Installation, start-up use and maintenance manual

Similar documents
Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

Installation, start-up use and maintenance manual

Installation, use and maintenance manual

Submittal Data GAHP Line W LB Series Ground Source Gas Fired Absorption Heat Pump Heating and Cooling

USER S INFORMATION MANUAL

GAS ABSORPTION HEAT PUMP

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

Columbia Boiler Company

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

User s Information Manual Models: 45, ,000 Btu/hr

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY:

Contents. Hazard definitions

Elite. User s Information Manual. Elite and Elite VWH* All Models

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS RSTP17C

MC Series Gas-Fired Heating Appliance

JH Series Installation

WHE 2.24 / WHE 2.24 FF

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

Surna 25-Ton Chiller Operating & Maintenance Manual

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Gas-Fired Indoor and Outdoor Duct Furnaces

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

Boiler Manual. Gas-fired water boilers. Featuring. Flexibility

C1050ES Tankless Water Heater

Project Name: Location: Engineer: Contractor: I. GENERAL

User s Information Manual

User s Information Manual

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Contents. Hazard definitions

FOR YOUR SAFETY WARNING FOR YOUR SAFETY IMPORTANT CAUTION

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

AFUE 95% Heating Input 50,000 to 200,000 Btuh

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

SKYPAK II, 3 Ton Series, gives you a

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

User s Information Manual

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

LGB Gas fired boiler

Universal Fire Tube Boiler Wall Mount Models

Inspection Checklist Mechanical Rough in

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

User s Information Manual

User s Information Manual Models: ER152, ER202, ER252, ER302, and ER402

SKYPAK II, 3 Ton Series, gives you a

User s Information Manual

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

User s Information Manual

Installation Instructions

Tankless Water Heater

USER S INFORMATION MANUAL (2,4)SG13B

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

USERS MANUAL FOR GAS BOILERS

WHAT TO DO IF YOU SMELL GAS

C1210ES Tankless Water Heater

USERS GUIDE 24, 30. For installation guide see reverse of book

Bosch 80% AFUE Gas Furnace BGS80 Model

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Gas Fired Residential Combi Boiler Floor and Wall Mount Models

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

Installation Requirements for Models:

BEACON/MORRIS RBD SERIES INFRARED RADIANT HEATER

Residential Gas Hybrid Water Heater

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

WATER-TUBE POOL HEATERS

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova

Installation, Operation and Maintenance Manual

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

M2 Series Startup Form

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

PDF Created with deskpdf PDF Writer - Trial ::

Vent Supplement Ultra-80, -105, -155, -230 & -310

Installation Instructions

OPERATING INSTRUCTIONS AND OWNER S MANUAL

PBG PACKAGED GAS BURNER

Installation & Operation Manual Models: TSU

940ES Tankless Water Heater

User Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown

IN020 Rev F Page 1 of 8

WARNING FOR YOUR SAFETY CAUTION. gas-fired indoor gravity and power vented duct furnaces AIR H

Owner s Guide Installation & Operation

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Suggested Specifications Prestige Excellence 110

Please read before proceeding

Direct Vent System Required

Installation & Operation Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown

DIVISION FINNED WATER-TUBE BOILERS

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

GPC PASTA PRO INSTALLATION & USER OPERATION MANUAL

Transcription:

Installation, start-up use and maintenance manual GA Line AYF 60-119 Model Air cooled absorption chiller-heater to product chilled water down to 37.4 F and hot water up to 185 F Natural gas/lpg fired

INDEX 1. GENERAL WARNINGS...3 2. OVERVIEW AND TECHNICAL DATA...5 2.1 OVERVIEW...5 2.2 INSTRUCTIONS FOR THE USER...7 2.3 TECHNICAL DATA: AYF60-119, HT, TK, LB...8 2.4 PRESSURE DROP...17 2.5 AYF60-119, HT, TK, LB DIMENSIONS...21 3. INSTALLATION...22 3.1 GENERAL RULES...22 3.2 INSTALLATION OF THE UNIT...23 4. HYDRONIC AND GAS INSTALLATION...26 4.1 WATER PIPING DESIGN AND INSTALLATION...26 4.2 GAS SUPPLY PIPING...32 4.3 DUCT FLUE EXHAUST (heating module)...33 4.4 SERVICE PLATE DIMENSIONS...34 5. ELECTRICAL CONNECTION...35 5.1 POWER SUPPLY...35 5.2 ELECTRICAL CONNECTION DIAGRAMS...36 5.3 DDC CONNECTION...44 6. START-UP AND ADJUSTMENT...55 6.1 INSTRUCTIONS ON HOW TO START AND SHUT-OFF THE UNIT...56 6.2 FILLING THE WATER PIPING...56 6.3 GAS PRESSURE ADJUSTMENT...59 6.4 CHILLED WATER TEMPERATURE REGULATION...62 6.5 HOT WATER TEMPERATURE REGULATION...63 7. SERVICING AND MAINTENANCE...64 8. ADAPTING TO ANOTHER GAS...67 9. SPARE PARTS...69 APPENDIX...88 ELECTRONIC SYSTEM OF THE AYF60-00 UNITS...88 TABLE OF OPERATING CODES GENERATED BY ELECTRONIC BOARD (firmware version 3.027)...92

NOTE Carefully read the information contained in this manual. It contains important instructions regarding installation, use and maintenance safety. Save this manual for any future needs. The manufacturer cannot be held responsible for any damages from improper, erroneous or irrational use. With the aim of continuously improving the quality of our products, manufacturer reserves the right to change reported instructions and drawings without any prior notice. 2 Installation, Start-Up, Adjustment and Maintenance Manual

1. GENERAL WARNINGS This manual is an integral and essential part of the product and must be given to the owner. Only qualified technicians, strictly complying with the manufacturer s instructions and the local standards, should install this product. The manufacturer will not accept responsibility for personal injuries or property damage resulting from improper installation. Qualified technicians are those having specific technical competence in air conditioning and gas appliances according to international and national standards. This appliance must be used exclusively for its intended purpose. All chilling and heating applications must be in accordance with the operating specifications of the unit. Any other use is considered improper and, therefore, dangerous. Steps must be taken to avoid improper use and potential dangers. The fluids used in the sealed refrigerant circuit may cause health problems if inhaled, ingested or when allowed to come into contact with the skin. It is recommended that no work be performed on the sealed refrigerant circuit except by a qualified service technician or engineer. Care should also be taken not to disturb or handle the valves of the chiller s sealed refrigerant circuit. The manufacturer will not accept contractual or non-contractual liability for damages resulting from improper installation or misuse of the unit or intentional disregard of any of the manufacturer s instructions. After unpacking the unit, check the unit for integrity. Due to the potential danger, keep all packaging materials (plastic bags, polystyrene foam, nails, etc.) away from children. Before installation, it is recommended that all chilled water and gas supply piping be flushed. If not flushed prior to installation, residual materials may be left in the piping that could cause improper functioning of the chiller. The installation of the appliance must conform to the requirements of the authority having jurisdiction or in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. The appliance electrical connections and grounding must be in accordance with the latest edition of the National Electrical Codes, ANSI/NFPA No. 70 and with any local codes. To ensure the electrical safety of this appliance, it must be correctly connected to an efficient grounding system. The manufacturer is not responsible for any damages caused by the failure of the grounding system. In the case of failure and/or poor unit performance, shut the unit down in the proper manner, disconnect the unit power supply and close the gas valve. Do not attempt any repair and call a qualified technician for service. The chiller should also be disconnected when not in use for a prolonged period of time. The manufacturer s authorized Service Technicians or authorized Service Engineer (TAC), using only original replacement parts, must perform repairs to the product. Failure to adhere to this guideline may compromise the safety of the unit. To ensure the correct operation and efficiency of the unit, it is essential that qualified service technicians perform annual maintenance in accordance with the manufacturer s instructions. Installation, Start-Up, Adjustment and Maintenance Manual 3

