NFS-320(E) Intelligent Addressable Fire Alarm System

Similar documents
NFS-320C. Intelligent Addressable Fire Alarm System

NFS-320. Intelligent Addressable Fire Alarm System

Data/ Specification Sheet

AutoPulse. AUTOPULSE IQ-318 AGENT RELEASING CONTROL PANEL Data/Specifications

NFS-320C. Intelligent Addressable Fire Alarm System

NFS-320. Intelligent Addressable Fire Alarm System. General. Features NFS-320. Intelligent Fire Alarm Control Panels FLASHSCAN INTELLIGENT FEATURES

NFS Intelligent Addressable Fire Alarm System

NFS-320C. Intelligent Addressable Fire Alarm System. General. Features NFS-320C. Intelligent Fire Alarm Control Panels FLASHSCAN INTELLIGENT FEATURES

NFS-320. Intelligent Addressable Fire Alarm System

Data/ Specification Sheet

A World of Solutions

NFS Intelligent Addressable Fire Alarm System

A World of Solutions in Fire Protection Systems

AFP-400 Analog Fire Panel MEA E. City of Chicago Class 1: 1291E Class 2: 1792E GENERAL FEATURES. A Pittway Company

NFS2-640(E) Intelligent Addressable Fire Alarm System

XLS140. Intelligent Addressable Fire Alarm System. General. Features. XLS140 with XLS-NCA2 display XLS-NCA 640-CHARACTER DISPLAY FEATURES:

NFS Intelligent Addressable Fire Alarm System. General. Features. NFS (left) and NFS with DVC audio option (right)

MEA. NFS-3030 Intelligent. Addressable Fire Alarm System

MS Rev. 2/DACT-UD: Intelligent Addressable FACP with Optional 2nd Loop

A World of Solutions

CCCF Certif. # MEA. NFS-640 Intelligent. Addressable Fire Alarm System Section: Intelligent Fire Alarm Control Panels

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Certificate of Conformity Certificate num. Registration date Version Valid until Number Issue date

Detection and Control Components

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

ECC-50/100C. Emergency Command Center

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Addressable Fire Alarm Control Panel

LifeAlarm Fire Alarm Control Panels

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

Specification/ Data Sheet

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

SECTION FIRE ALARM SYSTEMS

E3 Series Broadband System

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

Fire Alarm Control Panel NFS2-640/E. Installation Manual. Document /06/2012 Rev: K1 P/N 52741:K1 ECN

1 UL 864 Compliance. 2 Product Overview. Network Communications Module NCM-W/F Product Installation Document. 1.1 Products Subject to AHJ Approval

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Intelligent Analog/Addressable Fire Alarm/Voice Integration Systems. IntelliKnight TM Series

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

INTELLIGENT FIRE ALARM CONTROL PANEL

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

CATALOG NUMBER. Features. Description

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

AFP-200. Analog Fire Panel. Installation Manual. Technical Manuals Online! - Document /14/2002 Rev: H2

Fire Alarm Control Panel NFS2-640/E. Installation Manual. Document /10/14 Rev: P2 P/N 52741:P2 ECN

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Agent Release Control Panel

ONYXWORKS AND FIRSTVISION. Version 4

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Innovation that Endures

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

Intelligent Single Loop Fire Alarm Control Panel

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

ECC-50/100(E) Emergency Command Center

NetSOLO Classic. Voice Evacuation. Intelligent, Networked, Multi-Channel and Bulk Amplification Voice Evacuation System FEATURES & BENEFITS.

MONROE PUBLIC LIBRARY WATERFLOW MONITORING SYSTEM

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

Laptop / PC Programming Manual

E3 Series Broadband System

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

Software Release M2.7 Summary for the Notifier AM2020/AFP1010 Fire / Security Control Panels, Including NOTI FIRE NET and Peripherals

intelligent fire alarm ID60series panels

good things in small packages

TrueAlarm Fire Alarm Systems

MPC-6000 / MPC-7000 / RND-2

NETWORK FIRE ALARM CONTROL PANEL. Features

DS7400Xi Addressable Control/ Communicator

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

TECHNICAL DATA OBSOLETE

AL800ULADA. NAC Power Extender. Installation Guide

AFP-100 Intelligent Fire Panel

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

30.45 Electric Release PDRP-2001

ADR Analog Addressable Fire Alarm Control Panel. Technical Manual. Control Panels. 3000En. En pdf

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved*

June 10, 2002 DF C S2424

NBG-12LR and NBG-12LRA

Pompano Pet Lodge 930 Northwest 31 st Avenue Pompano Beach, FL 33069

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

July 14, 1999 DF C-100.

AUTOPULSE IQ-636X-2/E ANALOG ADDRESSABLE CONTROL SYSTEM

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

I. Synchronized Strobes 2=PROGRAMMING PROGRAMMING ENTER PASSWORD *****

Mircom FX /01/16

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

Fire Alarm Control Panel AFP Installation Manual. New Zealand Edition. Document DOC Rev: E 19/11/2018 ECN:

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved*

Section 4: Operating Instructions

The EN54 Part 2, 4 and 13 Fire System

NFS-3030/E. Fire Alarm Control Panel. Programming Manual. Technical Manuals Online! -

!+ NCA-2-TC Network Control Annunciator-2, 640-characters-Traditional Chinese Network Control Annunciator-2, Traditional Chinese $1,587.

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

Transcription:

NFS-320(E) Intelligent Addressable Fire Alarm System DN-7112:E Intelligent Fire Alarm Control Panels General The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX Series of Fire Alarm Controls from NOTIFIER. In stand-alone or network configurations, ONYX Series products meet virtually every application requirement. Designed with modularity and ease of system planning, the NFS-320 can be configured with just a few devices for small building applications, or for a large campus or high-rise application. Simply add additional peripheral equipment to suit the application. For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately). The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet, saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. NOTE: Unless called out with a version-specific R, C or E at the end of the part number, NFS-320 refers to models NFS-320, NFS-320R, NFS-320C, and NFS-320E; similarly, CPU-320 refers to the main circuit board for CPU-320, CPU-320C, and CPU-320E. Features Listed to UL Standard 864, 9th edition. One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7. Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (Addressable pull stations, normally open contact devices, two-wire smoke, notification, or relay). 318 devices maximum. Standard 80-character display. Network options: High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, NCS, NFS-3030, NFS-640, and NCA). Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NCA-2, DVC, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/ 400, AFP-1010, and AM2020). Up to 54 nodes when DVC is used in network paging. 6.0 amp power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization. Built-in Alarm, Trouble, Security, and Supervisory relays. VeriFire Tools online or offline programming utility. Upload/ Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware. Autoprogramming and Walk Test reports. Optional universal 318-point DACT. 80-character remote annunciators (up to 32). EIA-485 annunciators, including custom graphics. Printer interface (80-column and 40-column printers). History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file. Alarm Verification selection per point, with tally. NFS-320 Autoprogramming and Walk Test reports. Presignal/Positive Alarm Sequence (PAS). Silence inhibit and Auto Silence timer options. NAC coding functions: March time. Temporal. California two-stage coding. Canadian two-stage. Strobe synchronization. Field-programmable on panel or on PC, with VeriFire Tools program check, compare, simulate. Full QWERTY keypad. Battery charger supports 18 200 amp hour batteries Non-alarm points for lower priority functions. Remote ACK/Signal Silence/System Reset/Drill via monitor modules. Automatic time control functions, with holiday exceptions. Surface Mount Technology (SMT) electronics. Extensive, built-in transient protection. Powerful Boolean logic equations. FLASHSCAN INTELLIGENT FEATURES: Poll up to 318 devices in less than two seconds. Activate up to 159 outputs in less than five seconds. Multicolor LEDs blink device address during Walk Test. Fully digital, high-precision protocol (U.S. Patent 5,539,389). Manual sensitivity adjustment nine levels. Pre-alarm ONYX intelligent sensing nine levels. Day/Night automatic sensitivity adjustment. Sensitivity windows: Ion 0.5 to 2.5%/foot obscuration. Photo 0.5 to 2.35%/foot obscuration. Laser (VIEW ) 0.02 to 2.0%/foot obscuration. 7112pho1.jpg DN-7112:E 09/07/2010 Page 1 of 6

Acclimate Plus 0.5 to 4.0%/foot obscuration. IntelliQuad 1.0 to 4.0%/foot obscuration. Drift compensation (U.S. Patent 5,764,142). Degraded mode in the unlikely event that the CPU-320 microprocessor fails, FlashScan detectors revert to degraded operation and can activate the CPU-320 NAC circuits and alarm relay. Each of the four built-in panel circuits includes a Disable/Enable switch for this feature. Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515). Automatic detector sensitivity testing (NFPA-72 compliant). Maintenance alert (two levels). Self-optimizing pre-alarm. FSC-851 INTELLIQUAD ADVANCED MULTI-CRITERIA DETECTOR Detects all four major elements of a fire (smoke, heat, CO, and flame). Automatic drift compensation of smoke sensor and CO cell. High nuisance-alarm immunity. Six sensitivity levels. FSL-751 VIEW (VERY INTELLIGENT EARLY WARNING) SMOKE DETECTION TECHNOLOGY: Revolutionary spot laser design. Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524). Addressable operation pinpoints the fire location. No moving parts to fail or filters to change. Early warning performance comparable to the best aspiration systems at a fraction of the lifetime cost. FAPT-851 ACCLIMATE PLUS LOW-PROFILE INTELLIGENT MULTI-SENSOR: Detector automatically adjusts sensitivity levels without operator intervention or programming. Sensitivity increases with heat. Microprocessor-based technology; combination photo and thermal technology. FlashScan or classic mode compatible. Low-temperature warning signal at 40 F ± 5 F (4.44 C ± 2.77 C). RELEASING FEATURES: Ten independent hazards. Sophisticated cross-zone (three options). Delay timer and Discharge timers (adjustable). Abort (four options). Low-pressure CO2 listed. HIGH-EFFICIENCY OFFLINE SWITCHING 3.0 AMP POWER SUPPLY (6.0 A IN ALARM): 120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E). Displays battery current/voltage on panel (with display). VOICE FEATURES: Integrates with FireVoice-25/50 Series (see DN-7004). Integrates via serial connection with FireVoice-25/50ZS Series (see DN-7003). FlashScan, Exclusive World-Leading Detector Protocol At the heart of the NFS-320 is a set of detection devices and device protocol FlashScan (U.S. Patent 5,539,389). FlashS- NFS-320 Sample System Options 7112blok.wmf Page 2 of 6 DN-7112:E 09/07/2010

can is an all-digital protocol that gives superior precision and high noise immunity. In addition to providing quick identification of an active input device, this new protocol can also activate many output devices in a fraction of the time required by competitive protocols. This high speed also allows the NFS-320 to have the largest device per loop capacity in the industry 318 points yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test. ONYX Intelligent Sensing Intelligent sensing is a set of software algorithms that provides the NFS-320 with industry-leading smoke detection capability. These complex algorithms require many calculations on each reading of each detector, and are made possible by the highspeed microcomputer used by the NFS-320. Drift Compensation and Smoothing: Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72. Smoothing filters are also provided by software to remove transient noise signals, such as those caused by electrical interference. Maintenance Warnings: When the drift compensation performed for a detector reaches a certain level, the performance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit. Sensitivity Adjust: Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control functions. Self-Optimizing Pre-Alarm: Each detector may be set for Self-Optimizing pre-alarm. In this special mode, the detector learns its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks. Cooperating Multi-Detector Sensing: A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one. Field Programming Options Autoprogram. This timesaving feature is a special software routine. The FACP learns what devices are physically connected and automatically loads them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed. Keypad Program Edit (with KDM-R2) The NFS-320, like all NOTIFIER intelligent panels, has the exclusive feature of program creation and editing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the NFS-320 software is such that each point entry carries its own program, including control-by-event links to other points. This allows the program to be entered with independent per-point segments, while the NFS-320 simultaneously monitors other (already installed) points for alarm conditions. VeriFire Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confidence in the site-specific software. It is Windows -based and provides technologically advanced capabilities to aid the installer. The installer may create the entire program for the NFS-320 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel. Placement of Equipment in Chassis and Cabinet The following guidelines outline the NFS-320 s flexible system design. Wiring: When designing the cabinet layout, consider separation of power-limited and non-power-limited wiring as discussed in the NFS-320 Installation Manual. It is critical that all mounting holes of the NFS-320 are secured with a screw or standoff to ensure continuity of Earth Ground. Networking: If networking two or more control panels, each unit requires a Network Control Module or High-Speed Network Control Module (see Network Options on page 5). These modules can be installed in any option board position (see manual), and additional option boards can be mounted in front of them. KDM-R2 Controls and Indicators Program Keypad: QWERTY type (keyboard layout). 12 LED Indicators: Power; Fire Alarm; Pre-Alarm; Security; Supervisory; System Trouble; Signals Silenced; Points Disabled; Control Active; Abort; Pre-Discharge; Discharge. Keypad Switch Controls: Acknowledge/Scroll Display; Signal Silence; Drill; System Reset; Lamp Test. LCD Display: 80 characters (2 x 40) with long-life LED backlight. Configuration Guidelines The NFS-320 system ships assembled; description and some options follow. Note: Stand-alone and network systems require a main display. On stand-alone systems, the panel s keypad provides the required display. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYXWorks annunciation device is required. NFS-320: The standard, factory-assembled NFS-320 system includes the following components: one CPU-320 control panel mounted on chassis (120 V operation ships with grounding cable, battery interconnect cables, and document kit); includes integral power supply mounted to the CPU-320; one primary display KDM-R2 keypad/display; and one cabinet for surface or semi-flush mounting. Purchase batteries separately. One or two option boards may be mounted inside the NFS-320 cabinet; additional option boards can be utilized in remote cabinets. NFS-320R: Same as NFS-320 above, but in red enclosure. NFS-320C: Based on NFS-320 above. NFS-320C supports installation of an optional ACM-series annunciator in the same cabinet. UL- and ULC-listed. NOTE: For additional information on NFS-320C, see DN-60085. DN-7112:E 09/07/2010 Page 3 of 6

NFS-320E: Same as NFS-320 above, but with 240 V operation. TR-320: Trim ring for the NFS-320 cabinet. Option Modules FCPS-24S6/-24S8: Remote six-amp and eight-amp power supplies with battery charger. See DN-6927. COMPATIBLE DEVICES, EIA-232 PORTS PRN-6: 80-column printer. See DN-6956. VS4095/5: Printer, 40-column, 24 V. Mounted in external backbox. See DN-3260. COMPATIBLE DEVICES, EIA-485 PORTS ACM-24AT: ONYX Series ACS annunciator up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow. See DN-6862. AEM-24AT: Same LED and switch capabilities as ACM-24AT, expands the ACM-24AT to 48, 72, or 96 points. See DN-6862. ACM-48A: ONYX Series ACS annunciator up to 96 points of annunciation with Alarm or Active LED per circuit. Active/ Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See DN-6862. AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-48A to 96 points. See DN-6862. TM-4: Transmitter Module. Includes three reverse-polarity circuits and one municipal box circuit; mount on NFS-320 chassis or remotely. See DN-6860. LCD-80/FDU-80: 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See LCD-80/-80TM (DN-3198) and FDU-80 (DN-6820). LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM- R32; remote custom driver modules. See LDM data sheet, DN-0551. ACM-8R: Remote Relay Module with eight Form-C contacts. Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See ACM-8R data sheet, DN-3558. APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See DN-5952. SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers SCS-8L, SCE-8L; eight (expandable to 16) circuits. See SCS data sheet DN-4818. UDACT: Universal Digital Alarm Communicator Transmitter, 636 channel. See DN-4867. UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microprocessorcontrolled, field-programmable from IBM -compatible PCs (requires optional programming kit). Mounts in BB-UZC. See DN-3404. COMPATIBLE INTELLIGENT DEVICES BEAMHK: Heating kit for transmitter/receiver unit of FSB-200(S) below. See DN-6985. BEAMHRK: Heating kit for use with the reflector of FSB-200(S) below. See DN-6985. BEAMLRK: Long-range accessory kit, FSB-200(S) below. See DN-6985. BEAMMRK: Multi-mount kit, FSB-200(S) below. See DN- 6985. BEAMSMK: Surface-mount kit, FSB-200(S) below. See DN- 6985. FSB-200: Intelligent beam smoke detector. See DN-6985. FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985. FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria Detector. See DN-60412. FSI-851: Low-profile FlashScan ionization detector. See DN- 6934. FSP-851: Low-profile FlashScan photoelectric detector. See DN-6935. FSP-851T: Low-profile FlashScan photoelectric detector with 135 F (57 C) thermal. See DN-6935. FST-851: FlashScan thermal detector 135 F (57 C). See DN-6936. FST-851R: FlashScan thermal detector 135 F (57 C) with rate-of-rise. See DN-6936. FST-851H: FlashScan 190 F (88 C) high-temperature thermal detector. See DN-6936. DNR: InnovairFlex low-flow non-relay duct-detector housing (order FSP-851 separately). Replaces FSD-751PL/FSD- 751RPL. See DN-60429. DNRW: Same as above with NEMA-4 rating, watertight. See DN-60429. FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor detector. See DN-6937. FSL-751: FlashScan VIEW laser photo detector. See DN- 6886. B224RB: Low-profile relay base. See DN-60054. B224BI: Isolator base for low-profile detectors. See DN- 60054. B710LP: Low-profile base. Standard U.S. style. See DN- 60054. B501: European-style, 4" (10.16 cm) base. See DN-60054. B200S: Intelligent sounder base, capable of producing a variety of tone patterns including ANSI Temporal 3. Compatible with sychronization protocol. See DN-60054. B200SR: Intelligent sounder base, Temporal 3 or Continuous tone. See DN-60054. FMM-1: FlashScan monitor module. See DN-6720. FDM-1: FlashScan dual monitor module. See DN-6720. FZM-1: FlashScan two-wire detector monitor module. See DN- 6720. FMM-101: FlashScan miniature monitor module. See DN- 6720. FCM-1-REL: FlashScan releasing control module. See DN- 60390. FCM-1: FlashScan NAC control module. See DN-6724. FRM-1: FlashScan relay module. See DN-6724. NBG-12LX: Manual pull station, addressable. See DN-6726. ISO-X: Isolator module. See DN-2243. XP6-C: FlashScan six-circuit supervised control module. See DN-6924. XP6-MA: FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN-6925. Page 4 of 6 DN-7112:E 09/07/2010

XP6-R: FlashScan six-relay (Form-C) control module. See DN-6926. XP10-M: FlashScan ten-input monitor module. See DN-6923. NETWORK OPTIONS NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN- 6861. HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network communications modules. Wire, single-mode fiber, multimode fiber, and media conversion models are available. See DN-60454. RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT- WF). See DN-6971. ONYXWorks-NW: UL-listed graphics PC workstation for standard NOTI FIRE NET with wire media. Includes NFN Gateway wire version (NFN-GW-PC-W) and 19" color flat-screen LCD monitor. Each ONYXWorks workstation consumes one of 103 ONYXWORKS-HNW: UL-listed graphics PC workstation for wire high-speed NOTI FIRE NET. Includes high-speed NFN Gateway (NFN-GW-PC-HNW) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 network addresses. See DN-7048. ONYXWorks-NF: UL-listed graphics PC workstation for standard NOTI FIRE NET with fiber media. Includes NFN Gateway wire version (NFN-GW-PC-F) and 19" color flat-screen LCD monitor. Each ONYXWorks workstation consumes one of 103 ONYXWORKS-HNSF: UL-listed graphics PC workstation for single-mode-fiber high-speed NOTI FIRE NET. Includes HS- NFN Gateway (NFN-GW-PC-HNSF) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 ONYXWORKS-HNMF: UL-listed graphics PC workstation for multi-mode-fiber high-speed NOTI FIRE NET. Includes HS- NFN Gateway (NFN-GW-PC-HNMF) and 19" color flat-screen LCD monitor. Each ONYXWorks consumes one of up to 200 NFN-GW-EM-3: NFN Gateway, embedded. 411: Slave Digital Alarm Communicator. See DN-6619. 411UDAC: Digital Alarm Communicator. See DN-6746. BB-UZC: Backbox for housing the UZC-256. Required for NFS-320 applications. Black; for red, order BB-UZC-R. OTHER OPTIONS IPDACT-2/2UD, IPDACT Internet Monitoring Module: Mounts in IPENC enclosure. Connects to primary and secondary DACT telephone output ports for internet communications over customer-provided ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408. IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red. For Black order IPENC-B. IPSPLT: Y-adaptor option allow connection of both panel dialer outputs to one IPDACT-2/2UD cable input. DPI-232: Direct Panel Interface, specialized modem for extending serial data links to remotely located FACPs and/or peripherals; mount on NFS-320 chassis. See DN-6870. VeriFire-TCD: VeriFire Tools CD-ROM. Contains programming software for the ONYX Series. Includes local panel connection cable. See DN-6871. BAT Series: Batteries. NFS-320 utilizes two 12 volt, 18 to 200 AH batteries. This series of products replaces the previous PS Series. See DN-6933. NFS-LBB: Battery Box (required for batteries larger than 25 AH). NFS-LBBR: Same as above, but red. DN-7112:E 09/07/2010 Page 5 of 6

SYSTEM SPECIFICATIONS System Capacity Intelligent Signaling Line Circuits... 1 Intelligent detectors... 159 Addressable monitor/control modules... 159 Programmable internal hardware and output circuits... 4 Programmable software zones... 99 Special programming zones... 14 LCD annunciators per CPU-320/-320E... 32 ACS annunciators per CPU-320/-320E... 32 addresses x 64 points Specifications Primary input power, CPU-320 board: 120 VAC, 50/60 Hz, 3.0 A. CPU-320E board: 220/240 VAC, 50/60 Hz, 1.5 A. Total output 24 V power: 6.0 A in alarm. NOTE: The power supply has a total of 6.0 A of available power. This is shared by all internal circuits. Standard notification circuits (4): 1.5 A each. Resettable regulated 24V power: 1.25 A. Two non-resettable regulated 24V power outputs: 1.25 A 0.50 A. Non-resettable 5V power: 0.15 A. Battery charger range: 18 AH 200 AH. Use separate cabinet for batteries over 25 AH. Float rate: 27.6 V. Cabinet Specifications NFS-320 cabinet dimensions: Backbox: 18.12 in. (46.025 cm) width; 18.12 in. (46.025 cm) height; 5.81 in. (14.76 cm) depth. Door: 18.187 in. (46.195 cm) width; 18.40 in. (46.736 cm) height; 0.75 in. (1.905 cm) depth. Trim ring: Molding width is 0.905 in. (2.299 cm). Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 49 C/32 120 F and at a relative humidity 93% ± 2% RH (noncondensing) at 32 C ± 2 C (90 F ± 3 F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C/60 80 F. Agency Listings and Approvals The listings and approvals below apply to the basic NFS-320 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: file S635 ULC Listed: file S635 (NFS-320C only, excludes IPDACT) CSFM: 7165-0028:0243 FM Approved MEA: 128-07-E FDNY COA #6038 City of Chicago NOTE: For additional information on UL- and ULC-listed model NFS-320C, see DN-60085. For information on NFS-320SYS, see DN-60637 Standards The NFS-320 complies with the following UL Standards and NFPA 72 Fire Alarm Systems requirements: UL 864 (Fire). UL 1076 (Burglary). LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). AUXILIARY (Automatic, Manual and Waterflow) (requires TM-4). REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires TM-4). PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler Supervisory). Not applicable for FM. CENTRAL STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires UDACT). EMERGENCY VOICE/ALARM. OT, PSDN (Other Technologies, Packet-switched Data Network) NOTI FIRE NET, IntelliQuad, and ONYXWorks are trademarks; and Acclimate Plus, FlashScan, NION, NOTIFIER, ONYX, UniNet, VeriFire, and VIEW are registered trademarks of Honeywell International Inc. Microsoft and Windows are registered trademarks of Microsoft Corporation. Echelon is a registered trademark of Echelon Corporation. IBM is a registered trademark of IBM Corporation. 2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 6 of 6 DN-7112:E 09/07/2010 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com