Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Similar documents
Public Comment No. 22-NFPA [ New Section after 1.4 ] Statement of Problem and Substantiation for Public Comment

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

CITY OF PASADENA FIRE DEPARTMENT

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

FIRE SPRINKLER SYSTEMS POLICY

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

FIRE SPRINKLER SYSTEMS POLICY

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Fire Sprinkler System Design and Installation Requirements

Design & Construction Standards, Revised January

Center for Life Safety Education

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

PLAN REVIEW CHECKLIST

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

SECTION WET-PIPE SPRINKLER SYSTEMS

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

New Construction Fire Inspection Process

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

HIGH-RISE RETROFIT ORDINANCES - NO and NO


Annual Water-Based Fire Protection Systems Inspection

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Winnipeg Fire Department Fire Prevention Branch

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Changes in NFPA

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

INITIAL FIRE SAFETY ASSESSMENT

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

MONTECITO FIRE PROTECTION DISTRICT

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Sprinkler Permit Applications

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS

Slide 2 NFPA 25: 2017

WORKING DRAFT OF COMMITTEE MEETING OUTPUT


Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Sprinkler Standards Proposed Technical Changes

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Committee Input No. 60-NFPA [ Sections , ]

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

Second Revision No. 2-NFPA [ Section No ]

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

2. Welding Materials and Procedures shall conform to the ASME Code.

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

CHAPTER 7 ALTERATIONS LEVEL

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD



Environmental Health & Safety

Fire Sprinkler Submittal Requirements and Acceptance Testing

Public Comment No. 20-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

SAF-BCF SECOND REVISIONS WITH STATEMENTS

DIVISION 21 FIRE SUPPRESSION

FIRE & LIFE SAFTEY STANDARD

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

Committee on NFPA 51A

El Reno Fire Department Fire Alarm Plan Review Worksheet

INITIAL FIRE SAFETY ASSESSMENT

Western Michigan University Facilities Management Engineering Division

Design & Construction Standards, Revised January

FIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

DIVISION 21 - FIRE SUPPRESSION

Changes for the New Edition. Senior Engineer, NFPA NFPA

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

NFPA Edition Update

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

Public Comment No. 16-NFPA 13D-2014 [ Section No ]

WEST VIRGINIA UNIVERSITY

First Revision No NFPA [ Section No ]

Transcription:

Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this standard. 1.4.1 Technical documentation shall be submitted to the authority having jurisdiction to demonstrate equivalency. 1.4.2 The system, method, or device shall be approved for the intended purpose by the authority having jurisdiction. Supplemental Information File Name New_Annex_A.1.4.docx Description Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Wed Apr 08 13:10:45 EDT 2015 Committee Statement: Response Message: It is not the intent that portions of a future standard be selectively applied, only a complete edition of that future standard. See new annex A.1.4. Public Comment No. 22-NFPA 14-2014 [New Section after 1.4] of 42 5/14/2015 2:39 PM

A.1.4 It is the intent of the Committee to recognize that future editions of this standard are a further refinement of this edition and earlier editions. The changes in future editions will reflect the continuing input of the fire protection community in its attempt to meet the purpose stated in this standard. Compliance with all requirements of a future edition could be considered as providing an equivalent level of system integrity and performance of the system.

of 42 5/14/2015 2:39 PM Second Revision No. 22-NFPA 14-2015 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition. NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016 edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2014 edition. NFPA 101, Life Safety Code, 2015 edition. NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations, 2013 edition. NFPA 1002, Standard for Fire Apparatus Driver/Operator Professional Qualifications, 2009 2014 edition. NFPA 5000, Building Construction and Safety Code, 2015 edition. Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:27:28 EDT 2015 : Editorial revision. Response Message:

Second Revision No. 17-NFPA 14-2015 [ New Section after 3.3.3.2 ] 3.3.4 Construction Types. 3.3.4.1 Type I and Type II Construction. Those types in which the fire walls, structural elements, walls, arches, floors, and roofs are of approved noncombustible or limited-combustible materials. 3.3.4.2 Type III Construction. That type in which exterior walls and structural elements that are portions of exterior walls are of approved noncombustible or limited-combustible materials and in which fire walls, interior structural elements, walls, arches, floors, and roofs are entirely or partially of wood of smaller dimensions than required for Type IV construction or are of approved noncombustible, limited-combustible, or other approved combustible materials. 3.3.4.3 Type IV Construction. That type in which fire walls, exterior walls, and interior bearing walls and structural elements that are portions of such walls are of approved noncombustible or limited-combustible materials. Other interior structural elements, arches, floors, and roofs are constructed of solid or laminated wood or crosslaminated timber without concealed spaces within allowable dimensions of the building code. 3.3.4.4 Type V Construction. That type in which structural elements walls, arches, floors, and roofs are entirely or partially of wood or other approved material. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Wed Apr 08 10:48:45 EDT 2015 Committee Statement: Response Message: The definitions for construction types has been added to aid in the application of section 6.1..2. of 42 5/14/2015 2:39 PM

