Model FMD. Field Mounted Display Module

Similar documents
High Temperature Remote Gas Calibrator

Model TL104 MANTL104. Test Lamp for Flame Detection

Model 2602A. Zero Two Series Control for Hydrogen Sulfide Gas Applications

Model IR4000S CO 2. Single-Point Carbon Dioxide Monitor. Instruction Manual 12-11

Model 2280A. Four Channel Control Module Hydrogen Sulfide Gas Applications

Model 580A. Two Channel Control Module Combustible Gas Applications

Model 4802A. Zero Two Series Control Module

Model IR4000M. Multi-Point Monitor. Instruction Manual 12-10

Model TA502A. Zero Two Series Generic Trip Amplifier Module

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

FM Approved Fire & Gas Detection System

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

Analog Room Pressure Monitor RPC Series

DIGITAL METERS Large Display Temperature Meters Instruction Manual

Model S4000C. Intelligent Sensor for Combustible Gas Detection

Carbon Monoxide Transmitter

Beacon 800 Gas Monitor Operator s Manual

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SEC 2000 Millenium Infrared Gas Detector

Model TS4000. Intelligent Sensor for Toxic Gas Detection

Model IR400. Infrared Point Detector for Hydrocarbon Gas Applications

FUNCTIONAL SAFETY MANUAL

Safe T Net 210. Instruction Manual Part Number Mar2010

MODEL FL3102. Digital Frequency Infra-Red (DFIR) Flame Detector MANFL3102. Instruction Manual 07-08

Model TA102A. Zero Two Series Trip Amplifier Module For Combustible Gas Applications

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

RK Transmitter Technical Notice

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Model D12-IR. Digital Gas Transmitter...

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

RK-HC-04 M2A Transmitter Operator s Manual

Detcon MicroSafe. IR-640 Carbon Dioxide Sensor (0-5%CO2) IR642 Carbon Dioxide Sensor (10%-100%) Operator s Installation & Instruction Manual

RK Combustible Gas Transmitter Operator s Manual

Model SM100. Aspirated Sampling Module

GENERAL MONITORS. Protection for life. Product Guide. Total Solution Provider for Gas and Flame Detection

Model IR5500. Infrared Open Path Detector for Hydrocarbon Gas Applications

Model 4802A. Zero Two Series Control Module For Combustible Gas Applications

RK-04 M2 Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

RAEGuard 2 PID. User Guide

Certificate of Compliance

Oxygen (O2) Single-Point Gas Detection System

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/

Pioneer-R16 Gas Monitor Operator s Manual

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

SIL 2. Ultima X Series Gas Monitors CERTIFIED

M2 Rig Monitor Operator s Manual

Two-Channel Gas Controller

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

UNI-TROL TM GAS CONTROLLER

Instructions Toxic Gas Controllers R8471D/F/G Chlorine/Sulfur Dioxide/Nitrogen Dioxide 1.1 8/

Model S4000TH. Intelligent Sensor for Hydrogen Sulfide Gas Detection

Dräger Polytron 8700 IR Detection of flammable gases and vapors

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Beacon 110 Gas Monitor Operator s Manual

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Duct and Rough Service Carbon Monoxide Sensor

Model S4000CH. Intelligent Sensor for Combustible Gas Detection

Model TA202A. Zero Two Series Trip Amplifier Module For Hydrogen Sulphide Applications

Instructions Oxygen Controller R8471C 2.1 8/

Combustible Gas Detection and Control System

Dependable Solutions for Gas Detection

M2 Transmitter Operator s Manual

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Dräger Polytron 7000 Fixed gas detector

Gas Detection System SGAES-TG Operating Manual R01

Instructions. Explosion Proof Smoke Detector U Rev: 9/

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Combustible Gas and Hydrogen Sulfide Beacon 200 Rig Monitor Operator s Manual

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

CLEANROOM MONITOR CR3A Network - Installation Instructions

SenSmart Universal Gas Detector Series

Ammonia Leak Detector Manual

Operation & Maintenance Manual

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

RK Hydrogen Sulfide Transmitter Operator s Manual

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

Model TS4000H. Intelligent Sensor for Toxic Gas Detection

Warranty Registration

TXgard-Plus. Flameproof Toxic and Oxygen Gas Detector with Non-intrusive One-man Calibration. Installation, Operation and Maintenance Instructions

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Software Version 2.01 LEVEL MONITOR MODEL 220

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

RK Carbon Monoxide Transmitter Operator s Manual

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

Fisher LCP100 Local Control Panel

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

GAS PLUS ALARM SYSTEM

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

RK-05 Carbon Monoxide Transmitter Operator s Manual

DE20 INSTRUCTION MANUAL

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

Transcription:

Field Mounted Display Module The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 04-06 General Monitors reserves the right to change published specifications and designs without prior notice. MANFMD Part No. Revision MANFMD C/04-06

