG01. Cochran can provide this additional valve on request if not being supplied by your Installation Contractor. Please refer to quotation for any additional valves or mountings offered. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 6 of 11

Schedule 4: Feed Pump & Water Level Controls WATER LEVEL CONTROLS DIRECT MOUNTED PROBE TYPE Water Level Controls are Direct Mounted Probe Type which are located on the top centreline of the boiler shell. All ratings incorporate Modulating water level Control Including: Modulating Feed Water Control Valve High Water Alarm 1st Low Water Level Alarm and System Lockout 2nd Low Water Level Alarm and System Lockout NOTE: As standard the water level control probes do not have self-monitoring capability but this facility can be offered if required. FEED WATER PUMP ** The feed water pump is multistage type sized to suit the boiler working pressure and rating. The pump is fitted to the boiler and connected to the boiler feed check valve in suitably sized mild steel pipework. A feed water inlet strainer is supplied loose. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 7 of 11

Schedule 5: Combustion Equipment; Control Panel; Wiring & Testing COMBUSTION EQUIPMENT The Boiler is fitted with two off pressure jet or a rotary cup burner matched to the Boiler in accordance with the rating and is suitable for the fuel(s) specified in our tender. The burner is a complete unit prewired and includes fuel atomiser system, ignition equipment, windbox and control linkage, etc. In the case of gas fired units a matched gas train is supplied. CONTROL PANEL A Boiler control panel is fitted to the Boiler supports and includes the necessary control equipment, starters, water level alarms, controls for feed pump and mains isolation. Control pressure switches are attached to the side of the panel. ELECTRICAL WIRING Heat resistant cabling is used for wiring between water level controls and the control panel, all other wiring is in PVC covered wiring carried in flexible conduit. Colour Coding to BS EN 60204-1:2006. FUNCTIONAL TESTING An electrical functional test of the boiler safety and control system is carried out and witnessed by the Cochran Q.A. Department Inspectors. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 8 of 11

Schedule 6: Painting Surfaces are degreased prior to painting and one coat of primer, one coat of undercoat and one finishing coat is applied. Standard Colours are as follows:- Baseframe, all Valves, Platform and Ladder (when fitted) Front and Rear Casings Screen Plates Sheeting Burner Control Panel Feed Pump Black Silver Blue Unpainted Stucco Aluminium Manufacturer s Standard Manufacturer s Standard Manufacturer s Standard Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 9 of 11

Schedule 7: Terminal Points Flanges to BS EN 1092 except where otherwise stated. Screwed connections BSP except where otherwise stated. Description: Stop Valve (Outlet) Safety Valve (Outlet) Blowdown Valve (Outlet) Feed Water (Inlet) Drain Pipework (Outlets) Flue Gas (Outlet) Oil Flow (Connection) Oil Return (Connection) Gas (Inlet) when applicable Pilot Gas (Inlet) when applicable Flanged Flanged Flanged Flanged Screwed Vertical Flanged Screwed Screwed Flanged Screwed Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 10 of 11

Schedule 8: Tools/Documents TOOLS Tube cleaning brushes and rod handle are provided. DOCUMENTS General Arrangement Drawing and Electrical Wiring Diagrams are provided. Certificate of Compliance is provided, certified by independent Inspection Authority. Operation and Maintenance Manual is provided. NOTE: In order to take advantage of all Technical Developments, we reserve the right to amend details given in this Specification. Cochran Ltd, Newbie Works, Annan, Dumfries & Galloway DG12 5QU Page 11 of 11