MODELS W1LC220, 260 AND 320 STYLE B

Similar documents
MODELS B1PA024, 030 AND 036

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

MACH N-407 Heat Pump Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

MODELS E1FB180 & E1FB240

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

MAC-120HE-03 Air-Cooled Chiller

INSTALLATION MANUAL - 50 Hz

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

Condensing Unit Installation and Operating Instructions

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

Condensing Unit Installation and Operating Instructions

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

PACKAGE AIR CONDITIONER

Call us today! (800)

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

30GT FLOTRONIC AIR-COOLED CHILLERS

30GN FLOTRONIC II AIR-COOLED CHILLERS

Call us today! (800)

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Packaged Air-Cooled Water Chiller

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

User s Information and Installation Instructions

Water-Cooled Dual Compressor Screw Chiller

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

Call us today! (800)

R-410A AFFINITY SERIES DEX DEY Ton

PACKAGED AIR COOLED Product Data Catalog

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Installation, Operation, and Maintenance Information

R-410A MODELS: YD360 Thru Ton 60 Hertz

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530.

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

MODELS B3CH 048 AND 060 (WORLD 50 HZ)

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Contour TM Screw Compressors

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

Product Chillers A P P L I C AT I O N S

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

MODELS K2EU060A, K4EU090A, & K3EU120A

Installation Instructions

Installation, Operation, and Maintenance Information

VariCool VAV Engineering Guide

R-410A MODELS: PH-07 Thru -20 PJ-15 Thru Ton 60 Hertz

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

INSTALLATION AND OPERATING INSTRUCTIONS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

38LB/38LF AIR COOLED CONDENSING UNIT

T-Series Air Conditioner T15 Model

User s Information and Installation Instructions

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

YCIV Hz & Hz

CHILLER. Model CH3000. Operator s & Installation Manual

Supersedes: N1Y (1099) N1Y (0500) MODELS B1HA018 THRU THRU 5 TON (10 SEER)

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

WCH5**4. Product Specifications

SKYPAK II, 3 Ton Series, gives you a

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

WineZone Ceiling Mount Ductless Split 15

Transcription:

LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled Liquid Chillers provide chilled liquid for all air conditioning applications. They are competely self contained chilling systems utilizing an accessible hermetic compressor, liquid cooler, air cooled condenser coils and electrical control panel all mounted on a steel base. They are factory piped, wired, dehydrated, evacuated, leak tested, pressure tested, functionally tested and fully charged with Refrigerant-. All controls are located in the front of the unit and are readily accessible for maintenance, adjustment and service. All wiring (power and control) can be made through the bottom of the compressor compartment. REFERENCE Additional information on the design, installation, operation and service of air conditioning equipment is available in the following reference forms. 55.70-N - General Installation 55.70-N - Pre-start & Post-start Check List 55.70-N3 - General Service Information 55.05-NM - Evacuation and Charging 50.46-NM - Gauge Kit Accessory Renewal Parts: Refer to Parts Manual for complete listing of replacement parts on this equipment. The above forms and all other forms referenced in this instruction may be ordered from: INSPECTION Publications Distribution Center Unitary Products Group P.O. Box 59, York, Pa. 7405 As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s freight bill. A separate request for inspection by the carrier s agent should be made in writing. See Form 50.5-NM for additional information. CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES. WARNING INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.

570.05-N3Y TABLE OF CONTENTS General... Inspection... Reference... Approvals... Nomenclature... INSTALLATION Limitations... 3 Handling... 3 Location... 3 Clearances... 4 Compressor Hold-Down Nuts... 4 Discharge Line Hold-Down Bracket... 4 Chilled Liquid Piping... 4 Electrical Wiring... 5 Power Wiring... 5 Control Wiring... 5 Multiple Units... 5 Wiring To External Water Line Heaters... 5 OPERATION General... 8 Checking Prior To Initial Start Up... 8 Applying Power To The Unit... 8 Sequence of Operation... 8 Part-Winding Start... 9 Pumpdown... 9 Anti-Short Cycling... 9 Oil Failure... 9 High / Low Pressure Lockout... 9 Compressor Motor Protection System... 9 Compressor Motor Operation... 9 Condenser Fan Motor Control... 9 Water Cooler Freeze Prevention... 9 Electric Controls... 9 MAINTENANCE General... Cleaning Condenser Surface... Lubricating Fan Motors... Compressor Replacement... Secure Owner s Approval... TABLES No. Description Page Application Data... 3 Physical Data... 4 3 Electrical Data... 6 4 Electrical Data (International Models)... 6 5 Water Side Pressure Drop... 6 FIGURES No. Description Page Unit Handling... 3 Support Beam Locations... 4 3 Compressor Hold-Down Nuts... 4 4 Field Wiring Diagram... 5 5 Unit Dimensions and Clearances... 7 6 Condenser Fans Orientation... 9 PRODUCT NOMENCLATURE PRODUCT CATEGORY W = Air-Cooled Chiller PRODUCT GENERATION = New or Current W L C 0 A 5 PRODUCT IDENTIFIER LC = Liquid Chiller NOMINAL COOLING CAPACITY 0 = MBH (8.5 Tons) 60 = 6 MBH (.8 Tons) 30 = 35 MBH (7. Tons) VOLTAGE CODE 5 = 08/30-3-60 40 = 380-3-60 46 = 460-3-60 50 = 380/45-3-50 FACTORY INSTALLED HEAT A = Not Applicable (Cooling only) Unitary Products Group

LIMITATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform with the appropriate national codes. See Table for Application Data. Units with voltage codes 5 and 46 are certified by the Electrical Testing Laboratory (ETL) as meeting the requirements of the ANSI/UL 465 Central Cooling Air Conditioner Standard. If components are to be added to a unit to meet local codes, they are to be installed at the dealer s and/or the customer s expense. TABLE - APPLICATION DATA Unit Voltage Variations Power Supply Min. Volts Max. Volts 08/30-3-60 87 53 460-3-60 44 506 380/45-3-50 34 440 380-3-60 355 45 Limitations Model WLC0 WLC60 WLC30 Cooler Liquid Min. 30 35 45 (GPM) Max. 00 00 00 Leaving Liquid Min. 3 3 3 Temp. ( F) Max. 50 50 50 Air Entering Min. 0 0 0 Condenser ( F) Max. 5 3 For applications below 40 F leaving liquid temperature, a mixture of ethylene glycol and water must be used. Water in the cooler is protected from freeze-up to 0 F ambient by a heater under the insulation. 3 The LC30 unit will operate to 0 F air entering condenser if leaving liquid temperature is limited to maximum 44 F. INSTALLATION HANDLING These chillers are shipped as completely assembled units with a full operating charge. Care should be taken to avoid damage due to rough handling. CAUTION: Units are not designed for stacking. A unit should be lifted by inserting hooks through the holes in the base rails. CAUTION: Spreader bars of greater width than the unit must be used to avoid crushing the unit frame or panels with lifting chains or cables. When preparing to move the unit, always determine the center of gravity in order to equally distribute the weight. Slings connected to the compressor end of the unit will usually have to be made shorter than those to the rear of the unit, so the unit will lift evenly. Refer to Figure. LOCATION 570.05-N3Y These units are designed for outdoor installations on ground or rooftop. The location should be selected for minimum sun exposure and to insure an adequate supply of fresh air for the condenser. Avoid locations beneath windows or between structures where normal operating sounds may be objectionable. The condenser fans are propeller type and are not suitable nor intended for use with duct work in the condenser air stream. On either rooftop or ground level installations, rubber padding can be applied between the base rails of the unit and its support to lessen the transmission of vibration. GROUND LEVEL LOCATIONS It is important that the units be installed on a substantial base that will not settle. See Table for unit weights. Setting could cause strain on the refrigerant or water lines resulting in leaks. A one-piece concrete slab with footers that extend below the frost line is recommended. Model Dimensions (Inches)) D E X Y WLC0 08-5/8 56-3/4 6 43 WLC60 08-5/8 56-3/4 6 43 WLC30 8-5/8 64-3/8 30 45 FIG. - UNIT HANDLING Unitary Products Group 3