This page intentionally left blank ii

Table of Contents TABLE OF FIGURES...V TABLE OF TABLES...VI ABOUT THIS MANUAL... 1 Format Conventions...1 Notes, Cautions, and Warnings...1 Menu Formats...1 Other Sources of Help...1 Contacting Customer Support...1 1.0 BEFORE INSTALLATION... 2 1.1 System Integrity Verification...2 1.2 Commissioning Safety Systems...2 1.3 Notes and Warnings...2 2.0 PRODUCT OVERVIEW... 3 2.1 General Description...3 2.2 Features and Benefits...3 2.3 Applications...4 2.4 Display Assembly...4 2.4.1 Display Electronics...4 2.4.2 Enclosure Options...5 3.0 INSTALLATION... 6 3.1 3.2 Upon Receipt of Equipment...6 Display Location Considerations...6 3.3 Installation For Use With Model TS400 or TS420...6 3.3.1 Intrinsically-Safe Installation...6 3.3.2 General Purpose Installation Without Relays...7 3.3.3 General Purpose Installation With Relays...8 3.3.4 Explosion-proof Installation of Model TS400 or TS420...10 3.4 Installation For Use With Model IR2100 or IR7000...12 3.4.1 Installation Without Relays...12 4.0 OPERATION... 17 4.1 Relay Reset...17 4.2 Test Gas Mode...17 4.3 Setup Options...17 4.3.1 Display Range...17 4.3.2 Relay Settings (Optional)...18 4.3.3 Program Review Mode...18 4.4 Model IR2100 and IR7000 Calibration...19 4.5 Maintenance...19 5.0 CUSTOMER SUPPORT... 21 iii

5.1 General Monitors Offices...21 6.0 SPECIFICATIONS AND ORDERING INFORMATION... 22 6.1 Intrinsically Safe Installation...22 6.2 Specifications...23 6.2.1 System Specifications...23 6.2.2 Electrical Specifications...23 6.2.3 Mechanical Specifications...23 6.2.4 Environmental Specifications...23 6.2.5 Cable Requirements...24 6.3 Engineering Documentation...24 6.3.1 Outline and Dimensional Drawing, FMD with IR2100/IR7000...24 6.3.2 6.3.3 Outline and Dimensional, FMD with X/P Housing for TS400/TS420...26 Outline and Dimensional, FMD with Polyester Housing for TS400/TS420...27 6.3.4 Outline and Dimensional, FMD with Polyester Housing for IR2100/IR7000...28 6.4 Spare Parts & Accessories...29 iv

Table of Figures Figure 1: Field Mounted Display with TS400... 3 Figure 2: FMD with IR2100 (Increased Safety)... 5 Figure 3: FMD with TS400 (Explosion-Proof)... 5 Figure 4: Terminal Connections, Intrinsically Safe Wiring... 7 Figure 5: Terminal Connections, General Purpose Installation, No Relays... 8 Figure 6: Terminal Connections, General Purpose Installation, with Relays... 9 Figure 7: Relay Protection Circuits for DC and AC loads... 9 Figure 8: Terminal Connections, Explosion-proof Installation of TS400/TS420... 10 Figure 9: Wiring Diagram, General Purpose Installation with Relays... 13 Figure 10: Wiring Diagram, Intrinsically-Safe and General Purpose Installation, No Relays... 14 Figure 11: Wiring Diagram, Explosion-proof Installation of TS400/TS420... 15 Figure 12: Wiring Diagram, Explosion-proof Installation of IR2100/IR7000... 16 Figure 13: FMD Setup Options... 20 Figure 14: Control Drawing... 22 Figure 15: Outline and Dimensional Drawing, FMD with IR2100/IR7000... 25 Figure 16: Outline and Dimensional, FMD with X/P Housing for TS400/TS420... 26 Figure 17: Outline and Dimensional, FMD with Polyester Housing for TS400/TS420... 27 Figure 18: Outline and Dimensional, FMD with Polyester Housing for IR2100/IR7000... 28 v

Table of Tables Table 1: TB2 Connections... 11 Table 2: TB1 Connections... 11 Table 3: TB3 Connections... 12 Table 4: MODBUS Terminal Connections... 12 Table 5: GM Locations... 21 Table 5: Maximum Cable Lengths for Intrinsically Safe Applications... 24 Table 6: Maximum Cable Lengths for General Purpose Installations... 24 Table 7: Maximum Cable Lengths for Explosion Proof Installations... 24 vi

About This Manual This manual provides instructions for installing, operating, and maintaining the General Monitors (GM) FMD, Field Mounted Display Module. The intended audience includes installation personnel, field service technicians, and other technical staff involved in installing and using a FMD. Format Conventions Several format conventions are used throughout this manual for Notes, Cautions, Warnings, and User Menus. These conventions are described below. Notes, Cautions, and Warnings NOTE: Notes provide supplementary detail such as exception conditions, alternate methods for a task, time saving tips, and references to related information. CAUTION: These notices describe precautions to prevent hazardous conditions that may damage the equipment. WARNING: These notices describe precautions to prevent hazardous conditions that may cause injury to people working with the equipment. Menu Formats FMD User Menu keywords and LED digital display messages are shown in bold (example: rst). Other Sources of Help General Monitors provides extensive documentation, white papers, and product literature for the company s complete line of safety products, many of which can be used in combination with the FMD. Many of these documents are available online at the General Monitors website at http://www.generalmonitors.com. Contacting Customer Support For additional product information not contained in this manual, please contact General Monitors Customer Support. Refer to Section 5.0 for contact information. 1

