DECKMA. GmbH. Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM

Similar documents
Precept Marine Control Panel Application Guide

BA AFMS3000 Operating instructions

Intelligent Security & Fire Ltd

System 800 Addressable Fire Detection & Alarm System

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

Fire Alarm System FMS3000 Installation Instructions

DICTATOR Hold-Open Systems for Hazardous Areas

CONTROL DEVICE SLIDETRONIC HD

QA16 Addressable System

Technical Manual. Level Alarm Unit CARLA & WIDS

Control Panel Engineering and Commissioning Instructions

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Product Data Sheet. Remote Terminals. Features:

BSR Addressable Fire Detection control panel. Installation operation manual

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

BS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE

Addressable and Conventional Fire Protection

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

Panel Mounted Fault Annunciator Series

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

Intelligent Security & Fire Ltd

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

compact office 24V compact office 24V Lux

Ceiling Microwave presence/absence detector 12-24V AC/DC

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Parameterisable compact fault annunciator with permanent display

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Installation, Operating and Maintenance Manual

U ser's Guide PC6010

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Input module, input/output modules

compact office 24V compact office 24V Lux

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual

M1000 Alarm Annunciator

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

FX FIRE DETECTION SYSTEM

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Key-Operated Switch GMA 41 / GMA 44 SW. Operation Manual

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Operating Manual UV Monitor UVT 18

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Insulation fault evaluator EDS460-DG

Input module, input/output module

OPERATION AND ALARM PANELS

Flame detector FD 2011 / FD 2012

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

Sita200plus. 200detectors. Single loop analogue addressable System

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

SWARCO TRAFFIC SYSTEMS GMBH. TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00

operating device LOD , 144x72mm designed for retrofit

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A..

WIO200 Water In Oil measuring instrument

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

FDOOT221, FDO221, FDT221

500-IDx Conventional Fire Detectors with Siren!

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

MANUAL Oil Level Sensor

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation.

TCM-2 Thyristor Control Module DATA SHEET

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

5, SE GÅNGHESTER,

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

FLAME AMPLIFIER MODULE 3001

EBMHS (standard & slim-line PSU)

ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42

Remote alarm indicator and test combination MK2430

Panel Mounted Fault Annunciator Series

OilSET-1000 (12 VDC)

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

1.7. Insulation fault evaluators EDS460/490 EDS461/491

EBDSPIR-PRM-LV Product Guide

Intelligent Security & Fire Ltd

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Operating Manual VMD420

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

MSM - Expansion modules

The complete conventional fire warning system

DATASHEET. Burner control unit FDA 601x

Installation / Monitoring Technique

Analogue Dimming Microwave Presence/Absence Detector

1.7. Insulation fault evaluators EDS460/490 EDS461/491

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

LAE10 LFE10. Use. Series 02

C Note! LGI16... Burner Controls. Building Technologies

Transcription:

DECKMA GmbH Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM 815.5-2 815.5-6 VERSION 03/2003 Tel.: +49 (0)4105 / 65 60 0 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 25 E-mail: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de

OPERATING INSTRUCTIONS Fire Alarm Panel 815.5-2 GL and 815.5-6 GL Type approved by Germanischer Lloyd Certificate No. 35 947-85 HH DESCRIPTION CHAPTER A. Construction 2 B. Mode of Operation 2-3-4 C. Function Test 4-5 D. Reset of Detectors with Memory 5 E. Data 5 F. Detector List 6 G. Installation Instruction 7 - Firealarmpanel flush mounting 8 - Firealarmpanel wall mounting 9 - Connections diagram 10 - GL Certificate 11 Tel.: +49 (0)4105 / 65 60 0 * DECKMA GmbH * Fax: +49 (0)4105 / 65 60 25 E-mail: info@deckma-gmbh.de * Internet: www.deckma-gmbh.de

A. C O N S T R U C T I O N The Central Cabinet is constructed for desk mounting Page.8 or wall mounting Page. 9. The central cabinet of one unit, containing: 1. Working lamp 2. Two or Six detector groups - 1 accommodation and 1 engine room or 2 accommodation of 2 engine rooms with belonging indication for fire and fault. 3. Internal acoustic sounder 4. Relay for control of fire bell, fire and fault relay with each a set of potential free change over switches. 5. Function test respectively of fire and for fault in the two detector groups. B. M O D E O F O P E R A T I O N The central cabinet is in normal state: The central cabinet is connected to primary and secondary power supply with 24 V DC rated voltage. All lamps are dark, except for the green working lamp mark "Mains". At voltage drop-out from either primary or secondary power supply the following is indicated: A. Green pilot lamp labelled "Mains" flashes B. Internal acoustic signal C. Faulty relay changes over You can reset by the push button labelled "Reset". Then: A. The internal acoustic signal stops B. Fault relay change back to normal condition The green pilot lamp does not stop flashing until both primary and secondary voltage is connected to the central cabinet and you have reset by the push-button labelled "Reset".

