incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

Similar documents
incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

SMOKE CONTROL - NEW DIRECTIONS

technical specification smoke venting systems

GreenJet Transfer Fans

NOVENCO CAR PARK THRUST VENTILATION SYSTEM DESCRIPTION. Pure competence in air.

Technical Information

Colt ventilation systems for car parks, loading bays and service areas

Tunnel Axial Flow Fan

Case Study 1 Underground Car Park

Emergency Extract Ventilation

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

GreenPark. GreenJet Throw Performance

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Car Park Ventilation 1

Underground carpark ventilation

Colt Car Park Ventilation Systems. Smoke Control

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

INTRODUCTION. JAU /JCC/JVC Series Jet Fans - for car park ventilation

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Tunnel Fire Dynamics and Evacuation Simulations

Sprinklers Modeling for Tunnel Road Fire Fighting

Prescriptive Requirement for Smoke Control

Design of Fire safety in Multi Occupancy Residential Accommodation

General Principles of Smoke Control

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

UNIJET CAR PARK VENTILATION SYSTEM

CARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS

and Sprinkler System in Resalat Tunnel of Tehran

Chapter 17, Initiating Devices

AXIAL & JET FANS FOR TUNNEL VENTILATION

Mechanical Smoke Extract Shaft Systems

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

TUNNEL FANS STANDARD AND HOT SMOKE

TOXIC AND FLAMMABLE GAS CLOUD DETECTORS LAYOUT OPTIMIZATION USING CFD

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Research Needs for the Fire Safety Engineering Profession

Laboratory Fume Cupboards

MECHANICAL VENTILATION

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Coal Handling and Processing. Advanced Solutions for Coal-Related Environmental Dust Control. Better Air is Our Business

JET FANS CAR PARK VENTILATION SYSTEMS F400 - F300 - F200. EN Powered smoke and heat exhaust ventilators for use in Construction Works

Delhi Metro System. Emergency and Fire Safety Measures in. - by Sanjeev Kumar & Kailash Chandra Joshi. Fire Protection & Safety

TE Powrmaster Heater Range Controlling your working environment. heating ventilation integrity

Considerations in the Design of Smoke Management Systems for Atriums

Smoke control in car parks

Case Study 1 Underground car park

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Smoke detection in hazardous areas:

Computational simulation of road tunnel fire protection by sprinklers

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

Technical Catalogue laboratory furniture system

Enclosure 4- RISK ASSESSMENT

Performance Climate Changer Next generation air handler from Trane

Mechanical smoke ventilation systems. CI/SfB 37.4 Xy

Selected Laboratory Energy Efficiency Measures

Fire Engineering in High Rise 15 November 2013

Appendix SPAIN Madrid M30-Río-TUNNEL

Effective ventilation is necessary for the comfort

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

VENTILATION DESIGNED FOR CARE HOMES

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry.

Crossrail Fire Safety Designs

Tunnel Systems. Design & Supply Metro Axial Fans. Tunnel Axial Fans. Jet Fans.Fans for Escape Tunnel System Components. Engineering Support

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

Smoke Clearance in an Underground Car Park using the Jet Fan System

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Screw Compressors AS SERIES. Capacities from: 59 to 124 cfm Pressures from: 80 to 217 psig

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

Equipment guide for local exhaust ventilation (LEV)

Introduction. Products conforming with a European Council Directive. CE marked construction products. Other regulations

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

A GUIDE TO SELECTING THE RIGHT FAN

MINIMUM TANK GAP. Greater of 3 or one-sixth of sum of adjacent tank diameters. one-half of sum of adjacent tank diameters 20

Technical Catalog laboratory furniture system

How design fires can be used in fire hazard analysis

Myth & Reality of Basement Ventilation

VENTILATION & FIRE SAFETY

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.