1.0 Before Installation 1.1 System Integrity Verification General Monitors mission is to benefit society by providing safety solutions through industry leading products, services, and systems that save lives and protect capital resources from the dangers of hazardous flames, gases, and vapors. General Monitors safety products should be handled carefully and installed, calibrated, and maintained in accordance with the individual product instruction manuals. To ensure operation at optimum performance, General Monitors recommends that prescribed maintenance procedures be followed. 1.2 Commissioning Safety Systems Before power up, verify wiring, terminal connections, and stability of the mountings for all essential safety equipment including, but not limited to: Power supplies Control modules Field detection devices Signaling / output devices Accessories connected to field and signaling devices After the initial power up and any factory specified warm-up period of the safety system, verify that all signal outputs, to and from the devices and modules, are within the manufacturers specifications. Initial calibration / calibration checking / testing should be performed according to the manufacturers recommendations and instructions. Proper system operation should be verified by performing a full, functional test of all component devices of the safety system, ensuring that the proper alarm levels occur. Fault / Malfunction circuit operations should be verified. 1.3 Notes and Warnings WARNING: WARNING: Installation and maintenance must be carried out by suitably skilled and competent personnel. Toxic, combustible, and flammable gases and vapors are very dangerous. Extreme caution should be used when these hazards are present. 2

2.0 Product Overview 2.1 General Description The General Monitors Model FMD (Figure 1) is a 4-digit LCD display module designed for use with General Monitors Models TS400, TS420, IR2100, and IR7000 Gas Detectors. It is available in an explosion-proof junction box for explosion-proof and general-purpose installations, and in a glass-reinforced polyester junction box for intrinsically safe, increased safety, and general-purpose installations. For intrinsically safe installations, the FMD is 4-20mA loop-powered and provides a local display for the TS400 and TS420 (Figure 1). The display range can be selected via a magnetically activated switch to match the sensor range on the TS400/TS420. The operational mode and gas concentration is displayed on the 4-digit display. For explosion-proof and general purpose installations, the FMD is +24VDC (nominal) powered. Optional relays provide output of warning, alarm and fault conditions at the sensor. Operating mode, display range, warning, and alarm set points are user-selectable via a magnetically activated switch. Relays are user-programmable as latching or non-latching, normally deenergized or normally energized. Latching relays can be reset via a remote reset input or via the magnetic switch. 2.2 Features and Benefits Figure 1: Field Mounted Display with TS400 Microprocessor-based electronics: Monitor fault conditions; sensor inputs and provide outputs in the form of display codes and relay contacts. Setup Mode: Allows the user to set parameters, such as, operating mode, display range, alarm set points, relay settings, etc. These parameters are viewed on the display during the setup mode. 3

Test Gas Mode: Allows the user to test the attached gas detector with the warning and alarm relays disabled. Program Review Mode: Allows verification of user programmable options. Protection Options: The Model FMD can be installed in either intrinsically safe or explosionproof installations providing maximum installation flexibility. 2.3 Applications The Model FMD is a 4-digit, field-mounted display for gas detection applications. Below is a partial list of applications: Refineries Drilling platforms and rigs Gas and oil production platforms Gas collection facilities LPG/LNG processing and storage Gas turbines Solvent vapors Chemical & petrochemical plants Paint spray booths Aircraft hangars 2.4 Display Assembly 2.4.1 Display Electronics The display electronics are contained within an encapsulated module that is mounted to the lid of the enclosure. A lanyard, connecting the lid and base of the enclosure, protects the module during installation, and simplifies field wiring. In the +24VDC-powered versions of the product, an on-board power supply produces all necessary voltages from the incoming +24VDC. In the loop-powered version, the on-board power supply produces the necessary voltages directly from the 4-20mA loop. The 4-20mA loop is monitored continuously by the microprocessor, which converts the incoming loop current to display values, depending on the selected display range and operating mode. Display range, operating mode, and warning and alarm set points can be programmed via the magnetic switch. All settings are stored in non-volatile memory and are retained if power is lost. 4

2.4.2 Enclosure Options The FMD is available in two enclosures. The explosion-proof enclosure (Figure 3) is provided to allow installation in hazardous areas where the protection method in the plant is explosionproof. The IR2100 and IR7000 require this enclosure since their outputs are not intrinsically safe. The explosion-proof enclosure can also be used to install the Model TS400 and TS420 in hazardous areas where the protection method is explosion proof. A zener barrier is mounted in the base of the enclosure to maintain the TS400 and TS420 intrinsically safe approvals. The polyester enclosure (Figure 2) is provided for intrinsically safe protected hazardous areas for the TS400 and TS420. The polyester enclosure can also be used for increased-safety installations of the IR2100/IR7000. NOTE: An explosion-proof conduit seal must be mounted to the TS400 or TS420 at the time of manufacture to maintain the explosion-proof approvals. Figure 2: FMD with IR2100 (Increased Safety) Figure 3: FMD with TS400 (Explosion-Proof) 5