If the unit is sold or transferred to another owner, this manual will be provided for use to the new owner and/or installer. Under no circumstances should the unit be operated with any safety or electrical component bypassed or defective. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water. Keep the boiler area clean and free from combustible materials, gasoline and other flammable vapors and liquids. Take care not to obstruct the flow of combustion and ventilation air. Before starting the appliance: A qualified service technician must verify that: - The electric and gas supplies are the same as indicated on the rating plate - The fuel supply and water distribution systems are water tight - The appliance is supplied with the type of fuel for which it is preset - The gas supply pressure conforms to the pressure indicated on the rating plate - The gas supply system is appropriately designed for the gas rate needed by the unit, and equipped with all safety and control devices prescribed by standards in force. The electrical safety of this appliance is ensured only when it is correctly connected to an efficient grounding system, in accordance to the electrical standards in force. WARNING To guarantee the correct operation of the unit and avoid possible failures, ALWAYS turn off the unit by means of the thermostat or any switch that controls the operation of the unit. NEVER turn off the unit by shutting off the power supply. 4 Installation, Start-Up, Adjustment and Maintenance Manual

2. OVERVIEW AND TECHNICAL DATA 2.1 OVERVIEW The High Efficiency units AYF60-119 are 2 modules appliances; each AYF is composed by both a single water chiller (conditioning module, or cold module) and an high efficiency boiler (heating module, or hot module). AYF units are designed for outdoor installation, the combustion fuel is Natural Gas or LPG. The conditioning module is equipped with an air-cooled condenser. The absorption cooling cycle is based upon a solution of water and ammonia for the production of chilled water (temperature of chilled water is given by Technical Tables). The chilling system is fed by thermal energy provided by a gas burner, therefore the required electric energy is limited to driving the fan and pump motors (the only mechanical moving components of the unit). The evacuation of combustion gases occurs by mixing them with condenser air using an axial fan of the appliance; no flue is needed. The heating module evacuates the combustion gases by a proper vent, situated in the rear side of the unit. If necessary, a flue may be connected to bring the gases discharge far from the unit; in this case dimensions for boilers natural draught have to be followed. TYPES AND VERSIONS AYF60-119 units are supplied in 2 models: the 2 pipe and the 4 pipe one. AYF60-119/2 is the 2 pipe model: this appliance can alternately work as a chiller or as a boiler. The 2 pipes, inlet and outlet are both used for chilled and hot water, alternatively. AYF60-119/4 is the 4 pipe model: this appliance can work as a chiller and as a boiler at the same time. 2 pipes are used for the chilled water, and 2 for the hot one. Besides, the 2 modules work in an independent way the one from the other. AYF (2 and 4 pipes) are supplied in one standard version and 3 special versions. AYF60-119: this is the standard version. It can produce chilled water down to 37.4 F and hot water up to 183.2 F. AYF60-119 HT: high (air) temperature. The chilling module of this version is designed to work in hot climate areas. AYF60-119 TK: technologic version. The chilling module of this version is designed for the air-conditioning and refrigeration of technological applications (for example, in the industrial process, that could require chilled water up to 24h a day). AYF60-119 LB: low temperature. The chilling module of this version is designed for low temperature refrigeration applications, as cold rooms or food conservation. For further information see next paragraph, technical data. AYF60-119 units are Natural Gas or LPG fired and supplied with 208-230V 60Hz single-phase electrical power. AYF60-119 units could be controlled by DDC - Direct Digital Controller (available as Optional). DDC can control up to 16 units. Figure 1 Direct Digital Controller Installation, Start-Up, Adjustment and Maintenance Manual 5

CHILLER CONTROL AND SAFETY DEVICES The chiller module includes: Electronic Control Board with integrated microprocessor controls the operation of the chiller. High Temperature Limit Switch (manual reset) is located at the generator wall above the combustion chamber; the switch opens if the generator's sidewall temperature exceeds 330 F; the switch is manual reset. The switch can be reset when the generator sidewall temperature drops below 280 F. Safety Relief Valve on the sealed circuit. Differential Air Pressure Switch on the combustion circuit stops the burner ignition due to insufficient combustion air flow. Ignition Control Box controls the burner ignition. Checks the differential air pressure switch and starts the pre-mixer blower. After 30 seconds of purging, the ignition control box opens the gas valve and starts the ignition transformer sparking at the burner for 8 seconds. If no flame is detected, the ignition control box will close the gas valve and retry lighting after an inter-purge period of 30 seconds. The ignition control box will try a total of three times to light. The unit will stop if no flame has been established or detected after the 3 tries. Dual Gas Valve: two gas valves in the same housing, electrically controlled, which positively stops gas flow when either closes. Flow Switch monitors the chilled water flow and shuts down the unit when the water flow stops or drops to an insufficient level. HEATER CONTROL AND SAFETY DEVICES The heater module is controlled and monitored by the chiller module electronic control board through an electronic card situated on the heater. The heater module includes: Exhausted Gases Temperature Limit Switch (manual reset) is located on the flue gas pipe near the combustion chamber; the switch opens if the exhausted gases temperature exceeds 330 F; the switch is manual reset. The switch can be reset when the temperature drops below 280 F. High Temperature Limit Switch (auto reset) is located on the hot water generator wall above the combustion chamber; the switch opens if the outlet water temperature exceeds 212 F; the switch is auto reset. Safety Relief Valve on the hydronic circuit is set to release hot water if internal pressure exceeds 45 PSIg; the valve closes automatically when pressure is under 45 PSI g Differential Air Pressure Switch on the combustion circuit stops the burner ignition due to insufficient combustion air flow. Ignition Control Box controls the burner ignition. Checks the differential air pressure switch and starts the pre-mixer blower. After 30 seconds of purging, the ignition control box opens the gas valve and starts the ignition transformer sparking at the burner for 8 seconds. If no flame is detected, the ignition control box will close the gas valve and retry lighting after an inter-purge period of 30 seconds. The ignition control box will try a total of three times to light. The unit will stop if no flame has been established or detected after the 3 tries. Dual Gas Valve: two gas valves in the same housing, electrically controlled, which positively stops gas flow when either closes. Flow Switch monitors the chilled water flow and shuts down the unit when the water flow stops or drops to an insufficient level. 6 Installation, Start-Up, Adjustment and Maintenance Manual

2.2 INSTRUCTIONS FOR THE USER Correct operation and reliability of the unit is related to the proper use of the appliance. Before starting the unit check: - that shut-off valve is open; - that ON/OFF switch (mounted by electrician) is in the ON position - that pressure inside hydronic circuit is correct. The start-up of the unit is obtained through proper switches installed by the installer/electrician. In particular: for AYF/2 pipe unit - A summer/winter 2-way switch, for the selection of operations (conditioning or heating) - An external switch such as a timer, thermostat, ON/OFF switch for switching ON/OFF the chiller/heater. for AYF/4 pipe unit - A switch for chiller such as a timer, thermostat, ON/OFF switch - A switch for heater such as a timer, thermostat, ON/OFF switch NOTE If DDC (available as accessory) is used, management and control of AYF 60-119 unit will take place only through DDC: in this case, check the instructions contained in the specific DDC manual, supplied with DDC itself. WARNING The power supply line must not be used to turn the unit ON and OFF ; instead, use the dedicated control switch installed by the installer/electrician. The closing of switch will start the appliance Opening of the switch will properly shut down the appliance, i.e. after 10 minutes the appliance will shut off completely During start-up, a possible flame control box lockout could occur, due to the air remaining in the gas line. To reset the appliance: by means of the electronic control board, enter Menu 2 (actions menu) and execute reset as shown in APPENDIX, page 88. Once reset, the unit will restart ignition cycle. In case of frequent lockouts, please call authorized Service Engineers (TAC). NOTE Flame control box lockout and any other information on unit function (data, parameters, unit codes, etc.) are visualized on ECB display, placed in the chiller control box. Display is visible through the glass of the front panel. To reset the flame control box it is necessary to use the ECB knob (encoder): to use it and to execute all allowed operations (scrolling/selecting data: confirm, exit, data setting) it is necessary to remove the front panel of the unit and, without opening the control box, open the plug on the cover of the control box, corresponding the encoder, and interact with the knob using the proper tool supplied (4 ¾ pipe). SEASONAL STOPS Switching off operations shut off the unit by the opening of on/off switch (don t cut off power supply) wait until the shut off cycle stops completely the appliance (approx. 600 s) now you can cut off the main power supply by means of the main electrical switch installed by the installer/electrician shut the gas valve verify that antifreeze (glycol) is present inside the water system or empty completely the system. Restarting operations verify if the appliance needs any ordinary maintenance operation (eventually contact the assistance). Installation, Start-Up, Adjustment and Maintenance Manual 7

