Hold-open device Hold-open sstem DOA TS7EMR TS7EMF
DOA TS 7 EMF DOA TS 7 EMR Hold-open device Hold-open sstem The proven solution for controlled hold-open of fire and smoke check doors Universal application capabilit, stable hold-open point and assured qualit. The DOA TS 7 EMF is a combination of hdraulic door closer and electromagnetic hold-open unit. In conjunction with a smoke detection sstem (e.g. DOA Z-K/S), the TS 7 EMF can be used as a hold-open sstem for fire and smoke check doors. Also available is the DOA TS 7 EMR as an integrated sstem comprising hdraulic door closer, electro-magnetic hold-open device, power Benefits For the trade Efficient stocking thanks to non-handed, modular sstem Range of arm assemblies and accessories to provide an ideal solution even for special applications. For the fabricator/installer Eas to fix. Time-saving electrical connections. No adjustment of the holdopen point necessar. Optimum adaptabilit thanks to adjustable latching action. suppl unit and smoke detector. In the case of both sstems, hold-open of the door is performed under electromagnetic control. In the event of a fire, the door is reliabl closed b the integral hdraulic closer. The closing ccle is also initiated b manual door operation or automaticall in the event of a power failure. Qualit assured manufacture to DIN ISO 9001, EN 9001, BS 5750 Certified and verified b BSI Qualit Assurance Reg.-No. Q 64, FM 10756 For the specifier/architect Attractive, compact design. Wide range of applications. Hold-open possible between approx. 75 and 180. For the user To hold open, the door simpl has to be opened to the required point and released. Free selection of the holdopen point (opening angles over 75 ); variable at an time without the need for adjustment of setting controls. Convertible to free-swing door closer. Data and features TS 7 EMF TS 7 EMR1) Closing force Spring strength EN EN 4 5 6 4 5 6 Standard doors ) 1100 mm 0 mm 1400 mm Fire and smoke 1100 mm check doors ) 0 mm 1400 mm Non-handed Arm Standard Slide channel Closing speed variable b valve Latching speed b arm variable b valve Backcheck Delaed action Hold-open point variable (opening angles between 75 and 180 ) Free-swing arm assembl " " Weight in kg,4 4,9 Dimensions Length 0 60 in mm Overall depth,5 5 Height 60 65,5 Door closer compliant with EN 14 Hold-open device compliant with EN 15 Functions Smoke detector Door release Power suppl Smoke detection Scattered light principle Optical Connection of -wire sstem other detectors Smoke switch Total installed power (max.) for other detectors in W 5,7 Indicators Alarm red LED Standb green LED Input voltage 4VDC 0VAC ±% ±10% Output voltage 4VDC Power input max. in W 14,6 Floating change-over contact, 4VAC/DC safet extra-low voltage (SELV) A Reset Automatic with change-over to manual reset Test port for function test Connection terminals for external manual release Class of protection IP0 Ambient temperature range in C, +0 Yes No " Option 1) Also available as slave unit for equipping double doors (no integral power suppl unit or smoke detector) ) For applications involving particularl high or heav doors, and doors which have to close against wind or draught conditions, the next larger closer size should be selected. CERTIFIRE Approved CF117 ITT10 IMM/MM40
Standard and optional functions The closing speed of the DOA TS 7 EMF and TS 7 EMR is infinitel variable b means of a valve. In addition, the latching action can be adjusted via the closer arm. The electro-magnetic holdopen device is integrated in the hdraulic door closer. The hold-open point (available from an opening angle of 75 ) is freel selectable. The door merel has to be opened to that angle required and then released. Depending on the door width and the size of the opening angle, a degree of fall-back of between 1 and is possible. 1 Infinitel variable closing speed Infinitel variable latching action (adjustable at arm) Hold-open range 75 1 Free-swing arm assembl (option) Equipped with a free-swing arm assembl, the DOA TS 7 EMF and TS 7 EMR can also be emploed where doors are required to operate normall functioning in the same wa as doors without a door closer. If the door leaf is opened wide (min. 75 ), the closer spindle is held in this position b the electromagnetic hold-open device in the hdraulic closer bod. However, the door can be freel operated b virtue of the free-swing function integrated in the arm. In the event of a fire or power failure, the door is reliabl and securel closed automaticall b the hdraulic door closer. Tpical applications include fire and smoke check doors in senior citizen homes, homes for the disabled and hospitals etc. Note: In the case of double doors, the free-swing function ma onl be used on the active leaf. 1 Free-swing range Full controlled closing (de-energised) 1 F Approval certification TS 7 EMF The DOA TS 7 EMF has been approved as compliant with national building regulations b the German Institute for Building Technolog DIBt, Berlin, in conjunction with the smoke detector sstems DOA Z-K/S, DOA Z and other reputable smoke detector sstems. Acceptance inspection is mandator. When using the TS 7 EMF fixed to the top jamb, approval certification is additionall required in conjunction with the fire and smoke check door concerned. TS 7 EMR The DOA TS 7 EMR has been approved as a hold-open sstem b the German Institute for Building Technolog DIBt, Berlin. Acceptance inspection is mandator. Approval certification is additionall required in conjunction with the fire and smoke check door concerned.