3.0 Installation 3.1 Upon Receipt of Equipment All equipment shipped by General Monitors is packaged in shock absorbing containers that provide considerable protection against physical damage. The contents should be carefully removed and checked against the packing slip. If any damage has occurred or if there is any discrepancy in the order, notify General Monitors as soon as possible. All subsequent correspondence with General Monitors must specify the equipment part and serial numbers. Each Model FMD is completely checked at the factory; however, a complete checkout is necessary upon initial installation and start up to ensure system integrity. 3.2 Display Location Considerations There are no standard rules for display placement, since the optimum location varies with each installation. The customer must evaluate conditions at the facility to make this determination. Some factors to consider when selecting a display location: Where possible, the display should be easily accessible for installation, viewing of the display, and periodic maintenance. Observe the operating temperature limits of both the Field Mounted Display and the attached gas detector. Locate the units away from concentrated sources of heat. Although the FMD is highly EMI/RFI resistant, it should not be mounted close to radio transmitters or similar equipment. 3.3 Installation For Use With Model TS400 or TS420 The three distinct installation methods when the Field Mounted Display is to be used with the Model TS400 or TS420 are described below. 3.3.1 Intrinsically-Safe Installation For intrinsically safe installations, the FMD must be mounted in the polyester housing. A safety barrier must be mounted in the non-hazardous area (control room) to maintain the intrinsicsafety approval of the system. NOTE: Refer to Section 6.1 for intrinsic-safety wiring requirements. For this installation, the TS400 or TS420 is connected in series with the Field Mounted Display in the loop-powered configuration. A labeled terminal block is provided in the enclosure for field wiring of the gas detector and the Field Mounted Display (Figure 4). 6

+24V FMD RED 45198-4 IE FMD WHT TS400 RED TS400 WHT GND Figure 4: Terminal Connections, Intrinsically Safe Wiring +24VDC power is routed through the customer supplied safety barrier in the control room, into the +24V terminal in the enclosure. The loop return line is routed through the negative side of the customer supplied safety barrier to the GND terminal in the enclosure. The TS400/TS420 Red and White leads are connected to the TS400 RED and TS400 WHT terminals in the enclosure respectively. The TS400 Green lead must be attached to the EARTH terminal in the enclosure. The Field Mounted Display Red and White leads are connected to the FMD RED and FMD WHT terminals in the enclosure respectively. See Figure 9, for an example of Field Wiring. 3.3.2 General Purpose Installation Without Relays For general-purpose installations without relays, the FMD can be connected as either a looppowered or a +24VDC powered system. In loop-powered systems, connect as described in Section 3.3.1. NOTE: The customer supplied safety barrier is not necessary in this installation. For +24VDC-powered systems, a three-conductor cable is required. +24VDC and Ground are connected to the terminals marked +24VDC and GND respectively (Figure 5). 7

+24V 45198-3 DE A.O.(+) GND TS400 RED FMD RED TS400 WHT FMD BLU FMD BRN FMD WHT FMD WHT FMD BLK Figure 5: Terminal Connections, General Purpose Installation, No Relays The input to the customers 4-20mA monitoring device is connected to the terminal marked AO+ in the enclosure. The TS400/TS420 red lead is connected along with the FMD red lead to the terminal marked TS400 RED/FMD RED in the enclosure. The TS400/TS420 white lead and the FMD blue lead are connected to the terminal marked TS400 WHT/FMD BLU in the enclosure. The FMD brown lead is connected to the terminal marked FMD BRN. The FMD white lead is connected to the terminal marked FMD WHT in the enclosure. THE FMD black lead is connected to the terminal marked FMD BLK / FMD WHT in the enclosure. See Figure 10, for examples of Field Wiring. 3.3.3 General Purpose Installation With Relays For general-purpose installations with relays, the FMD must be connected as a +24VDCpowered system as described in Section 3.3.2. The terminal block provided for field wiring in the housing is different due to the need for additional terminals for the relay connections (Figure 6). The FMD wiring to the terminal block has been completed prior to shipment of the product. Field wiring is completed as follows: 1. Connect the +24VDC power supply and the TS400/420 Red lead to the terminal marked +24V. 2. Connect the +24VDC return line to the terminal marked GND. 3. Connect the TS400/420 white lead to the terminal marked AI. If the 4-20mA signal does not need to be monitored in the control room, jumper the terminal marked AO with the GND terminal. 4. If the 4-20mA signal must be monitored in the control room, connect the terminal marked AO to the wire connected to the 4-20mA signal-line in the control room. 8

