FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

Similar documents
Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1150

Architectural and Engineering Specification for a Fiber Optic Perimeter Intrusion Detection System. FiberPatrol FP1100X

Architectural and Engineering Specification for a Hybrid Perimeter Intrusion Detection and Intelligent Lighting System.

Fiber Optic Cable Fence Disturbance Sensor

Architectural and Engineering Specification for a Fiber Optic Pipeline Integrity Monitoring System. FiberPatrol FP7000

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website:

SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v doc

Taut Wire intrusion detection sensor (TWIDS)

Architectural and Engineering Specification for a. Flash / Flare

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

Product Specifications

Microphonic Cable Fence Disturbance Sensor (multiplex version)

WG Buried Cable Perimeter Detection System

FlexZone SIX STEPS TO AFFORDABLE PERIMETER PROTECTION EASY TO INSTALL LOW TOTAL COST OF OWNERSHIP HASSLE-FREE OPERATION & MAINTENANCE HOW-TO GUIDE

Section PERIMETER SECURITY SYSTEMS

INTREPID Perimeter Intrusion Detection System

Architectural and Engineering Specification for a Real-Time Locating System Flare

Product Specification

Buried ported coaxial cable outdoor intrusion detection system

Architectural and Engineering Specification for a Security Management System. StarNet 2

Pipeline Intrastructure Monitoring for Third-Party Interference Detection

INTREPID SINGLE-PLATFORM PERIMETER INTRUSION DETECTION AND MONITORING SYSTEM

G-MAX IVS R123 Vibration Sensors Perimeter Intrusion Detection System

Product Specifications

FiberSensor Fiber Optic Intrusion Detection System (IDS)

Perimeter security using Fibre optics

G.M. Advanced Fencing & Security Technologies Ltd

TOTAL PERIMETER SOLUTION

Presented By. BEI Security

Intrusion. Outdoor protection perimeter

Intelli-FLEX Perimeter Protection System-Relay Output Processor. product guide. (DC/DC relay version)

WG Buried Fibre Cable Long Perimeter Detection System

TW-8000 TAUT WIRE FENCE

Alarm annunciation, control and communication systems

P E R I M E T E R m i n i c a t a l o g u e

BLG77 Rising Fenced Barrier

ONYX FirstVision Specification Interactive Firefighters Display

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

SECTION AUTOMATIC TRANSFER SWITCHES

INTREPID Buried Cable Perimeter Intrusion Detection System

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Engineering Specifications

Perimeter Product Overview. Effective protection for your business

Intrusion Outdoor Protection Perimeter

TOTAL PERIMETER SOLUTION

The New Standard In Safety

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

INTREPID Buried Cable Perimeter Intrusion Detection System

RaySense. Fiber Optic Distributed Vibration Sensing (DVS) for Pipeline Security and Leak Detection

For Complete Fire and Gas Solutions

Protecting Station Platform & Rail Perimeters. TransitVUE IDS The Latest in Fiber Optic Station Platform & Rail Perimeter Security Sensor Systems

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

Airport Perimeter Security

BL41 Extra-long Barrier

Perimeter Intrusion Detection System

The Fiber SenSys Perimeter Intrusion Detection System From JM Fiber Optics!

STRIKE GUARD DELIVERS:

Gallagher Perimeter Product Overview

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

TrueAlarm Analog Sensing

LaserFOCUS VLF-250 Engineering Specification

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

CARD ACCESS CONTROL SYSTEM

Open-area Smoke Imaging Detector. Engineering Specification

Access CONTROL. MANAGEMENT Software

APPLICATION DATA SHEET

The next generation thermometer from the global leader

Introducing the innovative ipids Indoor Outdoor Detection System MANUFACTURING SECURITY SOLUTIONS

PERIMETER DEFENCE. Panorama Intruder Detection System Long Range, Day & Night, Automatic Panorama Intruder Detection