Mode of operation of the detector groups: The detector groups are working after the one-loop-principle where the detectors are parallel connected to the line and the line is finished with an end resistor. The end resistor determines the current of rest in the loop. If the fault has stopped the light in the yellow lamp mark "Fault" of the group in question stops, if the fault is stationary, nothing happens. The yellow fault lamp of the group in question will not stop lighting until the fault has been repaired and the button mark "Reset" has been pushed. Fire Alarm: Fire Alarm occurs when a detector has been released. At release of a detector a resistance is connected parallel on the line (parallel with the end resistor) then the current (no-signal current) will increase. Fire Alarm is indicated by: A. Internal acoustic signal B. External acoustic signal C. Fire relay changes over D. Light in the red fire lamp of the group in question You can reset by pushing the button mark "Reset", then: A. The internal acoustic signal stops B. The external acoustic signal stops C. Fire relay changes back to normal condition D. If the detector is in normal state, light in the red fire lamp of the group in question stops lighting - if the Detector is in alarm state, nothing happens. The red fire lamp of the group in question will stop lighting until the detector is in normal state and the button mark "Reset" has been pushed. If the central cabinet looses it is working voltage, the green working lamp mark "Mains" goes out.

C. F U N C T I O N T E S T Test of fire is achieved by pushing the button placed below the red fire lamp. Indication as mentioned in the passage about fire alarm. Test of fault in the detector loop is achieved by pushing the button placed below the yellow fault lamp. Normal state. A fixed current of rest passes through the loop. Both the fault and fire alarm lamps are dark. Fault Alarm If a loop is broken the current of rest ceases and the group in question will indicate "Fault". Fault is indicated by A. Internal acoustic signal B. Fault relay changes over C. Light in the yellow lamp mark "Fault" of the group in question You can see reset by pushing the button mark "Reset", then: A. The internal acoustic signal stops B. Fault relay changes back to normal condition Indication as mentioned in the passage about fault alarm. Test to fire alarm bells are achieved at the same time as test of fire is done. Test of power supply fault: Is obtained by switching-off of primary and secondary power supply of by removing primary of secondary fuse in central cabinet. D. RESET OF DETECTOR WITH ELECTRICAL MEMORY Detectors with electrical memory and which are connected with the central cabinet can be reseted by pushing the function test button "Fault" of the group in question, then te detector loop is broken and the connected detectors are reseted.

E. D A T A E1. Voltage The operating voltage is 2x 24 V DC +30% -25 % E2. Current consumption Normal state, detectors not incl. app. 100 ma Alarm state, detector and bells not incl. app. 250 ma Detector, normal state app. 0,1 ma Detector, alarm state app. 40 ma E3. Limits Max. load of fire bell output Max. number of detectors per group Max. number of man call points 2,0 A 25 pcs unlimited

F. D E T E C T O R L I S T Engine room Opt. Smoke detector Heat detector Type 130A + 143 AS Type SLR-EM+ YBM-R4M+ MBB-1 Type 215A + 143 AS Type DCD-1EM+ YBM-R4M+ MBB-1 60 C Type DCD-1REM+ YBM-R4M+ MBB-1 90 C Manual call point Type NS-CPWP WR 4072 UV-Flame Detector Type 810A + 133 AS Type 1121+1411+1421 NS DUV Accommodation Opt. Smoke detector Type 130A + 143 A Surface Type 130A + 143 UH Flushm. Type SLR-EM+ YBM-R4M. Heat detector Type 215 A + 143 A Surface Type 215 A + 143 UH Flushm. DCD-1EM+ YBM-R4M 60 C DCD-1REM+ YBM-R4M 90 C Manual call point Type NS-CP WR 2072

G. I N S T A L L A T I O N I N S T R U C T I O N Installation instruction for automatic fire alarm and fire indication system, type 815.5-6 (2) GL. 1. The central is mounted on the navigation bridge as the screw for the 2 upper holes in the cabinet are screwed in the bulkhead until approx. 3 mm from the bulkhead surface. The cabinet is "pulled" down over the screws and kept to the bulkhead by means of internal mounted plate springs. Further the cabinet is fastened with a third screw at the bottom in the middle. 2. The detector group/s is/are connected with the central cabinet; remember the end resistance at the last detector in each group; and so are fire bells and voltage supply 24 V. The central cabinet is put back into normal state. 3. The system is ready for tests, which are to be done according to the check list, see this.

Type Approval Certificate This is to certify that the undernoted product(s) has/have been tested in accordance with the relevant requirements of the GL Type Approval System. Certificate No. 3594785 HH Company DECKMA GmbH Bahnhofstraße 79 D-21224 Rosengarten-Klecken Product Description Fire Detection System Type 815.5 Environmental Category Technical Data / Range of Application C, EMC1 Power supply: 2 x 24 V DC Connection: up to 6 conventional fire detection lines Loop voltage: 24 V DC Output: 1 c/o contact each for failure and fire alarm Contact rating: 2 A 24 V DC Degree of protection: IP 42 Test Standard Guidelines for the Performance of Type Approvals, Edition 2003 Documents Manual: 815.5 Circuit diagram: 821.5A S529, 8215.5 1S525, 8215.5 2S526, 8215.5 3S527 Drawing: 8015.5 6S530, 8015.5 6S528, Test reports: DASA 478.100.94, EMV Services 01/0221-1-1, EMV Services 03/3202-1-1 Remarks None Valid until 2007-12-19 Page 1 of 1 File No. I.A.01 Hamburg, 2003-12-18 Type Approval Symbol J. Wittburg T. Huthoff This certificate is issued on the basis of "Regulations for the Performance of Type Tests, Part 0, Procedure". Internet Publication: GL-Approvals