DOA TS 9 7 EMF DOA TS 7 EMR Hold-open Gleitschienen- device Hold-open Türschließersstem sstem Applications and installation 51 4 60,5 98 8 84 50 50 DOA TS 7 EMF hold-open device 5,5 51,5 108,5 91,5 5 60 65,5 101 11 18 18 51 DOA TS 7 EMR hold-open sstem 5 410 5,5 51,5 108,5 91,5 65,5 101 11 18 18 4 51 DOA TS 7 EMF slave unit for hold-open sstem 4
Applications and installation min. 55/max. 65 mm 8 110 4 V DC 95,5 67,5 1 109,5 19,5 50 50 Door opening up to 180 requires min. 6 mm pivot offset at the hinges or a corresponding wall recess for the door closer. Standard fixing of DOA TS 7 EMF hold-open device (door leaf fixing). Example shows LH door (ISO 6); mirror arrangements appl to RH (ISO 5) doors. 109,5 4,5 19,5 50 50 ø 0 (4 V DC) 1 8 67,5 7,5 min. 55/max. 65 mm Door opening up to 180 with standard arm onl possible where 70 mm Top jamb fixing of DOA TS 7 EMF hold-open device (frame installation). 41,5 19,5 00 5 14 0 0 V AC min. 55/ max. 65 mm 4 65 1,5 69,5 109,5 6 18,5 40,5 Door opening up to 180 with standard arm onl possible where 70 mm DOA TS 7 EMR. hold-open sstem. Example shows RH door (ISO 5); mirror arrangements appl to LH (ISO 6) doors. 5
DOA TS 7 EMF Accessories Mounting backplate For pull and push side fixing. For mounting the DOA TS 7 EMF to fire and smoke check doors and also doors in which no direct fixing is possible; with hole group per Supplement 1 to EN 14. 4 65 11 0,5 0 14 4 ø 5,5 ø 0 60 Upstand bracket For pull-side installation of the arm on particularl narrow door frames. 58 6 1 6 6
DOA TS 7 EMF DOA TS 7 EMR Accessories Extended adjustable arm For push side fixing. For adapting the DOA TS 7 EMF/EMR to door sets with frame reveal depths between 70 and 15 mm. 70 15 1 50 M 10 95 min. 05 mm/max. 40 mm Extended arm assembl For push side fixing. For increasing the door opening to 180 in door sets with a frame reveal depth of max. 70 mm and where < 70 mm. 70 1 0 M 10 95 min. 5 mm/max. mm DOA HT manual switch According to the code of practice for hold-open sstems issued b the DIBt, Berlin, a manual release switch must be installed in the case of free-swing door closers. HT-UP HT-AP 8 Tür schliessen 8 AP 51 18 UP 7
DOA TS 7 EMF DOA TS 7 EMR Example applications Hold-open sstem DOA TS 7 EMF + Z-K + x 0 VAC Z-K TS 7 EMF HT HT NC C NO 8 9 7 10 6 14 5 1 4 18 k Ω 14 18 k Ω 1 5 5 1 11 11 9 9 14 18 k Ω 7 7 Z-K DOA TS 7 EMF Junction box b others 10 A fuse b others 0 V AC ± 10% Z-K Z-K Z-K TS 7 EMF HT = x 0,5 mm = x 0,5 mm = x 0,5 mm = x 0,5 mm DOA TS 7 EMR + x 0 VAC TS 7 EMR TS7EMR HT 18 k Ω 14 6 5 4 1 1 11 11 10 9 8 7 C NC NO HT 18 k Ω 14 18 k Ω 5 1 9 7 14 1 1 0 V AC ± 10% Junction box b others 10 A fuse b others TS 7 EMR TS 7 EMR HT = x 0,5 mm = x 0,5 mm = x 0,5 mm 8
Hold-open sstems Regulations/Information The use of hold-open sstems is subject to special regulations based on official approval requirements. These relate in particular to the final inspection (acceptance), continuous monitoring and maintenance. The regulations and instructions provided below are intended as an aid, pursuant to statutor regulations that appl e.g. in German, to ensure that all participants are properl informed of the most important requirements that relate to the installation and operation of hold-open sstems. Further information can be found in the following documents: Richtlinien für Feststellanlagen des Deutsches Instituts für Bautechnik, Berlin [Code of practice relating to hold-open sstems issued b the German Institute for Building Technolog, Berlin] General building regulations pertaining to the approval of the hold-open sstem concerned EN 15 1. General 1.1 In the case of fire doors (and similar shutters/closures/ barriers) that are held open b hold-open sstems, the sweep area necessar for the closing operation must be