T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

Similar documents
HP970 and TP970 Series Standard Covers and Accessories

T7300F Series 2000 Commercial Microelectronic Conventional or Heat Pump Thermostat

T8524 Deluxe Electronic Thermostat

TG509, TG510, TG511, TG512 Versaguard Universal Thermostat Guards

T7100D Microelectronic Conventional Thermostat

T8011R Programmable Heat Pump Thermostat

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

C6097A,B Pressure Switches

T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

CONTROLS THERMOSTATS Bulletin No November 2001 Supersedes September 2001 INNOVATOR PROGRAMMABLE THERMOSTATS ENGINEERING DATA

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats

T7200D,E Series 2000 Commercial Microelectronic Thermostats

Installation and Advanced Programming Instructions. HP8211-1RJ and HP8321-1RJ Heat Pump Thermostats

Commercial Touchscreen Thermostat

Document # R01

Owner s Manual. Digital Thermostat. Heat/Cool & Heat Pump 7-Day Programmable S1-THEM22P7S COMMERCIAL. Model HVAC SERVICE PARTS

T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS

T6984F,G Electronic Floating Control Thermostats

F25F Media Air Cleaner

DAY/TIME Button: Selects hour, minute and day setting.

1 For All Programmable Digital Thermostat

DAY/TIME Button: Selects hour, minute and day setting.

CP CP

RA889A Switching Relay

Q7300L Series 2000 Commercial Thermostat Subbases

Installer Guide. WARNING Important Safety Information. 1 Specifications

T6984 A,D,E Electronic Floating Control Thermostats

Honeywell/36. Programmable Thermostat OWNER S GUIDE

T8011F Flush Mount Programmable Heat PumpThermostat OWNER S GUIDE

OWNER S MANUAL. Part Number P CONTENTS

Programmable Digital Thermostat

OWNER S MANUAL. Part Number P

T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat

T6590 Series FAN-COIL CONTROLLER FEATURES APPLICATIONS PRODUCT DATA

Owner s Manual. Part Number 33CS250-01

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

T6590 Series FAN-COIL CONTROLLER

T8624D Chronotherm IV Deluxe Programmable Multistage Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

T-32-TS Touchscreen Thermostat. Installation Manual

T8611M Deluxe Programmable Heat Pump Thermostats

Auto-Changeover: Cool Setpoint: Deadband: Dehumidify: Differential: Heat Setpoint: Humidify: Icon: Mode: Non-Programmable Thermostat:

Installer Guide. WARNING Important Safety Information. 1 Specifications

7-Day. Digital Thermostat. residential. & 2-cool

Safety & Installation Instructions

T8600D Chronotherm IV Deluxe Programmable Thermostats

Programmable Load Management Thermostat

Deluxe Programmable Heat Pump Thermostat T8611M

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

ATC32U03 igate Communicating, Programmable Thermostat

OWNER S MANUAL. Part Number P RF

OWNER S MANUAL Venstar Inc. 08/07

Honeywell CT3550 PROGRAMMABLE THERMOSTAT. Table of Contents OWNER S GUIDE

MagicStat CT3300 Programmable Thermostat

Owner s Manual. Part Number 33CS250-RC

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat.

I2:00 Mo MODEL TSTATBBPB501 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

T8602C Chronotherm IV Deluxe Programmable Thermostats

Carrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad

Auto-Changeover: A mode in which the thermostat will turn on the heating or cooling based on room temperature demand.

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

CT2800 Programmable Thermostat

Owner s Manual. Part Number 33CS250-FS and 33CS220-FS

Deluxe Programmable Thermostats

OPERATING MANUAL. Need Help? This manual covers: T955WH Wireless Thermostat System. Table of Contents

MODEL TSTAT THERMOSTATS THERMIDISTAT TM CONTROL BUILDER S MODEL THERMOSTAT FEATURES/BENEFITS NON-PROGRAMMABLE THERMOSTAT

Must be installed by a trained, experienced technician

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

HEAT HEAT HEAT COOL COOL

PerFormance Pro t4900 school series InstallatIon GUIDe

T855S. Caution. Page. Table of Contents Table of Contents Thermostat Operation Thermostat Quick Reference Programming Features Warranty Information