Before restarting the unit check that the water system is completely filled. In the case you need to add water to the hydronic system, ADD ALWAYS adequate glycol percentage into the water. The quantity of antifreeze has to be conform to minimum external ambient temperatures or model of installed unit. Pressurize the system, making sure that water pressure is not below 14.5 PSIg. Before proceeding with the start-up, please control the following: - the gas supply tap is opened - the electric main switch is ON - Adequate water pressure and flow rate in the hydronic system 2.3 TECHNICAL DATA: AYF60-119, HT, TK, LB AYF60-119 (STANDARD VERSION) 1 AYF60-119/2 AYF60-119/4 PERFORMANCE RATINGS - COOLING Cooling Capacity 2 Nominal Btu/hr 60,500 Gas Input (HHV) Nominal Btu/hr 94,900 Ambient Operating Temperature Maximum 120 F Minimum 32 Condenser Air Flow 3 Nominal 6,000 CFM Minimum 2,000 Inlet (to the unit) Chilled Water Maximum F 113 Temperature Outlet (to plant) Chilled Water Temperature Chilled Water Flow Minimum F 37.4 Nominal Maximum Minimum GPM 12.2 14.1 11.0 PERFORMANCE RATINGS HEATING Heating Capacity Nominal Btu/hr 110,900 Gas Input (HHV) Nominal Btu/hr 129,000 Ambient Operating Temperature Inlet (to the unit) Hot Water Temperature Outlet (to plant) Hot Water Temperature Hot Water Flow Maximum Minimum F Maximum F Maximum F Nominal Maximum Minimum GPM 12.2 14.1 11.0 116.6-7.6 167 ELECTRICAL RATINGS Required Voltage, 60 Hz, Single 3 Phase V 208-230 Minimum Circuit Ampacity (MCA) Unit only A 8.0 Maximum Over Current Protection (MOCP) A 10.9 Operating Consumption - chiller 4 0.75 Operating Consumption - heater kw 0.076 Operating Consumption matched SERVICE PLATE CONNECTIONS Chilled Water Inlet/Outlet 5 FPT 1 1/4 Hot Water Inlet/Outlet FPT 1 1/4 Gas FPT ½ Electrical knockouts Inches 185 7 / 8 8.8 14.1 6.6 0.826 8 Installation, Start-Up, Adjustment and Maintenance Manual

PHYSICAL DATA Pressure drop chiller Pressure drop heater Pressure drop matched Feet of Head/PSIg 17.13/7.40 Operating pressure Maximum PSIg 45 9.67/4.20 8.30/3.60 Refrigerant Type (chiller) R717 Unit Chilled Water volume 6 1.05 Unit Hot Water volume Gallons 1.32 Matched water volume 1.58 Shipping weight Pounds 1030 Operating weight Pounds 970 Dimensions Width Length Height Inches 48 7 / 8 48 1 / 2 50 3 / 4 Heater gases duct internal diameter Inches 5 1 / 8 Table 1 AYF60-119 TECHNICAL DATA Notes: 1. All illustrations and specifications contained herein are based on the latest information available at the time of publication approval. Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue models. 2. Cooling capacity at standard conditions of 95 F ambient temperature. Chilled water Outlet temperature 45 F, chilled water Inlet temperature 55 F. Cooling capacity characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For cooling capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor. 3. Units are factory-wired for 208-230 volts operation. 4. May vary by ±10% as a function of both power supply and electrical motor input tolerance. 5. Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes.. 6. "Chilled Water" refers to a solution of quality tap water and 10% by volume of inhibited permanent antifreeze. Higher antifreeze concentrations may be required in certain applications. COOLING CAPACITY in Btu/hr AMBIENT AIR TEMPERATURE ( F) OUTLET CHILLED WATER ( F) 37.4 41.0 44.6 48.2 32 59,307 59,912 61,123 62,323 41 59,307 59,912 61,123 62,333 50 59,307 59,912 61,123 62,323 59 59,307 59,912 61,123 62,333 68 59,307 59,912 61,123 62,323 77 58,701 59,912 61,123 62,333 86 54,465 59,307 61,123 62,333 95 40,546 52,650 60,517 61,727 104 - - 53,255 56,281 113 - - 40,546 47,203 120 - - - 39,336 Table 2 AYF60-119 COOLING CAPACITY Installation, Start-Up, Adjustment and Maintenance Manual 9

AYF60-119 HT 1 AYF60-119/2 HT AYF60-119/4 HT PERFORMANCE RATINGS COOLING Cooling Capacity 2 Nominal Btu/hr 58,400 Gas Input (HHV) Nominal Btu/hr 94,900 Ambient Operating Temperature Maximum 131 F Minimum 32 Condenser Air Flow 3 Nominal 6,000 CFM Minimum 2,000 Inlet (to the unit) Chilled Water Maximum F 113 Temperature Outlet (to plant) Chilled Water Temperature Chilled Water Flow Table 3 AYF60-119 HT TECHNICAL DATA 10 Minimum F 41 Nominal Maximum Minimum GPM 11.8 14.1 11.0 PERFORMANCE RATINGS HEATING Heating Capacity Nominal Btu/hr 110,900 Gas Input (HHV) Nominal Btu/hr 129,000 Ambient Operating Temperature Inlet (to the unit) Hot Water Temperature Outlet (to plant) Hot Water Temperature Hot Water Flow Maximum Minimum F 116.6-7.6 Maximum F 167 Maximum F 185 Nominal Maximum Minimum GPM 11.8 14.1 11.0 ELECTRICAL RATINGS Required Voltage, 60 Hz, Single Phase 3 V 208 230 Minimum Circuit Ampacity (MCA) Unit only A 8.0 Maximum Over Current Protection (MOCP) A 10.9 Operating Consumption - chiller 4 0.75 Operating Consumption - heater kw 0.076 Operating Consumption matched SERVICE PLATE CONNECTIONS Chilled Water Inlet/Outlet 5 FPT 1 1/4 Hot Water Inlet/Outlet FPT 1 1/4 Gas FPT ½ Electrical knockouts Inches 7 / 8 PHYSICAL DATA Pressure drop chiller Feet of Pressure drop heater Head/PSIg Pressure drop matched 16.25/7.10 Operating pressure Maximum PSIg 45 8.8 14.1 6.6 0.826 9.11/3.92 8.30/3.60 Refrigerant Type (chiller) R717 Unit Chilled Water volume 6 1.05 Unit Hot Water volume Gallons 1.32 Matched water volume 1.58 Shipping weight Pounds 1098 Operating weight Pounds 1035 Dimensions Width Length Height Inches 48 7 / 8 48 1 / 2 50 3 / 4 Heater gases duct internal diameter Inches 5 1 / 8 Installation, Start-Up, Adjustment and Maintenance Manual