570.05-N3Y Additionally, the slab should NOT be tied to the main building foundations as noise due to vibration may be transmitted. For ground level installations, precautions should be taken to protect the unit from tampering and unauthorized persons from injury. Screws on access panels will prevent casual tampering. Further safety precautions such as a fenced enclosure or locking devices on the panels may be advisable. Check local authorities for safety regulations. ROOFTOP LOCATIONS Choose a spot with adequate structural strength to safely support the entire weight of the unit and service personnel. Care must be taken so as not to damage the roof. Consult the building contractor or architect if the roof is bonded. The unit must be mounted level on a minimum of two beams. The beams should () be positioned perpendicular to the roof joists, () extend beyond the dimensions of the section to distribute the load on the roof, (3) be capable of supporting the weight of the unit and (4) be positioned parallel to the longer base rails of the unit OR parallel to the shorter base rails of the unit as shown in Figure. The area within the clearances and the area under the unit must be kept clear of all obstructions that would impede free air flow to the unit. In installations where low ambient operation is intended and snow accumulation is expected, additional unit height must be provided to insure full air flow. COMPRESSOR HOLD-DOWN NUTS For shipping, the compressor hold-down nuts are tightened, drawing the compressor mounting feet down to the shipping stops. CAUTION: After the unit is in its final position, remove the compressor hold-down nuts and shipping spacers. Install rubber grommets (shipped in bag tied to compressor). Replace the hold-down nuts and tighten until they start to bind the rubber grommets. Continue to tightened additional half turn. See Figure 3. Model Dimensions (Inches) D E P Q R WLC0 08-5/8 56-3/4 6 44 73 WLC60 08-5/8 56-3/4 6 44 73 WLC30 8-5/8 64-3/8 0 48 76 FIG. - SUPPORT BEAM LOCATIONS CLEARANCES The units must be installed with sufficient clearance for air to enter the condenser coil and not be recirculated after discharge. Sufficient clearance must also be provided for service access. Refer to the unit illustration in Figure 5 for minimum clearances. FIG. 3 - COMPRESSOR HOLD-DOWN NUTS DISCHARGE LINE HOLD-DOWN BRACKET CAUTION: Do NOT remove the discharge line support brackets located within the compressor compartment. It reduces vibration during unit operation. CHILLED LIQUID PIPING The cooler inlet and outlet liquid connections are 3 inch nominal pipe size. The connections are made with grooved ends designed to accept Victaulic grooved pipe couplings only. Remove the shipping caps and discard. CAUTION: The liquid piping RETURNING to the chiller MUST be attached to the cooler connection CLOSEST to the compressor end of the unit. The liquid piping LEAVING the cooler MUST be attached to the cooler connection FURTHEST from the compressor end of the unit. See Figure 5 for liquid inlet and outlet connections. TABLE - PHYSICAL DATA Model Condenser Compressor Unit Weight Fan Coil (Lbs.) Oper. Fan (Propeller) Cap. Motors 3 (Copper Tube - Aluminum Fin) Charge, Reduction Nom. No. Stages (R-) (%) Cap. of of Qty. Dia. Face Tube Fins Pitch Nom. (Lbs.) (In.) (Deg.) CFM HP RPM Rows Rows Area OD per Ship. Oper. (Tons) Cyl. Cap. (Ft. Deep Wide ) (in.) inch WLC0 0 4 3 4 30 7,00 3/4 075 38.8 3 48 3/8,00,00 6.0 00,50 WLC60 5 4 3 4 30 6,500 3/4 075 38.8 4 48 3/8,50,30 9.0 00,50 WLC30 30 6 3 4 4 30,000 3/4 075 45.0 3 54 3/8,30,400 33.0 00,66,33 All compressors are semi-hermetic. During low ambient conditions, the motor for one of these fans will operate at 450 RPM. 3 These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48 frame. Their rotation is clockwise when viewing the shaft end of the motor. 4 Unitary Products Group