Welcome! Opening Remarks. FadyAbu Jamra, President of ASHRAE Qatar Oryx Chapter Mark Stevens, Executive Director, AMCA International

Unit 2 Fire Safety (Zone 2)

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Guidance on Video Smoke Detection Technology (VSD)

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Transcription:

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

Car park ventilation What are the regulations? Ventilation of car parks is important to prevent the build-up of toxic fumes and flammable gases from motor exhausts and also to clear smoke in the event of a fire. The Building Regulations specify what is required to maintain safe conditions, in particular Approved Document B and Approved Document F. Guidance is also given in BS 7346-7:2013. Why ventilate? There are broadly two methods of complying with the Building Regulations regarding ventilation and these are natural or mechanical ventilation. Whichever method is used, the required results are defined as: Smoke clearance: To provide sufficient openings for enclosed car parks to allow any smoke being produced to leave the space naturally, or if this cannot be achieved then to remove smoke via a mechanical extract system. Fume exhaust: To provide sufficient openings arranged such that a through draught at low to mid level is created to allow CO to leave the car park naturally, or if this cannot be achieved then to limit the concentration of CO within the space via a mechanical extract system.

& Natural ventilation In an ideal world, this is the preferred method of ventilating car parks as it simply requires openings to fresh air being provided to equal a percentage of the floor area of the car park. The areas to be provided are currently: 5% for ventilation of everyday vehicle pollution and smoke with at least 50% being provided between opposite faces of the building; the openings provided must be sufficient to create a through draught. 2.5% for smoke clearance only with at least 50% being provided in opposite faces of the building. If only 2.5% is provided a supplementary CO ventilation system will be required to limit the concentration of CO within the space. This method obviously relies on a path to outside being freely available, which is not usually the case in underground car parks - hence the need for mechanical extract systems.

Mechanical extract These systems use powered fans to control the build-up of CO in the car park. The regulations for fume exhaust state that the system should be capable of limiting the concentration of CO within the car park to below 30 parts per million (averaged over an eight-hour period). For smoke clearance, ten air changes per hour (the number of times the volume within the car park is extracted within one hour) should be extracted. The regulations for smoke clearance state that the system should have an extract facility which is split into two parts, each part capable of providing 50% of the required duty and extracting from both high and low level. Extract fans should be fire rated at 300 C for one hour. A standard 10ach/ hr smoke clearance system - as described in this brochure - is not applicable to deep basements (more than 10m or three storeys below ground) or for buildings with two or more basement storeys with a footprint greater than 900m 2 ; in this case the system should be designed to assist firefighters. Traditional systems These use sheet metal ductwork to transport the fumes or smoke being extracted to the external atmosphere. The ducts must be evenly distributed around the car park and also drop to low levels to provide the low level extract points. Accommodating large ducts can be problematic due to the low headroom in most car parks; low level ducts can be subject to damage from vehicles.

Jet fan systems & Otherwise known as UniJet, jet thrust, jet vent, impulse and induction systems; whereby jet fans replace ductwork and drive fumes or smoke towards extract fans - keeping pollution within acceptable levels and clearing smoke (see page 10 for an explanation of the different fan types). Developed in the Netherlands, jet fan systems originated around 15 years ago and have become increasingly popular as they overcome many of the problems associated with sheet metal ductwork. Jet fan Discharge to atmosphere Ground level Underground level 1 Underground level 2

Benefits of jet fan systems Space saving jet fan systems are more discreet and take up considerably less room than ducted ones. Energy saving they are often combined with CO detection to initiate CO control; this ensures that fans are precisely controlled to dilute pollution without running unnecessarily. Low noise because the main extract fans are relatively small and (for CO control) run at lower speeds than traditional systems, the noise generated is considerably lower. Cost saving jet fan systems cost less than a comparable ducted system, are quicker to install and easier to maintain. How they comply with the regulations In a smoke clearance system the main extract fans are sized to extract a minimum of ten air changes per hour as detailed in the Building Regulations; the jet fans are positioned to ensure that fumes and smoke are transported quickly and efficiently to the main extract points. For everyday ventilation of pollution either a CO detection system is used to limit the concentration of CO to below 30ppm (over an eight-hour period) or as an alternative the system can operate continuously at six air changes per hour.