of 42 5/14/2015 2:39 PM Second Revision No. 2-NFPA 14-2015 [ Section No. 4.1.4 ] 4.1.4 The materials or devices listing instructions shall identify and specify the existing system components, including the fluids conveyed, with which the newly listed materials, devices, or components are compatible. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 11:54:18 EDT 2015 Committee Statement: Delete this section. Compatibility is a complex subject that cannot be codified in a single section. The majority of the issues that the industry has encountered in regards to compatibility relate to CPVC. NFPA 13 has added language and the labs are working towards some compatibility protocols. NFPA 14 should wait to add compatibility language once the 13 Committee and the labs have landed in a more defined place. Response Message: Public Comment No. 4-NFPA 14-2014 [Section No. 4.1.4]

of 42 5/14/2015 2:39 PM Second Revision No. 23-NFPA 14-2015 [ Section No. 4.4.2.4.2 ] 4.4.2.4.2 The minimum throat thickness shall be not less than the thickness of the pipe, the thickness of the welding fitting, or 3 16 in. (4.8 4.5 mm), whichever is least. [13:6.5.2.4.2] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:34:08 EDT 2015 : Editorial revision. Response Message:

of 42 5/14/2015 2:39 PM Second Revision No. 24-NFPA 14-2015 [ Section No. 5.2.1.1 ] 5.2.1.1 Pressure Gauges. Approved pressure gauges conforming in accordance with Section 5.5 shall be connected as follows: (1) On the water side and air side of the dry pipe valve (2) At the air pump supplying the air receiver where one is provided (3) At the air receiver where one is provided (4) In each independent pipe from air supply to dry pipe system (5) At quick-opening devices [13:7.2.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:37:09 EDT 2015 : Editorial revision. Response Message:

of 42 5/14/2015 2:39 PM Second Revision No. 25-NFPA 14-2015 [ Section No. 5.2.1.4.3.1 ] 5.2.1.4.3.1 Connection pipe from the air supply to the dry pipe valve shall not be less than 1 2 in. (15 mm) in diameter and shall enter the system above the priming water level of the dry pipe valve. [13:7.2.6.4.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:40:26 EDT 2015 : Editorial revision. Response Message:

of 42 5/14/2015 2:39 PM Second Revision No. 26-NFPA 14-2015 [ Section No. 5.2.1.4.3.2 ] 5.2.1.4.3.2 A check valve shall be installed in this the air line filling connection, and a listed or approved shutoff valve of either the renewable disc type or ball valve type shall be installed on the supply side of this check valve and shall remain closed unless filling the system. [13:7.2.6.4.2] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:42:17 EDT 2015 : Editorial revision. Response Message:

of 42 5/14/2015 2:39 PM Second Revision No. 27-NFPA 14-2015 [ Section No. 5.2.1.4.6 ] 5.2.1.4.6 Where the air compressor supplying the dry pipe system has a capacity less than 5.5 ft 3 /min (156 160 L/min) at 10 psi (0.7 bar), no an air receiver or air maintenance device shall not be required. [13:7.2.6.6.2] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:45:29 EDT 2015 : Editorial revision. Response Message:

0 of 42 5/14/2015 2:39 PM Second Revision No. 28-NFPA 14-2015 [ Section No. 5.2.1.4.12 ] 5.2.1.4.12 In addition to the standard hydrostatic test, an air pressure leakage test at 40 psi (2.8 2.7 bar) shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1 1 2 psi (0.1 bar) for the 24 hours shall be corrected. [13:25.2.2.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:47:53 EDT 2015 : Editorial revision. Response Message:

1 of 42 5/14/2015 2:39 PM Second Revision No. 29-NFPA 14-2015 [ Section No. 5.2.2 ] 5.2.2 Auxiliary Systems. A wet standpipe system shall be permitted to supply an auxiliary dry standpipe system, provided the water supply is capable of supplying the system demand. [ 13: 7.1.3] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 08:50:57 EDT 2015 : Editorial revision. Response Message:

Second Revision No. 21-NFPA 14-2015 [ Section No. 6.1.2 ] 6.1.2 Protection of Aboveground Piping. 6.1.2.1* Standpipe system piping shall be protected from mechanical damage and fire damage in accordance with this section. 6.1.2.2* Feed mains, standpipes, horizontal standpipes, and branch lines supplied by standpipes shall be located in enclosed exit stairways or shall be protected by a degree of fire resistance equal to that required for enclosed exit stairways in the building in which they are located Standpipe systems shall be protected in accordance with Table 6.1.2.2. Table 6.1.2.2 Protection of Aboveground Piping High - Rise Buildings Non - High - Rise Buildings Construction Type Sprinkler Protection Standpipe Horizontal a Branchline Standpipe Horizontal a Branchline I AS b N/A N/A N/A N/A I NS c N/A N/A II AS N/A N/A N/A N/A II NS N/A N/A III, IV, & V AS/NS N/A N/A Notes: a Refers to either a horizontal standpipe or the horizontal portion of any standpipe such as a feed main. b AS = fully sprinklered building in accordance with NFPA 13 c NS = nonsprinklered or partially sprinklered building 6.1.2.2.1 In buildings equipped with an approved automatic sprinkler system, horizontal standpipes, feed mains, and branch lines shall not be required to be protected. Protection shall consist of one of the following methods: (1) Enclosure in a fire-rated exit stairway (2) Enclosure in fire-rated construction with such rating equal to that of the enclosed fire rated exit stairway (3) Listed fire wrap or other insulating material applied directly to the pipe with such rating equal to that of the enclosed fire-rated exit stairway 6.1.2.2.2 Piping connecting standpipes to 1 1 2 in. (40 mm) hose connections shall not be required to be protected. Where exit stairways are not required to be enclosed in fire-rated construction, standpipe systems shall not be required to be protected. 6.1.2.2.3 Where exit stairways are not required to be enclosed in fire-rated construction, standpipe systems shall be permitted to be installed without the fire resistance required by 6.1.2.2 Class II standpipe systems are not required to be protected. 6.1.2.2.4 Where additional standpipes are needed to meet travel distance requirements in non-high-rise buildings, protection of piping is not required. 6.1.2.2.5 Seismic bracing, where required, shall be in accordance with NFPA 13. 2 of 42 5/14/2015 2:39 PM

6.1.2.2.6 Piping subject to mechanical damage shall be protected by steel posts, concrete barriers, or other approved means. 6.1.2.3 Where standpipe system piping that is normally filled with water passes through an area subject to freezing temperatures, it shall be protected to maintain the temperature of the water in the piping between 40 F and 120 F (4.4 C and 48.9 C). 6.1.2.3.1 Antifreeze solutions shall not be used to protect standpipe system piping from freezing. 6.1.2.3.2 Listed heat tracing shall be permitted to be used for protection from freezing. 6.1.2.3.2.1 Heat tracing shall be installed and insulated in accordance with the manufacturer s specifications. 6.1.2.3.2.2* Where heat tracing is utilized, it shall be specifically listed for use on fire suppression systems. 6.1.2.3.2.3 Where heat tracing systems are used, they shall be supervised by one of the following methods: (1) Central station, proprietary, or remote station signaling service (2) Local signaling service that will cause a signal at a constantly attended location 6.1.2.4 Where corrosive conditions exist or piping is exposed to the weather, corrosion-resistant types of pipe, tube, fittings, and hangers or protective corrosion-resistive coatings shall be used. 6.1.2.5 Where standpipe systems are required to be protected against damage from earthquakes, standpipe systems shall be protected in accordance with NFPA 13. Supplemental Information File Name NFPA_14_Protection_of_Pipe_task_Group_Draft_Final_Report_-_1.docx Description Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Wed Apr 08 13:47:37 EDT 2015 Committee Statement: Response Message: Based on committee input #87 the task group on protection of pipe provided the new attached language which was reviewed and agreed upon by the technical committee on standpipes at the 2nd draft meeting. Clarification for protection of was necessary in order to provide under what circumstances standpipe system piping requires protection and when it does not. 3 of 42 5/14/2015 2:39 PM

Final Report - Protection of Pipe Task Group Replace Section 6.1.2 with text as shown below. 6.1.2 Protection of Aboveground Piping. 6.1.2.1* Standpipe system piping shall be protected from mechanical and fire damage in accordance with this section. A.6.1.2.1 Standpipes should not be installed in non-sprinklered areas of combustible construction. 6.1.2.2* Standpipe systems shall be protected in accordance with Table 6.1.2.2. A.6.1.2.2. Where pipes that supply combined systems in areas or buildings that are sprinklered, or are installed in non-sprinklered, combustible buildings or areas the piping should be protected. Protection of pipe should also be provided in any area of a structure or building that poses a degree of hazard greater than that normal to the general occupancy of the building or structure. This includes areas for the storage or use of combustibles or flammables; toxic, noxious, or corrosive materials; and heatproducing appliances. Construction Type Table 6.1.2.2 - Protection of Aboveground Piping Sprinkler Protection High Rise Non High Rise Standpipe Horizontal 1 Branchline Standpipe Horizontal 1 Branchline I AS 2 N/A N/A N/A N/A I NS 3 N/A N/A II AS N/A N/A N/A N/A II NS N/A N/A III, IV & V AS / NS N/A N/A 1 - Refers to either a horizontal standpipe or the horizontal portion of any standpipe such as a feed main. 2 AS = fully sprinklered building in accordance with NFPA 13 3 NS = non sprinklered or partially sprinklered building 6.1.2.2.1 Protection shall consist of one of the following methods: a.) Enclosure in a fire rated exit stairway. b.) Enclosure in fire rated construction with such rating equal to that of the enclosed fire rated exit stairway. c.) Listed fire wrap or other insulating material applied directly to the pipe with such rating equal to that of the enclosed fire rated exit stairway.