Figure 6: Terminal Connections, General Purpose Installation, with Relays Connections for the relays are clearly marked on the base-plate inside the junction box (Figure 6). The labels for the alarm and warn relays are based on relay settings of normally deenergized. If either of these relays is configured as normally energized, the normally open (NO) and normally closed (NC) contacts must be reversed. The fault relay is configured at the factory as normally energized and cannot be changed. The labels for the relay contacts are based on this setting. See Figure 9, for an example of Field Wiring. WARNING: Inductive loads (bells, buzzers, relays, solenoids) must be clamped to avoid damage to the relays in the FMD. Unclamped inductive loads can cause voltage spikes in excess of 1000V.Refer to Figure 7for clamping requirements. Figure 7: Relay Protection Circuits for DC and AC loads 9

3.3.4 Explosion-proof Installation of Model TS400 or TS420 For explosion-proof installations, the TS400/TS420 must be ordered from the factory with the explosion-proof conduit seal installed and mounted in the explosion-proof enclosure. The TS400/420 and the FMD are shipped pre-wired in the housing. The TS400/420 wiring is done below the terminal board to TB4 (Figure 8) in the housing to separate the intrinsically safe wiring from the XP rated wiring above the terminal board. An included shunt-diode barrier is mounted in the base of the explosion-proof enclosure to protect the TS400/TS420 s intrinsically safe outputs. Field wiring to the control room must be explosion-proof rated. Field wiring is completed using the terminal blocks marked TB1 and TB2 in the junction box. A label is mounted to the lid of the junction box and terminals are clearly marked to help simplify field wiring. +24VDC NOMINAL +26VDC MAX. CHECK WIRING BEFORE ENERGIZING 81219-1 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 Figure 8: Terminal Connections, Explosion-proof Installation of TS400/TS420 10

TB2 is used to make the power, ground and 4-20mA connections. The terminals are as follows: TB 2 Pin Function 1 Ground 2 AO 3 AO Return 4 +24VDC 5,6 Unused Table 1: TB2 Connections Connect a +24VDC power supply to TB2-4 and power supply return to TB2-1. If the 4-20mA is to be monitored in the control room, connect the control room input to TB2-2. If the 4-20mA is not to be monitored in the control room, jumper TB2-2 to TB2-3. If the optional relays are installed, relay connections are made on terminal block TB1. The terminals are as follows: TB2 PIN Function 1 Warn NO 2 Warn NC 3 Warn Com 4 Alarm NO 5 Alarm NC 6 Alarm Com 7 Fault NO 8 Fault NC 9 Fault Com 10 Relay Reset 11 Relay Reset Rtn Table 2: TB1 Connections The labels for the alarm and warn relays are based on relay settings of normally de-energized. If either of these relays is configured as normally energized, the normally open (NO) and normally closed (NC) contacts must be reversed. The fault relay is configured at the factory as normally energized and cannot be changed. The labels for the relay contacts are based on this setting. TB1-10 and TB1-11 are provided for the connection of a remote switch to reset latched relays. Connect a normally open, momentary switch between these terminals. Pressing the switch will reset any latched warn or alarm relays. NOTE: If the optional relays are not installed, terminal block TB1 will not be installed. See Figure 11, for an example of field wiring. 11

3.4 Installation For Use With Model IR2100 or IR7000 When used as a display for the Model IR2100 or IR7000, the FMD must be mounted in the explosion-proof junction box. A wiring label is included on the lid of the junction box to simplify field wiring. 3.4.1 Installation Without Relays Terminal Block TB3 provides screw terminal connections for wiring of the Model IR2100 or IR7000. The gas detector wires should be stripped to approximately 0.25 inches to prevent the possibility of shorting. The TB3 terminals are as follows: TB3 Pin Function 1 Chassis Ground 2 Cbuss+ 3 Cbuss- 4 +24VDC 5 +24V Common 6 4-20mA 7 Remote Cal Table 3: TB3 Connections Field wiring is made on terminal block TB2 as described in Section 3.3.4 above. Two additional terminals are provided on TB2 for field wiring of the two MODBUS connections from the gas detector. The additional terminals are: TB2 Pin Function 5 Cbuss+ 6 Cbuss- Table 4: MODBUS Terminal Connections NOTE: Terminal Block TB1 and J2 are not installed since there are no relays. See Figure 12 for an example of field wiring. 3.4.2 Installation With Relays For units with the optional relays installed, the installation is identical to that described in Section 3.4.1 with the exception that terminal block TB1 is installed to allow field wiring of the relays. For a description of terminal block TB1 and how to field wire the relays, please refer to Section 3.3.4. 3.4.3 Zero Switch Installation The zero switch option is installed identically to the FMD installation without relays as described in Section 3.4.1 above. For a description of the Zero and Calibration procedure for the Model IR2100 or IR7000, please refer to the appropriate Instruction Manual. 12

3.5 Applying Power Before applying power to the system for the first time, all wiring connections should be checked for correctness, and the housing cover should be securely fastened. Refer to the operating manual of the attached gas detector for required warm-up or stabilization period. Refer to Section 3.3.3. Figure 9: Wiring Diagram, General Purpose Installation with Relays 13