SECTION AUTOMATIC TRANSFER SWITCHES

TLS-300 UST Monitoring and Leak Detection System

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

Specification for On-Line UPS Battery Monitoring and Data Management System

BL 53 Security Barrier ENGINEERING SPECIFICATIONS

IRONCLAD Product Information

Industrial Grade Gas Detection Detecting The Difference

Network Display Unit Installation Instructions

Secure the other corner. bracket using the remaining screw,

SECTION INTRUSION DETECTION

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

SECTION POWER SUPPLIES AND DISTRIBUTION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

Danfoss gas detection units

ACTIVE INFRARED BARRIER

Gallagher D10 Tautwire Sensors & D21 Disturbance Sensors Integration with Gallagher

Access Control. Total Perimeter Protection Solutions from one Source

VIDEO VISITATION APPLICATION: FUNCTIONS AVAILABLE:

SECTION SECURITY TESTING AND COMMISSIONING

SECTION LIGHTING CONTROLS

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

GE LightSweep Lighting Control System Guideform Specification

Fire and Gas Monitoring Panel ST7-HV

SECTION GENERATOR PARALLELING CONTROLS

EC-BOS-602/616 AX Security

Multi-layered Perimeter Protection Systems Quality detection systems for high security sites

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Transcription:

Architectural/Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System FlexPS Disclaimer Senstar, and the Senstar logo are registered trademarks, and FlexPS, Silver Network and Crossfire are trademarks of Senstar Corporation. The information in this document is subject to change without notice. Senstar reserves the right to make changes to product design or manufacturing methods, as engineering progresses, or as other circumstances warrant. Copyright 2011. Senstar Corporation. All rights reserved. G5DA0115-001 Rev A Page 1 January 2011

G5DA0115-001 Rev A Page 2 January 2011

Part 1 General Fence Mounted Perimeter Intrusion Detection System... 4 1.1 System Summary... 4 1.2 Submittals... 4 1.3 Spares... 4 1.4 Product Support... 4 Part 2 Products Fence Mounted Perimeter Intrusion Detection System... 4 2.1 Fence Mounted Perimeter Intrusion Detection System... 4 2.2 Manufacturers... 4 2.3 Regulatory Requirements... 5 2.4 System Manufacturing Quality Requirements... 5 2.5 Fence Mounted PIDS with Standalone Processors... 5 2.6 Networking Capabilities... 9 Part 3 Execution Fence Mounted Perimeter Intrusion Detection System... 10 3.1 Site Assessment... 10 3.2 System Installation... 10 3.3 System Calibration... 10 3.4 Training... 11 G5DA0115-001 Rev A Page 3 January 2011

PART 1 GENERAL - FENCE MOUNTED PERIMETER INTRUSION DETECTION SYSTEM 1.1 SYSTEM SUMMARY A The contractor shall install a fence-mounted electronic perimeter intrusion detector. The system shall be used to protect the perimeter of the facility from unauthorized intrusions. The system shall consist of a sensor cable and a microprocessor-based dual zone signal processor. The system shall detect intruders by processing electrical signals generated by the minute vibration of the sensor cable caused by intruders cutting, climbing, or lifting the fence fabric. The system shall be integrated into the facility s Security Management System. 1.2 SUBMITTALS A Contractor submittals to the facility owner ( Owner ) shall include the following as a minimum: 1.3 SPARES.1 site conditions report per article 3.1.2 configuration and calibration settings for each processor in the system after installation and calibration are complete per article 3.3.3 sensitivity plots for each zone in the system per article 3.3.4 all manufacturer-supplied calibration and operating software for the system A The contractor shall deliver to the Owner spare system components consisting of:.1 for each system component a minimum quantity of one or 10% of the number that comprise the system, whichever is greater 1.4 PRODUCT SUPPORT A The product shall carry a minimum one-year warranty from the date of purchase. B The supplier shall warrant that the product shall be supported by spare parts and assemblies for a minimum of 10 years from date of purchase. PART 2 PRODUCTS - FENCE MOUNTED PERIMETER INTRUSION DETECTION SYSTEM 2.1 FENCE MOUNTED PERIMETER INTRUSION DETECTION SYSTEM A The contractor shall supply a fence-mounted Perimeter Intrusion Detection System (PIDS). The fence-mounted PIDS shall detect intruders attempting to breach the perimeter fence by cutting, climbing, or lifting the fence fabric. 2.2 MANUFACTURERS A The FlexPS system from Senstar Corporation (www.senstar.com ) meets the requirements stated herein for a fence-mounted PIDS and shall be the basis of design. G5DA0115-001 Rev A Page 4 January 2011