Final Report - Protection of Pipe Task Group 6.1.2.2.2 Where exit stairways are not required to be enclosed in fire rated construction, standpipe systems shall not be required to be protected. 6.1.2.2.3 Class II standpipe systems are not required to be protected. 6.1.2.2.4 Where additional standpipes are needed to meet travel distance requirements in non-high rise buildings, protection of piping is not required. 6.1.2.2.5 Seismic bracing, where required, shall be in accordance with NFPA 13. 6.1.2.2.6 Piping subject to mechanical damage shall be protected by steel posts, concrete barriers or other approved means. Remainder of Section 6.1 is unchanged.

4 of 42 5/14/2015 2:39 PM Second Revision No. 3-NFPA 14-2015 [ Section No. 6.3.3 ] 6.3.3 Listed indicating-type valves shall be provided at the standpipe for controlling branch lines where the distance to the remote hose station exceeds 20 40 ft (6 12 m) measured along the pipe. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 12:08:06 EDT 2015 Committee Statement: On horizontal standpipe systems in a mall, the 20'-0" limitation would be too restrictive and this change would require control valves for every hose valve. Granted the 40' number is arbitrary but I believe more realistic. Response Message: Public Comment No. 5-NFPA 14-2014 [Section No. 6.3.3]

5 of 42 5/14/2015 2:39 PM Second Revision No. 18-NFPA 14-2015 [ New Section after 6.3.6.1.3 ] 6.3.6.1.3.1 The location of the T-wrench shall be acceptable to the AHJ. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Wed Apr 08 11:54:00 EDT 2015 : Moved requirement to separate section. Renumber 6.3.6.1.3.1 to 6.3.6.1.3.2. Response Message: Public Comment No. 7-NFPA 14-2014 [New Section after 6.3.6.1.3]

6 of 42 5/14/2015 2:39 PM Second Revision No. 19-NFPA 14-2015 [ Section No. 6.3.6.1.3 [Excluding any Sub-Sections] ] Where a post-indicator valve cannot be used, an underground valve with an approved roadway box, complete with T-wrench and where acceptable to the AHJ, shall wrench, shall be permitted. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Wed Apr 08 11:54:22 EDT 2015 Committee Statement: Response Message: Added a space (editorial) and removed language in regards to the AHJ approval of the wrench location. Another comment will add that language as a subsection Public Comment No. 6-NFPA 14-2014 [Section No. 6.3.6.1.3 [Excluding any Sub-Sections]]

Second Revision No. 5-NFPA 14-2015 [ Section No. 6.4.2 ] 6.4.2 A listed check valve shall be installed as near as practicable to the point where the fire department connection piping connects to the system main piping in each fire department connection and shall be located in an accessible location. [ 13: 8.17.2.5.1]. 6.4.2.1 The requirements of 6.4.2 shall apply to manual dry systems. The check valve shall be installed as close as possible to the fire department connection inlets. 6.4.2.1.1 The check valve shall be located where it is not subjected to freezing conditions. 6.4.2.2 The requirements of 6.4.2 shall apply to manual dry systems. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 12:14:43 EDT 2015 Committee Statement: In areas not subject to freezing temperatures, it is very common for the FDC check valve to be installed above ground at the FDC inlet assembly. This avoids costly underground vaults and greatly facilitates Inspection, testing, and maintenance. The proposed change better correlates with the requirements of NFPA 13 and expresses the committees intent to keep as much of the FDC piping as wet as possible. Response Message: Public Comment No. 26-NFPA 14-2014 [Section No. 6.4.2] 7 of 42 5/14/2015 2:39 PM