Notes: 1. All illustrations and specifications contained herein are based on the latest information available at the time of publication approval. Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue models. 2. Capacity at standard conditions of 95 F ambient temperature. Chilled water Outlet temperature 45 F, chilled water Inlet temperature 55 F. Capacity characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor. 3. Units are factory-wired for 208-230 volts operation. 4. May vary by ±10% as a function of both power supply and electrical motor input tolerance. 5. Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes.. 6. "Chilled Water" refers to a solution of quality tap water and 10% by volume of inhibited permanent antifreeze. Higher antifreeze concentrations may be required in certain applications. COOLING CAPACITY in Btu/hr AMBIENT AIR TEMPERATURE ( F) OUTLET CHILLED WATER ( F) 41.0 44.6 50.0 54.5 57.2 32.0 59,637 59,637 59,637 59,637 60,222 35.6 59,637 59,637 59,637 59,637 60,222 39.2 59,637 59,637 59,637 59,637 60,222 42.8 59,637 59,637 59,637 59,637 60,222 46.4 59,637 59,637 59,637 59,637 60,222 50.0 59,637 59,637 59,637 59,637 60,222 53.6 59,637 59,637 59,637 59,637 60,222 57.2 59,637 59,637 59,637 59,637 60,222 60.8 59,637 59,637 59,637 59,637 60,222 64.4 59,637 59,637 59,637 59,637 60,222 68.0 59,637 59,637 59,637 59,637 60,222 71.6 59,637 59,637 59,637 59,637 60,222 75.2 59,637 59,637 59,637 59,637 60,222 78.8 59,053 59,637 59,637 59,637 60,222 82.4 59,053 59,637 59,637 59,637 60,222 86.0 59,053 59,637 59,637 59,637 60,222 89.6 57,883 59,637 59,637 59,637 60,222 93.2 56,129 59,053 59,053 59,053 59,637 95.0 54,960 58,368 58,468 59,053 59,637 96.8 53,791 57,883 58,468 58,468 59,637 100.4 50,867 56,714 57,883 57,883 59,053 104.0 47,944 54,375 56,714 57,299 58,468 107.6-51,452 54,960 56,714 57,883 111.2-47,944 53,206 55,545 56,714 114.8 - - 50,282 53,791 55,545 118.4 - - 46,774 50,867 53,206 131.0 - - - 47,359 50,282 Table 4 AYF60-119 HT COOLING CAPACITY Installation, Start-Up, Adjustment and Maintenance Manual 11

AYF60-119 TK 1 AYF60-119/2 TK AYF60-119/4 TK PERFORMANCE RATINGS - COOLING Cooling Capacity 2 Nominal Btu/hr 60,500 Gas Input (HHV) Nominal Btu/hr 94,900 Ambient Operating Temperature Maximum 120 F Minimum 10.4 Condenser Air Flow 3 Nominal 6,000 CFM Minimum 2,000 Inlet (to the unit) Chilled Water Maximum F 113 Temperature Outlet (to plant) Chilled Water Temperature Chilled Water Flow Minimum F 37.4 Nominal Maximum Minimum GPM 12.2 14.1 11.0 PERFORMANCE RATINGS HEATING Heating Capacity Nominal Btu/hr 110,900 Gas Input (HHV) Nominal Btu/hr 129,000 Ambient Operating Temperature Inlet (to the unit) Hot Water Temperature Outlet (to plant) Hot Water Temperature Hot Water Flow Maximum Minimum F Maximum F Maximum F Nominal Maximum Minimum GPM 12.2 14.1 11.0 116.6-7.6 167 ELECTRICAL RATINGS Required Voltage, 60 Hz, Single Phase 3 V 208 230 Minimum Circuit Ampacity (MCA) Unit only A 8.0 Maximum Over Current Protection (MOCP) A 10.9 Operating Consumption - chiller 4 0.75 Operating Consumption - heater kw 0.076 Operating Consumption matched SERVICE PLATE CONNECTIONS Chilled Water Inlet/Outlet 5 FPT 1 1/4 Hot Water Inlet/Outlet FPT 1 1/4 Gas FPT ½ Electrical knockouts Inches 7 / 8 PHYSICAL DATA Pressure drop chiller Feet of Pressure drop heater Head/PSIg Pressure drop matched 17.13/7.40 Operating pressure Maximum PSIg 45 185 8.8 14.1 6.6 0.826 9.67/4.20 8.30/3.60 Refrigerant Type (chiller) R717 Unit Chilled Water volume 6 1.05 Unit Hot Water volume Gallons 1.32 Matched water volume 1.58 Shipping weight Pounds 1098 Operating weight Pounds 1035 Width 48 7 / 8 Dimensions Length Inches 48 1 / 2 Height 50 3 / 4 Heater gases duct internal diameter Inches 5 1 / 8 Table 5 AYF60-119 TK TECHNICAL DATA 12 Installation, Start-Up, Adjustment and Maintenance Manual

Notes: 1. All illustrations and specifications contained herein are based on the latest information available at the time of publication approval. Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue models. 2. Capacity at standard conditions of 95 F ambient temperature. Chilled water Outlet temperature 45 F, chilled water Inlet temperature 55 F. Actual capacity will vary with ambient (condenser) air temperature and leaving water temperature. Capacity characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor. 3. Units are factory-wired for 208-230 volts operation. 4. May vary by ±10% as a function of both power supply and electrical motor input tolerance. 5. Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes. 6. "Chilled Water" refers to a solution of quality tap water and 10% by volume of inhibited permanent antifreeze. Higher antifreeze concentrations may be required in certain applications. COOLING CAPACITY in Btu/hr AMBIENT AIR TEMPERATURE ( F) OUTLET CHILLED WATER ( F) 37.4 41.0 44.6 48.2 10.4 71,410 71,410 72,015 72,620 17.6 70,805 70,805 71,410 72,015 24.8 70,200 70,200 70,200 71,410 32.0 69,595 69,595 69,595 70,200 39.2 68,989 68,989 68,989 69,595 46.4 67,779 68,384 68,384 68,989 53.6 67,779 67,779 67,779 68,384 60.8 67,174 67,174 67,779 67,779 68.0 65,964 65,964 67,174 67,174 75.2 64,148 64,148 66,569 66,569 82.4 59,307 61,727 65,358 65,358 89.6 51,439 57,491 62,938 64,148 95.0 41,757 52,650 60,517 62,333 100.4 - - 56,886 59,912 107.6 - - 50,229 55,070 113.0 - - - 49,624 120.0 - - - 42,057 Table 6 AYF60-119 TK COOLING CAPACITY Installation, Start-Up, Adjustment and Maintenance Manual 13