2.3 REGULATORY REQUIREMENTS Architectural & Engineering A The system shall comply with FCC 47 CFR Part 15, Subpart B requirements for Class A devices. B The system shall comply with EN 61000-6-4: 2007. C The system shall comply with EN 50130-4: 1995 + amendments A1:1998 & A2:2003. D The system shall comply with Industry Canada ICES-003, Issue 4 requirements for Class A devices. 2.4 SYSTEM MANUFACTURING QUALITY REQUIREMENTS A The manufacturer s quality management system shall be certified as conforming to ISO 9001:2008. B All electronic elements intended for outdoor installation shall be conformal coated and units shall be tested during manufacture over their entire operational temperature range on a sample basis. C All sensor cable furnished shall be tested over its entire length during manufacture and test results showing the sensitivity over the length of the cable shall be furnished by the manufacturer. 2.5 FENCE MOUNTED PIDS WITH STANDALONE PROCESSORS A Detection Capabilities.1 Sensor Cable a. The PIDS sensor shall be a continuous cable that is attached to the fence along the full length to be protected..2 Processor a. The PIDS processor shall have the following detection capabilities:.1 process the signal from the sensor cable to detect intruders attempting to breach the perimeter fence by cutting, climbing, or lifting the fence fabric.2 provide two separate zones of detection by independently processing the signal from two sensor cables.3 each sensor cable forming a zone can be up to 300 m (984 ft.) in length.4 use digital signal processing techniques.5 provide separate calibration settings for each zone.6 be capable of being calibrated to function on different types of metal fencing including but not limited to chain-link, expanded mesh, and welded mesh. The calibration capabilities shall include setting the lower and upper frequency limits that the processor responds to in increments of 100 Hertz in order to optimize the processing to the specific characteristics of the fence G5DA0115-001 Rev A Page 5 January 2011

.7 utilize adaptive algorithms in the detection process to optimally discriminate between actual intrusions and environmental activity.8 utilize the sensor input from both zones in the detection process to optimally discriminate between actual intrusions and nuisance alarms caused by environmental effects such as high winds that affect both zones (this processing technique is known as common mode rejection).3 System Detection Performance a. The probability of detection (Pd) of an intruder cutting the fence, lifting the fence fabric, or climbing unaided over the fence shall be 95% with a 95% confidence factor, when the system is installed according to the manufacturer s directions. B False Alarm Rate.1 The maximum rate for alarms generated by internal electronic processes of the processors (cables excluded) shall be less than one per zone per year, averaged over the total number of zones in the system. C Nuisance (Environmental) Alarms.1 The system shall not suffer nuisance alarms from any of the following sources: b. ambient temperature changes c. motion of nearby objects or vegetation that are not striking the fence d. motion of surface or ground water e. sunrise/sunset f. seismic vibration caused by nearby vehicular or rail traffic g. acoustic or magnetic effects h. snow i. fog.2 The system shall utilize adaptive processing and ambient compensation to minimize the probability of nuisance alarms from the following sources: a. wind b. rain and hail c. sandstorms D Fence Compatibility.1 The system shall provide the specified detection performance when installed on different types of metal fencing including but not limited to chain-link, expanded mesh, and welded mesh. It shall be possible to use multiple passes of sensor cable to obtain the specified detection performance for fences of any height. The manufacturer shall provide guidelines regarding the height of fence that can be protected with one, two, and multiple passes of sensor cable. E Protection of Gates.1 The system shall be capable of monitoring or bypassing swinging and sliding gates by using a Gate Bypass Module. The system shall be capable of placing G5DA0115-001 Rev A Page 6 January 2011