Intrinsically Safe Installation Refer to Section 3.3.1 General Purpose Installation without Relays Refer to Section 3.3.2 Figure 10: Wiring Diagram, Intrinsically-Safe and General Purpose Installation, No Relays 14

Explosion-Proof Installation of TS400/TS420 with Relays Refer to Section 3.3.4 Explosion-Proof Installation of TS400/TS420 without Relays Refer to Section 3.3.4 Figure 11: Wiring Diagram, Explosion-proof Installation of TS400/TS420 15

Installation for IR2100/IR7000 without Relays Refer to Section 3.4.1 Installation for IR2100/IR7000 with Relays Refer to Section 3.4.2 Figure 12: Wiring Diagram, Explosion-proof Installation of IR2100/IR7000 16

4.0 Operation This chapter discusses what general maintenance to perform, describes the electrical inputs, outputs, accepting & resetting alarm, calibration & fault conditions, and fault diagnostics. 4.1 Relay Reset If the optional relays are installed and are set to latching, they must be manually reset after an alarm condition occurs. To reset the relays, hold the magnet over the GMI logo on the cover of the housing for approximately 5 seconds. The display will show a set of horizontal bars for about 5 seconds. When the word clr appears on the display, move the magnet away from the logo and then reapply it. All latching relays will now be reset and the FMD will return to normal operation automatically. Refer to Figure 13: FMD Setup Options for menu options. NOTE: A relay can only be reset when the displayed gas level is below the set point for the relay. 4.2 Test Gas Mode Test Gas Mode provides the capability to test the gas detector response with the relays disabled. To enter test gas mode, hold the magnet over the GMI logo on the cover of the housing for approximately 5 seconds. The display will show a set of horizontal bars for about 5 seconds. Remove the magnet when clr is displayed. The display will then begin scrolling through a list of setup options. When the display shows the word test, apply and remove the magnet again. The relays are now disabled. The display will flash the current gas reading to show that the relays are disabled. WARNING: Alarms via the 4-20mA output and MODBUS communications cannot be disabled by the Field Mounted Display. Ensure that these alarms are disabled externally. Apply the test gas to the gas detector. The display will show the flashing gas reading for as long as the gas is applied. Remove the gas when testing is completed. When the gas concentration falls below 5% FS, the FMD will return to normal operation, confirmed by the non-flashing display. Refer to Figure 13: FMD Setup Options for menu options. 4.3 Setup Options Figure 13 provides a flow diagram for navigating the setup options menu on the Model FMD. 4.3.1 Display Range The full-scale range of the display is field selectable. This allows the field-mounted display to be used with all models of the TS400, TS420, IR2100, and IR7000. To select a new display range, hold the magnet over the GMI logo on the cover of the housing for approximately 5 seconds. The display will show a set of horizontal bars for about 5 seconds. 17

When the word clr appears on the display, remove the magnet. The display will begin scrolling through a list of setup options. When the word FACt is displayed, apply and remove the magnet to the GMI logo again. The display will now scroll through a list of available setup options. When the word rng appears, apply and remove the magnet. The unit will display the currently selected display range. To select a new display range, apply and remove the magnet until the desired range appears. The new display range is now stored in non-volatile memory and will be retained if power is removed. The display will continue scrolling. When End is displayed, apply and remove the magnet. The display will now continue to scroll through a list of setup options. When done is displayed, apply and remove the magnet and the unit will return to normal operation. NOTE: The high and low alarm relay set points are automatically scaled to the new display range. The scaling will maintain the alarms at the same percent of full-scale as the previous setting. The unit is shipped from the factory with the warn set point at 30% of full-scale, and the alarm set point at 60% of full-scale. If it is desired to change the relay settings, see the next section. 4.3.2 Relay Settings (Optional) The high and low alarm relay settings are field selectable. They can be set as latching or nonlatching, and normally energized or de-energized. The alarm set points are also programmable. The fault relay settings are not field selectable and are factory set as energized and nonlatching. To change the relay settings, hold the magnet over the GMI logo on the cover of the housing for approximately 5 seconds. The display will show a set of horizontal bars for about 5 seconds. When the word clr appears on the display, remove the magnet. The display will begin scrolling through a list of setup options. When the word FACt is displayed, apply and remove the magnet to the GMI logo again. The display will now scroll through a list of available setup options. When the word AL appears, apply and remove the magnet. To change the high alarm settings, apply the magnet to the GMI logo when the display reads Hi. The current setting for latching (LA) or non-latching (nl) is displayed first. Apply and remove the magnet until the desired setting is displayed. Next, the current setting for normally energized (En) or de-energized (de) is displayed. Apply and remove the magnet until the desired setting is displayed. Finally, the high alarm set point is displayed. Apply and remove the magnet until the desired setting is displayed. Apply the magnet when the words End and done appear to return to normal operation. 4.3.3 Program Review Mode The field-mounted display has a program review mode that allows the user to review all of the user-selectable settings. To access the program review mode, hold the magnet over the GMI logo on the cover of the housing for approximately 5 seconds. The display will show a set of horizontal bars for about 5 seconds. When the word clr appears on the display, remove the magnet. The display will now scroll through a set of options. When the display reads Pr, reapply the magnet. The display will now scroll through all of the current settings for the unit. After all settings have been displayed, the unit will return to normal operation automatically. See Figure 13 for the user programmable options for the Model FMD. 18