AYF60-119 LB 1 AYF60-119/2 LB AYF60-119/4 LB PERFORMANCE RATINGS COOLING Cooling Capacity 2 Nominal Btu/hr 45,400 Gas Input (HHV) Nominal Btu/hr 94,900 Ambient Operating Temperature Maximum 120 F Minimum 32 Condenser Air Flow 3 Nominal 6,000 CFM Minimum 2,000 Inlet (to the unit) Chilled Water Maximum F 113 Temperature Outlet (to plant) Chilled Water Temperature Chilled Water Flow Minimum F 14 Nominal Maximum Minimum GPM 11.4 12.8 10.1 PERFORMANCE RATINGS HEATING Heating Capacity Nominal Btu/hr 110,900 Gas Input (HHV) Nominal Btu/hr 129,000 Ambient Operating Temperature Inlet (to the unit) Hot Water Temperature Outlet (to plant) Hot Water Temperature Hot Water Flow Maximum Minimum F Maximum F Maximum F Nominal Maximum Minimum GPM 11.4 12.8 10.1 116.6-7.6 167 ELECTRICAL RATINGS Required Voltage, 60 Hz, Single Phase 3 V 208-230 Minimum Circuit Ampacity (MCA) Unit only A 8.0 Maximum Over Current Protection (MOCP) A 10.9 Operating Consumption - chiller 4 0.75 Operating Consumption - heater kw 0.076 Operating Consumption matched SERVICE PLATE CONNECTIONS Chilled Water Inlet/Outlet 5 FPT 1 1/4 Hot Water Inlet/Outlet FPT 1 1/4 Gas FPT ½ Electrical knockouts Inches 7 / 8 PHYSICAL DATA Pressure drop chiller Feet of Pressure drop heater Head/PSIg Pressure drop matched 17.05/7.40 Operating pressure Maximum PSIg 45 185 8.8 14.1 6.6 0.826 14.03/6.09 8.30/3.60 Refrigerant Type (chiller) R717 Unit Chilled Water volume 6 1.05 Unit Hot Water volume Gallons 1.32 Matched water volume 1.58 Shipping weight Pounds 1098 Operating weight Pounds 1035 Width 48 7 / 8 Dimensions Length Inches 48 1 / 2 Height 50 3 / 4 Heater gases duct internal diameter Inches 5 1 / 8 Table 7 AYF60-119 LB TECHNICAL DATA 14 Installation, Start-Up, Adjustment and Maintenance Manual

Notes: 1. All illustrations and specifications contained herein are based on the latest information available at the time of publication approval. Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue models. 2. Capacity at standard conditions of 95 F ambient temperature. Chilled water Outlet temperature (40% mono-ethylene glycol) 23 F, chilled water Inlet temperature 32 F. Actual capacity will vary with ambient (condenser) air temperature and leaving water temperature. Capacity characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor. 3. Fan speed is reduced when external temperature is less than 91.4 F. 4. Units are factory-wired for 208-230 volts operation. 5. May vary by ±10% as a function of both power supply and electrical motor input tolerance. 6. Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes. COOLING CAPACITY in Btu/hr AMBIENT AIR TEMPERATURE ( F) OUTLET CHILLED WATER ( F) 14.0 19.4 23.0 28.4 32.0 23.0 52,007 52,217 52,426 52,801 53,176 24.8 52,007 52,217 52,426 52,801 53,176 26.6 52,007 52,217 52,426 52,801 53,176 28.4 52,007 52,217 52,426 52,801 53,176 30.2 52,007 52,217 52,426 52,801 53,176 32.0 52,007 52,217 52,426 52,801 53,176 33.8 52,007 52,217 52,426 52,801 53,176 35.6 52,007 52,217 52,426 52,801 53,176 37.4 52,007 52,217 52,426 52,801 53,176 39.2 52,007 52,217 52,426 52,801 53,176 41.0 52,007 52,217 52,426 52,801 53,176 42.8 52,007 52,217 52,426 52,801 53,176 44.6 52,007 52,217 52,426 52,801 53,176 46.4 52,007 52,200 52,392 52,784 53,176 48.2 52,007 52,183 52,358 52,767 53,176 50.0 52,007 52,166 52,324 52,750 53,176 51.8 51,965 52,127 52,290 52,733 53,176 53.6 51,904 52,080 52,256 52,716 53,176 55.4 51,822 52,022 52,221 52,699 53,176 57.2 51,718 51,952 52,187 52,681 53,176 59.0 51,588 51,884 52,181 52,678 53,176 60.8 51,430 51,793 52,157 52,666 53,176 62.6 51,241 51,677 52,113 52,644 53,176 64.4 51,020 51,533 52,047 52,610 53,172 66.2 50,763 51,360 51,957 52,563 53,169 Installation, Start-Up, Adjustment and Maintenance Manual 15

68.0 50,469 51,155 51,841 52,503 53,166 69.8 50,134 50,915 51,696 52,423 53,149 71.6 49,757 50,638 51,520 52,314 53,107 73.4 49,334 50,322 51,311 52,174 53,038 75.2 48,864 49,965 51,067 52,002 52,937 77.0 48,343 49,564 50,785 51,795 52,805 78.8 47,771 49,117 50,464 51,551 52,637 80.6 47,143 48,622 50,101 51,267 52,432 82.4 46,458 48,076 49,694 50,941 52,188 84.2 45,713 47,476 49,240 50,571 51,901 86.0 44,905 46,822 48,738 50,155 51,571 87.8 44,033 46,109 48,186 49,690 51,194 89.6 43,093 45,337 47,580 49,174 50,768 91.4 42,084 44,502 46,919 48,605 50,291 93.2 41,003 43,602 46,201 47,981 49,760 95.0 39,847 42,635 45,400 47,299 49,174 96.8 38,614 41,599 44,584 46,557 48,530 98.6 37,302 40,491 43,681 45,753 47,825 100.4 35,907 39,309 42,711 44,884 47,057 102.2 34,428 38,051 41,673 43,949 46,225 104.0 32,863 36,713 40,564 42,945 45,325 105.8 31,208 35,295 39,383 41,869 44,356 107.6 29,461 33,794 38,126 40,720 43,314 109.4 27,620 32,206 36,793 39,496 42,198 111.2 25,682 30,531 35,379 38,193 41,006 113.0 23,645 28,765 33,885 36,810 39,735 120.0 - - 28,004 31,587 35,176 Table 8 AYF60-119 LB COOLING CAPACITY 16 Installation, Start-Up, Adjustment and Maintenance Manual

2.4 PRESSURE DROP AYF60-119 /4 PRESSURE DROP TABLES PRESSURE DROP (ft W.C. ) 3.25 3.67 4.11 4.56 5.02 5.50 5.99 6.50 7.02 7.56 6.60 7.04 7.48 7.93 8.37 8.81 9.25 9.69 10.13 10.57 MIN WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 8.11 8.67 9.11 9.25 9.67 9.85 10.46 11.08 11.72 12.38 11.01 11.45 11.78 11.89 12.20 12.33 12.77 13.21 13.65 14.09 NOM. HT NOM. MAX WATER FLOW (GPM) Table 9 - AYF60-119/4, TK, HT CHILLER SIDE PRESSURE DROP (ft W.C. ) 8.61 9.03 9.46 9.91 10.38 10.86 11.35 11.86 12.38 12.91 6.60 7.04 7.48 7.93 8.37 8.81 9.25 9.69 10.13 10.57 MIN WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 13.47 14.03 14.61 15.21 15.82 16.44 17.08 17.73 11.01 11.45 11.89 12.33 12.77 13.21 13.65 14.09 NOM. MAX WATER FLOW (GPM) Table 10 - AYF60-119/4 LB CHILLER SIDE PRESSURE DROP (ft W.C. ) 0.65 1.42 2.18 2.95 3.71 4.48 5.24 6.00 6.77 7.53 4.40 4.84 5.28 5.72 6.16 6.60 7.04 7.48 7.93 8.37 MIN WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 8.30 9.06 9.83 10.59 11.36 12.12 12.89 13.65 14.42 15.18 8.81 9.25 9.69 10.13 10.57 11.01 11.45 11.89 12.33 12.77 NOM. WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 15.95 16.71 17.48 18.24 13.21 13.65 14.09 14.53 MAX WATER FLOW (GPM) Table 11 - AYF60-119/4, HT, TK, LB - HEATER SIDE Installation, Start-Up, Adjustment and Maintenance Manual 17

