MONOBLOCK GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Similar documents
MONOBLOCK NG SERIES GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

DUOBLOCK DUAL FUEL (GAS-HEAVY OIL) BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

MONOBLOCK DUAL FUEL (GAS-LIGHT OIL) BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

MONOBLOCK HEAVY OIL BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL

HOT GAS GENERATOR INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CONDENSING BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ROOF TOP SERIES CONDENSING BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Forced draught gas burner

Indirect gas-fired air heater

CONDENSING BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Forced draught gas burner

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Light oil / kerosene burner

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS

RIELLO 40 GS/M SERIES

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Light oil burners. One stage operation

TWO STAGE HEAVY OIL BURNERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

Quest Power Electric Heat EHS 31 Pro

BGH Series Hot Surface Ignition Control

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Parts Available from

USERS MANUAL FOR GAS BOILERS

Infrared Diesel Heater

DH-Direct Fired Poultry Farm Diesel Heater

Weishaupt WG10 and WG20 gas burners LN (Low NO x ) version 2/2002 CA

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

1. GENERAL SAFETY RULES

Owner s Manual Phoenix FireBird

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

Oil burners Brûleurs fioul Stookoliebranders

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

15 20 kw kw kw

Installation & Maintenance Manual

DF400/DF600. Construction Heaters. Installation and Maintenance Manual

1 VICTRIX ZEUS Superior kw I features

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

Light oil - kerosene burner

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HOT WASHER MODEL NO: KING150

Installation/Instruction Manual

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

LOW NOx MODULATING GAS BURNERS

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

HEAT ONLY & COMBI BOILER

Gas-Gebläsebrenner Brûleur gaz à air soufflé Forced draught gas burner Gasventilatorbrander Quemador de gas de aire soplado

Installation, operating and servicing instructions

Forced draught natural gas/propane burner

A/23 MFFI - A/27 MFFI

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

INSTALLATION AND MANINTENANCE INSTRUCTIONS

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

User s Information Manual

User s Information Manual

UV Flame Supervision System

DOMESTIC HOT WATER Follow operational sequence

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual

Installation & Maintenance Manual

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

F900 SERIES BOILING PAN G9781. User, installation and servicing instructions. Read these instructions before use T REV.

Operator: Save these instructions for future use!

en Direct oil-fired space heaters HD... Operator's manual

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

EUROFLAT SERIES TYPES C... S... M...

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Operating instructions

INSTRUCTION AND MAINTENANCE MANUAL

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

User and Installation Instructions. Wall Mounted Water Boiler WMB3F/B and WMB3F/W IS435 ECN3461

User Guide Compact-7 series

USER'S INFORMATION MANUAL

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

One-Touch Dispense. Multi-temp selections. 208 F For tea, coffee, instant noodle. 194 F Keep warm around 194 F. 176 F Keep warm around 176 F.

Operating instructions

Propane Flame Projector Safety instructions and operating manual

Operator: Save these instructions for future use!

Kyung Dong Oil Boiler. Contents. 1. General Warnings Safety Warnings

Operating instructions

PVE SERIES POWER VENTER SYSTEM MANUAL

40E ELECTRIC FAN HEATER

Installer manual ELK 213 Immersion heater

PC 640 GB. Built-in cooking tables 60 Instructions for installation and use

Operator: Save these instructions for future use!

Single stage operation forced draught natural gas/propane burner

Transcription:

MONOBLOCK GAS BURNERS INSTALLATION, OPERATING AND MAINTENANCE MANUAL ONE-STAGE, TWO-STAGE AND MODULATING OPERATION ECO 1 ECO 2 ECO 30 ECO 45 www.ecostar.com.tr

DEAR USER, ECOSTAR ECO 1, ECO 2, ECO 30, ECO 45 GAS burners are prepared and manufactured according to the latest technical developments and safety rules. It is easy to use for our customers. We recommend that you read this manual and safety warnings thoroughly before the use of the device in order to ensure safe, cost effective and environmental-friendly use. If you encounter any issue that is not explained clearly in this manual or you could not understand, please contact with our service department. We thank you for choosing ECOSTAR brand. Ecostar Gas Burners are manufactured in accordance with TS EN 676 +A2 standards. This Operating Manual is an integral part of the burner and must be maintained in a plastic dossier and hung at a clearly visible place in the burner room. TERMO ISI SİSTEMLERİ SAN.VE TİC.A.Ş. Esentepe Mah.Milangaz Cad. No:75 K:3 Kartal Monumento Plaza Kartal/İSTANBUL/TÜRKİYE Tel: +90 216 442 93 00 Fax: +90 216 370 45 03 www.ecostar.com.tr e-mail:servis@ecostar.com.tr 02.01.2017 Rev.06 1