How they work & Jet fans were originally developed for ventilating tunnels and work by propelling a small jet of air at extremely high velocity which causes surrounding air to be entrained; in a confined space like a tunnel or enclosed car park they can quickly move a large volume of gas. Each jet, impulse or induction fan has a characteristic thrust which smoke control engineers and designers use to position fans in an enclosed or underground car park, to ensure relatively even distribution of air. They are used to control zonal areas of the car park, directing airflow based on the detected location of fume or smoke build-up. On activation of the system via smoke detection, the jet fans should shut down for an agreed period of time to let the people escape (the main extract fans should activate immediately to provide 10ach/hr). jet fan Jet fan velocity profile

Designing a jet fan smoke control system By using jet fans it is possible to provide a more sophisticated system than smoke clearance which is intended to offer safe conditions for occupants escaping the car park in a fire, and to assist firefighters in locating and extinguishing the fire. The basic procedure to be followed when designing smoke control systems can be summarised as: Design for a fire: The extract rate for a smoke clearance system is relative to the size of the car park, whereas a smoke control system is designed to extract smoke for a given fire (e.g. 4MW for a car park with sprinklers or 8MW if sprinklers are not provided ) and is independent of the overall size of the car park. Guidance for the design fire size is given in BS 7346-7:2013. Develop a control philosophy: Independent control of fans is required to cater for fires occurring in different zones within the car park. Reversible jet fans are available and can be programmed to drive smoke in opposite directions dependent on the fire location. Zone the car park: The car park is divided into smoke control zones with fire zones being sacrificed in a fire, while safe conditions are maintained in adjacent zones. See diagram below. Plan view Profile view

& CFD: Computational Fluid Dynamics (CFD) is often used to help design complex smoke control systems and is a useful tool for predicting their performance. In the early days of jet fan systems CFD was often used as a sales aid by specialists to convince approving authorities that such systems were effective and it has now become strongly associated with car park ventilation, however for smoke clearance systems it is not usually required. Guidance is given in BS 7346-7:2013 and this states that as a minimum the report should be prepared stating the CFD software and version used, the boundary conditions, geometry layout and simplifying assumptions, grid specification, sensitivity analysis, results and the modelling objectives. The CFD should show temperatures and smoke spread. Results should, as a minimum, show in the horizontal plane smoke spread and temperatures at 1700mm from FFL. Modelling should always be based on the worst case scenarios.

Available fan types Jet thrust fan, jet fan, jet vent fan or impulse fan: An axial flow fan mounted within an inlet and outlet cylindrical silencer. Tested as a complete unit, jet fans can provide up to 50N of thrust. Suitable for most small to medium sized car parks. Induction fan: A centrifugal fan with an air inlet positioned beneath the body of the fan and discharging through a reduced size opening, induction fans can provide up to 100N of thrust. Careful coordination is required if a sprinkler system is used. Suitable for medium to large car parks, benefit can be achieved from the greater coverage area. Attenuation is not provided on an induction fan.

References The Building Regulations Approved Document B - Volume 2 - Buildings other than dwelling houses (2006 Edition) Approved Document F - Ventilation (2006 edition) BS 7346-7:2013 Components for smoke and heat control systems Part 7: Code of practice on functional recommendations and calculation methods for smoke and heat control systems for covered car parks

Smoke control Building automation BEMS Natural ventilation Service and software Contact us t. 08702 406 460 e. info@groupscs.co.uk w. groupscs.co.uk SCS Group Capital Business Park Parkway Cardiff CF3 2PZ SCS Group 3rd Floor 26 Finsbury Square London EC2A 1DS SCS Group Manufacturing 303 Old Barn Farm Road Woolsbridge Industrial Park Three Legged Cross Wimborne BH21 6SP t. 08702 406 460 e. enquiries@easivent.co.uk w. easivent.co.uk Easivent is part of the SCS Group, supplying high quality products via its website easivent.co.uk SCS Group Contractors guide to car park ventilation V3 April 2018