8 of 42 5/14/2015 2:39 PM Second Revision No. 6-NFPA 14-2015 [ Section No. 6.4.5.2.2.1 ] 6.4.5.2.2.1 The sign in 6.4.5.2.2 shall not be required when the system demand pressure is less than 150 psi (10.3 bar). Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 13:02:26 EDT 2015 Committee Statement: Since signs have a significant probability of getting lost or stolen, it is important for the firefighters to have the sign indicating the pressure required at the FDC for the standpipe system. A FDC without a sign should be indicative of only 2 conditions (1) it is an older system installed prior to the time when NFPA 14 started to require the sign, or (2) the sign is missing. An inspector upon seeing a FDC for a standpipe system without a sign can investigate as to whether or not the sign is required. For those who attempt to draw a similarity with sprinkler systems, please consider that firefighters must operate the standpipe system inside the building on floors well above ground level. The pump operator should NOT be in a position to guess what pressure to use at the FDC and wait for the firefighters to call for more pressure thereby making firefighting a trial and error operation. Response Message: Public Comment No. 27-NFPA 14-2014 [Section No. 6.4.5.2.2.1]

9 of 42 5/14/2015 2:39 PM Second Revision No. 7-NFPA 14-2015 [ Section No. 7.3.2.2.1 [Excluding any Sub-Sections] ] Hose connections on one side of a horizontal exit shall not be required where another outlet on that side of the horizontal exit can reach the portions of the building on the other side of the Where all floor areas are reachable from an exit stairway hose connection on the same side of a horizontal exit within the distances required by 7.3.2.2.1.1 or 7.3.2.2.1.2that would have been protected by the outlet that was as applicable, the hose connection on the other side of the horizontal exit shall be permitted to be omitted. Supplemental Information File Name A.7.3.2.2.1_2016_Horizontal_Exit.pdf Description Figure A.7.3.2.2.1 Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 13:23:17 EDT 2015 Committee Statement: Response Message: The attached language is proposed to correlate NFPA 14 with the IBC. As currently written, NFPA 14 is opposite of the building code. A revised annex diagram is part of this change as well. Public Comment No. 23-NFPA 14-2014 [Section No. 7.3.2.2.1 [Excluding any Sub-Sections]]

0 of 42 5/14/2015 2:39 PM Second Revision No. 8-NFPA 14-2015 [ Section No. 7.3.2.5 ] 7.3.2.5* A single hose connection shall be permitted to be installed in the open corridor or open breezeway between open stairs that are not greater than 75 ft (23 m) apart. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 13:32:54 EDT 2015 Committee Statement: The language has been modified to indicate that the corridors and breezeways are open. The location of the hose valve has been clearly identified in the addition of annex language from PC#17. Fire operations will utilize the standpipe outlet on the level below the fire floor. Response Message: Public Comment No. 25-NFPA 14-2014 [Section No. 7.3.2.5]

1 of 42 5/14/2015 2:39 PM Second Revision No. 9-NFPA 14-2015 [ Section No. 7.6.2 [Excluding any Sub-Sections] ] Standpipes that are part of a combined system in a building that is partially sprinklered shall be at least 6 in. (150 mm) in size. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 13:57:13 EDT 2015 : This modification is based on the Committee Rejection Statement for PI #96. Response Message: Public Comment No. 9-NFPA 14-2014 [Section No. 7.6.2 [Excluding any Sub-Sections]]

2 of 42 5/14/2015 2:39 PM Second Revision No. 30-NFPA 14-2015 [ Section No. 8.3.1.5 ] 8.3.1.5 Valves. Specific friction loss values or equivalent pipe lengths for alarm valves, dry pipe valves, deluge valves, strainers, pressure-regulating device, backflow preventer, and other devices shall be made available to the authority having jurisdiction. [13:14 23.4.3.3] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 09:01:02 EDT 2015 : Editorial revision. Response Message:

3 of 42 5/14/2015 2:39 PM Second Revision No. 10-NFPA 14-2015 [ Section No. 10.1 [Excluding any Sub-Sections] ] The volume water flow rate and pressure of a public water supply shall be determined from waterflow test data or other approved method. [ 24: 5.1.2] Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 13:58:21 EDT 2015 : Volume uses units of gallons. The correct reference is water flow rate - gpm Response Message: Public Comment No. 28-NFPA 14-2014 [Section No. 10.1 [Excluding any Sub-Sections]]

4 of 42 5/14/2015 2:39 PM Second Revision No. 11-NFPA 14-2015 [ Section No. 11.4.1 ] 11.4.1* General. All new systems, including yard piping and fire department connection piping, shall be tested hydrostatically at not less than 200 psi (13.8 bar) or 50 psi (3.5 bar) in excess of the system working pressure, whichever is greater, and shall maintain that pressure at ±5 psi (±0.35 bar) for 2 hours. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:08:17 EDT 2015 Committee Statement: The +/- 5 psi should apply only to the hydrostatic test of the underground fire main. This is covered in 11.4.3. It is not difficult to maintain the hydrostatic test pressure without leakage for the aboveground piping portion of the standpipe system. If temperature changes result in pressure fluctuations, the test should be conducted during a time when the change in ambient temperature is minimal (i.e., avoid sunrise and sunset). Contractors who have a difficult time maintaining the hydrostatic test pressure need to improve their workmanship practices. NFPA 14 should not be a mechanism to compensate for poor workmanship practices. Response Message: Public Comment No. 19-NFPA 14-2014 [Section No. 11.4.1]