CONTENTS WARNINGS... 3 Warning Symbols and Descriptions... 3 General Safety Rules... 4 TERMS OF WARRANTY... 6 Out of Warranty Conditions... 6 BURNER S GENERAL FEATURES... 7 Purpose of Use and Work Limits of Burners... 7 Code Key... 7 Burner Components... 8 TECHNICAL DATA... 11 Capacity Table... 11 Back Pressure-Capacity Diagrams... 12 Burner Dimensions... 13 Gas Hood Pressure Loss Diagram... 14 Flame Length and Diameter... 17 Noise Level... 17 BURNER HANDLING INFORMATION... 17 INSTALLATION... 19 Burner Installation Picture... 19 COMMISSIONING... 20 Before Commissioning... 20 Ignition and Ionizasyon System... 20 General Controls... 21 Combustion Adjustment... 22 Gas Adjustment... 22 Air Pressure Switch Adjustment... 25 Servomotor Adjustment... 25 Emission Measurement... 26 Capacity Adjustment... 26 Program Relay... 27 Function Controls and Adjustments... 27 Final Checks... 27 Gas Pass Equipment Required in Gas Line... 30 MAINTENANCE... 31 Monthly Maintenance... 31 Seasonal Maintenance... 31 Installation And Disassembly Instructions For Maintenance Purposes... 32 TROUBLESHOOTING... 35 PERIODICAL FLUE GAS MEASUREMENT REPORT... 36 AFTER-SALES SERVICES... 37 NOTES... 38 02.01.2017 Rev.06 2

WARNINGS Warning Symbols and Descriptions Symbols Symbol Descriptions Important information and useful hints. Warning of danger to life or property. Warning of electrical voltage. Product handling information. P F Impulse connection detecting combustion chamber pressure P L Impulse connection detecting combustion air pressure P BR Impulse connection detecting burner gas head CLEAN THE GAS BURNER. CLEAN GAS LINE. ЧИСТАЯ ЛИНИЯ ГАЗ. "Clean the gas line" warning on gas line. Electric motor direction of rotation Carry in an upright position. Fragile Item. Protect against water. 02.01.2017 Rev.06 3

General Safety Rules All personnel engaged in installation, disassembly, commissioning, operation, control, maintenance and repair should have received the necessary training and fully read and understood this manual. No changes that might damage the safety of the burner unit must be made by persons and/or organizations on the burner unit. All operation, commissioning and installation works (except for burning adjustment) should be carried out when the burner is not operating and after disconnecting the power supply. Noncompliance with these rules may lead to serious bodily injuries and even death by electrical shocks or uncontrolled flame formation. Repairs concerned with safety elements should be carried out only by the manufacturing company. The device should never be used by children, mentally handicapped and inexperienced persons. Children must not be allowed to play with the device. Keep the device away from explosive and flammable materials. Device must intake air, ventilation and air discharge holes must not be closed. If you sense gas leakage; Shut down valves of all gas devices. Open all doors and windows. Do not turn on electric devices or do not turn them off if they are working. Do not use burner derived tools such as match and lighter. Inform the gas company. Do not store any inflammable materials in boiler room. Wear hearing protectors if there is noise in boiler room. In case of fıre or other emergency; Switch off the main switch Close the main fuel shut-off valve outside the plant. Take appropriate actions 02.01.2017 Rev.06 4

The burner installation must be carried out in accordance with the instructions. Vibration can damage the burner and its components. Keep boiler doors closed while starting burner and during burner operation. Check combustion values to be correct by using flue gas analyzer at the whole adjustment range between minimum, full load, and ignition load. Use lifting device or belt for lifting fan motor, if necessary During the first commissioning of the burner or in case of any revision carried out in the electrical system or motor cables by any reason, direction of the fan rotation must certainly be checked by the authorized technical service. 02.01.2017 Rev.06 5

