COMFORT CONDITIONS IN A HABITAT FOR HUMANITY HOUSE IN CENTRAL TEXAS

Similar documents
New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

AN ANALYSIS OF THE RESIDENTIAL ENERGY SAVINGS FROM THE IMPLEMENTATION OF THE 2001 IECC AND 2006 NAECA APPLIANCE STANDARDS IN THE STATE OF TEXAS

Neil A. Moyer James B. Cummings David Chasar Principal Research Engineer Program Manager Research Engineer

2006 Building Science Press All rights of reproduction in any form reserved.

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Ventilation in Humid Climates: Data from Field Experiments

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

The Art of Building Science

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

The Unplanned Impacts On Houses By Powered Attic Ventilators

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

ENERGY SYSTEMS LABORATORY

RESNET HERS Rater Sample Test Questions 2

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS

Using Infrared for Residential Energy Surveys

Basic Building Science insights for Spray Foam, HVAC and Moisture

THE FACTOR 9 HOME: A NEW PRAIRIE APPROACH

Axiom Property Inspections

2006 Building Science Press All rights of reproduction in any form reserved.

LIMITED INDOOR MOLD ASSESSMENT

Building Envelope Air Leakage Failure in Small Commercial Buildings Related to the Use of Suspended Tile Ceilings

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

HOME PERFORMANCE ENERGY ANALYSIS

HVAC Equipment Access Equipment Location

Supplement A- Improving Forced Air Heating Systems

Relative Humidity in Schools Jim Cummings and Chuck Withers

Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

Pro Eco-Energy. Home Assessment

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny

Canadian Property Inspections

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Attic ventilation options can be confusing to roofing contractors

Deemed Savings, Installation & Efficiency Standards

SAFETY AND INSTALLATION MANUAL MODEL 8100

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

PART 5: HVAC & DHW SYSTEMS

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

Installation Instructions

HYGROTHERMAL PERFORMANCE BENEFITS OF THE CELLULOSE FIBRE THERMAL INSULATION STRUCTURES

Passive building in Hot and Humid Climates

COST EFFECTIVE PASSIVE SOLAR FOR NEW HOME CONSTRUCTION

OCCUPANT INTERACTION WITH VENTILATION SYSTEMS 7th AIC Conference, Stratford-upon-Avon, UK

Energy Upgrade California Home Upgrade Offered by The Energy Network

Unvented Roof Summary Article

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Available online at ScienceDirect. Energy Procedia 78 (2015 )

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Space Coast Home Inspections LLC

Museum Archive Dehumidification in Hot & Humid Climates

Cascade Inspection Services, LLC

The Use Of Attic Space For Cooling and Dehumidification

Maine Single-Family Residential Baseline Study

Home Performance Science

Bedroom 100. True or False: Space heaters are more energy efficient and inexpensive to heat large areas than central heating systems.

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Extra Mile Inspection, Inc.

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Montana Weatherization Program WEATHERIZATION FINAL INSPECTION REPORT (Mobile Homes) Client Name Address Contact phone # Inspector Name and QCI#

Sample Report Site Visits Any Capitol, Any State Date

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

Equipment Specifications and Required Information Quantity Rebate

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Insight. No Sweat. Condensation on ductwork and boots in hothumid and mixed-humid climates. By Joseph W. Lstiburek, Ph.D., P.Eng.

Jeff Brown Inspections

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems

Basic Home Energy Audit

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

Energy problems in small apartment buildings

Low-Impact Remodeling

Figure 1: Low energy dwellings testsite

Zoning System Design Manual

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Rater Provider Monthly Webinar REM Rate Modeling Tips March 23rd 2013

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

South Richland Provincial and Estate Homes

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II

Getting in the Zone with Zonal Pressure Diagnostics

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

Effect of Moisture on Building Systems!

ENERGY & WATER EFFICIENCY: HOME ASSESSMENTS. Jim Riggins Monument, CO

Prepared by: (415) itioner. Contributors: Me!

PLYMOUTH NJC Realty Holdings LLC Buildings Specification for: Pilgrim Circle Nashua NH. Total Living Space 1750 sq. ft.