5 of 42 5/14/2015 2:39 PM Second Revision No. 12-NFPA 14-2015 [ New Section after 11.5.1 ] 11.5.1.1 The test required by 11.5.1 shall be permitted to be waived where acceptable to the AHJ. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:34:47 EDT 2015 Committee Statement: The practice of flowing the entire system demand at the remote hose locations has been in the standard a long time. While it can prove that water is getting to the roof, is it necessary? The pump(s) are required to be tested. Usually these are in locations that make disposal of the thousands of gallons of water practical. By requiring the test on the roof, that water has to go somewhere. There have been multiple occurrences of a standpipe test discharge causing a roof leader drain to fail and flooding a building out at CO. All standpipes are required to be hydraulically calculated. If plans and calculations are performed and the system is installed to those plans, why are we not trusting the math? Do we require a bucket test for the remote area of a sprinkler system? If the committee cannot bear to lose this test, they should require a permanent drain adjacent to the remote standpipe capable of handling the flow for the acceptance. Response Message: Public Comment No. 11-NFPA 14-2014 [New Section after 11.5.1]

6 of 42 5/14/2015 2:39 PM Second Revision No. 13-NFPA 14-2015 [ Section No. 11.5.2 [Excluding any Sub-Sections] ] For a manual standpipe, a fire department pumper, or portable pump of a capacity to provide the required flow and pressure shall, or other approved means shall be used to verify the system design by pumping into the fire department connection. Supplemental Information File Name New_Annex_A.11.5.2.docx Standpipe_Flow_Test_Methods.pdf Description New annex A.11.5.2 Figure A.11.5.2 Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:41:28 EDT 2015 Committee Statement: It is not always necessary to use a pump to test a standpipe system. The proposed Annex material shows 3 test methods, the last of which does not use a pump. Consider where one provides 750 gpm at 75 psi at the FDC inlet resulting in 25 psi available at the hydraulically most remote standpipe outlet. If the standpipe required 100 psi at the hose valve, then adding 75 psi to both the FDC inlet pressure (75 psi) and the remote hose valve pressure (25 psi) means that if the FDC were supplied at 150 psi (75 psi + 75 psi), then 100 psi (25 psi + 75 psi) would be available at the hose valve outlet. Relying on the hydraulic calculations to demonstrate that the standpipe system will perform as calculated is dangerous. In testing numerous standpipe systems, I have experienced from 5 psi to 20 psi additional pressure over what the hydraulic calculations indicated. Testing of the standpipe is necessary in order to provide firefighters with the proper flows to fight a fire. The standpipe system represents the last chance at effecting extinguishment of the fire. A standpipe system that fails in a fire can result in firefighter injury or death. NFPA 14 should ensure that the system performs adequately when the system is new. Consider that standpipe training conducted by many fire departments includes how to use the standpipe assuming the supply from the FDC is inoperative. Many fire departments do not trust standpipe systems because they have had many problems. Response Message: Public Comment No. 20-NFPA 14-2014 [Section No. 11.5.2 [Excluding any Sub-Sections]]

A.11.5.2. It is not always necessary to use a pump to test a standpipe system. See Figure A.11.5.2(a), Figure A.11.5.2(b), and Figure A.11.5.2(c) for examples of possible test methods. When using the method shown in Figure A.11.5.2(c) it is necessary to flow the system demand while observing the pressures at the FDC inlet and the hydraulically remote standpipe hose valve. While the standpipe test may indicate that a greater pressure is required at the FDC inlet than what was indicated in the hydraulic calculations, this is not necessarily a cause for failing the test. This greater pressure, if acceptable to the AHJ based on the ability of the fire apparatus to provide the additional pressure, needs to be incorporated into the standpipe sig required at the FDC by Section 6.4.5.2.2.