TERMS OF WARRANTY Main and auxiliary equipment and all components used in Ecostar gas burners are guaranteed for 1 year by TERMO ISI SİST. A.Ş starting from the date of commissioning under the maintenance, adjustment, operating conditions and relevant mechanic, chemical and thermal effects explained herein. Please note that this warranty is only valid if the device(s) is commissioned and maintained by our authorized services. Our company reserves the right to make any modifications on the product and all instructions thereof for improvement purposes. Out of Warranty Conditions Any damage arising out of or in relation to customers non-compliance to their responsibilities with regards to installation, commissioning, operation and maintenance, Any damage arising out of or in relation to commissioning, repairs and maintenance carried out by unauthorized services, Any damage that may occur during transportation or storage of the product, Not preserving the product in its original packaging until the installation stage, Incorrect and poor electrical connections, Failures due to incorrect voltage applications, frequent repetition of voltage fluctuations, Any damage that may occur as a result of incorrect fuel usage or, foreign substances in the fuel used or using of the product without any fuel, Any damage that may occur due to foreign particles entered into the product during installation and operation, Failures due to incorrect device selection, Any damage to unit due to natural disasters, Devices without any warranty certificates, Warranty Certificates without the stamp and signature of the authorized dealer or service, Devices with any falsification on the warranty certificate or without an original serial number. The risks during transportation of device under the responsibility of customer belong to the customer. Presence of misuse faults are indicated in the reports issued by authorized service stations or our authorized agent, dealer, representative or our factory in case of unavailability of authorized service stations. Customers may apply consumer protection arbitrator committee with regards to this report and request for an expert report. 02.01.2017 Rev.06 6

BURNER S GENERAL FEATURES ECOSTAR gas burners are manufactured such that they operate in gas pressure of min. 20 mbar and max. 300 mbar., at 15%...+10% of nominal voltage, between the ambient temperature range of - 15ºC.+60 C and declared capacity and boiler pressure ranges with Natural Gas and Liquid Petrol Gas. Purpose of Use and Work Limits of Burners This product works at any load value equivalent to its max. capacity or covered by its capacity range; - In hot water and steam boilers, - In direct and indirect hot air generators, - Industrial appliances operating at temperature below 600 0 C, - -15 0 C +60 0 C ambient temperature range, - 1N 230 VAC/3N 380VAC /50 Hz feed voltage (-%15 +%10) values, - Max. 95% relative humidity, - In well-ventilated open and closed spaces compatible with protection class IP 40. - Operation with Natural gas and LPG. This device must never be operated with open flame! Code Key 02.01.2017 Rev.06 7

Burner Components ECO 1 Assembly No Part Name Assembly No Part Name 1 Body Group 11 Air Damper 2 Fan 12 Gas Pipe Connection Flange 3 Combustion Head 13 Transformer-Relay Plate 4 Fan Motor 14 Gasket 5 Flame Tube 15 Pressure Switch Adaptor 6 Control Relay 16 Observation Glass 7 Transformer 17 Boiler Connection Flange 8 Pressure Switch 18 Ignition Electrode 9 Gas Pipe 19 Ionization Electrode 10 Damper Gauge 20 Gas Valve 02.01.2017 Rev.06 8

ECO 2 Assembly No Part Name Assembly No Part Name 1 Body Group 14 Pressure Switch 2 Flame Tube 15 Pressure Switch Adaptor 3 Gasket 16 Fan 4 Flame Tube Extension 17 Purger 5 Boiler Connection Flange 18 Relay Mounting Plate 6 Gasket 19 Transformer 7 Gas Intake Pipe 20 Pressure Switch Adaptor 8 Combustion Head 21 Fan Motor 9 Diffuser 22 Observation Glass 10 Ionization Electrode 23 Handling Shaft 11 Ignition Electrode 24 Control Relay 12 Air Damper 25 Gas Valve 13 Damper Gauge 02.01.2017 Rev.06 9

ECO 30-45 Assembly No Part Name Assembly No Part Name 1 Body Group 16 Pressure Switch Adaptor 2 Gasket 17 Air Damper Long 3 Flame Tube 18 Air Damper Short 4 Flame Tube Extension 19 Servomotor Coupling 5 Fan Motor 20 Servomotor 6 Fan 21 Damper Motion Rod 7 Transformer 22 Air Damper Motion Transfer Rod 8 Electrical Panel Mounting Plate 23 Gas Intake Pipe 9 Electrical Panel 24 Combustion Head 10 Handling Shaft 25 Diffuser 11 Fixing Plate 26 Ionization Electrode 12 Observation Glass 27 Ignition Electrode 13 Purger 28 Boiler Connection Flange 14 Pressure Switch 29 Gasket 15 Pressure Switch Adaptor 30 Gas Valve 02.01.2017 Rev.06 10

TECHNICAL DATA Capacity Table GAS BURNERS CAPACITY TABLE BURNER TYPE CAPACITY CAPACITY NATURAL GAS CONSUMPTION LPG GAS CONSUMPTION FAN MOTOR POWER MAIN SUPPLY Min. kcal/h Max. kcal/h Min. kw Max. kw Min. Nm³/h Max. Nm³/h Min. Nm³/h Max. Nm³/h kw VAC ONE STAGE GAS BURNERS ECO 1 G C 1 8.600 43.000 10 50 1,0 5,2 0,4 1,9 0,11 1N 230 ECO 1 G C 1a 17.200 86.000 20 100 2,1 10,4 0,8 3,8 0,11 1N 230 ECO 2 G C 1 51.600 172.000 60 200 6,3 20,8 2,3 7,6 0,15 1N 230 ECO 2 G C 1a 86.000 299.280 100 348 10,4 36,3 3,8 13,3 0,15 1N 230 TWO STAGE GAS BURNERS ECO 2 G C 2 51.600 172.000 60 200 6,3 20,8 2,3 7,6 0,15 1N 230 ECO 2 G C 2 a 86.000 299.280 100 348 10,4 36,3 3,8 13,3 0,15 1N 230 ECO 30 G C 2 163.400 387.000 190 450 19,8 46,9 7,3 17,2 0,37 1N 230 ECO 30 G C 2a 223.600 602.000 260 700 27,1 73,0 9,9 26,8 0,75 3N 380 ECO 45 G C 2 288.100 645.000 335 750 34,9 78,2 12,8 28,7 0,75 3N 380 ECO 45 G C 2/L 288.100 749.920 335 872 34,9 90,9 12,8 33,3 0,75 3N 380 ECO 45 G C 2a 331.100 928.800 385 1.080 40,1 112,6 14,7 41,3 1,10 3N 380 ECO 45 G C 2b 331.100 1.075.000 385 1.250 40,1 130,3 14,7 47,8 1,50 3N 380 MODULATING GAS BURNERS ECO 2 G C 3 51.600 172.000 60 200 6,3 20,8 2,3 7,6 0,15 1N 230 ECO 2 G C 3 a 86.000 299.280 100 348 10,4 36,3 3,8 13,3 0,15 1N 230 ECO 30 G C 3 163.400 387.000 190 450 19,8 46,9 7,3 17,2 0,37 1N 230 ECO 30 G C 3a 223.600 602.000 260 700 27,1 73,0 9,9 26,8 0,75 3N 380 ECO 45 G C 3 288.100 645.000 335 750 34,9 78,2 12,8 28,7 0,75 3N 380 ECO 45 G C 3/L 288.100 749.920 335 872 34,9 90,9 12,8 33,3 0,75 3N 380 ECO 45 G C 3a 331.100 928.800 385 1.080 40,1 112,6 14,7 41,3 1,10 3N 380 ECO 45 G C 3b 331.100 1.075.000 385 1.250 40,1 130,3 14,7 47,8 1,50 3N 380 H u Natural Gas =8250 kcal/nm 3 H u LPG=22500 kcal/nm 3 02.01.2017 Rev.06 11

Back Pressure-Capacity Diagrams 02.01.2017 Rev.06 12

02.01.2017 Rev.06 13

Burner Dimensions 02.01.2017 Rev.06 14

Gas Hood Pressure Loss Diagram Gas hood pressure loss measurements are conducted in atmospheric pressure. Consider the below data while conducting measurement in counter pressure boilers. P m : Gas hood pressure while burner is connected to the boiler and working P F : Combustion chamber pressure P Br : Burner net gas hood pressure P Br = P m - P F 02.01.2017 Rev.06 15

02.01.2017 Rev.06 16

Flame Length and Diameter Noise Level Product operates within the range of 75 decibels max. and 85 decibels. BURNER HANDLING INFORMATION Lift the product by holding the handles as seen in the picture. Prevent strong impacts on top of the product and vibration while handling the product. Do not leave the product in wet environment. 02.01.2017 Rev.06 17

Dimensions of the box used for handling Burner L x W x H (cm) Weight (kg) ECO 1 GC1(300 mbar) 65 X 43 X 37 18 ECO 1 GC1a(300 mbar) 65 X 43 X 37 18 ECO 2 GC1(300 mbar) 65 X 43 X 37 22 ECO 2 GC1(21 mbar) 65 X 43 X 37 26 ECO 2 GC1a(300 mbar) 65 X 43 X 37 22 ECO 2 GC1a(21 mbar) 65 X 43 X 37 26 ECO 2 GC2(300 mbar) 65 X 43 X 37 24 ECO 2 GC2(21 mbar) 65 X 43 X 37 24 ECO 2 GC2a(21 mbar) 65 X 43 X 37 26 ECO 2 GC2a(300 mbar) 65 X 43 X 37 24 ECO 2 GC3(300 mbar) 65 X 43 X 37 26 ECO 2 GC3a(300 mbar) 65 X 43 X 37 26 ECO 30 GC2(300 mbar) 80 X 54 X 40 40 ECO 30 GC2(21 mbar) 80 X 54 X 40 40 ECO 30 GC2a(300 mbar) 80 X 54 X 40 46 ECO 30 GC2a(21 mbar) 80 X 54 X 40 50 ECO 30 GC3(300 mbar) 80 X 54 X 40 42 ECO 30 GC3(21 mbar) 80 X 54 X 40 42 ECO 30 GC3a(300 mbar) 80 X 54 X 40 48 ECO 30 GC3a(21 mbar) 81 X 54 X 40 44 ECO 45 GC2(300 mbar) 97 X 56 X 45 52 ECO 45 GC2(21 mbar) 97 X 54 X 40 56 ECO 45 GC2a(300 mbar) 97 X 54 X 45 56 ECO 45 GC2a(21 mbar) 97 X 54 X 45 60 ECO 45 GC2b(300 mbar) 97 X 54 X 45 62 ECO 45 GC2L(300 mbar) 97 X 56 X 45 52 ECO 45 GC2L(21 mbar) 97 X 54 X 40 56 ECO 45 GC3(21 mbar) 97 X 54 X 45 58 ECO 45 GC3a(300 mbar) 97 X 54 X 45 60 ECO 45 GC3b(300 mbar) 97 X 54 X 45 64 ECO 45 GC3L(300 mbar) 97 X 54 X 45 54 ECO 45 GC3L(21 mbar) 97 X 54 X 45 58 02.01.2017 Rev.06 18

INSTALLATION Burner Installation Picture 1- Burner 2- Burner connection flange 3- Drift Bolts 4- Gasket 5- Boiler flange You must definitely ensure sealing between boiler and burner! Device must be shipped in original packaging! Do not lift the device holding from servomotor, gas valve, impulse pipes or pressure switch during installation! Clean the inside of fuel line thoroughly before installing the burner to the fuel line. Any damage that may occur due to solid objects and metal particles from the fuel line shall not be covered by our company. 02.01.2017 Rev.06 19

While installing the burner in reverse flame front mirror boilers, flame tube tip must be adjusted such that it gets inside by 50 mm-100 mm from flue pipes (50mm A 100mm). Otherwise flue gas temperature will rise and fuel consumption will increase. COMMISSIONING Before Commissioning Ignition and Ionizasyon System Electrical Connection Perform electrical connections according to the diagram provided with the burner. Follow general security rules during installation of electric wiring and making connections. Connect the earthing terminal in electric panel to the earthing installation. 02.01.2017 Rev.06 20

General Controls Make sure to perform the following controls before commissioning the burner. Are the electrical connections correct? Is there electricity current? Is there gas? Has the heating system been filled with water? Is the thermostat set at the required temperature? Has the boiler explosion lid been controlled? Is there sufficient air in boiler room (ventilation section cm² = boiler capacity kw x 7) Has the boiler been installed correctly? Has the boiler cover been closed properly? Has the air of the gas line been removed? Has a sealing test been made? Operation of one-stage burner Open the main gas valve, check the gas pressure from the manometer at the valve. (max.300 mbar) Check the boiler thermostat or pressure switch settings. Bring the operating switch on the burner panel to position 1. Burner fan motor will be activated. Ignition will take place at the end of pre-purge process. 3 sec. later, the gas valve will be opened and combustion will occur. Flame control system (ionization) will start flame control. After the boiler water heated up or the boiler pressure has risen, the burner will turn off. Operation of two-stage burner Open the main gas valve, check the gas pressure from the manometer at the valve. (max.300 mbar) Check the boiler thermostat or pressure switch settings. Bring the operating switch on the burner panel to position 2. Burner fan motor will be activated. Ignition will take place at the end of pre-purge process. 3 sec. later, the gas valve will be opened and combustion will occur. Flame control system (ionization) will start flame control. Burner will switch to the second stage (max. capacity) according to the heat requirement. After the boiler water heated up or the boiler pressure has risen, the burner will turn off. Operation of a modulating burner Open the main gas valve; check max 300 mbar gas pressure from the manometer. Open operating switch on the burner panel. Switch on the modulating control switch. Switch automatic-hand switch to automatic. Check the temperature and pressure set values from the modulating control unit. Ignition will take place at the end of pre-purge process. 3 sec. later, the gas valve will be opened and combustion will occur. Flame control system (ionization) will start flame control. In modulating burner, the burner goes into max. capacity according to the signal from the modulating control unit. When the boiler water temperature or steam pressure increase, the modulating control unit will cause burner to run with min. capacity. If the boiler water temperature or steam pressure increases despite the operation of burner with min. capacity, the modulating control unit will stop the burner. 02.01.2017 Rev.06 21

Combustion Adjustment Gas Adjustment Follow the instructions of the valve manufacturer during installation, dismantling and adjustment of the gas valve VGD 20 4011-5011 Series Gas Valve SKP 75 Connection Diagram 1 Air-gas adjustment ratio 2 Zero "0" point (start) adjustment 3 Boiler counter pressure impulse connection 4 Gas pressure impulse connection 5 Air pressure impulse connection MB DLE Series Monoblock Gas Valve 1- Pressure switch 2- Pressure switch electrical connection 3- Electrical connection of the valve 4- Operation gauge 5- The sealing ring 6- Set cover 7- Hydraulic disk brakes or settings 8- Coil 9- Measuring element connection (1/8) 10- Measuring element connection (1/8) 11- Output flange 12- Measuring element connection (1/8) 13- Gas flow way 14- Measuring element connection (1/8) 15- The vent plug 16- Filter chamber cover 17- Inlet flange 18- Measuring element connection (1/8) 19- Measuring element connection (1/8) 02.01.2017 Rev.06 22

- Consider the below torque values for bolts tightened on the valve. - Tighten flange bolts according to cross ordering and use proper tools. - Sealing and function check must be performed if the valve is dismantled and re-installed over the line due to any reason. - Before dismantling the valve from the line, you can perform filter replacement according to the below order. o Cut off the gas flow (turn off the ball valve) o Remove the 4 bolts (1,2,3,4) on the cover seen in the picture and take out the cover (5). o Take the filter cartridge (6) out of its socket and replace with a new one o Close the cover and tighten the bolts. In frequently performed filter replacement operations, use M4x14 bolt instead of self-tapping bolts used for fixing the cover. o Perform sealing and function control Max. torque values; 02.01.2017 Rev.06 23

MB ZRD(LE) 405 412 Series Gas Valve 02.01.2017 Rev.06 24

Air Pressure Switch Adjustment While the burner is working without any problem, the air pressure switch is adjusted to desired minimum pressure as follows. Unscrew the screw of the transparent cover and remove the cover. Turn the adjustment wheel in the direction to increase the pressure, note the pressure value at which the burner is failed. Set the pressure switch to a value 1 mbar lower than the pressure value at which the burner failed and close the pressure switch lid. It is recommended that this adjustment is carried out when the burner is at minimum load. Servomotor Adjustment The amount of air is adjusted by means of the servomotor. The servomotor adjustment at two-stage and modulating burners is made by the cams on the servomotor. SQN70 At Two-Stage Burners; I. Red Cam: Adjusts 2nd level max. air. II. Blue Cam: Resets the clamp. III. Orange Cam: Adjusts 1st level min. air. IV. Black Cam: Adjusts 2nd level valve opening degree. At Modulating Burners; I. Red Cam: Performance max. air adjustment. II. Blue Cam: Resets the clamp. III. Orange Cam: Performs min. air adjustment. IV. Black Cam: Not used. Do not open servomotor. Do not interfere with. It may damage servomotor or change burner settings. 02.01.2017 Rev.06 25

Emission Measurement In emission measurements, the following values are accepted as reference according to TS EN 676 +A2 standard. CO < 100 mg/ kwh (93 ppm) %3 O 2 %5 NO x < 170 mg/ kwh Excess air ratio 1,2 λ 1,3 It is important for the boiler to be sealed in order to avoid incorrect measurements during emission measurements. Boiler temperature must be between 40 C and 80 C while making emission measurement in hot water boilers. Capacity Adjustment Exemplary Application: Suppose the required burner capacity is (C) 500 kw. H u = 8250 kcal/m 3 (lower heating value) P = 860 kcal/kw (Value of 1 kw in kcal) Q = C x P Q = 500x860 = 430000 kcal V = Q / H u V = 430000/8250 = 52,12 m 3 /h Set the required gas flow rate over the valve and check this value on the gas counter. Should there be no gas flowmeter in the system, set the burner by using the gas tip lost pressure diagram given at page 15-16. In order to ensure the emission values set the air klappe in each gas flow increase. 02.01.2017 Rev.06 26

Program Relay LME 22 Yellow led on: Indicates that the burner is making pre-purge. Yellow led flashing: Indicates that the burner is igniting. Green led flashing: Indicates poor combustion. Red led on: Indicates burner malfunction. Press and hold the light button for 2 sec. to reset the program relay. Function Controls and Adjustments Operation testing: If the burner switch is turned on and safety circuit is complete (gas pressure switch, thermostat, water level gauge, lower pressure gas pressure switch, upper pressure gas pressure switch, gas leakage control device), turn on the ball valve, burner will start working and turn off the gas valve. Program operation of the relay must be normal until ignition time. During opening of the magnetic valve, gas pressure will drop down and the lower pressure switch will stop the burner for safety. When the ball valve is opened again, gas pressure will increase and lower pressure switch will trip in from safety position and the burner will automatically start operating. Disconnect the ionization circuit or remove the photocell when the burner is operating: Burner will give a fault after burning up. Increase the value of the air pressure thermostat: Burner starts operating, however it should give a fault due to the insufficiency of air pressure. Magnetic valves must not be energized during pre-purge. Check if valves are in closed position! Final Checks Switch of all purges after completion of all necessary measurements. Start and stop the burner at least 3 times to check the operation of the program. Make sure that all safety circuits on the burner and boiler operate properly before leaving the installation site. 02.01.2017 Rev.06 27

If the value measure from PL point is below 0.5 bar, set the impulse pipe as follows. 02.01.2017 Rev.06 28

If the flame tube of the burner is longer than standard (standard flame tube length of the burner), please do not forget to support burner body during maintenance and installation/commissioning. 02.01.2017 Rev.06 29

Gas Pass Equipment Required in Gas Line Pe < 300 mbar Pe > 300 mbar Pe < 300 mbar Pe > 300 mbar Q<1200kW Q<1200kW Q>1200kW Q>1200kW 1- Compensator 1- Compensator 1- Compensator 1- Compensator 2- Ball valve 2- Ball valve 2- Ball valve 2- Ball valve 3- Gas filter 3- Gas filter 3- Gas filter 3- Gas filter 4- Inlet manometer + valve 4- Inlet manometer + valve 4- Inlet manometer + valve 4- Inlet manometer + valve 8 Multi-block (safety and operation solenoids) 5- Regulator 8 Multi-block (safety and operation solenoids)) 5- Regulator 9- Sealing Control Set 6- Outlet manometer + valve 9- Sealing Control Set 6- Outlet manometer + valve 7- Safety discharge valve 7- Safety discharge valve 8 Multi-block (safety and operation solenoids) 8 Multi-block (safety and operation solenoids) 9- Sealing Control Set 9- Sealing Control Set Threaded and flanged connections may vary depending on the gas pressure and consumption. 02.01.2017 Rev.06 30

MAINTENANCE Monthly Maintenance Monthly maintenance is a comprehensive process where general checks of burner and peripheral components are performed to prevent possible faults. After completion of maintenance and adjustment processes, make sure to perform an emission analysis. Clean the filters on the main line and multiblock. Check the burner gas tip. Perform insulation measurements of ignition and ionization electrodes, replace electrodes should there be leakage to the body. Check ignition cables and sockets. Check all wiring points. Tighten loose connections. Clean the dust and layers accumulated on the fan and air klappes. Check gas line pressure, it must be the same with the first adjusted pressure, otherwise burner load and emission values will also have changed. Check all bolts of the burner. Tighten loose bolts. After starting the burner and adjusting air klappe, perform flue gas emission measurement and check if there is an ideal combustion. Seasonal Maintenance Comprehensive maintenance work when the burner is re-started after long periods of shut-down or interruptions. After completion of maintenance and adjustment processes, make sure to perform a combustion analysis. Check insulation resistance of electric motor. Replace ignition and ionization electrodes with new ones. Clean air fan and clamps. Check the operating function. Check boiler thermostats. Check cleanliness of boiler inside and clean if necessary. Follow installation directions during maintenance. 02.01.2017 Rev.06 31

Installation And Disassembly Instructions For Maintenance Purposes ECO 1 For Intervention to Ignition System Remove 3 bolts number 1, which fix the flame tube on the Body, and pull back and lower the body provided that the flame tube stays on the boiler. Make the necessary intervention to ignition and ionization circuit. For Intervention to the Air Klappe: For Intervention to Fan and Motor: Remove cable of the electric motor from program relay. Remove bolts number 1 that connect the air vent to the body. Detach the air vent from the body. In order to take the fan out of the electric motor, remove the bolt number 2 in fan core and interfere the fan. Remove the bolts number 3 on the electric motor and take the motor off the body. Remove 1 bolts number 2 that fix the klappe on the shaft. Detach the klappe and the shaft number 2 from the body. 02.01.2017 Rev.06 32

ECO 2 For Intervention to Ignition System Remove 3 bolts number 1 that fix the body on the flame tube and pull back the body by sliding it on the lift shaft. For Intervention to Fan and Motor: Remove cable of the electric motor from program relay. Remove bolts number 1 that connect the electric motor to the body. Detach the motor and the fan from the body. In order to take the fan out of the electric motor, loosen the bolt number 2 in fan core. For Intervention to the Air Klappe: Remove the bolt number 1 from the shaft. Remove 2 bolts number 2 that fix the klappe on the shaft. Detach the klappe and the shaft from the body. 02.01.2017 Rev.06 33

ECO 30, ECO 45 For Intervention to Ignition System Remove 3 bolts number 1 that fix the body on the flame tube and pull back the body by sliding it on the lift shaft. For Intervention to Fan and Motor: Remove cable of the electric motor from program relay. Remove bolts number 1 that connect the air vent to the body. Detach the air vent from the body. In order to take the fan out of the electric motor, remove the bolt number 2 in fan core and interfere the fan. Remove the bolts number 3 on the electric motor and take the motor off the body. For Intervention to the Air Klappe: Remove bolts number 1 that fix the klappe on the mil. Detach servomotor expanding bushing number 2 after detaching the klappe. Detach servomotor number 3 and shaft from the air vent. 02.01.2017 Rev.06 34

TROUBLESHOOTING Problem Cause Explanation-Suggestion Burner cannot be commissioned Flame appears and goes into failure mode. Burner starts up, but fails after 10 seconds. Gas is cut or does not come Fuse failure Relay failure Boiler thermostat, pressure switch failure Gas pressure error Ionization electrode failure Program relay failure Air pressure switch adjustment Program relay failure Gas valve might be closed. Open the valve. Check burner power supply. The fuse on the main panel or the fuse on the burner might be tripped. Reset the thermal relay. Check adjustment of the thermal relay according to the current in motor label. If the failure is not removed, replace the thermal relay. If there is a problem with the burner thermostats, pressure switches and steam tank this may be due to an unadjusted or faulty water level device; adjust it and if broken, replace it. Supply gas pressure might be low. Ionization electrode may be faulty or contaminated. Remove and clean. Replace it with a new one. Air pressure switch might be adjusted to a high value. There may be dirt in the air pressure switch. Air pressure switch might be broken. Replace it with a new one. Burner starts up, but fails after 30 seconds. Boiler cover is overheating. Fan motor failure Gas valve, gas pressure drop Ignition electrode failure Gas valve adjustment Sealing problem Check fan motor coils, motor contactor and outlet from program relay. Gas valve might be closed. Supply gas pressure might be low. Check gas inlet manometer. Ignition electrodes might be misadjusted or ignition cables might have come out of their terminals. Adjust ignition electrodes with a distance of 3-5 mm. between them. Check the starting setting of the gas valve. Burner must be adjusted to sufficient start gas flow for its activation. Ensure sealing between the boiler cover and burner. If required, use insulating material between the boiler connecting flange and boiler cover. 02.01.2017 Rev.06 35

PERIODICAL FLUE GAS MEASUREMENT REPORT Fuel Consumption CO (ppm) O 2 (%) CO 2 (ppm) NO X (ppm) Yield (%) Flue Temp. Date Signature (m³/h) (ºC) 02.01.2017 Rev.06 36

AFTER-SALES SERVICES Dear Customer, We believe that providing a good service is as important as providing a good product. Therefore, we continue offering wide range of comprehensive services to our conscious customers. Our contact details for your requests and complaints Esentepe Mah.Milangaz Cad. No:75 K:3 Kartal Monumento Plaza KARTAL/İSTANBUL/TÜRKİYE Tel: +90 216 442 93 00 Fax: +90 216 370 45 03 Factory Contact Details Türkgücü OSB Bülent Ecevit Bulvarı No:11 ÇORLU/TEKİRDAĞ/TÜRKİYE Tel: +90 282 685 44 80-81 Fax: +90 282 685 42 09 Also you can contact with us: Web site : www.ecostar.com.tr E - mail : servis@ecostar.com.tr Please observe the following recommendations. Use the product in accordance with the principles of this manual. For any service demands regarding the product, please contact our Service Center from the abovementioned phone numbers. Upon your purchase, register your warranty certificate during installation. 02.01.2017 Rev.06 37

NOTES Please record and forward your measurements and observations to us www.ecostar.com.tr 02.01.2017 Rev.06 38