AYF60-119 /2 PRESSURE DROP TABLES In 2 pipe type AYF60-119 units, the correct pressure drop has to be taken as the maximum one between the chiller and the heater one, according to the following indication: - For AYF60-119 /2, AYF60-119 /2 TK and AYF60-119 /2 HT the maximum pressure drop is the one of the heater module of the unit. - For AYF60-119 /2 LB the maximum pressure drop is the one of the chiller module of the unit. PRESSURE DROP (ft W.C. ) 0.74 1.67 2.60 3.52 4.45 5.37 6.30 7.22 8.15 9.08 4.40 4.84 5.28 5.72 6.16 6.60 7.04 7.48 7.93 8.37 MIN WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 10.00 10.93 11.85 12.78 13.70 14.63 15.56 16.25 16.48 17.13 8.81 9.25 9.69 10.13 10.57 11.01 11.45 11.78 11.89 12.20 NOM. HT NOM. WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 17.41 18.33 19.26 20.18 21.11 22.04 12.33 12.77 13.21 13.65 14.09 14.53 MAX WATER FLOW (GPM) Table 12 - AYF60-119/2, TK, HT (MAX=HEATER SIDE) PRESSURE DROP (ft W.C. ) 11.63 12.04 12.48 12.93 13.39 13.87 14.36 14.87 15.39 15.93 6.60 7.04 7.48 7.93 8.37 8.81 9.25 9.69 10.13 10.57 MIN WATER FLOW (GPM) PRESSURE DROP (ft W.C. ) 16.48 17.05 17.63 18.22 18.83 19.46 20.09 20.75 11.01 11.45 11.89 12.33 12.77 13.21 13.65 14.09 NOM. MAX WATER FLOW (GPM) Table 13 - AYF60-119/2 LB (MAX=CHILLER SIDE) 18 Installation, Start-Up, Adjustment and Maintenance Manual

PRESSURE DROP GRAPHS PRESSURE DROP (FEET OF HEAD) 12.00 10.00 8.00 6.00 4.00 AYF60-119 /4, HT, TK CHILLER SIDE 2.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 WATER FLOW (GPM) Graph 1 - AYF60-119 /4, HT, TK PRESSURE DROP CHILLER SIDE PRESSURE DROP (FEET OF HEAD) 18.00 16.00 14.00 12.00 10.00 AYF60-119 /4 LB CHILLER SIDE 8.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 MONOETHYLENE GLYCOL (40%) - WATER FLOW (GPM) Graph 2 - AYF60-119 /4 LB PRESSURE DROP CHILLER SIDE Installation, Start-Up, Adjustment and Maintenance Manual 19

PRESSURE DROP (FEET OF HEAD) 24.00 22.00 20.00 18.00 16.00 14.00 12.00 10.00 8.00 6.00 4.00 2.00 0.00 AYF60-119 /4, HT, TK, LB HEATER SIDE 3.00 5.00 7.00 9.00 11.00 13.00 15.00 WATER FLOW (GPM) Graph 3 - AYF60-119 /4, HT, TK, LB PRESSURE DROP HEATER SIDE PRESSURE DROP (FEET OF HEAD) 22.00 20.00 18.00 16.00 AYF60-119 /2, HT, TK (MAX = HEATER SIDE) 14.00 11.00 12.00 13.00 14.00 WATER FLOW (GPM) Graph 4 - AYF60-119 /2, HT, TK PRESSURE DROP (MAX DROP = HEATER SIDE) 20 Installation, Start-Up, Adjustment and Maintenance Manual

PRESSURE DROP (FEET OF HEAD) 21.00 19.00 17.00 15.00 13.00 AYF60-119 /2, LB (MAX = CHILLER SIDE) 11.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 MONOETHYLENE GLYCOL (40%) - WATER FLOW (GPM) Graph 5 - AYF60-119 /2, LB PRESSURE DROP (MAX DROP = CHILLER SIDE) 2.5 AYF60-119, HT, TK, LB DIMENSIONS 15-1 2" 6-3 4" 50-3 4" 50-1 2" 62-1 4" 15-1 2" 42-2" 1 (*) 38-2" 1 (*) 48-2" 1 48-7 8" 4" Figure 2 - AYF60-119, HT, TK, LB DIMENSIONS. - (*) VIBRATION DAMPING POSITIONS. Installation, Start-Up, Adjustment and Maintenance Manual 21

3. INSTALLATION 3.1 GENERAL RULES Only qualified technicians, in compliance with the manufacturer s instructions, should carry out the installation and maintenance of the AYF60-119 unit. The installation of the appliance must conform to the requirements of the authority having jurisdiction or in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. All wiring should be installed in accordance with the latest edition of the National Electrical Codes, ANSI/NFPA No. 70, and with any local codes. The manufacturer cannot be held responsible for any damages to persons, animals or goods due to improper, erroneous or irrational installation of these appliances. To ensure that a correct installation and maximum unit performances are obtained, the following rules have to be followed: - Unpack the unit carefully, checking that it has not suffered damage during transport. Each unit is factory tested before shipping, if damage is found report this immediately to the haulage contractor. - Each unit must be installed outdoors in an area of free natural air circulation and does not require particular weather protection. In no case must the unit be installed in a room. - No overhead obstructions should block the outlet of air from the unit top. - The unit should not be installed so that the fan discharge is in close proximity to the fresh air intakes of a building or in such a manner that hot or contaminated air from flues, dryer vents, chimney, etc., could be drawn into the unit by the condenser fan. - The front and rear sides of the unit must have a minimum clearance of 31-1 / 2 inches and 24 inches, respectively, (for safety, maintenance and servicing) from any combustible surface, walls or other stationary constructions. The left and right sides require a minimum distance of 18 inches for proper airflow toward the condenser. - Be sure that gas supply provided from the gas main meets the manufacturer s specifications. Inlet gas pressure to the unit must not exceed 14.0" W.C. on natural gas or propane gas. The minimum Inlet gas pressure at the unit is 5.0" W.C. on natural gas and 11.0" W.C. on propane gas. - The water distribution system must comply with all applicable codes and regulations. When replacing an existing appliance, it s important to check the condition of the entire water distribution system to ensure safe operation. WARNING The electrical safety of the unit is obtained only when it is correctly connected to an efficient grounding system, which meets existing applicable safety standards. Never use gas supply piping to ground the appliances. The ground wire should be longer than power supply wires for safety reasons. If the power supply wires are accidentally stretched, the ground wire will be the last to break. By following this rule, good ground continuity will be assured. 22 Installation, Start-Up, Adjustment and Maintenance Manual

3.2 INSTALLATION OF THE UNIT HANDLING OF THE UNIT ON SITE When arriving at the installation site, visually inspect the unit for any signs of damage to the package, which may indicate possible unit damage. Once on site, the units must remain in the factory packaging and only be unpacked at the moment before installation. Before locating and unpacking the unit, make a hole in the package to check for ammonia odor. If ammonia odor is present, contact the factory. LOCATION The AYF60-119 must be installed outdoors in an area of free natural air circulation; no combustible construction shall be over the unit. The AYF60-119 shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.). The installation inside a room or a building is not allowed. There must be a minimum clearance of 4 feet horizontally from electric meters, gas meters, regulators, and relief equipment and in no case located above or below these items unless a 4 feet horizontal distance is maintained. The unit can be installed at ground level, on a platform or on the roof (if it can withstand the weight). The noise generated by the condenser fan during unit operation is not excessive. However, avoid locating the unit in an area adjacent to bedrooms or neighboring buildings (see Figure 3). Also, avoid installing the unit in building corners, where air turbulence can take place or the unit noise (reverberation) can be amplified. GOOD IDEAL AVOID INSTALLATION IN THIS AREA BEDROOMS LIVING ROOM GARAGE BETTER Figure 3 - LOCATION OF THE UNIT CLEARANCES A free space is to be provided around the unit to allow for proper unit operation and for servicing. The minimum clearance from walls, obstructions and other units should be as follows (see Figure 4): right / left side: 18 inches rear side: 24 inches front side: 31-1 / 2 inches Installation, Start-Up, Adjustment and Maintenance Manual 23