4.4 Model IR2100 and IR7000 Calibration The field-mounted display simplifies field zeroing and calibration of the IR2100 and IR7000 by providing cues on the display for the operator. Please refer to the appropriate instruction manual for the gas detector being used for complete calibration instructions. To re-zero the gas detector or perform a complete gas calibration, apply the magnet to the GMI logo on the display cover. The display will show a set of horizontal bars for about 5 seconds. When the word clr appears on the display, remove the magnet. The display will now scroll through a set of options. When the word CAL is displayed, apply and remove the magnet. After a few seconds CAL will begin to flash, followed by a flashing AC on the display. The gas detector is now automatically re-zeroing. NOTE: For the Model IR7000, Nitrogen must be applied to the gas detector at the time of zeroing. Refer to the IR7000 Manual for instructions. After approximately 2 minutes, the display will show a non-flashing AC. This means that the zero operation is complete. If gas calibration is not required, simply wait 30 seconds and the gas detector and FMD will return to normal operation. NOTE: The CAL option is only available in IR2100 mode. If gas calibration is required, when the AC stops flashing, apply the magnet to the GMI logo again. The word CAL will be displayed for a few seconds, followed by a flashing CP. Apply the calibration gas as described in the instruction manual for the gas detector. After approximately 30 seconds, the display will show a non-flashing CP, which means the gas calibration is proceeding. When calibration is complete, the display will show CC. Remove the calibration gas. When the gas at the detector has fallen below 5% FS, the gas detector and FMD will return to normal operation. 4.5 Maintenance For routine maintenance for the attached gas detector please refer to the appropriate instruction manual. The field-mounted display requires no routine maintenance, with the exception that the display window may need to be cleaned occasionally, depending on the conditions at the installation site. Use a commercial window cleaning solution and a soft cloth to clean the display window. 19

Operate "clr" N "Pr" "test" N "CAL" N "FACt" "done" * Reset Relays Mode Test Gas Mode IR2100/7000 Zero and Calibration Operating Mode Choose from TS400, TS420, IR2100 Range Apply Gas and Remove when complete Zero Display "ZEro" Apply 4.00mA and Zero Display Hi Alm nl/la Hi Alm de/en Span Display "SPAn" Apply 12.00mA and Span Calibrate Display Hi Setpoint Select Display Range "rng" Select from available ranges (see Manual) Low Alm nl/la Low Alm de/en Alarm Settings "AL" High Alarm "Hi" Latching/Non-Latching Energized/De-Energized Setpoint Low Setpoint N "End" LowAlarm "Lo" Latching/Non-Latching Energized/De-Energized Setpoint * Menu does not appear in TS400/TS420 Figure 13: FMD Setup Options 20

5.0 Customer Support 5.1 General Monitors Offices Area UNITED STATES Corporate Office: 26776 Simpatica Circle Lake Forest, CA 92630 9776 Whithorn Drive Houston, TX 77095 Table 5: GM Locations Phone/Fax/Email Toll Free: +1-800-446-4872 Phone: +1-949-581-4464 Fax: +1-949-581-1151 Email: info@generalmonitors.com Phone: +1-281-855-6000 Fax: +1-281-855-3290 Email: gmhou@generalmonitors.com UNITED KINGDOM Heather Close Lyme Green Business Park Macclesfield, Cheshire, United Kingdom, SK11 0LR IRELAND Ballybrit Business Park Galway, Republic of Ireland SINGAPORE No. 2 Kallang Pudding Rd. #09-16 Mactech Building Singapore 349307 MIDDLE EAST LOB12, #G20 P.O. Box 61209 Jebel Ali, Dubai United Arab Emirates Phone: +44-1625-619-583 Fax: +44-1625-619-098 Email: info@generalmonitors.co.uk Phone: +353-91-751175 Fax: +353-91-751317 Email: info@gmil.ie Phone: +65-6-748-3488 Fax: +65-6-748-1911 Email: genmon@gmpacifica.com.sg Phone: +971-4-8815751 Fax: +971-4-8817927 Email: gmme@emirates.net.ae 21