Standpipe Flow Test Methods Test with pump through FDC 250 gpm 100 psi 250 gpm 250 gpm 150 psi Figure A.11.5.2(a)

Standpipe Flow Test Methods Test by Re-Circulating Water 100 psi No Hydrant No Water Discharge In-Line Flow Meter 250 gpm 250 gpm 150 psi 250 gpm Figure A.11.5.2(b)

Standpipe Flow Test Methods Test through FDC Without Pump FDC Valve 250 gpm 250 gpm 25 psi Test 75 25 ADD 75 75 Total 150 100 Flow 750 gpm 75 psi 250 gpm 750 gpm Figure A.11.5.2(c)

7 of 42 5/14/2015 2:39 PM Second Revision No. 31-NFPA 14-2015 [ Section No. 11.5.7.4 ] 11.5.7.4 In addition to the standard hydrostatic test, an air pressure leakage test at 40 psi (2.8 2.7 bar) shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1 1 2 psi (0.1 bar) for the 24 hours shall be corrected. [13:25.2.2.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 09:36:33 EDT 2015 : Editorial revision. Response Message:

8 of 42 5/14/2015 2:39 PM Second Revision No. 14-NFPA 14-2015 [ Section No. 11.8.4 ] 11.8.4 One set of instruction manuals for all major components of the standpipe system shall be provided to the building owner. The manual shall contain the following: (1) An explanation of the operation of the component (2) Instructions Manufacturer's instructions for routine maintenance (3) Instructions Manufacturer's instructions concerning repairs (4) Parts Manufacturer's parts list and identification for serviceable components (5) A copy of the current edition of NFPA 25 Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:44:50 EDT 2015 Committee Statement: Response Message: Section 11.9 indicates that the manufacturer's instructions are to be provided. 11.8.3 would allow the contractor to provide handwritten instructions. Public Comment No. 29-NFPA 14-2014 [Section No. 11.8.4]

9 of 42 5/14/2015 2:39 PM Second Revision No. 32-NFPA 14-2015 [ Section No. 12.2 ] 12.2 Fire Department Connections. The standpipes shall be provided with conspicuously marked and readily accessible fire department connections on the outside of the building at the street level at a location approved by the local fire department and shall have at least one standard hose outlet at each floor. [241:8.7.4.2.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 09:39:49 EDT 2015 : Editorial revision. Response Message:

0 of 42 5/14/2015 2:39 PM Second Revision No. 33-NFPA 14-2015 [ Section No. A.4.4.2.4.1 ] A.4.4.2.4.1 Partial penetration welds on outlet fitting connections are considered adequate, since there is no significant load on the joint other than that caused by pressure internal to the pipe (see Figure A.4.4.2.4.1). [13: A.6.5.2.4.1] The load due to the internal pressure can be accommodated with a weld that has a conservative weld throat thickness that can be calculated as follows: where: P = rated system gauge pressure (psig psi ) D = outside diameter (OD) of the fitting (in.) [A.4.4.2.4.1] [13:A.6.5.2.4.2] For example: If you assume a pressure of 300 psig psi (21 bar) and the OD [outside diameter] of the outlet fitting of 3 in. (75 mm), the result of the thickness calculation is 0.0315 in. (0.8 mm). When compared to the minimum throat thickness of 3 16 in. (0.18 in. 5 mm ), there is a factor of more than 5 times the calculated thickness value. [13:A.6.5.2.4.2] Figure A.4.4.2.4.1 Weld Descriptions. [13:Figure A.6.5.2.4.1] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 09:42:35 EDT 2015 : Editorial revision. Response Message:

1 of 42 5/14/2015 2:39 PM Second Revision No. 34-NFPA 14-2015 [ Section No. A.5.2.1.4.2 ] A.5.2.1.4.2 The compressor should draw its air supply from within the operating criteria allowed by the manufacturer of the compressor. Air piping should not be attached to the intake of the compressor unless acceptable to the compressor manufacturer. Damage, air reduction, or reduced life expectancy can result if guidelines are not followed. [ 13: A.7.2.6.3] Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 10:11:20 EDT 2015 : Editorial revision. Response Message:

2 of 42 5/14/2015 2:39 PM Second Revision No. 15-NFPA 14-2015 [ New Section after A.7.3.2.2 ] A.7.3.2.5 Paragraph 7.3.2.1 requires that a standpipe be provided in each required exit stairwell. One arrangement that might be found in certain residential buildings is that two remotely located exit stairs provide the occupants two distinct means of egress. This section allows a single hose connection to be located anywhere between the exit stairs, provided the exit stairs are open and are located within 75 ft (23 m) of each other. (See Figure A.7.3.2.5 ). Figure A.7.3.2.5 Single Hose Valve in Open Stairs/Corridors/Breezeways. Supplemental Information

3 of 42 5/14/2015 2:39 PM File Name NFPA_14_Single_Hose_Valve_in_Open_Breezeway.pdf Description Figure A.7.3.2.5 Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:46:49 EDT 2015 Committee Statement: Response Message: This section and figure is being submitted on behalf of the Horizontal Exit task group. The task group was assigned the task to create an annex figure for section A.7.3.2.5. Public Comment No. 17-NFPA 14-2014 [New Section after A.7.3.2.2]