Building Science Basics

Transcription:

COMFORT CONDITIONS IN A HABITAT FOR HUMANITY HOUSE IN CENTRAL TEXAS V. Kootin-Sanwu J. S. Haberl, Ph.D., P.E, B.IGm, Ph.D Research Assistant Energy Systems Associate Professor and Associate Associate Professor, Cheju University, Laboratory, Energy Systems Laboratory, Director, Energy Systems Laboratory, Democratic Republic of South Korea. Department of Architecture, Texas Department of Architecture, Texas Previously, Visiting Scholar, Department A&M University A&M University of Architecture, Texas A&M University. College Station, TX College Station, TX College Station, TX ABSTRACT This paper presents preliminary results of an analysis of measured comfort conditions for a Habitat for humanity house in central Texas. In the case study house indoor-outdoor temperature, humidity and C02 levels have been monitored in an attempt to ascertain how comfort levels are being maintained. Temperature measurements of the slab in three locations have also proved useful in determining the impact of cold floors in the wintertime. This paper presents an analysis of the findings and recommendations concerning future design modifications that could make the Habitat houses more comfortable without substantially raising costs. INTRODUCTION Habitat for Humanity is an international, volunteer, religious organization that has been established to develop affordable, low cost housing. Habitat homes are low cost, high quality, energy efficient houses constructed with volunteer labor and materials that utilize no or low interest loans to keep monthly payments low. Qualified Habitat homeowners are required to participate in the construction of their homes. Their "sweat equity" also keeps the cost of the homes low. Habitat for Humanity provides services to homeowners from local offices located in all 50 of the United States and in 5 1 countries around the world (Habitat 2000). The design of each Habitat home varies with location with the overall goal of providing a low cost, energy efficient, durable home. Several efforts have been performed to evaluate the effectiveness of the energy efficiency features in selected Habitat homes in hot and humid locations including efforts in Texas (Haberl et al. 1998a, 1998b) and Florida (Parker et al. 1996; 1997; 1998). These reports have shown that efficient equipment selection, selected envelope measures (i.e., white roofs), and overall construction quality as effective energy conserving measures for Habitat houses located in hot and humid climates. However, all the previous efforts have assumed that the indoor environments in the Habitat houses are comfortable and healthy andlor performed a limited analysis of the indoor conditions. This paper reports on efforts to investigate the indoor environment of a monitored Habitat for Humanity house in central Texas. METHODOLOGY Background The Habitat for Humanity house used in this study is a single-story 1048 ft2, three-bedroom house with an attic space (Figure 1) and is located in Bryan, Texas. The measured data are recorded with an onsite data logger that was installed during the 1997 construction period. The house consists of a kitcheddining area, utility room and two bathrooms. The house has a 64ft2 front porch and a 42Ppatio at the rear of the house. Figure 1: Case Study Habitat House. This photo shows thefiont (north side) of the case study house shortly afcer construction was completed. The house is constructed with Cinch concrete slab-on-grade with grade beams at 10-foot centers laid over an impermeable vapor barrier. The exterior 2 x 4 stud walls (16 inch O.C.) are composed of % inch gypsum, R-13 blown-in cellulose insulation, '/z inch foil-faced foam-board insulation, Tyvek water barrier, and vinyl sidmg. The ceiling is % inch gypsum supported by 2 x 6 inch joists (24 inch O.C.),

R-19 blown-in fiberglass insulation, and R-6 duct insulation. The roof construction consists of composite shingles on felt underlayment, with a 518 inch plywood deck supported by 2 x 6 inch trusses (24 inch O.C.) and has an 18 inch overhang. The house's heating and cooling systems consists of a central, forced-air natural gas furnace and air conditioner. A 50-channel data logger was installed during the construction of the house to record 15-minute energy and environmental conditions. Electrical monitoring includes the whole-house electricity, and sub-metering for the clothes dryer, air-conditioner, air-conditioner blower, refrigerator, freezer, clothes washer and dishwasher. Additional thermal metering includes the whole-building natural gas and thermal metering of the domestic water heater. Environmental metering include three ground temperatures beneath the house, indoor temperature, humidity and Cozy attic temperature and humidity, HVAC supply air temperature and humidity, and ambient temperature, humidity, Cozy horizontal solar and wind speed as indicated in Table 1. Table 1: Energy and Environmental Channels Recorded by the Data Logger. This table contains the channel descriptions from the data logger installed at the case study house. The channel types include power monitoring (KW), analog channels (AN), and digital channels (DIG). All sensors were calibrated against NIST-traceable instruments at the Energy Systems Laboratory (ESL) (Turner et al., 1992). Data from the data logger are downloaded weekly, inspected for errors and loaded, into the ESL's relational database. PHOTOGRAPHS Photos of the monitoring equipment are included in Figures 2-5. Figure 2 is a photo of the electrical panel for the case study house where the current transformers and voltage reference were installed. Figure 2: Electrical and Thermal sensors for the Case Study House. This photo shows the electrical panel for the case study house where the current transfonners and voltage reference were installed. Directly below the distribution panel is the power supply for the logger and the Btu meter for the domestic water heater. Figure 3. This is a photo of the data logger and weather station for the case study house located on a pole at the rear of the house to provide for easy access.

Data, telephone and 24 VAC power are provided in buried conduit that runs between the house and the support pole. Figure 4 is a photo of the indoor monitoring station for temperature, humidity and COz located in the hallway return air plenum. Figure 5 is a photo of the combined temperature-humidity sensor and PVC radiation shield located in the attic of the case study house. RESULTS Temperature measurements. Preliminary results of the monitoring efforts are included in Figures 6 to 13. Figure 6 shows measured 15-minute temperatures fiom the attic, Figure 4: Indoor Environmental Sensors. This photo shows the indoor monitoring station for temperature, humidity and C02 located in the hallway return air plenum. Figure 5. Attic Temperature and Humidity Sensor. This figure shows the combined temperaturehumidity sensor and PVC radiation shield located in the attic of the case study house Figure 6: 15-minute Environmental Temperatures Measured at the Case Study House. This figure shows measured 15-minute temperatures from the attic, ambient, and indoor air sensors, along with ground temperatures located below the slab in the center of the house [C], and 3 feetfrom the edge of the slab on the [N] and south [S] sides. ambient, and indoor air sensors, along with ground temperatures located below the slab in the center of the house [C], and 3 feet from the edge of the slab on the m] and south [S] sides for a three week period in January-February 1999. It is clear from figure 6 that the ceiling and walls of the house are exposed to significant variations in diurnal exterior temperatures with ambient wall temperatures varying fiom 30 F to 80 F and attic temperatures varying fiom 30 F to over 100 F. The attic temperatures rise significantly above the ambient temperatures during the dame, as the solar heat gain penetrates the surface of the roof. However, the attic temperatures almost always drop to the same temperature as the ambient temperatures each evening - an effect of night sky radiation and the vented attic. The elevated attic temperatures contribute to the duct heat gain during the cooling season, and to a lesser extent, contribute to the space heat gain because of the R- 19 insulation.

During this same period the measured ground temperatures directly below the concrete slab varied little with the center of the slab remaining the closest to the indoor air temperature. The temperatures near the edges of the slab are slightly lower than the central slab temperature indicating the uninsulated edges of the concrete slab are allowing the exterior cold temperatures to penetrate into the interior of the house. Figure 7 shows measured ground temperatures located below the slab in the center of the house [C], and 3 feet fiom the edge of the slab on the [N] and south [S] sides for a 6-month period fiom December 1998 to June 1999. These measured temperatures clearly show that there are significant periods in the winter when the edges of the concrete slab are well Figure 7: Daily Ground Temperatures Measured at the Case Study House. This figure shows measured ground temperatures located below the slab in the center of the house [C], and 3 feetji-om the edge of the slab on the [N] and south [S] sides for a 6 month periodji-om December 1998 to June 1999. drop in temperature on February 1 lh. During the warming period the slab temperatures converged towards the room temperature. Whereas, one day following the outdoor temperature drop the temperatures at the edges of the slab started to drop away from the center slab temperature. Second, in Figure 7 the temperature of the center of the slab remains relatively constant throughout the 6-month period due to the direct contact with the conditioned air in the building. Finally, the edges of the slab vary from about 60 F in the middle of the winter to almost 80 F by the summer, indicating a siguficant influence fiom the outdoor temperature. COz measurements. Figures 9 and 10 show measured indoor-outdoor C02 concentrations. Figure 9 shows 15-minute measured indoor and outdoor C02 concentrations for one week for the period 12/28/98 to 1/5/99. Clearly, there are significant periods when the house is well above the 1,000 ppm recommended by ASHRAE. Figure 10 shows 15-minute measured indoor ind outdoor C02 concentrations for the 2-112 month period from 5/13/98 to 713 1/98. During this period, there is a period of 10 days when the indoor C02 concentration never falls below 1,000 ppm and isolated spikes when the C02 concentrations topped 2,500 ppm. However, there are also periods when the C02 concentrations did not rise above 1,000 and a few days when the indoor C02 concentrations matched the outdoor concentrations. Clearly, one can conclude fiom these data that the C02 concentrations are very dependent upon how many people are in the house and whether or not the house has any windows open. I I I 50 60 70 b0 SO 100 110 Floor temperature (F) Figure 8: Percentage ofpeople dissatisfied as a function offloor temperature. below the 77 F recommended by ASHRAE for bare feet in contact with an uncarpeted floor (Figure 8). Several other features are evident as well from Figures 6 and 7. First, in Figure 6 during the threeweek period that is shown there was a warming period in the middle of February followed by 40+ F Figure 9: 15-minute Measured Indoor and Outdoor COr Concentrations. This figure shows measured 15- minute indoor-outdoor COr concentrations ji-om the case study house for the period 12/28/98 to 1/5/99.

C I 3". i... ". "".... 3.3." I "3,".."M. M,", vr."..nn W'"..,..".":" 9. r.r 7"". mm. m.n. 373.r ma. "23". vrm. I-.,..l."L) " an." 3.l",.A," ms.r.,.l,.",;,..",*,.r Figure 10: 15-minute Measured Indoor and Outdoor COZ Concentrations. This figure shows one week of measured 15-minute indoor-outdoor C02 concentrationsfrom the case study house for the period 5/I 3/98 to 7/31/98. Temperature-humidity measurements. Indoor tem~erature-humidity measurements were also recorded td help analyze the thermal comfort of the house as shown in Figures 11 and 12. In Figure 11 the indoor-outdoor temperature and humidity are displayed on the psychrometric chart for the 3-month period from January 1999 to March 1999. Figure 12 shows the indoor-outdoor temperature and humidity for the Month of August 1999. The second mode is a group of indoor temperature-humidity data that fall outside the comfort zone and represent either a) periods when ambient temperatures were cold but the heating system was not active (i.e., temperatures colder than the comfort zone), orb) periods when the humidity levels are above the 60% RH recommended by ASHRAE for mold and mildew control. During the cooling season (Figure 12), a dramatically different picture emerges about the indoor comfort conditions. In this period, which represents the month of August 1999, ambient conditions varied from 75 F to 100 F and were always more humid than the AS= comfort zone, forcing the Habitat homeowner to continuously m her air conditioner. This continuous air-conditioning produced a very tight grouping of the indoor temperature-humidity measurements that range from 65 to 75 F and remained almost entirely within a 40 to 50% RH band. During the heating mode (Figure 11) several features can be seen in the data. First, there are two distinct indoor temperature-humidity groups: one group where the heating system was clearly operating and the resultant temperature-humidity condition stayed within the confines of the ASHIWE comfort chart for heating (i.e., 60% RH, 68-75 F and 36 Twb). Figure 12: Indoor/outdoor temperature and humidity displayed on the psychrometric chart (cooling mode). This figure shows the measured indoor temperaturehumidity displayed on the psychrometric chart during the cooling season for the month of August 1999. DISCUSSION This paper has presented preliminary results of efforts to measure the energy use and environmental conditions of a Habitat for Humanity house in central Texas. In general, these measurements show that the Habitat house is providing year-around comfort conditions for the homeowner. However, a closer look at the data reveals the following features: Figure 11: Indoor/outdoor temperature and humidity displayed on the psychrometric chart (heating mode). This figure shows the measured indoor temperaturehumidity displayed on the psychrometric chart during the heating season for the period Janualy to March 1999. 1) The attic temperatures are hot during sunny days even in the winter and very hot during sunny days at other periods. Therefore, it is recommended that alternative designs be investigated that will avoid placing air-conditioning equipment and ductwork in

the attic where it is exposed to the extreme temperature. 2) Slab temperatures at the edge of the slab are dropping well below the 77 F floor temperature recommended by ASHRAE for bare feet on uncarpeted concrete floors. This may be indicating the need for perimeter insulation. This recommendation runs counter to ASHRAE Standard 90.1 and 90.2. Both of these standards recommend levels of insulation based upon cost effective heat loss mitigation. However, the measurements reported in this paper would indicate that insulation should be recommended based upon comfort conditions. Additional study is also needed to determine the interaction of winter-time thermostat settings and the insulated slab temperatures for optimum comfort conditions. For example the indoor air temperatures were 72-75 F and to as low as 55"F,which would indicate a need for slab heating in order to maintain the 77 F temperature 3) Interior comfort conditions vary during the heating season. The Habitat homeowner in the case study house allows the temperatures to drop as low as 559: during the heating season. This may also be contributing to low slab temperatures. High humidity conditions have been observed for the heating season as well. When the heating system is on it does appear to maintain temperatures at or near the ASHRAE recommended conditions. 4) Interior comfort conditions are well maintained during the cooling season. Indoor comfort conditions during periods of continuous air-conditioning are well below the 60% RH ASHRAE recommended humidity limit for mold and mildew control. Measurements reveal that the homeowner in the case study house prefers indoor temperatures well below the ASHRAE recommended temperatures. 5) Indoor-outdoor C02 measurements indicate higher than expected indoor C02 concentrations and may be indicating that the house is too tight and in need of a ventilation system during the peak cooling period. This is also confil~l~led by blower door measurements that showed 0.3 to 0.5 ACH at 50 Pascals. Indoor COz levels seem to be influenced by door-window opening or closing, use of exhaust fans and number of occupants. C02 levels tend to be higher in the summer (less infiltration due to stack effect). Obviously, during the monitoring period there were periods when the homeowner opened the windows and the C02 levels approached the ambient levels. ACKNOWLEDGMENTS Funding for this project was provided by the Texas A&M Research Enhancement Program (Energy Resources Program) and by the College of Architecture's College Research Council. Special thanks are also due to Kelly Milligan, Kim Carlson, Peter Klima and Pat Tollefson for assisting with the equipment installation and calibration. Jim Sweeney, Robert Sparks and Ron Chambers were also helpful with data polling and archiving. Thanks also to Patricia Burke and Jim Davis of the Bryan-College Station Habitat office. Special thanks are also given to the Habitat homeowners who willing allowed us to scrutinize their energy use and environmental conditions over a 2+ year monitoring period. REFERENCES ASHRAE 1993. Standard 90.2-1993 - Energy- Efficient Design of New Low-Rise Residential Buildings and User's Manual, American Society of Heating, Refrigeration and Air Conditioning Engineers, Atlanta, GA. ASHRAE 1989. Energy Code for Commercial and High-Rise Residential Buildings Based on ASHRAEES 90.1-1989, American Society of Heating, Refrigeration and Air Conditioning Engineers, Atlanta, GA. ASHRAE 1997. ASHRAE Fundamentals Handbook, American Society of Heating, Refrigeration and Air Conditioning Engineers, Atlanta, GA. Haberl, J., Bou-Saada, T., Reddy, A., Soebarto, V. 1998a. "An Evaluation of Residential Energy Conservation Options Using Side-by-side Measurements of Two Habitat for Humanity Houses in Houston, Texas", Proceedings of the 1998 ACEEE Summery Study, pp. 1.115-1 -134, (August). Haberl, J.S., Bou-Saada, T., Soebarto, V., Reddy, A. 1998b. 'Wse of Calibrated Simulation for the Evaluation of Residential Energy Conservation Options of Two Habitat for Humanity Houses in Houston, Texas ", Proceedings of the Eleventh Symposium on Improving Building Systems in Hot and Humid Climates, Texas Building Energy Institute, Ft. Worth, Texas, pp. 1-15, (June). Habitat 2000. Habitat for Humanity International, 12 1 Habitat St., Americus, GA, 3 1709,912-924- 693 5. Parker, D., Sherwin, J. Floyd, D. 1998. "Measured Energy Savings From Retrofits Installed in Lowincome Housing in Hot and Humid Climates", 11' Symposium on Improving Building Systems in Hot and Humid Climates, Ft. Worth, Texas, (June).

Parker, D., Mazzara, M., Sherwin, J. 1996. "Monitored Energy Use Patterns in Low Income Housing in a Hot and Humid Climate", 10& Symposium on Improving Building Systems in Hot and Humid Climates, Dallas, Texas (May). Parker, D., Sherwin, J. 1997. "Measured Energy Savings From a Comprehensive Residential Retrofit", Florida Solar Energy Center, Report No. FSEC-CR-978-97. Turner, W. D., Haberl, J. S., Bryant, J., Finstad, C., Robinson, J. 1992. "Calibration Facility for the LoanSTAR Program", Solar Engineering 1992: The 1992 ASME-JSES-XSES International Solar Energy Conference, Maui, Hawaii, April 5-9, 1992, Edited by Stine, W., Kreider, J., and Watanabe, K., Vol. 2, pp. 1269-1275.