kept constantl clear. This area must be clearl identified b lettering, floor markings or similar. Where necessar, structural measures must also be implemented to ensure that cables, leads, lines, pipes, stored/deposited goods or components (e.g. false ceilings or other overhead items/elements) are reliabl prevented from falling into the sweep area. 1. Wherever possible, smoke detectors should be used for hold-open sstems. For hold-open sstems for fire doors in emergenc escape routes, smoke detectors must be used. 1. Each hold-open device must also be capable of being released b hand, without adversel affecting the functional capabilities of the automatic release device. In the case of door closers with electro-magnetic holdopen, the manual release ma be performed b a small tug applied to the door leaf. If holding electro-magnets or free-swing door closers are used, a pushbutton must be provided to facilitate manual release. The manual release pushbuttons emploed for this purpose must be red and carr the wording Close Door or equivalent. The pushbutton must be located in the immediate vicinit of the door and must not be concealed b the door when this is held open.. Final inspection (acceptance).1 In German and countries governed b DIN regulations: Following on-site installation of the operable hold-open sstem, its functional integrit and qualit of installation must be confirmed b an acceptance inspection procedure. The acceptance inspection ma onl be performed b skilled personnel of manufacturers of monitoring and/or hold-open devices, skilled personnel authorized b same, or skilled personnel from an accredited inspection agenc.. In German and countries governed b DIN regulations: Once the acceptance inspection has been successfull completed, the operator shall permanentl fix on the wall in the immediate vicinit of the door, a plate supplied b the manufacturer of the hold-open sstem measuring 105 mm x 5 mm and carring the inscription Hold-open sstem Inspected b... (compan logo with month and ear of acceptance inspection) or equivalent. The operator is to be provided with a certificate detailing the successful acceptance inspection; this certificate must be retained b the operator.. Periodic surveillance.1 The hold-open sstem must be kept b the operator in a constantl good operating condition, and inspected at least once a month to ensure that it is functioning properl.. In addition, the operator is obliged at least once a ear, or at shorter intervals if specified in the approval certificate, to inspect all the devices to ensure that the are operating and interacting properl and without fault, and to carr out or instigate adequate maintenance. The associated test, inspection and the maintenance work ma onl be performed b an expert or an appropriatel trained person.. The scope, result and time of the periodic inspection are to be recorded. These records must be retained b the operator. 9
DOA TS 7 EMF DOA TS 7 EMR Hold-open device Hold-open sstem Standard equipment and optional accessories TS 7 EMF hold-open device Pull-side door leaf fixing Standard arm Free-swing arm Extended adjustable arm Extended arm assembl Mounting backplate Upstand bracket Manual switch HT-UP 5901 HT-AP x 7540xx00 x 50005xx x 7540xx01 x 7540xx4 700xx10 80014xx 590 Spring strength EN 4 50101xx Spring strength EN 5 50401xx Spring strength EN 6 50701xx # # # # # # # # # TS 7 EMF hold-open device Push-side top jamb fixing Spring strength EN 4 51101xx Spring strength EN 5 51401xx Spring strength EN 6 51701xx # # # # # # TS 7 EMR hold-open sstem Spring strength EN 4 54101xx Spring strength EN 5 54101xx Spring strength EN 6 541401xx # # # Slave unit for TS 7 EMR hold-open sstem Spring strength EN 4 540901xx Spring strength EN 5 541001xx Spring strength EN 6 541101xx # # # Order No. = Closer bod separate = Arm assembl separate # = Optional accessor Colour xx Silver 01 Special colour 09 10
DOA TS 7 EMF specification text Hold-open device with electrohdraulic hold-open function and integral pressure compensation feature for stable, infinitel variable and temperature-immune hold-open positions at door opening angles between 75 and 180. Closing speed and latching action infinitel variable. Non-handed. Operating voltage 4 V DC. General building regulations approval issued b DIBt, Berlin, for use in hold-open sstems. Acceptance inspection mandator. Installation Y Door leaf fixing Y Top jamb fixing Spring strength Y EN 4 Y EN 5 Y EN 6 Arm tpe Y Standard Y Free-swing Y Extended adjustable arm Y Extended arm assembl Accessories Y Mounting backplate Y Upstand bracket Y Manual switch Colour Y Silver Y Special colour (sim. to RAL ) Make DOA TS 7 EMF TS7EMF DOA TS 7 EMR specification text Hold-open device with electro-hdraulic hold-open function and integral pressure compensation feature for stable, infinitel variable and temperatureimmune hold-open positions at door opening angles between 75 and 180. With integral power suppl unit and smoke detector. Closing speed and latching action infinitel variable. Non-handed. Connections for further detectors, external manual release device and floating alarm contact. Designed for 0 V AC power suppl, operating voltage 4 V DC. Generall approved as holdopen sstem per building regulations b DIBt, Berlin. Acceptance inspection mandator. Y Slave unit for double doors, without power suppl unit and smoke detector. Operating voltage 4 V DC Spring strength Y EN 4 Y EN 5 Y EN 6 Arm tpe Y Standard Y Free-swing Y Extended adjustable arm Y Extended arm assembl Accessories Y Manual switch Colour Y Silver Y Special colour (sim. to RAL ) Make DOA TS 7 EMR TS7EMR 11
Division Door Control worldwide www.dorma.com Central Europe DOA GmbH + Co. KG Breckerfelder Str. 4 48 D-5856 Ennepetal Tel. +49 /79-0 Fax +49 /79-495 Scanbalt DOA Danmark A/S Sindalvej 6 8 DK-610 Rødovre Tel. + 44/54 0 00 Fax + 44/94 95 04 Australia DOA Door Controls Pt. Ltd. 5 Abbott Road Hallam/Victoria 80 Australia Tel. +61 /97 96555 Fax +61 /9796955 South Africa DOA Door Controls (Pt.) Ltd. Kings Court, 4A Mineral Crescent ZA-000 Crown/Gauteng Johannesburg Tel. +7 11/8 0080 Fax +7 11/80091 Door Control Automatic Glass Fittings and Accessories Securit/ Time and Access (STA) Movable Walls Emerging Markets DOA GmbH + Co. KG Breckerfelder Str. 4 48 D-5856 Ennepetal Tel. +49 /79-0 Fax +49 /79-495 Far East DOA Door Controls Pte. Ltd. No. Jalan Terusan, Jurong Singapore 61985 Tel. +65 6 68/76 Fax +65 6 65/79 14 France DOA France S.A.S. Europarc 4, rue Eugène Dupuis F-94046 Créteil Tel. + 1/41 94400 Fax + 1/4194401 Gulf DOA Gulf Door Controls FZE Jebel Ali Free Zone, Roundabout 8, Unit VC 0 Dubai, United Arab Emirates Tel. +971 48/8 90 14 Fax +971 48/8 90 North America DOA Architectural Hardware DOA Drive, Drawer AC Reamstown, PA 17567 Tel. +1-800-5-848 Fax +1-800-74-974 South America DOA Sistemas de Controles para Portas Ltda. Av. Piracema, 1400 Centro Empresarial Tambore CEP 06400 Barueri/ São Paulo, Brasil Tel. +55 11/41 91 44 Fax +55 11/41 91 1 9 South-East Europe DOA AUSTRIA GmbH Pebering Strass A-501 Eugendorf Tel. +4 6 5/ 8488 Fax +4 6 5/ 8491 South Europe DOA Italiana S.r.l. Via. A. Canova 44/46 I-005 Lissone (MI) Tel. +9 09/4 40 1 Fax +9 09/4 40 10 DOA Ibérica, S.A. Camino San Martin de la Vega, 4 E-8500 Arganda del Re (Madrid) Tel. +4 91/8 757850 Fax +4 91/8757881 UK/Ireland DOA UK Ltd. Door Controls Division Wilbur Wa GB-Hitchin Hertfordshire SG4 0AB Tel. +44 14 6/47 76 00 Fax +44 14 6/47 76 01 WN 05 40 5, 07/04, TS 97 EMF/EMR, GB,. DD. 07/04 Subject to change without notice