The chilled liquid lines that are exposed to outdoor ambient should be wrapped with supplemental heater cable and insulated to protect against freeze-up during low ambient periods and to prevent formation of condensation on lines in warm humid climates. The unit provides electrical contact closure when the outdoor ambient is low and cooler water is not flowing to energize these supplemental heaters but power must be supplied from a separate power source. Refer to Figure 4. A water flow switch is installed on the leaving water connection of the cooler. For proper operation, there should be s straight horizontal run of at least 5 pipe diameters down stream of the switch. The chilled liquid piping system must be laid out so that the circulating pump discharges into the cooler. Hand stop valves are recommended for use in all lines to facilitate servicing. Drain connections should be provided at all low points to permit complete drainage of the cooler system and piping. The cooler barrel is provided with a 3/4 inch drain connection on the bottom of the cooler and a /4 inch air purge connection on the top of the cooler. A strainer (40 mesh) is recommended for use on the inlet to the cooler. NOTE: When filling the piping system with liquid, purging the system of air is essential for the unit to achieve design capacity. Be sure to slowly fill the system with liquid and to open all purge connections in the system including the /4 inch connection on top of the cooler. Close all connections after all air has been purged from the system. As an aid to servicing, thermometers and pressure gauges are recommended in the inlet and outlet water lines. A /4 inch plugged connection is provided on each connection for the field to install these devices. ELECTRICAL WIRING WARNING: All power and control wiring must be in accordance with national and local electrical codes. POWER WIRING These units are designed for single point power source. Check the available power and unit nameplate to see if the voltages are the same. Run the necessary number of properly sized wires to the unit. Provide a disconnect switch and fusing as required. Route the conduit to the large knockout located on the bottom of the electrical box. Remove the plastic plug from the knockout and discard. See Table 3 or 4 for electrical data. The disconnect switch may be bolted to the side of the unit but not to any of the removable panels; this would interfere with access to the unit. Make sure that no refrigerant lines or coils will be punctured when mounting the disconnect switch, and note that it must be suitable for outdoor installation. CONTROL WIRING 570.05-N3Y All control wiring is connected to the field wiring terminal block, 5 TB, located in the bottom of the control box. A more detailed description of operating controls is given in the Operation Section. WARNING: All control wiring is 0 volts single phase. Properly sized and insulated wiring should be used. An indoor room thermostat is not required to operate these units. Each unit contains an automatic temperature control which maintains a constant return liquid temperature to the cooler. Several recommended and optional field hookups are connected to the 5TB terminal strip. They are:. Chilled Water Pump Starting Circuit - terminals K and H. (Recommended, not to be used for normal start.). Day/Night Switch Contacts for Cycling Unit On and Off with Unit Pumpdown - terminals G and C. Remove jumper J. (Recommended) 3. Low Leaving Liquid Temperature Alarm - terminals B and 33. (Optional) 4. Loss of Liquid Flow Alarm/Aux Pump Start - terminals A and 33. (Optional) MULTIPLE UNITS For increased compressor protection and to reduce power inrush at start-up on multiple chiller installations, provisions must be made to prevent simultaneous start-up of two or more units. Also, some method may be employed to automatically cycle on or off one or more of the units to permit more efficient operation at part load conditions. WIRING TO EXTERNAL WATER LINE HEATERS When the outdoor ambient drops below 36 F and there is no water flow, a contact in the unit closes across terminals W and L on the 6TB terminal block located in the bottom of the control box. This contact closure may be used to energize field installed heaters located on water lines to the unit. See Figure 4. FIG. 4 - FIELD WIRING DIAGRAM WARNING: The unit contact closure does NOT provide power for the heaters. Single phase 0 or 40 volt power must come from a separate, field installed fused disconnect. Heater power must not exceed 00 watts. Unitary Products Group 5

570.05-N3Y TABLE 3 - ELECTRICAL DATA Model WLC0 WLC60 WLC30 Compressor Condenser Fan Motors Power Supply Qty. RLA LRA Power Supply HP Qty. A5 08/30-3-60 88.5 48 08/30--60 3/4 A46 460-3-60 44.3 4 460--60 3/4 A5 08/30-3-60 0 470 08/30--60 3/4 A46 460-3-60 5 35 460--60 3/4 A5 08/30-3-60 35 565 3 08/30--60 3/4 A46 460-3-60 67.5 83 460--60 3/4 50 Amps on part winding start. 4 Based on three, 75 C insulated copper conductors in steel conduit. 9 Amps on part winding start. 5 Based on a 3% voltage drop. 3 340 Amps on part winding start. 3 3 FLA (each) 4. 4.5 4. 4.5 4. 4.5 Unit Ampacity (Amps) Max. Fuse Size (Amps) Min. Wire Size, 4 (AWG) 5 50 Max. Wire Lg. 5 (Ft.) 59 @ 08 85 @ 30 63 80 6 30 45 75 /0 89 @ 08 7 @ 30 7 90 4 395 86 5 3/0 9 @ 08 6 @ 30 94 5 3 33 TABLE 4 - ELECTRICAL DATA (International Models) Model WLC0 WLC60 WLC30 Compressor Condenser Fan Motors Power Supply Qty. RLA LRA Power Supply HP Qty. A50 380/45-3-50 38.0 65 380/45--50 3/4 A40 380-3-60 5. 08 460--60 3/4 A50 380/45-3-50 57 00 380/45--50 3/4 A40 380-3-60 56 49 460--60 3/4 A50 380/45-3-50 6.7 5 3 380/45--50 3/4 A40 380-3-60 77.8 307 460--60 3/4 00 Amps on part winding start. 4 Based on three, 75 C insulated copper conductors in steel conduit. Amps on part winding start. 5 Based on a 3% voltage drop. 3 50 Amps on part winding start. 3 3 FLA (each) Unit Ampacity (Amps) Max. Fuse Size (Amps) Min. Wire Size, 4 (AWG) 55 70 6 Max. Wire Lg. 5 (Ft.) 58 @ 380 308 @ 45 75 90 4 3 80 00 4 69 @ 380 30 @ 45 80 00 4 93 88 0 3 305 @ 380 355 @ 45 0 50 3 TABLE 5 - WATER SIDE PRESSURE DROP WLC0 WLC60 WLC30 GPM PSIG FEET 30..8 35.6 3.7 40.0 4.6 45 5.7 50 3.0 6.9 55 3.5 8. 60 4. 9.5 65 4.7 0.8 GPM PSIG FEET 35.6 3.7 40.0 4.6 45 5.7 50 3.0 6.9 55 3.5 8. 60 4. 9.5 65 4.7 0.8 70 5.4 75 6. 4.0 GPM PSIG FEET 45 5.7 50 3.0 6.9 55 3.5 8. 60 4. 9.5 65 4.7 0.8 70 5.4 75 6. 4.0 80 6.8 5.8 85 7.6 7.5 90 8.5 9.5 95 9. 6 Unitary Products Group

570.05-N3Y BASIC UNIT DIMENSIONS MODEL A B C D E F G WLC0 9 6-/8 47-/ 08-5/8 56-3/4 0-/ 8-/8 WLC60 9 6-/8 47-/ 08-5/8 56-3/4 0-/ 8-/8 WLC30 8-/ 68-5/8 48-/ 8-5/8 64-3/8 0-/ 8-5/8 COOLER DIMENSIONS & WEIGHTS MODEL COOLER SIZE (Dia. x Lg.) WATER CONNS.* (Inlet & Outlet) J K L M COOLER WEIGHT (Lbs.) Oper. Dry WATER CHARGE (gallons) WLC0 8" x 6 3" 0 6 -/ 4 466 386 9.6 WLC60 8" x 6-/ 3" 4 68 -/ 4 498 48 9.6 WLC30 8" x 7 3" 4 7 -/ 3 540 450 0.8 *Nominal pipe size - victaulic type. CLEARANCES FRONT 36" BACK 4"* LEFT SIDE 4"* RIGHT SIDE 4"* TOP 0" *One side only. NOTE: The area within the clearances shown above and area under the unit must be kept clear of all obstructions that would impede free air flow to the unit. In installations where winter operation is intended and snow accumulations are expected, additional unit height must be provided to insure full air flow. All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. FIG. 5 - UNIT DIMENSIONS AND CLEARANCES Unitary Products Group 7

570.05-N3Y GENERAL The operation of models WLC0, WLC60 and WLC30 are very similar except models WLC0 and WLC60 have only one stage of unloading. The WLC30 unit has two stages of unloading. CHECKING THE SYSTEM PRIOR TO INITIAL START UP OPERATION 5. Allow the unit to operate, but be ready to stop the unit should any unusual noise or other adverse condition develop. NOTE: Opening the DAY/NIGHT switch will only shut the unit off after completion of the pumpdown cycle. Turning OFF the main power supply will stop the unit immediately. 6. To determine if the unit is operating properly, the refrigerant subcooling and superheat should be checked. With the system piping and electrical wiring completed, the unit is ready to have electrical power applied. Before applying power, however, the following checks should be made:. Compressor shipping brackets have been removed and rubber isolators installed.. The Return Liquid Temperature Control (TC) has been adjusted to the desired Return Liquid Temperature and Between Stage Differential. 3. The Freeze Control thermostat (FC) has been set to the proper setting. (Factory setting is 36 F.) 4. Fan blades rotate freely. 5. Compressor crankcase oil level shows /3 to / in sight glass. 6. Suction, discharge and liquid line king valves, located in the compressor section, are open. CAUTION: Suction, discharge and liquid line valves are shipped closed. 7. The power supply voltage is the same as the unit nameplate voltage. 8. Proper fuses are in main disconnect power circuits. APPLYING POWER TO THE UNIT CAUTION With the preceding steps completed, make sure the DAY/NIGHT switch is in the NIGHT or UNOC- CUPIED position or the unit will start immediately and compressor damage may occur.. The main power disconnect switch may now be turned ON. CAUTION: Check to insure that the compressor crankcase heater is energized. Allow at least 4 hours warm-up to allow all liquid refrigerant to be driven from the compressor. After warm-up, the crankcase should be warm to the touch.. Start the chilled water circulating pump. Assure that the flow rate is approximately correct by checking the water pressure drop across the cooler with the data shown in Table 5. 3. Check that the liquid freeze prevention thermostat (FC) does not need to be reset. It may have tripped if the unit was exposed to low outdoor temperatures during shipment. 4. Turn the DAY/NIGHT switch to the DAY or OCCUPIED position. If the water flow switch is closed, the unit will start after the required time delays built into the control circuit, provided the return liquid temperature is warm and the temperature control (TC) is calling for cooling. SEQUENCE OF OPERATION NOTE: The contact opening and closing times for 50 HZ units are 5/6 of those listed for 60 HZ units. System start-up and staging is controlled by the TC which is energized through the day/night switch, optional field installed pump aux. contact, FC and WFS. The FC opens below 36 F leaving water temperature and closes above 4 F with manual reset. The WFS closes at water flow rates above 30 GPM. The TC is a solid state thermostat which maintains the desired chilled (supply) liquid temperature by sensing and regulating the return liquid temperature (see the ELECTRICAL CON- TROLS section). It employs an encapsulated thermistor located in a well in the return liquid line. NOTE: The timing intervals described in the following procedure are nominal. Some variations will naturally occur due to differences in individual components, ambient temperature, or line/control voltage. When the first stage of the TC calls for cooling:. TC-3 closes and energizes relay 6R. 6R- will energize compressor protector module MP, and after a minute time delay MP contacts will close. Contact 6R-3 closes energizing contactors M, 3M, relays R, 0R, and timer TR. 6R- energizes liquid line solenoid valve LLS, and liquid refrigerant will flow to the expansion valve.. Relay R contacts close, with R- and R- closing in parallel with contacts 6R- and 6R-3 respectively maintaining operation during the pumpdown cycle. 3. Contactor M energizes the compressor, and contactor 3M energizes the condenser fans. 0R- opens to de-energize compressor crankcase heater CCH while the compressor runs. 4. After minutes, low pressure bypass timer TR- opens. If the compressor suction pressure remains abnormally low after initial start-up, the compressor circuit will lock out as described in the HIGH / LOW PRESSURE LOCKOUT section. When the second stage of the TC calls for cooling:. Contacts TC-7 will close to energize relay 5R, and condenser fan No. will start up, providing the temperature of the outdoor air is above the 45 F set point of thermostat TH.. Contact TC-8 will open to de-energize compressor solenoid valve SOL, and the compressor will operate at full capacity. 8 Unitary Products Group

PART-WINDING START Units with voltages of 08/30 and 380/45 have two compressor contactors and include part winding start. On start-up, timer 4TR prevents contactor M from being energized until second after contactor M is energized. This -second delay reduces the LRA of the compressor substantially. Refer to the electrical data in Table 3 or 4. PUMPDOWN When the compresor is running at part load and when the liquid cooling requirement becomes satisfied, contact TC-3 will open to de-energize relay 6R. Contact 6R- will open to de-energize liquid line solenoid valve LL-S, and no refrigerant will flow to the cooler. Contact 6R- will open but contact R- will keep the condensing section in operation until the low side of the system is pumped out and low pressure control LP opens to shut the unit down. ANTI-SHORT CYCLING When low pressure control LP opens to de-energize the compressor and the condenser fans, relay R will also be de-energized. R- opens and de-energizes MP. When MP is re-energized, contacts MP close after a minute delay which provides anti-short cycle protection. OIL FAILURE If the oil to suction pressure differential drops below 4 psig (± ), OPA in the oil pressure control will close and energize timer TR. If this low pressure condition exists for more than 90 seconds, TR contact will open to shut down the compressor and condenser fans. HIGH / LOW PRESSURE LOCKOUT If the compressor discharge pressure exceeds 398 psig or the suction pressure drops below 30 psig, HP or LP will open and shut down the compressor and outdoor fans. At the same time, lockout relay 9R will energize. 9R- will open and prevent the unit from restarting when HP or LP closes. The unit can be reset by momentarily opening the unit disconnect switch provided HP and LP have closed. After reset, the unit will start after the minute time delay provided there is a call for cooling. CONDENSER FAN MOTOR CONTROL Condenser fans cycle with changes in compressor capacity and with the temperature of the outdoor air to provide stable operation over a wide range of conditions. One of the condenser fan motors can operate at a reduced speed without overheating. When the discharge pressure drops below 80 psig, the speed of this motor drops from 075 to 450 RPM. When the discharge pressure rises above psig, the motor will return to 075 RPM. This speed reduction is accomplished by using a choke coil to reduce the voltage to the motor. A 0 second time delay relay is included in the control circuit so this motor will always start at high speed. Refer to Figure 6. EXAMPLE: WLC0 and WLC60 - Under 65 F, the # condenser fan will shut off. Under 45 F, the # condenser fan will shut off. At / capacity, the # condenser fan will shut off. When the discharge pressure drops below 80 psig, head pressure control HP will close to energize relay 4R. When contact 4R- opens and contact 4R- closes, condenser fan #3 will be powered through choke coil CH and its speed will drop to 35% of nominal RPM. Timer 3TR will remain open for 0 seconds after unit start-up so the condenser fan will always start at high speed. WATER COOLER FREEZE PREVENTION 570.05-N3Y Off-cycle cooler freeze protection is provided when liquid is not flowing to the cooler and the outdoor ambient is low. Under these conditions, the cooler heater HTR and 5R are energized through the 7TH thermostat which closes below 36 F. The cooler heater is a pad type heater fixed to the cooler under the insulation. The 5R contact closes to energize field installed water line heaters. The power for these heaters comes from a separate disconnect switch. See Figure 4. COMPRESSOR MOTOR PROTECTION SYSTEM The solid state motor protection system consists of a solid state overload protector module and three sensors embedded in the compressor motor windings. The sensors are connected to the solid state overload protector module MP. Refer to the wiring label on the inside of the compressor terminal box cover. This system provides minute off-time delay before the compressor can restart. COMPRESSOR MOTOR OPERATION As the motor winding temperature rises, the resistance of the three sensors increases. If safe temperatures are exceeded, the electronic device will open its relay contact and will shut the unit down. After the motor cools to a safe temperature, the unit can be restarted - provided the anti-cycle timer has completed its cycle. FIG. 6 - CONDENSER FANS ORIENTATION ELECTRIC CONTROLS RETURN LIQUID TEMPERATURE CONTROL (TC) The YORK model TC-6A return liquid temperature control is a 4 stage solid state thermostat that maintains the desired chilled liquid temperature by sensing and regulating the liquid temperature returning to the cooler. The control is mounted in the Unitary Products Group 9

570.05-N3Y compressor compartment, to the left of the main control box in front of the compressor. The return water temperature is sensed by a thermistor (SENSOR) located in the return liquid line. Its resistance varies with changes in return liquid temperature. Changes in the thermistor resistance are interpreted by the controller and are amplified to energize output relay contacts. The circuitry is such that the controller shuts down the compressor in the event the thermistor is disconnected or accidentally cut. The return water temperature is adjustable between 4 F and 70 F. This adjustable range is much greater than applicable to this chiller. See Table for limitations in leaving liquid temperatures. The Between Stage Differential is adjustable between F and 3.75 F. On both the WLC0 and 60, the control is factory adjusted to 54 F Return Liquid Temperature with the Between Stage Differential set at F which results in a 44 F (0 Range) leaving liquid temperature at nominal conditions. Check that these settings are still correct or change the setting as required but do not exceed the application limitations in Table. If the factory temperature control settings which provide 44 F leaving liquid temperature with a 0 F liquid temperature range are not desired for the WLC0 or 60 installation, the required leaving liquid temperature and liquid temperature range must be specified before the new temperature control settings can be determined. To determine the Between Stage Differential setpoint on the temperature control for the WLC0/60, divide the specified range by 4. The Return Liquid Temperature setpoint on the control is calculated by adding the specified liquid temperature range to the specified leaving liquid temperature. EXAMPLE: (WLC0/60) Specified 45 F leaving liquid temperature with an 8 F liquid temperature range. Calculate Between Stage Differential Setpoint. 8 F - 4 F = F Calculate Return Liquid Temperature Setpoint. 45 F + 8 F = 53 F On the WLC30, the Return Liquid Temperature Control is factory adjusted to 57.3 F Return Liquid Temperature with the Between Stage Differential set at 3.33 F. Because the WLC30 is a 3 stage machine, these settings result in a return liquid temperature of 54 F and a leaving liquid temperature of 44 F (0 F) range). Check that these settings are still correct or change the settings as required but do not exceed the application limitations in Table. In the factory temperature control settings which provide 44 F leaving liquid temperature with a 0 F liquid temperature range are not desired for the WLC30 installation, the required leaving liquid temperature and liquid temperature range must be specified before the new temperature control settings can be determined. To determine the Between Stage Differential setpoint on the temperature control for the WLC30, divide the specified range by 3. The Return Liquid Temperature setpoint on the control is calculated by adding the specified liquid temperature range and the calculated Between Stage Differential to the specified leaving liquid temperature. EXAMPLE: (WLC30) Specified 45 F leaving liquid temperature with an 8 F liquid temperature range. Calculate Between Stage Differential Setpoint. 8 F 3 =.66 F Calculate Return Liquid Temperature Setpoint. 45 F + 8 F +.66 F= 55.66 F As an example of how the TC-6A control works in application, consider the WLC0 or 60 chiller with the control set to maintain a 54 F return water temperature with a F Between Stage Differential. The flow rate is set to.4 GPM/measured TON, (0 F range) and the working fluid is water. The WLC0 and 60 are stage machines with stages at 50% and 00% capacity. All temperatures considered are for a TC-6A control and thermistor working at design conditions. Allowable tolerances could change the actuation temperatures by ±.5 F. With the RETURN water temperature to the cooler rising due to increasing cooling load for the application, the compressor will start at part load when the RETURN water temperature reaches 50.5 F. The LEAVING water temperature will quickly drop to 45.5 F. If the cooling load continues to increase, the compressor will be fully loaded by the controller when the RETURN water temperature reaches 55.5 F. Under increasing load, the minimum LEAVING water temperature will be 45.5 F and the maximum 50.5 F. As the demand for cooling load decreases, the controller will unload compressor stages in reverse order to the way they were loaded at 5.75 and 47.75 F RETURN water temperature. During decreasing load, the minimum LEAVING water temperature will be 4.75 F and the maximum 45.5 F. FREEZE CONTROL PREVENTION THERMOSTAT (FC) The leaving liquid freeze prevention thermostat is designed to prevent the liquid temperature in the cooler from dropping below the freezing point of the fluid while the unit is running. CAUTION: Freezing fluid in the cooler can cause damage which can lead to total replacement of the cooler. If the temperature of the liquid leaving the cooler drops below its set point the control energizes R. R- opens and shuts the compressor off immediately. The control must be manually reset when the bulb temperature rises to 6 F above the setpoint cutout temperature. The body of the control is in the compressor compartment attached to the left hand side of the control box. The sensing bulb is the capillary type located in a well in the leaving water connection at the far end of the cooler. This is a cross ambient sensing device that is not effected by changes in ambient temperature. The freeze control is factory set to shut down the unit at 36 F (± ) and is manually reset when the bulb temperature reaches 4 F. This setting is for a working liquid of pure water and many light brine applications. In heavy brine applications, the control may be field adjusted using the adjustment screw at the top of the control. CAUTION: It is recommended that the adjusted cutout temperature be at least 4 F above the freezing point of the fluid. In no brine application should the setpoint be adjusted below 30 F. If during delivery to the job site or during non-operational periods when the ambient temperature of the freeze control bulb drops below 36 F, the freeze control may have tripped and needs to be manually reset before the unit will start. 0 Unitary Products Group

GENERAL It is good practice to include the WLC chiller in the routine schedule of daily or weekly operational checks. This should include but not be limited to checking compressor crankcase oil level, checking refrigerant liquid line sight glass for proper charge and signs of moisture, and checking for obstructions on the condenser coil such as leaves or paper that would reduce normal air flow. WARNING:Prior to performing any service or maintenance, disconnect all electrical power to the unit. CLEANING CONDENSER SURFACE Dirt should not be allowed to accumulate on the condenser coils. The underside of the coils will collect dirt and other foreign matter first. Cleaning should be as often as necessary to keep the condenser coils clean. Use a brush, vacuum cleaner attachment, or other suitable means. Take care so as not to damage or bend the condenser fins. MAINTENANCE LUBRICATING FAN MOTORS The condenser fan motors are equipped with factory lubricated and sealed ball bearings, requiring no maintenance. COMPRESSOR REPLACEMENT Obtain replacement compressors or parts from your local Copeland Wholesaler. See Instruction Form 55.7-RD. for replacement compressor reference data. SECURE OWNER S APPROVAL 570.05-N3Y WHEN THE SYSTEM IS FUNCTIONING PROPERLY, EX- PLAIN THE OPERATION OF THE UNIT TO THE OWNER OR DESIGNATED REPRESENTATIVE. EXPLAIN THE FUNC- TION OF THE LOCKOUT PROTECTION FEATURES AND HOW TO RESET THEM. SHOW HIM THE LOCATION OF ALL DISCONNECT SWITCHES. INSTRUCT HIM HOW TO STOP AND START THE UNIT. BE SURE THE WARRANTY REGISTRATION CARD HAS BEEN FILLED OUT AND RETURNED TO THE FACTORY. Unitary Products Group

Unitary Products Group P.O. Box 59, York, Pennsylvania USA 7405-59 Subject to change without notice. Printed in U.S.A Copyright by York International Corporation 994. All Rights Reserved. Code: SBY 570.05-N3Y