Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower

Similar documents
An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Pressure Enthalpy Charts

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Numerical Simulation of Window Air Conditioner

Optimizing Electric Humidifier Operation with an Air Side Economizer

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

ENSC 388: Engineering Thermodynamics and Heat Transfer

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Bench Top Cooling Tower H893

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

CTI Sponsored Educational Program

Air Conditioning Clinic

AR/IA/UP 241 Lecture 5: Psychrometrics

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Mechanical Engineering Laboratory

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Prediction of Sweet Corn Seeds Field Emergence under Wet Soil Condition

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Performance Optimization of the Evaporative Condenser Design

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Heating Ventilation and Air Conditioning Laboratory

R07. Answer any FIVE Questions All Questions carry equal marks *****

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout

Thermo-physical properties found on most psychrometric charts

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

A/C Cooling Load calculation and measurement

In-Field Quantification of Fan Performance in Tunnel-Ventilated Freestall Barns ABSTRACT INTRODUCTION

2. HEAT EXCHANGERS MESA

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Impacts of room temperature on the performance of a portable propane air conditioner

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Optimization of Compressors used in Air Conditioning Units

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

All rights reserved, Armando B. Corripio, PhD, PE, Solid Dryer Design Introduction Continuous Dryer Design...

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Mathematical Simulation of Longan Fruit Drying

Redesign of Bennett Hall HVAC System

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

Air & Water Heat Pump R832

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Drying Parawood with Superheated Steam

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

LOW RECIRCULATION RATE EVAPORATORS

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Performance investigation of Air-conditioning system using ejector as expansion device

Mechanical Heat Pump R515

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Investigation of Evaporator Performance with and without Liquid Overfeeding

Inbred Planting Technique for Nakhon Sawan 3 Hybrid Maize Seed Production

Technical Development Program

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Refrigerant Mass and Oil Migration During Start-up Transient

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Specific Energy Consumption of Heat Pump Drying System

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

System Modeling of Gas Engine Driven Heat Pump

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Fan Selection. and Energy Savings

Transcription:

Kasetsart J. (Nat. Sci.) 42 : 378-384 (2008) Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower Montri Pirunkaset* and Santi Laksitanonta ABSTRACT This paper presents the effect of blade angles on the packing characteristic curves of a small cooling tower on the site experimental data. The volumetric heat transfer coefficient (KaV/L) can be illustrated graphically and varied with the water to air flow ratio (L/G) for the blade angles of 59, 67, 75, and 83, respectively. The curves can be constructed by the experimental data from the cooling tower testing in accordance with the procedure of CTI standard. It was found that the characteristic curves can be represented in the form of KaV/L = C(L/G) -n in the different range of L/G for each blade angle. Finally, it was found that the cooling tower can operate under all the given approaches (5 C, 6 C, 7 C and 8 C) at the blade angle of 67 by maintaining the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. Key words: blade angles, performance of a small cooling tower INTRODUCTION During installation, the manufacturer must set up the proper blade angle for controlling the air flow through the tower as much as possible. The commercial cooling tower must provide the high heat transfer between the hot water and cold air by adjusting the proper blade angle during installation. Therefore, the manufacturer must determine the tower characteristic curves at various blade angles under the given wet bulb temperature, approach, hot water temperature, and water flow rate((nicholas et al., 1983). For residential air conditioning duty, the small packaged cooling towers usually have the adjustable blade angles. Therefore, the purpose of this research is to study the effect of the blade angles on the performance of the counter flow cooling tower with a small size (3 to 10 tons of refrigeration). MATERIALS AND METHODS The counter-flow cooling tower testing laboratory includes the circulated system of cooled water and hot water as shown in Figure1. The counter-flow cooling tower system includes heater tank, cold water tank, balancing tank, cooling tower, cold water pump, hot water pump, control panel, and measuring devices. 1) The counter-flow cooling tower is the heat exchanger between the hot water and air, and the specifications are following as: - The cooling tower size (using the corrugated packing) 5 tons of refrigeration Department of Mechanical Engineering, Faculty of Engineering, Kasetsart University, Bangkok 10900, Thailand. * Corresponding author, e-mail: fengmtp@ku.ac.th