T8131C Programmable Thermostat OWNER S GUIDE

HEAT COOL. Meets Commercial California Title 24

MODEL TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

1 For All Programmable Digital Thermostat. Meets Residential California Title 24

Installation Instructions

ATC32U01 igate Communicating, Programmable Thermostat

MODEL TSTAT THERMOSTATS THERMIDISTAT TM CONTROL ELECTRO-MECHANICAL THERMOSTATS FEATURES/BENEFITS NON-PROGRAMMABLE THERMOSTAT

SC Installation, Operation & Application Guide

5+2 Day. up to HEAT COOL

H1008A,D Automatic Humidity Controls

Comfort System T-21-P Touchscreen Thermostat Installation Manual

CR7075 Two-Stage Lighting Controller

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

OPERATING MANUAL. Need Help? This manual covers the following models: T915. Table of Contents

Owner s Manual. Part Number 33CSCPACHP-01

Installation, Start-Up, and Operating Instructions

CAUTION: ELECTRICAL HAZARD

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

Owner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON

Microelectronic Programmable Thermostat Owner s Manual. 1 J.H Form Number

Product Manual SZ1022/SZ1031/SZ1035/

EL-TSTAT-8820 Safety & Installation Instructions

Product Manual SZ1009

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION

T4700 Chronotherm Electronic Programmable Line Voltage Thermostat OWNER S GUIDE

Transcription:

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat 1.0 GENERAL 1.1 Overview GUIDE SPECIFICATION The contractor shall furnish, install, and place in operating condition an HVAC control system described herein. All units shall be located in accordance with the plans. 1.2 Type of System 1.2.1 System Requirements a. Control up to three heating and two cooling stages for heat pump or three heating and three cooling stages for gas heat, electric heat or compressor cooling applications. b. Permit seven day programming. c. Provide two occupied and two unoccupied periods per day. d. Offer automatic heat/cool changeover with 2 F minimum deadband. e. Provide override capability for a 1, 3, 8 or 12 hour period. f. Include a comfort adjust feature to modify setpoints for the override duration. g. Provide Proportional plus Integral (P + I) temperature control. h. Permit automatic or manual changeover between heating and cooling setpoints. i. Display room temperature in F, C or no room temperature display. j. Display time in 12 or 14 hour clock format. k. Disable system and fan selections so both are in AUTO continuously. l. Use multiple remote sensors (optional). m. Use both local and remote temperature sensor (optional). n. Use in conjunction with an economizer (optional). o. Setpoint range stops for lowest cooling setpoint temperature and highest heating setpoint temperature (optional). p. Permit deadband between heating and cooling setpoints to be adjustable between 2 F and 10 F (optional). q. Permit extended fan operation after calls for heating or cooling are completed (optional). 1.2.2 System Components 1.3 Codes and Standards 1.4 Wiring a. Seven day programmable thermostat. b. Subbase. c. Duct mount return air sensor (optional). d. Wall mount sensor (optional). e. Discharge air sensor (optional). 1.3.1 The system shall comply with applicable provisions of ASHRAE 90-75. 1.3.2 These specifications are based on equipment from Honeywell to set a standard for design and quality. 1.4.1 All wiring meets National Electrical Codes and local electrical codes. U.S. Registered Trademark Copyright 1997 Honeywell Inc. All Rights Reserved 63-4364-1