F Architectural & Engineering monitored gates in access mode (no alarm when the gate is used), or secure mode within a secure zone, by either local or remote command. Armored Sensor Cable.1 The sensor cable shall be available encased in an armor jacket, for use in areas that have a high potential of physical damage to the cable. G Standalone Processor Alarm Outputs.1 The sensor processor shall have a minimum of four Form C relay outputs to indicate alarm conditions. Each relay shall be rated for up to at least 0.5A at 30V. For each relay it shall be possible to assign one or more conditions from the following list under which the relay will activate: a. side A sensor alarm b. side B sensor alarm c. side A supervision alarm d. side B supervision alarm e. enclosure tamper f. input power fail g. battery fail h. internal hardware fault i. fail safe (assert on total loss of power) H Processor Self-Test Inputs I J.1 The processor shall provide two dry contact inputs that, when the processor is used in a standalone mode (no network), function as inputs that command a selftest cycle to be performed. Self-test shall consist of internal circuitry tests, testing cable continuity and termination, and testing of detection processing. Processor Audio Output.1 The processor shall provide a high-impedance analog audio output that is an audio representation of the signal generated by the sensor cable. The audio output shall be selectable between sensor cable A, sensor cable B, sensor cables A and B, and inactive. Tamper Detection.1 The processor shall detect and indicate tampering conditions including opening the processor cover and cutting or short-circuiting the sensor cable. K Processor Calibration Port.1 For calibration purposes the processor shall provide a standard USB connector for attachment of a Windows PC. L Environmental Operating Range.1 The system shall operate within specifications under the following environmental conditions: a. temperatures between -40 C (-40 F) and 70 C (158 F) b. relative humidity between 0 and 95%, non-condensing G5DA0115-001 Rev A Page 7 January 2011

M The processor shall be housed in a painted aluminum enclosure meeting the requirements of NEMA 4X and IP 66. N Standalone Processor Input Power.1 The processor when used in a standalone mode (no network) shall accept DC power ranging from 12 to 48V and require less than 0.5 watt. O Processor Internal Battery Backup P.1 There shall be an option for the processor to have an internal backup battery. When fully charged the internal backup battery shall be capable of powering the FlexPS processor for a minimum of 12 hours. The processor shall include a battery charging circuit to charge the internal backup battery. Processor Reliability and Maintainability.1 The processor shall have a predicted mean time between failures (MTBF) of greater than 100,000 hours when calculated per Telcordia Reliability Prediction Procedure, Parts Count Method, at 70 C. The processor shall have a mean time to replace (MTTR) of less than 10 minutes. Q Lightning Protection.1 The processor shall provide both transorb and gas discharge devices on all inputs and outputs including power. R Ease of Installation S.1 The system shall be simple to install and shall have the following characteristics as a minimum: a. the sensor cable must be capable of being attached directly to the fence without needing to be put in a conduit b. the sensor cable must be capable of being attached to the fence with standard UV-resistant cable ties c. it shall be possible to mount the processor directly on a fence post that forms part of the fence to be protected d. it shall be possible to connect the sensor cable directly to the processor without the need for any intermediary cable e. all electrical connections to the processor, including the sensor cables, shall be made with screw-terminals on removable connectors f. cable ingress/egress shall be accommodated by cable glands that require no additional sealing compounds to provide an environmental seal g. configuration and calibration shall be accomplished via a Windowsbased software tool with an intuitive graphical user interface h. it shall be possible to store processor configuration and calibration settings to a computer file for record keeping and to use the stored file to configure other processors and/or a replacement processor Processor Locking.1 The system manufacturer shall provide an optional kit that allows the processor cover to be locked with a padlock. T Backwards Compatibility G5DA0115-001 Rev A Page 8 January 2011