6.0 Specifications and Ordering Information 6.1 Intrinsically Safe Installation Model FMD Figure 14: Control Drawing 22

6.2 Specifications 6.2.1 System Specifications Display Ranges: 1.0, 3.0, 5.0, 10.0, 20.0, 25.0, 50.0, 100, 500, 1000, 2000, 5000 Electrical Classification: Explosion Proof Housing Class I, Div. 1 & 2, Groups B, C & D, T6; Class II, Groups E, F & G, T6; Class III, T6 Class I, Zones 1 & 2, Group IIC, T6 Polyester Housing EEx ia / EExe, IIC, T6; Class I, Groups A, B, C & D, T6; Class II, Groups E, F & G, T6 Class I, Zone 0,1&2, Group IIC, T6* Accuracy: ±1% of input signal Approvals: CSA, UL, ATEX, and CE Marking. Warranty: Two years NOTE: Zone 0 and Group A applicable for Intrinsically Safe version only. 6.2.2 Electrical Specifications Input Power: 3.5 22mA loop-powered or 20 36VDC @ 50mA max. Relay Ratings: 2A @ 30VDC, 0.5A @ 125VAC resistive load max. Status Indicators: 4-digit, backlit LCD display 6.2.3 Mechanical Specifications Explosion-proof housing: Dimensions: Mounting Holes: Weight: Polyester Housing: Dimensions: Mounting Holes: Weight: 6.4 L x 4.1 W x 3.3 H (161mm x 104mm x 84mm) 5 (127mm) center to center 5.6 lbs (2.24 kg) 4.72 L x 4.72 W x 3.15 H (120mm x 120mm x 80mm) 4.07 (103mm) corner to corner 2.4 lbs (1 kg) 6.2.4 Environmental Specifications Operating Temperature Range TS400/TS420: -4 F to +122 F (-20 C to +50 C) when used with: IR2100: -40 F to +167 F (-40 C to +75 C) R7000: -40 F to +149 F (-40 C to +65 C) Storage Temperature Range: -40 F to +185 F (-40 C to +85 C) Operating Humidity Range: 5% to 100% RH non-condensing 23

6.2.5 Cable Requirements For Intrinsically Safe applications of the FMD with the TS400/TS420 and a 300Ω input impedance device, the following maximum cable lengths apply: 14 AWG 6,700 ft. 2,000m 16 AWG 4,200 ft. 1,280m 18 AWG 2,750 ft. 840m 20 AWG 1,750 ft. 530m 22 AWG 1,150 ft. 350m Table 6: Maximum Cable Lengths for Intrinsically Safe Applications For General Purpose installations (+24V powered) of the FMD with the TS400/TS420 and a 300Ω input impedance device the following maximum cable lengths apply: 14 AWG 20,000 ft. 6,100m 16 AWG 13,000 ft. 4,000m 18 AWG 8,500 ft. 2,600m 20 AWG 5,500 ft. 1,700m 22 AWG 3,500 ft. 1,100m Table 7: Maximum Cable Lengths for General Purpose Installations For Explosion Proof Installations of the FMD with the TS400/TS420 and the Zener Barrier and a 30Ω input impedance device, the following maximum cable lengths apply: 14 AWG 1,900 ft. 580m 16 AWG 1,200 ft. 365m 18 AWG 800 ft. 245m 20 AWG 500 ft. 150m 22 AWG 350 ft. 110m Table 8: Maximum Cable Lengths for Explosion Proof Installations For installation of the FMD with the IR2100 or IR7000, please see the respective Operations Manual. NOTE: These are maximum cable lengths. Conservative design practice dictates shorter cable runs wherever possible. 6.3 Engineering Documentation 6.3.1 Outline and Dimensional Drawing, FMD with IR2100/IR7000 24

Ref Drawing 81041 Figure 15: Outline and Dimensional Drawing, FMD with IR2100/IR7000 25

6.3.2 Outline and Dimensional, FMD with X/P Housing for TS400/TS420 PROCESS CONTROL EQUIPMENT FOR USE IN CLASS I, DIV 1, GROUPS B, C AND D HAZARDOUS LOCATIONS. PROVIDES INTRINSIC SAFE OUTPUTS FOR USE IN CLASS I, DIV 1, GROUPS B, C AND D HAZARDOUS LOCATIONS WHEN CONNECTED IN ACCORDANCE WITH DRAWING 81218. OPEN CIRCUIT BEORE REMOVING COVER. KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE. SERIAL NO. CONFIG. NO. MANUAL CONDUIT SEALS REQUIRED WITHIN 50mm OF ENCLOSURE. READ AND UNDERSTAND THE INSTRUCTION MANUAL BEFORE OPERATING OR SERVICING. Figure 16: Outline and Dimensional, FMD with X/P Housing for TS400/TS420 26

6.3.3 Outline and Dimensional, FMD with Polyester Housing for TS400/TS420 Figure 17: Outline and Dimensional, FMD with Polyester Housing for TS400/TS420 27

6.3.4 Outline and Dimensional, FMD with Polyester Housing for IR2100/IR7000 Figure 18: Outline and Dimensional, FMD with Polyester Housing for IR2100/IR7000 28

6.4 Spare Parts & Accessories General Monitors Screwdriver 10450-1 Calibration Magnet 30060-1 Replacement Fuse (63mA) 951-216 29

ADDENDUM Product Disposal Considerations This product may contain hazardous and/or toxic substances. EU Member states shall dispose according to WEEE regulations. For further General Monitors product WEEE disposal information please visit: www.generalmonitors.com/customer_support/faq_general.html All other countries or states: please dispose of in accordance with existing federal, state and local environmental control regulations. 30