1.5 Testing Guarantee Service 1.5.1 Prior to installation, the contractor shall provide copies of submittals. 1.5.2 The contractor is responsible for assuring that conduit and wire quantity, size, and type are suitable for the equipment supplied. 1.5.3 Upon completion, the contractor shall conduct a total system test for the owner and engineer. 1.5.4 All components, parts, and assemblies supplied by the manufacturer shall be guaranteed against defects in materials and workmanship for 12 months. Warranty service shall be performed by the contractor. 2.0 SEQUENCE OF OPERATIONS The heating and cooling setpoints shall be individually adjustable for both the occupied and unoccupied periods. The thermostat shall have a minimum deadband of 2 F (no mechanical heating or cooling shall operate within this deadband). Space temperature deviation above the cooling setpoint or below the heating setpoint shall generate a demand signal to control the system as follows. 2.1 Heating 2.1.1 The thermostat shall control the heating output based on the demand signal communicated from the thermostat program, taking into account both space temperature deviation (proportional error) and the duration of that temperature deviation (integral error). 2.1.2 The thermostat shall energize heating equipment when space temperature falls below heating setpoint. 2.1.3 In heat pump applications, auxiliary heat shall be controlled at 2 F below heating setpoint. 2.2 Cooling 2.2.1 The thermostat shall control the cooling output based on the demand signal communicated from the thermostat program, taking into account both space temperature deviation (proportional error) and the duration of that temperature deviation (integral error). 2.2.2 The thermostat shall energize cooling equipment when space temperature exceeds cooling setpoint. 2.2.3 A solid state enthalpy changeover control shall determine the capability of the outdoor air to provide free cooling (optional). The system shall operate as follows: a. Free Cooling Available From Outdoor Air: On a call for cooling, the system shall enable the economizer to provide free cooling. If this does not meet the space demand, the system shall call for mechanical cooling to satisfy the programmed setpoint. b. Free Cooling Not Available From Outdoor Air: On a call for cooling, the system shall hold the economizer to minimum position and cooling shall be energized to satisfy the programmed setpoint. 2.3 Economizer Interface The auxiliary relay contacts of the subbase shall be connected to the economizer s minimum position potentiometer. 2.3.1 Occupied Period: The auxiliary relay contact will close, allowing the economizer to operate normally and be available for free cooling if outdoor conditions permit. 2.3.2 Unoccupied Periods: The auxiliary relay contact will open, defeating the economizer minimum position. 2.4 Heating Setback and Cooling Setup Initiation of heating setback or cooling setup for each of 7 days shall be provided by a programmed time schedule manually entered into the thermostat. When all or a portion of a manually programmed schedule is unavailable, the thermostat shall control to the default program as follows: 63-4364 1 2

Table Of Default Program Occupied Unoccupied Heating Setpoints 70 F (21 C) 55 F (13 C) Cooling Setpoints 78 F (26 C) 90 F (32 C) Start Times 8:00 am 10:00 pm 2.5 Setpoint Recovery from Unoccupied to Occupied The thermostat shall employ Intelligent Recovery. This shall select the optimum time to begin building warm up or cool down based on setpoints and occupied program as follows: 2.5.1 Heat pump: 5 F per hour in heating and cooling. 2.5.2 Conventional heat/cool: 3 F per hour in heating. 5 F per hour in cooling. 2.6 Fan Operation Fan operation shall be selectable as follows: 2.6.1 Heat Pump Applications a. Intermittent: fan is energized with calls for heating or cooling in the occupied and unoccupied periods. b. Continuous Occupied: fan is energized continuously in the occupied periods and energized with calls for heating and calls for cooling in the unoccupied periods. c. Continuous Recovery: fan is energized continuously in the occupied periods and in the recovery mode. Fan is also energized with calls for heating and calls for cooling in the unoccupied periods. 2.6.2 Conventional Heat/Cool Applications a. Intermittent: fan is energized with calls for heating (optional) or cooling in the occupied and unoccupied periods. b. Continuous Occupied: fan is energized continuously in the occupied periods and energized with calls for heating (optional) and calls for cooling in the unoccupied periods. c. Continuous Recovery: fan is energized continuously in the occupied periods and in the recovery mode. Fan is also energized with calls for heating (optional) and calls for cooling in the unoccupied periods. 2.7 Heating and Cooling Operation Minimum On and Off Times The thermostat shall incorporate a program to maintain minimum-stage operation in both the heating and cooling: 2.7.1 Heat Pump Applications a. Cooling: 2 minutes on and 4 minutes off b. Heating: 2 minutes on and 4 minutes off 2.7.2 Conventional Heat/Cool Applications 2.8 Power Interruption a. Cooling: 2 minutes on and 4 minutes off b. Heating: 2 minutes on and 4 minutes off The system shall cycle off and provide timed restaging of heating or cooling equipment upon restoration of power. The restaging operation shall occur according to minimum stage operation times incorporated in the thermostat. A power interruption is enunciated by a blank LCD display. 2.8.1 During a power interruption less than 2 hours, the thermostat retains all programmed occupied and unoccupied start times and temperatures as well as the present time and day. 2.8.2 During a power interruption greater than 2 hours, the thermostat retains all programmed occupied and unoccupied start times and temperatures. Only the present time and day will need to be reprogrammed. 3 63-4364 1