.1 The system manufacturer shall provide optional retrofit kits to allow the processor to be installed in Senstar Intelli-FLEX enclosures and Senstar (MSi/PPI) FPS-2 and FPS-5 enclosures. The processor shall be compatible with the sensor cables used by these systems. 2.6 NETWORKING CAPABILITIES A When a network-capable system is required the requirements of this section shall apply..1 System with Network Capability a. The processors shall be capable of communicating alarm, status, and configuration information to and from a central location over an integrated sensor network. B Physical Media Options.1 The processors shall provide the following physical media options for the sensor network: a. EIA-422 capable of point-to-point runs of up to 1.2 km (4,000 ft.) b. multi-mode fiber optic capable of point-to-point runs of up to 2.2 km (7,200 ft.) c. single-mode fiber optic capable of point-to-point runs of up to 10 km (32,000 ft.) C Redundant Network Communications.1 The sensor network shall be capable of being connected in a loop configuration and of being polled from both ends of the loop to provide redundant communications paths to each processor. D Network Management.1 The system shall include network management software to manage the communications over the sensor network. The network management software shall be capable of running on a standard Windows PC. E Network-Based Global Sensor Processing F.1 The system s network management software shall include a global sensor processing capability such that activity on multiple zones of the system is evaluated in making alarm decisions. Network Management Software Interfaces.1 The system s network management software shall provide the following interfaces: a. a TCP/IP-based interface for communicating alarm, status, and configuration data to and from security management systems. The system supplier shall furnish complete documentation of this interface to facilitate integration with security management systems. b. a TCP/IP-based interface to be used by the system s PC-based software calibration and configuration tool to allow calibration and configuration of all processor settings to be done from a central location once the device address is set on the processor G5DA0115-001 Rev A Page 9 January 2011

G Network Manager Tools Architectural & Engineering.1 The system s network management software shall provide the following tools to facilitate system commissioning and trouble-shooting: a. system status tool that provides a visual display of the status of all processors in the system b. system event log tool that provides a searchable log of system events c. system plot tool that can store and recall the instantaneous response data for all networked sensors and display a plot of the instantaneous response from a minimum of 8 sensor zones simultaneously H Networked Processor Dry Contact Inputs I J.1 In networked mode the processor dry contact inputs shall function as generalpurpose supervised inputs and the state of the dry contact inputs shall be communicated over the network. Networked Processor Relay Outputs.1 In networked mode the processor relay outputs shall function as general-purpose outputs and the state of the relay outputs shall be controlled via the network. Networked Processor Self-Test.1 In networked mode it shall be possible to initiate a self-test over the network. K Networked Processor Input Power.1 The processor when used in networked mode (with network card installed) shall accept DC power ranging from 12 to 48V and require less than 1.0 watt. L Network Backwards Compatibility.2 The system processors shall be capable of interfacing to Senstar Crossfire and CEnDe networks and provide the full range of communications capabilities as provided by those networks. PART 3 EXECUTION - FENCE MOUNTED PERIMETER INTRUSION DETECTION SYSTEM 3.1 SITE ASSESSMENT A Before installation begins, the installation contractor shall provide a report to the Owner documenting any site conditions that may prevent the system from operating satisfactorily. Examples of such conditions include excessively loose fence fabric and objects such as signs and tree branches hitting the fence. 3.2 SYSTEM INSTALLATION A The system shall be installed in accordance with the manufacturer s recommended procedures as defined in the manufacturer s Product Guide for the system. 3.3 SYSTEM CALIBRATION A The installation contractor shall calibrate the system in accordance with the manufacturer s recommended procedures as defined in the manufacturer s Product G5DA0115-001 Rev A Page 10 January 2011

3.4 TRAINING Architectural & Engineering Guide. The installation contractor shall submit to the Owner the calibration and configuration settings for each processor in the system. The installation contractor shall submit to the Owner a response plot for each zone in the system. A The installation contractor shall train the Owner s maintenance personnel in the calibration and system maintenance procedures as given in the manufacturer s Product Guide. G5DA0115-001 Rev A Page 11 January 2011