Kasetsart J. (Nat. Sci.) 42(5) 379 Figure 1 The apparatus of counter-flow cooling tower system for the experiment and testing. -Water volume flow rate ( V w ) 65 L/min - Air volume flow rate ( V a ) 55 m 3 /min - Hot water temperature (HWT) 37 C - Cold water temperature (CWT) 32 C - Inlet wet bulb temperature (WBT) 27 C - Fan horsepower 0.20 hps 2) There are 3 units of water pumps, namely 2.1 Cold water pump is used to pump the water from cold water tank to heater tank and it has the discharge pressure of 22 m of water, pumping flow rate from 10 to 80 L/min, motor horsepower of 0.37 kw, motor speed of 2900 rpm, and water connection diameter of 25 mm. 2.2 Hot water pump is used to pump water from the heater tank to the cooling tower and it has the same specifications as the cold water pump. 2.3 Balancing pump is used to control the level of water in heater tank, cold water tank, and cooling tower. It has the discharge pressure of 35 m, pumping flow rate of 30 L/min, motor horsepower of 0.33 kw, motor speed of 2900 rpm, and water connection diameter of 25 mm. 3) There are 3 units of water tanks, namely 3.1 Heater tank is used to supply the hot water for testing of the cooling tower and it has the 7 units of heater. Each unit has capacity of 2 kw by using current at 9.09 A and 220 V. 3.2 Cold water tank is used to supply cold water to the heater tank by pump and it has volume of 240 liters. 3.3 Balancing tank is used to supply water for controlling water level in the heater tank, cold water tank, and cooling tower during testing and experiment. It has volume of 200 liters, height of 85 cm, and diameter of 55 cm. 4) Measuring Devices, consisted of: 4.1 The orifice meter is used to measure pressure drop across the orifice plate by different height of mercury with range from 0 to 300 mm of Hg and its dimension of 60mm 440mm 28mm. The relationship between the different height of mercury, h Hg (mm) and the water flow rate, V w (L/min) can be found from the experiment and written as:

380 Kasetsart J. (Nat. Sci.) 42(5) V w = 7. 5485 h Hg (1) 4.2 Anemometer is used to measure and record the air velocity by measuring the outlet air velocity (at the top of packing). 4.3 The digital instrument and recorder of temperature is used to measure water and air temperatures namely, wet bulb and dry bulb temperature, inlet and outlet water temperature of packing, and water film temperature. 4.4 The wet bulb and dry bulb thermometer on glass tube type, this instrument is used to measure wet bulb and dry bulb temperature of the inlet air (at the bottom of packing). Methods Tower characteristics and performance Cooling tower characteristics are generally presented in the form of an empirical correlation. This correlation defines the relationship between the heat transfer coefficient, KaV/L and water-air flow ratio, L/G under the operating condition. Cooling tower data are most often plotted in the form of KaV/L versus L/G for the various wet bulb temperature (approach) and cooling range. These graphs have been published by the Cooling Tower Institute (Cooling Tower Institute, 1982). Common practice is to neglect the effect of air velocity and develop the tower correlation in the form of a power law relation as (Mills, 1995): KaV C L n = (2) L G A commercial cooling tower of 5 tons of refrigeration is used to perform the structural equipment of model, which can be operated and tested in accordance with CTI standard. Cooling tower performance is specified in term of the cooling range, approach, wet bulb temperature and water flow rate. The rating of a tower is established by developing series of charts that related these variables (Hill et al., 1990). Calculation of KaV/L The Tchebycheff method for numerically b evaluating the integral ydx uses values of y at a predetermined values of x within interval a to b. It can be selected that the sum of these values of y multiplied by a constant times the interval (b- a) gives the desired value of integral. In its four-point form, the values of y are taken at selected values of x of 0.102673, 0.40620, 0.59379, and 0.89732 of the interval (b-a). For the determination of KaV/ L, rounding off these values to the nearest tenth is entirely adequate. The approximate formula becomes (Cooling Tower Institute, 1982): b ( b a) ydx = a ( y 1 + y 2 + y 3 + y 4 ) (3) 4 where y 1 = value of y at x = a + 0.1( b-a ), y 2 = value of y at x = a + 0.4( b-a ) y 3 = value of y at x = a + 0.6( b-a ), y 5 = value of y at x = a + 0.9( b-a ) The water temperatures on the divided cross section of packing can be calculated in 4 positions. Each position can be determined from bottom to top of the packing as T 2 +0.1(T 1 -T 2 ), T 2 +0.4(T 1 -T 2 ), T 2 +0.6(T 1 -T 2 ), and T 2 +0.9(T 1 -T 2 ), respectively. So, the enthalpy difference at each position can be calculated and the value of KaV/ L can be evaluated as KaV Cw ( T T = 1 2) 1 1 1 1 + + + L 4 h1 h2 h3 h4 (4) where h 1 = saturated air and moist air enthalpy difference at T 2 +0.1(T 1 -T 2 ) h 2 = saturated air and moist air enthalpy difference at T 2 +0.4(T 1 -T 2 ) h 3 = saturated air and moist air enthalpy difference at T 2 +0.6(T 1 -T 2 ) h 4 = saturated air and moist air enthalpy difference at T 2 +0.9(T 1 -T 2 ) C w = specific heat of water, T 1 = hot water temperature, T 2 = cold water temperature