31-1 2" 24" 31-1 2" 24" 18" 18" 18" 18" 18" SINGLE UNIT MULTIPLE UNITS Figure 4 CLEARANCES FOR CORRECT INSTALLATION OF THE UNIT The same clearances must be kept to combustibles for vent and hot water pipes There MUST NOT be any obstructions or structural overhangs (roof edges, balconies) over the top of the unit. The re-circulation of the air discharged from the condenser results in a poor unit performance. When the unit is installed in close proximity to buildings, keep the unit away from the roof edge drip line. In no case should the unit be placed within 6 feet of any external air intakes of the building. For installations on balconies or roofs, the unit should not be located within 8 feet from chimney flues, outlets and other such vents. It is important that the unit is located so that hot or contaminated air IS NOT drawn into the air intakes of the unit. GROUND INSTALLATION Ground level units should be supported on a LEVEL concrete pad with a minimum thickness of 4" and slightly larger than the unit base (see Figure 5 for typical slab dimensions). Local soil conditions will actually dictate the slab thickness required to prevent shifting. 4 CONCRETE SLAB 50 TYPICAL 50 TYPICAL Figure 5 DIMENSIONS OF THE UNIT BED 24 Installation, Start-Up, Adjustment and Maintenance Manual

Do not allow the concrete slab touch the foundation of a structure. Unit operational noises can be transmitted inside the structure if they are connected. Ground level installations should use vibration-damping base supports, available from the factory. Another option is to use 4" thick concrete blocks positioned under the unit, instead of the factory base supports. ROOF / TERRACE INSTALLATION If the unit must be lifted by a hoist for installation, leave it on the crate base. Attach hoist lines to the crate base and use spreader bars to prevent the hoist lines from damaging unit cabinet panels. FRONT VIEW SIDE VIEW Figure 6 HANDLING OF THE AYF60-119 UNIT Although approved for installation on a combustible base, the unit must not be installed directly on the roof surface. Use base supports for the installation (see Figure 5). Both the unit and the supporting base weight should be sufficiently supported by the roof joists. Provide for a gangway all around the unit for maintenance purposes. Installation on roofs directly above sleeping quarters should be avoided if possible. If not possible, special consideration must be given to the transmission characteristics of the building structure. The use of vibration isolators under the equipment (acoustically insulated bases) and approved flexible connections (vibrationdamping pipe fittings) between the unit and the piping system is recommended. LEVELING The unit should be level both front to back and side to side. Place a level on the top of the unit to check for level. If the unit is not level, metal shims are recommended for use under proper corners to obtain level. If the shim(s) thickness exceeds 1/2", support shims should be inserted under the center of the unit. Installation, Start-Up, Adjustment and Maintenance Manual 25

4. HYDRONIC AND GAS INSTALLATION 4.1 WATER PIPING DESIGN AND INSTALLATION Piping for the unit is to be designed and installed as a closed hydronic circuit. WARNING A non-return valve has to be mounted just after the hydronic circuit pump, to prevent gravity circulation of the water. An expansion tank must be installed on the circuit; it must be properly sized according to hydronic system size, maximum thermal expansion and maximum water pressure When the boiler of the unit is used in connection with refrigeration system, it must be installed so the chilled medium is piped in parallel with the boiler, with appropriate valves to prevent the chilled medium from entering the boiler. The following items (not supplied) must be installed close to the unit (see Figure 7): - FLEXIBLE CONNECTIONS to avoid vibration transmission to the unit water lines. - MANOMETERS to measure Inlet and Outlet pressure. - WATER FILTER (2 filters for AYF 4 pipe) mounted in the water inlet line to remove debris from the water lines. - WATER CHARGE SYSTEM (2 systems for AYF 4 pipe) If automatic water charge system is used, glycol percentage must be checked once a year. - WATER FLOW RATE VALVE (2 valves for AYF 4 pipe) for adjusting proper water flow rate. - WATER PUMP (2 pumps for AYF 4 pipe) properly sized for system. Consult manufacturer s pump specifications to ensure the pump s capacity is sufficient to overcome piping resistance and maintain proper flow rate for the hydronic system. A safety factor of 5 ft. of head is recommended when sizing the pump. - ON/OFF WATER AND GAS VALVES - EXPANSION TANK properly sized based on the hydronic system size, maximum thermal expansion, and maximum water pressure. - FILL VALVE for filling, draining or flushing the hydronic system. - AIR BLEED set at the highest point in the hydronic system for removal of air. 26 WARNING To ensure the correct operation of the unit and to avoid the water freezing, add 10% by volume of mono-ethylene glycol (antifreeze) to the circulation water. Add more mono-ethylene glycol as needed for the minimum external temperature of the installation zone (see Table 16, page 58). As said above, when using an automatic water charge system it s compulsory to check the mono-ethylene glycol percentage once a year. There must be correct chilled water flow when the unit is operating and during the shut down period (600 seconds, between turning the burner off and complete shutdown of the appliance). Piping (diameters of pipes etc.) must be sized appropriately in order to ensure the correct chilled and hot water flow necessary for the proper operation of the unit. The water lines should also be sized so the maximum velocity of the water/mono-ethylene glycol solution in the lines does not exceed 6 feet per second to avoid excessive noise. With multiple installation of different units, it s necessary that units not operating during winter time can be excluded; this can be done by use of automatic or manual control valves. Different pumps or variable flow pumps are to be used. Installation, Start-Up, Adjustment and Maintenance Manual

Absorption cooling unit side does not require obligatory installation of cold-water storages (because there is no compressor in the system). The use of the cold-water storage is anyhow suggested, in order to absorb frequent variations of thermal load, that reduces the working time of the unit, reduces the energy consumption and consequently saving money. It is recommended specially when water quantity in the system is lower than 18.5 gallons for each installed AYF60-119 unit. GAS P WATER OUTLET P FLEXIBLE JOINTS EXPANSION VESSEL COLD-WATER STORAGE GAS P WATER OUTLET P WATER CIRCULATION PUMP PRIMARY AND SECONDARY COLD- WATER STORAGE Figure 7 EXAMPLE OF HYDRONIC SYSTEMS WITH SINGLE WATER STORAGE (TOP) and PRIMARY- SECONDARY WATER STORAGE (BOTTOM) When rigid pipes are used, it is recommended to use flexible connections between the unit and piping to avoid vibration transmission. All piping must be properly insulated according to federal and local codes to avoid thermal losses and condensate on the water lines. All seams and joints should be carefully made so as to be air and watertight. For size of water connections on the unit, refer to TECHNICAL DATA sheet (2.3) Connections at the coil or heat exchanger must be performed in accordance with the recommendations of the coil or heat exchanger manufacturer. If the heat exchanger is an air coil, the air coil must be installed downstream from the furnace to avoid condensation in the furnace. Additionally if the heat exchanger is an air coil, a P trap must be provided to drain condensate. The height of the P trap must be sufficient to ensure drainage of condensate. Any horizontal run of the condensate drain line must slope ¼ for each running foot and not be smaller than ¾ I.P.S. to assure the condensate will drain by gravity. The condensate drain line must be insulated and ran to a suitable drain. Installation, Start-Up, Adjustment and Maintenance Manual 27