2.9 Calibration 2.9.1 No calibration and no adjustment shall be required for mixed air temperature, throttling range, reset ratio, band width, or discharge air temperature. 2.9.2 Temperature setting displayed on thermostat shall be adjustable within +/-3 F of measured room temperature (optional). 2.10 Security Two levels of security shall exist: 2.10.1 A keypad lockout switch located on the back of the thermostat shall allow for three types of keypad lockout. a. Lock out all keys on the thermostat. b. Lock out all keys on the thermostat except System and Fan settings, temporary setpoint adjustments, and clock and day adjustments. c. Lock out thermostat installer setup mode only. 2.10.2 Thermostat shall allow for door to be locked by use of two Allen head screws to lock the cover and not allow access to the keypad. 2.11 Overrides Temperature setpoints can be overridden in three ways: 2.11.1 Thermostat shall allow for a 1, 3, 8 or 12 hour timed override from unoccupied setpoint to occupied setpoint from the thermostat keypad. In addition the thermostat shall allow for the adjustment of the occupied setpoint during the timed override from the keypad. 2.11.2 Thermostat shall allow for a 1, 3, 8 or 12 hour timed override from unoccupied setpoint to occupied setpoint from a remote sensor with a temporary occupied key (optional). In addition the thermostat shall allow for the adjustment of the occupied setpoint during the timed override from a remote sensor with warmer/cooler keys (optional). 2.11.3 Thermostat shall allow for a continuous override to the unoccupied setpoint from the thermostat keypad. 63-4364 1 4

3.0 MAJOR EQUIPMENT Model Number Description Features T7300F2002 T7300F2010 Q7300A2008 Q7300A2016 Q7300A2040 Q7300A2057 Q7300C2004 Q7300C2012 Q7300C2053 Q7300D2002 Q7300D2010 Q7300G2005 Q7300L2004 thermostat; taupe color. thermostat; taupe color. 7-day programming 2 occupied and 2 unoccupied periods per day System and fan setting fixed to AUTO only 7-day programming 2 occupied and 2 unoccupied periods per day Selectable for automatic or manual changeover 1-heat/1-cool applications 2-heat/2-cool applications 2-heat/1-cool applications 2-heat/2-cool applications Includes O and B terminals for changeover control 2-heat/1-cool heat pump applications O and B terminals available for changeover control. 2-heat/2-cool heat pump applications O and B terminals available for changeover control. 3-heat/2-cool heat pump applications O and B terminals available for changeover control. 3-heat/2-cool heat pump applications 2-heat/1-cool heat pump applications 3-heat/3-cool applications Used with ML7984 Valve Actuator in 2-heat/1-cool applications Two speed fan capability Auxiliary dry contacts for damper control during occupied mode Auxiliary dry contacts for water pump interlock during heat mode 5 63-4364 1

4.0 OPTIONS 4.1 Remote Temperature Sensors 4.1.1 T7022A1022 Duct Mount Return Air Sensor (continuous fan required). 4.1.2 T7047C2007 Remote Space Sensor. 4.1.3 T7047G2008 Remote Space Sensor (use with one-half of an averaging sensor network). 4.1.4 T7147A2000 Remote Space Sensor and Override Module. 4.1.5 T7147A2018 Remote Space Sensor and Override Module with WARMER/COOLER switches. 4.2 System Accessories 4.2.1 T675A Remote Bulb Temperature Control, low ambient compressor lockout. 4.2.2 W859F Economizer Control Packages. 4.2.3 W7459 Solid State Economizer Control Packages. 4.2.4 M7514 Damper Actuators. 4.2.5 C7400 Solid State Enthalpy Sensor. 4.2.6 R8222 Switching Relay. 4.2.7 W950 Status Panels. 4.2.8 ML7984 Direct Coupled Valve Actuator. 63-4364 1 6

7 63-4364

Home and Building Control Home and Building Control Honeywell Asia Pacific Inc. Honeywell Inc. Honeywell Limited-Honeywell Limitée Room 3213-3225 Honeywell Plaza 155 Gordon Baker Road Sun Hung Kai Centre P. O. Box 524 North York, Ontario No. 30 Harbour Road Minneapolis, MN 55408-0524 M2H 3N7 Wanchai Hong Kong Honeywell Latin American Division Honeywell Europe S.A. Miami Lakes Headquarters 3 Avenue du Bourget 14505 Commerce Way Suite 500 1140 Brussels Miami Lakes FL 33016 Belgium 63-4364 1 J.H. Rev. 6-97 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. Helping You Control Your World