Kasetsart J. (Nat. Sci.) 42(5) 381 The blade angle adjustment The blade angles can be adjustable in four positions as shown in Figure 2. In each position of the blade angle, the performance of cooling tower can be tested by maintaining the speed of fan motor at 900 revolutions per minute Procedure of experiment The procedure of this research can be discussed as: 1) To fill water into a system (cold water tank, hot water tank, and balancing tank). 2) To set up the blade angle of 59. 3) To set up the different height of mercury at 10 mm (the water volume flow rate of 23.87 L/min). 4) To start the heater and fan motor until the water temperature reaches 40 C and system reaches steady state. 5) To record the air volume flow rate, the outlet water temperature, the wet bulb temperature, and the dry bulb temperature. 6) To set up the new values of water flow rate by increasing the different height of 14, 18, 22,.., 50 mm and repeat from the item (4) to (5) for each different height. 7) For the other blade angles (67, 75, and 83 ), the experiment can be repeated as the item (3) to (6). RESULTS AND DISCUSSIONS The experiments are based on the setting of blade angles in cooling tower of 5 tons of refrigeration at the blade angle 59, 67, 75, and 83 of respectively. For the testing of cooling tower, the hot water temperature remains constant at 40 C and the variation of circulating water flow rates are from 23.87 to 53.38 L/min and wet bulb temperatures varied from 25 to 27 C. The characteristic curves for each blade angle in Figure 3 can be fit in the form of equation (2). The exponent, n and constant, C of the equation (2) for the various blade angles are shown in Table 1. The cooling tower with 5 tons of refrigeration and the packing area of 3.463 ft 2 can be operated under the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. The approach of 5 C, 6 C, 7 C and 8 C for cooling tower can be drawn in the same graph of the characteristic curves for each blade angle and the operating points can be represented as Table 2 to Table 5. Figure 2 Adjustment of blade angles at 59, 67, 75 and 83.

382 Kasetsart J. (Nat. Sci.) 42(5) Figure 3 The volumetric heat transfer coefficient at blade angles of 59, 67, 75 and 83. Table 1 The exponent, n and constant, C of the equation (2) for the various blade angles. Blade angle n C the range of L/G 59 0.8955 0.3403 0.576 to 1.420 67 0.7781 0.3879 0.507 to 1.125 75 0.6505 0.4350 0.415 to 0.924 83 0.5482 0.4935 0.360 to 0.807 Table 2 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of 59. 26 31 36 Out off range of L/G 26 32 37 0.596 0.541 17.16 3432.2 26 33 38 0.694 0.472 17.16 2949.4 26 34 39 0.799 0.416 17.16 2563.7 Table 3 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of 67. 26 31 36 0.530 0.636 17.16 3858.2 26 32 37 0.643 0.547 17.16 3182.8 26 33 38 0.763 0.479 17.16 2684.6 26 34 39 0.763 0.479 17.16 2296.0

Kasetsart J. (Nat. Sci.) 42(5) 383 Table 4 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of 75. 26 31 36 0.553 0.640 17.16 3698.7 26 32 37 0.691 0.553 17.16 2963.2 26 33 38 0.841 0.487 17.16 2440.8 26 34 39 Out off range of L/G Table 5 The operating point (L/G, KaV/L) under the approach of 5 C, 6 C, 7 C and 8 C, range of 5 C, and wet bulb temperature of 26 C for blade angle of 83. 26 31 36 0.607 0.649 17.16 3371.4 26 32 37 0.780 0.566 17.16 2627.4 26 33 38 Out off range of L/G 26 34 39 Out off range of L/G For the adjustment of blade angle at 67 o, the cooling tower can operate in all approaches (5 C, 6 C, 7 C and 8 C) by maintaining the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h. Under the constant demand of WBT = 26 C, CWT = 32 C, HWT = 37 C, it was found that L/G, KaV/L and CFM are dependent upon the blade angles of fan as shown in Figure 4. The air quantities decreased with blade angles by maintaining the water flow rate of 17.16 GPM. So, the ratio of L/G and KaV/L increased with blade angle. GPM,(gallon/min), CFM (ft 3 /min x100) 40 35 30 25 20 15 10 5 0 CFM GPM 51 59 67 75 83 91 Blade angle L/G KaV/L 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 KaV/L, L/G Figure 4 The effect of blade angle on KaV/L, L/G, and CFM for HWT = 37 C, CWT = 32 C and WBT = 26 C.

384 Kasetsart J. (Nat. Sci.) 42(5) CONCLUSIONS This research studied the effect of blade angles on the packing characteristic curves of a small cooling tower. The curves can be constructed by the experimental data from the cooling tower testing in accordance with the procedure of CTI standard. As the lack of performance curves at the various blade angles, the fan blades may not be adjusted properly by manufacturers during installation. In each blade angle, it is important to find the operating points between the characteristic curves and approach curves and these points must not be out-off range of L/G for each characteristic curve. It was found that the cooling tower can operate in all approaches (5 C, 6 C, 7 C and 8 C), the cooling range of 5 C, wet bulb temperature of 26 C, and water flow rate of 3.9 m 3 /h by the adjustment of blade angle at 67. LITERATURE CITED Cooling Tower Institute. 1982. Acceptance Test Code for Water Cooling Towers. CTI Code ATC-105. 8 p. Hill, G.B., E.J. Pring and P.D. Osborn. 1990. Cooling Towers Principles and Practice. 3 rd ed. Butterworth-Heinemann Ltd., London. 191 p. Mills, A. F. 1995. Heat and Mass Transfer. Richard D. Irwin Inc., Chicago.1239 p. Nicholas P.Ch. and N.Ch. Paul. 1983. Cooling Tower (Selection Design and practice). 2 nd ed. Ann arbor Science Publishers, the Butterworth-Group, Michigan. 347 p.