4 of 42 5/14/2015 2:39 PM Second Revision No. 16-NFPA 14-2015 [ Section No. A.7.10.1.2 ] A.7.10.1.2 See Section 14.4 of NFPA 13. When performing a hydraulic design, the hydraulic characteristics of each water supply need to be known. The procedure for determining the hydraulic characteristics of permanent water supplies, such as pumps, is fairly straightforward and is described in NFPA 20. The procedure for determining the hydraulic characteristics of fire apparatus supplying a standpipe system are similar. Lacking better information about local fire apparatus, a conservative design would accommodate a 1000 gpm (3785 L/min) fire department pumper performing at the level of design specifications set forth in NFPA 1901. NFPA 1901 specifies that fire department pumpers must be able to achieve three pressure/flow combinations. These are 100 percent of rated capacity at 150 psi (1034 kpa) net pump pressure, 70 percent of rated capacity at 200 psi (1379 kpa) net pump pressure, and 50 percent of rated capacity at 250 psi (1724 kpa) net pump pressure. Therefore, a 1000 gpm (3785 L/min) pumper can be expected to deliver no less than 1000 gpm (3785 L/min) at 150 psi (1034 kpa), 700 gpm (2650 L/min) at 200 psi (1379 kpa), and 500 gpm (1893 L/min) at 250 psi (1724 kpa). Residual supply pressure on the suction side of a pump from a municipal or other pressurized water supply can also be added. The 150 psi (1034 kpa) suggested pressure is also found in NFPA 13E. It also states that this is the pressure to be provided unless the sign at the fire department connection states otherwise. It is not the intent of this standard to limit the maximum pumper pressure at the fire department connection inlet for manual or automatic standpipes to 150 psi (1034 kpa). To perform a hydraulic design, one should determine the minimum required pressure and flow at the hydraulically most remote hose connection and calculate this demand back through system piping to each water supply, accumulating losses for friction and elevation changes and adding flows for additional standpipes and sprinklers at each point where such standpipes or sprinklers connect to the hydraulic design path. When considering fire apparatus as a water supply, flows are calculated from system piping through the fire department connection and back through connecting hoses to the pump. If the pressure available at each supply source exceeds a standpipe system's pressure demand at the designated flow, the design is acceptable. Otherwise, the piping design or the water supply needs to be adjusted. The intent of the standard is to require that each vertical standpipe serving two or more hose connections be capable of individually flowing 500 gpm (1893 L/min) and 250 gpm (946 L/min) at each of the two hydraulically most demanding connections at the required residual pressure. Given the requirement in 7.10.1.1.3 for the hydraulically most remote standpipe to supply this pressure and flow rate and given the minimum standpipe sizes in Section 7.6, the ability of standpipes that are not hydraulically most remote to satisfy this requirement is implicit and should not require additional hydraulic calculations. Submitter Full Name: Chad Organization: [ Not Specified ] Submittal Date: Tue Apr 07 14:49:00 EDT 2015 Committee Statement: During the first draft, the committee made it clear that even with automatic standpipes, a calculation to the fire department connection is required. Many AHJ's refer to NFPA 13E which is a recommended practice and cite section 4.3.4 and limit the maximum pressure at the FDC inlet to 150 PSI for calculation purposes. This language makes it clear that the 150 psi is not a maximum.

5 of 42 5/14/2015 2:39 PM Response Message: Public Comment No. 12-NFPA 14-2014 [Section No. A.7.10.1.2]

6 of 42 5/14/2015 2:39 PM Second Revision No. 35-NFPA 14-2015 [ Section No. A.8.2.3 ]

7 of 42 5/14/2015 2:39 PM A.8.2.3

8 of 42 5/14/2015 2:39 PM See Figure A.8.2.3(a), Figure A.8.2.3(b), Figure A.8.2.3(c), and Figure A.8.2.3(d) for copies of typical forms. Figure A.8.2.3(a) Summary Sheet. [13:23.3.5.1.2(a)] Figure A.8.2.3(b) Graph Sheet. [13:23.3.5.1.2(b)]

9 of 42 5/14/2015 2:39 PM Figure A.8.2.3(c) Supply and Node Analysis Sheet. [13:23.3.5.1.2(c)]

0 of 42 5/14/2015 2:39 PM Figure A.8.2.3(d) Detailed Worksheet. [13:23.3.5.1.2(d)]

1 of 42 5/14/2015 2:39 PM Submitter Full Name: CHAD DUFFY Organization: NATIONAL FIRE PROTECTION ASSOC Submittal Date: Tue Apr 21 14:05:30 EDT 2015

2 of 42 5/14/2015 2:39 PM : Forms are extracted from NFPA 13 and need to align with the current edition. Response Message: