NTD-125-*, NTD-204-* & NTD-220-* Nuaire Round & Rectangular Thermal Ducting Installation Guide

Similar documents
FOR EVERY DUCTING SOLUTION DUCTING & ANCILLARIES

Installation and Maintenance

VENTILATION FOR STUDENT ACCOMMODATION

Installation and Maintenance

Installation and Maintenance

Installation and Maintenance

Installation and Maintenance

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Bracket

RESIDENTIAL VENTILATION DUCTING SOLUTIONS

Installation and Maintenance

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

Installation and Maintenance

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS.

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4.

MRXBOX95AB-WH1. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Wall Mounting. Installation and Maintenance

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan Installation Guide. Fig. 2 Fan components.

MRXBOX95-WM2. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

MRXBOX95-WM2H. Mechanical Ventilation Unit with Heat Recovery and Integral Humidistat for Wall Mounting Installation and Maintenance

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan with Humidity Enabler Installation Guide

Airflex Radial & ISO Thermal pipe

MRXBOX95-WALL. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Extract air.

WHHR Midi & Midi Lite

Application and Installation Guide (excluding Solar Air Collectors)

DUCTING FOR HRV SYSTEMS The distribution of airflows

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.com In Canada, call or visit

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Acoustic solution for MRXBOX95(AB)-WH1 and MRXBOX95(AB)-WM2

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

INSTALLATION GUIDE ISODRIVE MOTOR. ST - 900m 3 /hr.

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.com In Canada, call or visit

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

MODEL: DV72 R & L. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

Installation Manual for BR500

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

Installation Manual for isodrive 650 Motor

230V/24V DC SELV Surface and Semi-Recessed Mounted Domestic Fans INSTALLATION AND MAINTENANCE. n Wall mounting kit

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

Smoke extraction duct of sheet steel

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System

Chrome. Approximately 26 seconds drying time. 1.0kW Automatic Eco Fast Dryer Epoxy Coated. 1.2mm thick steel cover

Thank you for choosing EnviroVent

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

AP-EH500-L/RQA9837. Installation Guide

HEAT RECOVERY AIR HANDLING UNIT

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

CANOPY RANGEHOOD OFFBOARD INSTALLATION INSTRUCTIONS

SMALL DIAMETER CORR/GUARD & SLEEVED CORR/GUARD

INSTALLATION MANUAL AND USER GUIDE

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole.

Lo-Carbon Quadra Centrifugal Fan

Thank you for choosing EnviroVent

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

Sunwarm Air Solar Energy Ventilation System Installation and Maintenance Details for:

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR)

Installation and Maintenance Instructions

Installation Instructions

Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

OPERATING AND INSTALLATION INSTRUCTIONS FOR WHISPAIR RANGEHOODS UTILISING ON BOARD FAN MOTOR UNITS

DRI-365 Anti-Condensation and Whole House Positive Input Ventilation Unit

HOTLINE:

Purge Ventilation Unit. Product Manual. ventilation systems TP625

Ventilation Fan Model VFB24ACTH VFB24ADTH VFB24AXTH

Lo-Carbon Quadra SELV

Installation Manual for isodrive 1600 Motor

HRU ECO 3 RF APPENDIX Q ELIGIBLE NEW

Questions on Installation? Call: 800.GE.CARES (US) WARNING RISK OF FIRE 4" DIA. METAL DUCT (RECOMMENDED) 4" DUCT CLAMPS (2) OR 4" SPRING CLAMPS (2)

IF IN DOUBT, INSTALLATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH CURRENT WIRING REGULATIONS.

Natural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised

Questions on Installation? Call: 800.GE.CARES (US) WARNING RISK OF FIRE TOOLS YOU WILL NEED 4" DIA. METAL DUCT (RECOMMENDED)

The Range HIGHEST INDOOR AIR QUALITY IN NEW HOMES


HRXD MVHR UNIT Mechanical Ventilation with Heat Recovery.

INSTALLATION INSTRUCTIONS

vent With family and friends to take care of, it goes without saying you need the help of reliable kitchen appliances.

INSTALLATION MANUAL AND USER GUIDE

CANOPY RANGEHOOD ONBOARD INSTALLATION INSTRUCTIONS

Energysaver Space Heater Co-Axial Flue System Installation Manual

Corr/Guard PRESSURE RATED VENTING SYSTEM IMPORTANT: DO NOT INSTALL WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY.

Vertical Termination Part No: 3CGRVT 16 7/8" 18 Vent Pipe Extension Part No: 3CG18 9 7/8" Wall Hanger Part No: 3CGWH 7 7/8" 7 3/8"

CondenseSure Siphon INSTALLATION INSTRUCTIONS UK/IE GREENSTAR EXTERNAL 500ML SIPHON

SECTION (15820) - AIR DUCT ACCESSORIES

Installation Instructions

IDEO 325 ECOWATT. Counter-flow, high-efficiency heat recovery unit IDEO 325 ECOWATT. Low noise. Heat recovery units. Wireless programmable control

MODEL ESP-D SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL

DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

METIS. Installation instructions. Riser rail kit INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER.

Warnings, Safety Information and Guidance

Installation and Maintenance. Opus OK / Genie NKF1 Kitchen Extract Unit. Contents IMPORTANT WARNING IMPORTANT! Introduction WARNING!

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

Transcription:

1.0 INTRODUCTION NTD-125-*, NTD-204-* & NTD-220-* Nuaire Installation Guide Nuaire Ductmaster Ducting (NTD) is a range of ing and ancillaries intended for installation in domestic properties. Nuaire Ducting is available in three different sizes and profiles, based on the internal dimension: 125 mm Ø or 204 x 60 mm and 220 x 90 mm rectangular. Unlike other thermal ing systems Nuaire s unique ing design negates the need for solid plastic inner ing to achieve the required thermal properties and leakage rates stipulated by building regulations. Nuaire s thermal ing clamps connect system is designed to use with Nuaire Ducting and allows quick and easy installation without the need for any tapes or sealants. IMPORTANT The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU Nuaire Ducting is supplied in 1 meter lengths. If shorter lengths are required the can be cut to the desired length (see section 4.0). 2.1 Ducting Clamps Nuaire thermal ing clamps are available in 2 options to match 125 mm Ø or 204 x 60 mm or 220 x 90 mm rectangular. All types are with or without fixing lugs. Figure 2. Circular and Rectangular Ducting Clamps Using Nuaire thermal ing will achieve a level of leakage substantially lower than the maximum allowed for a class A as defined in DW/143 (Ductwork leakage testing). 2.0 INSTALLATION Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations. The ing must be installed indoors, on a suitable vibration free solid surface away from direct sources of frost, heat, and water spray or moisture generation. Prior to installation a dimensional check of the chosen installation location should be undertaken to ensure suitability. IMPORTANT NTD-204-CONL or NTD-220-CONL Rectangular clamp with fixing lugs. NTD-204-CON or NTD-220-CON Rectangular clamp without fixing lugs. IMPORTANT NTD-125-CONL Round clamp with fixing lugs. NTD-125-CON Round clamp without fixing lugs. Do not place heavy objects on the ing as this could cause distortion or breakage. Distorted ing could result in air flow leakage at the seal joint with the connector. ing clamps with and without fixing lugs must be used on the bends and T pieces as shown below. Figure 1. Rectangular Ducting Figure 3. Ducting Clamp Use Rectangular T Piece with clamps, 2x with lugs, 1 x without. 90 Round bend with clamps, 1x with lugs, 1x without. Round T Piece with clamps, 2x with lugs, 1x without. Rectangular 90 bend clamps 1x with lugs, 1x without. 1

3.0 Use of Flexible Duct Connections with Plenums and Bends Where it is necessary to use semi-rigid acoustic flexible (max length 300mm) between the MVHR unit and a plenum or bend please ensure that a rigid 125mm dia. PVC connector is installed into the plenum or bend for successful connection. Figure 4. Using the PVC connector (Part no. PVC593WH) plenum connector Semi-rigid acoustic flexible ing 90 bend connector Semi-rigid acoustic flexible ing 3.2 Installation of a Condensation Trap in Ducting Figure 6. Use of Condensate Trap (Code Contrap125) with Duct Connectors (Code PVC593WH) connector Condensation trap connector 3.3 Installation of an Attenuator in Ducting Figure 7. Use of Condensate Trap (Code Contrap125) with Duct Connectors (Code PVC593WH) MVHR unit 3.1 Use of Flexible Duct Connections Between Air Valves and Plenums / Bends Figure 5. Use of Standard Flexible Ducting (Max Length 300mm) Between an Air Valve (Part no. VS125) and Plenum or Bend Attenuator (spigot fits into thermal ) 90 bend plenum connector connector Attenuator (spigot fits into thermal ) Standard flexible ing Standard flexible ing Air valve Air valve 2

4.0 Cutting Ducting Lengths A flush, square 90 cut is required to ensure that an air tight seal is made with centre ridge in the clamp. If an angled cut is made, this will not allow the clamps to create a seal on the. We advise that the is cut with a very sharp blade or fine toothed saw (we recommend a minimum of 14 teeth per inch). The cutting blade length should be at least the same length as the wall thickness of the ing. Ensure is placed into Duct Clamp connector prior to installation to check the squareness of the cut ing. Figure 8. Square 90 Cut Is Required to Ensure an Air Tight Seal 5.0 Fitting Clamps with Fixing Lugs IMPORTANT Only clamps with fixing lugs (NTD-204-CONL) and (NTD-125-CONL) should be used for fitting / securing to the installation surface. 1. Establish the installation position for the ing and clamps with lugs and drill 2 holes to suit the clamp position. Figure 10. Features of Circular Clamp with Lugs (NTD-125-CONL) Square cut edge of length must meet centre ridge of clamp to ensure air tight seal. 205mm Fixing hole centres Clamp viewed from below An angled cut made on the will not allow the clamps to make an air tight seal. Male / female fixings either side of the clamp. Cutting edges located inside the clamps dig in / press into the foam ing when fitted. Centre flange in the clamp should form a self air tighr seal with square cut ing end. Figure 11. Features of 204 x 60mm Clamp with Lugs (NTD-204-CONL) Clamp viewed from below Figure 9. Circular and Rectangular (204 x 60mm) NTD Cutting Aids. 295mm Fixing hole centres NTD-125-CUTTINGAID Male/female fixings either side of the clamp. NTD-204-CUTTINGAID Cutting edges located inside the clapms dig in/press into the foam ing when fitted. Centre flange in the clamp should form an air tight seal with square cut ing. Figure 12. Features of 220 x 90mm Clamp with Lugs (NTD-220-CONL) 312mm Fixing hole centres IMPORTANT Nuaire Ducting is supplied in 1 metre lengths. If shorter lengths are required the can be cut to the desired length with a fine toothed saw. (We recommend a minimum of 14 teeth per inch). Failure to make a square cut may result in air flow leakage when connecting to other ing pieces. Ensure is placed into Duct Clamp connector prior to ins tallion to check the squareness of the cut ing (figs. 9 and 10). Male/female fixings either side of the clamp. Pips located inside the clamp dig into the foam when fitted. 3

2. Having drilled 2 fixing holes to suit the clamp position, remove the top half of the clamp from the bottom half. Using appropriate fixings fix the top half of the clamp to the solid surface (fixings supplied by others). Figure 16. Joining 2 Lengths of Rectangular Ducting Figure 13. Hole Centres on Circular Lugged Clamps Figure 14. Hole Centres on Rectangular Clamps 4. For final installation into the clamp, push the up into the clamp fixed to the solid surface. The centre joint of the 2 lengths should be located on the centre ridge of the clamp. Take the bottom half of the clamp and push up so that the fixing tabs on each side fit into the slots on the female half, then press together. Ensure the ing is fully pressed into the clamp to create an air tight seal. Failing to do so may cause air leakage. Figure 17. Hole Centres on Circular Clamps 3. Having drilled 2 fixing holes to suit the clamp position, remove the top half of the clamp from the bottom half. Using appropriate fixings fix the top half of the clamp to the solid surface (fixings supplied by others). Square cut edge of joined lengths must meet centre ridge of clamp. Figure 15. Joining 2 Lengths of Circular Ducting Male fixing tabs on each side of the bottom half of the clamp fit into the 2 slots on the top half. Figure 18. Hole Centres on Rectangular Clamps Square cut edge of joined lengths must meet centre ridge of clamp. Male fixing tabs on each side of the bottom half of the clamp fit into the 2 slots on the top half. 4

Figure 19. Installed Circular Ducting Figure 20. Installed Rectangular Ducting 6.0 Fitting Clamps without Fixing Lugs The clamps without fixing lugs (NTD-204-CON or NTD-220-CON) and (NTD-125-CON) should only be used to connect two ing items together; they should not be used for installing to any surface. Straight runs of Nuaire white plastic ing should be supported by either clip type PVC122-5WH or PVC coated steel banding every 1.0m (maximum). Straight runs of Nuaire Duct should be supported every 1.0m (maximum) if using PVC coated steel banding or when using Clamps with Mounting Lugs (Types NTD-204-CONL, NTD-125-CONL, NTD- 220-CONL). With both thermal ing or rigid ing systems, care should be taken to ensure that bends, T-pieces, transitions, and plenum sections are also adequately supported by at least one lugged clamp/pvc clip/ banding support, as applicable. When banding is used, work support locations should ideally be at the midpoint between clamps. Figure 21. Using PVC Bands to Support Ducting Use PVC bands to support 5

7.0 TYPICAL MVHR DUCT ARRANGEMENT FOR 204 x 60mm Figure 22. Example MVHR Duct Arrangement Uninsulated round to rectangular fan plenum (204 x 60mm) Part no. PVC540WH. Uninsulated T piece (204 x 60mm) Part no. PVC582WH. Supply air to bedrooms via Air Valve in ceilings. Part no. VS125. Inline attenuator Part no. PVCSIL-1500. Duct support clamps for insulated ing (204 x 60mm) Part no. NTD-204-CON Part no. NTD-204-CONL. Top of ceiling void. Supply air to lounge via Air Valve in ceilings. Part no. VS125. Air brick Part no. PVC505NS. Exhaust air from kitchen/bathroom to outside via air brick (Part no. PVC505NS). Minimum 300mm Extract air from kitchen via Air Valve in ceilings (Part no. VS125). Extract air from bathroom via Air Valve in ceilings (Part no. VS125). Nuaire MRXBOX95B-LP1H ceiling void mounted unit. Intake air from outside via air brick (Part no. PVC505NS) Supply and extract s from external grilles to the ubit should be insulated ing. Air valve. Part no. VS125. Duct support clip for uninsulated ing (204 x 60mm) Part no. PVC122-5WH. Condensate drain Part no. MVHR-DRAIN. Insulated 90 horizontal bend (204 x 60mm) Part no. NTD-204-90H. Insulated rectangular pipe (204 x 60mm) Part no. NTD-204-1M. 8.0 SPARES & SERVICE ENQUIRIES Spare parts and replacement components are available from Nuaire. Please contact us for further details. Our Technical Support department will be happy to provide any assistance required, initially by telephone and if necessary, will arrange for an engineer to call. Telephone 029 2085 8400 technicalsupport@nuaire.co.uk Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and dimensions of equipment and the right is reserved to make such changes without prior notice. 6

Range Details 125mm dia. Ducting INSULATED "T" PIECE NTD-125-TP 125mm Ø Insulated T Piece INSULATED 90 BEND NTD-125-90H 125mm Ø Insulated 90 Bend INSULATED 45 BEND NTD-125-45H 125mm Ø Insulated 45 Bend INSULATED DUCT 1M LENGTH NTD-125-1M 125mm Ø Insulated Duct 1m Length ROUND DUCT CLAMP FOR INSULATED DUCT NTD-125-CONL 125mm Ø One Piece Connector & Duct Clamp NTD-125-CON 125mm Ø One Piece Connector & Duct Clamp 7

Range Details 204 x 60 mm Ducting INSULATED "T" PIECE NTD-204-TP 204mm x 60mm Insulated T Piece INSULATED 90 HORIZONTAL BEND NTD-204-90H 204mm x 60mm Insulated 90 Horizontal Bend INSULATED 45 HORIZONTAL BEND NTD-204-45H 204mm x 60mm Insulated 45 Horizontal Bend INSULATED 90 VERTICAL BEND NTD-204-90V 204mm x 60mm Insulated 90 Vertical Bend INSULATED 45 VERTICAL BEND NTD-204-45V 204mm x 60mm Insulated 45 Vertical Bend INSULATED PLENUM NTD-204-PL 204mm x 60mm Insulated Plenum INSULATED DUCT 1M LENGTH NTD-204-1M 204mm x 60mm Insulated Duct 1m Length RECTANGULAR DUCT CLAMP FOR INSULATED DUCT NTD-204-CONL 204mm x 60mm One Piece Connector & Duct Clamp NTD-204-CON 204mm x 60mm One Piece Connector & Duct Clamp 8

Range Details 220 x 90 mm Ducting INSULATED "T" PIECE NTD-220-TP 220mm x 90mm Insulated T Piece INSULATED 90 HORIZONTAL BEND NTD-220-90H 220mm x 90mm Insulated 90 Horizontal Bend INSULATED 45 HORIZONTAL BEND NTD-220-45H 220mm x 90mm Insulated 45 Horizontal Bend INSULATED 90 VERTICAL BEND NTD-220-90V 220mm x 90mm Insulated 90 Vertical Bend INSULATED 45 VERTICAL BEND NTD-220-45V 220mm x 90mm Insulated 45 Vertical Bend INSULATED PLENUM NTD-220-PL 220mm x 90mm Insulated Plenum to 125mm Ø INSULATED PLENUM NTD-220-PL150 220mm x 90mm Insulated Plenum to 150mm Ø INSULATED DUCT 1M LENGTH NTD-220-1M 220mm x 90mm Insulated Duct 1m Length 9

Range Details 220 x 90 mm Ducting RECTANGULAR DUCT CLAMP FOR INSULATED DUCT NTD-220-CONL 220mm x 90mm Duct Clamp with Fixing Lugs NTD-220-CON 220mm x 90mm Duct Clamp withuot Fixing Lugs INSULATED 220 x 90 TO 204MM REDUCER NTD-220-RED204 220 90 to 204mm x 60mm Insulated 220 x 90 to 204mm Reducer INSULATED 220 x 90 TO 125MM DIAMETER ADAPTOR NTD-220-STR125 220 x 90 to 125mm Dia. Insulated 220 x 90 to 125mm Rectangular to Round In-line Adaptor INSULATED 220 x 90 TO 150MM DIAMETER ADAPTOR NTD-220-STR150 220 x 90 to 150mm Dia. Insulated 220 x 90 to 150mm Rectangular to Round In-line Adaptor 10