DDC 9 GAS P P AYF 60-119/2 UNIT 1 2 3 4 5 6 7 8 LEGEND 1 FLEXIBLE HOSES 4 WATER FILTER 7 EXPANSION VESSEL 2 MANOMETERS 5 ON / OFF VALVE 8 EVENTUAL WATER STORAGE * 3WATER FLOW RATE VALVE 6 WATER PUMP 9 DDC DIRECT DIGITAL CONTROLLER * with water volume in primary circuit lower than 18.5 gallons NOTE: ANTIFREEZE GLYCOL HAS TO BE ADDED TO WATER Figure 8 WATER PIPING DIAGRAM FOR A SINGLE AYF60-119 UNIT, 2 PIPE VERSION. DOMESTIC HOT WATER CIRCUIT AYF 60-119/4 UNIT DDC 13 14 11 12 P P GAS P 8 3 P 1 2 4 5 6 7 9 10 LEGEND 1 FLEXIBLE HOSES 6 ON / OFF VALVE 11 DOMESTIC WATER PUMP 2 MANOMETERS 7 PRIMARY CHILLED WATER PUMP 12 HEATING PUMP 3 HOT WATER EXPANSION VESSEL 8 PRIMARY HOT WATER PUMP 13 DOMESTIC HOT WATER BOILER 4 WATER FLOW RATE VALVE 9 CHILLED WATER EXPANSION VESSEL 14 DDC DIRECT DIGITAL CONTROLLER 5 WATER FILTER 10 EVENTUAL COLD WATER STORAGE * * * with water volume in primary circuit lower than 18.5 gallons Figure 9 SINGLE AYF60-119 UNIT, 4 PIPE VERSION WITH PRODUCTION OF DOMESTIC WATER. ANTIFREEZE FOR DOMESTIC WATER HAS TO BE SUITABLE FOR HUMAN ALIMENTATION. 28 Installation, Start-Up, Adjustment and Maintenance Manual

AYF60-119 /4 units are not foreseen for direct production of domestic hot water. For this use it s necessary to install an extra boiler, as shown in Figure 9, page 28. AY00-119 WITH AYF60-119 /2 CONNECTION The following figure shows a configuration with a AYF60-119 /2 unit and a single heater stand-alone: 1 GAS GAS AYF 60-119/2 UNIT 2 AY 00-119 P P UNIT P P DDC 10 3 4 5 6 T 9 8 7 LEGEND 1 FLEXIBLE HOSES 4 WATER FILTER 7 WATER PUMP WITH VARIABLE FLOW 2 MANOMETERS 5 ON / OFF VALVE 8 EXPANSION VESSEL 3 WATER FLOW RATE VALVE 6 TWO STAGE THERMOSTAT FOR HEATERS 9 EVENTUAL COLD WATER STORAGE * 10 DDC - DIRECT DIGITAL CONTROLLER (available as optional) * if water volume in primary circuit Is lower than 18.5 gallons per AYF/2 unit NOTE: ANTIFREEZE GLYCOL HAS TO BE ADDED TO WATER. Figure 10 EXAMPLE OF SYSTEM WITH AYF 60-119 /2 AND AY00-119 Installation, Start-Up, Adjustment and Maintenance Manual 29

The following figure shows a configuration with 2 AYF60-119 /2 unit: 1 GAS GAS AYF 60-119/2 UNIT 2 P P AYF 60-119/2 UNIT P P DDC 9 3 4 5 8 7 6 LEGEND 1 FLEXIBLE HOSES 4 WATER FILTER 7 EXPANSION VESSEL 2 MANOMETERS 5 ON / OFF VALVE 8 EVENTUAL COLD WATER STORAGE * 3 WATER FLOW RATE VALVE 6 WATER PUMP 9 DDC DIRECT DIGITAL CONTROLLER * if water volume in primary circuit lower than 18.5 gallons per AYF60-119 /2 unit NOTE: ANTIFREEZE GLYCOL HAS TO BE ADDED TO WATER Figure 11 EXAMPLE OF SYSTEM WITH 2 AYF60-119 /2 (2 PIPE VERSION) 30 Installation, Start-Up, Adjustment and Maintenance Manual

DDC 6 AYF 60-119/4 UNIT GAS AYF 60-119/4 UNIT 1 GAS 13 DOMESTIC WATER CIRCUIT P P P P P P 2 P P 12 3 4 5 11 8 7 9 10 LEGEND 1 FLEXIBLE HOSES 6 DDC DIRECT DIGITAL CONTROLLER 11 HEATING WATER PUMP 2 MANOMETERS 7 PRIMARY HOT WATER PUMP 12 DOMESTIC WATER PUMP 3 WATER FLOW RATE VALVE 8 CHILLED WATER PUMP 13 DOMESTIC HOT WATER BOILER 4 WATER FILTER 9 EXPANSION VESSEL 5 ON / OFF VALVE 10 EVENTUAL COLD WATER STORAGE * * if water volume in primary circuit lower than 18.5 gallons per AYF60-119 /4 unit Figure 12 EXAMPLE OF SYSTEM WITH 2 AYF 60-119/4 (4 PIPE VERSION) AND DOMESTIC WATER BOILER Installation, Start-Up, Adjustment and Maintenance Manual 31

4.2 GAS SUPPLY PIPING All gas piping must conform to the latest edition of National Fuel Gas Code ANSI Z223.1 and all local gas piping codes. Your gas utility must be contacted regarding local requirements, type and size of gas lines. Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the chiller, when it underwent the tests specified in the standards shown on the rating plate. For Natural Gas the minimum Inlet gas pressure to the unit is 5" W.C. and the maximum is 14 W.C. For Propane Gas the minimum Inlet gas pressure to the unit is 11" W.C. and the maximum is 14" W.C. For size of gas connection to the unit see Figure 15, page 34. WARNING Gas supply pressure higher than those stated above could damage the gas valve, resulting in a fire hazard. Vertical gas piping must be trapped and a means provided to drain condensate that may accumulate in the piping during the cold season. Insulation may also be necessary for the gas piping to prevent excessive accumulations of condensate. An approved union should be installed in the gas line near the unit and down stream of any external shut-off valve that may be required by local codes. Be sure to use materials resistant to the LPG corrosive action when making pipe connections. Use an approved sealing compound resistant to propane gas on all male pipe threads. The chiller and its gas connections must be leaked tested before placing the unit in operation. The unit and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the gas piping system at test pressures in excess of 1/2 PSIg. The unit must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas piping system at test pressures equal to or less than 1/2 PSIg. APPROVED UNION TO UNIT APPROVED GAS SHUT-OFF VALVE FROM GAS SUPPLY SEDIMENT TRAP Figure 13 TYPICAL GAS CONNECTION 32 Installation, Start-Up, Adjustment and Maintenance Manual

4.3 DUCT FLUE EXHAUST (heating module) The heater installed inside the heating module of AYF units is a forced-draught Type B23 design. When the installation requires a flue for the exhaustion of the products of combustion, this shall be done according to the standards in force. In the following Table the necessary data for exhaust duct dimensioning: NATURAL GAS COMBUSTION Flue flow Flue temperature CO 2 % SCF F 1750 293 9.2 LPG COMBUSTION Flue flow Flue temperature CO 2 % SCF F 1522 284 11.3 Table 14 AY 00-119 UNIT AND AYF60-119 UNITS HEATING MODULE FLUE FLOW AND TEMPERATURE Units are supplied with Flue system Kit which is to be mounted as shown in Figure 14, page 33: - 1 flue pipe L= 33 ½ ; 5 1 / 8 ; - 1 T piece 3 1 / 8-5 1 / 8 ; - 1 condense drainer 5 1 / 8 ; - 1 terminal 5 1 / 8 ; - 2 clamps to fix the pipe to rear panel; - 3 clamps for pipes; To install flue system proceed as follows: - position 2 clamps that fix the pipe to the rear panel of the unit by means of holes; - use 1 clamp for pipes and mount condense drainer to T piece; after that insert T piece in the 3 1 / 8 flue pipe already mounted on the heater; - use 1 clamp for pipes and mount exhaust flue pipe with L=33 ½ to T piece; - bloc T piece and flue pipe with 2 clamps that are already fixed to the rear panel of the unit; - position flue terminal using a clamp for pipes; - check the fixing of the elements; A B C D E B D F D LEGEND A TERMINAL 5 1 / 8 B CLAMPS TO FIX THE PIPE TO REAR PANEL C FLUE PIPE L= 33 ½, 5 1 / 8 D CLAMPS FOR PIPES E "T" PIECE 3 1 / 8-5 1 / 8 F CONDENSE DRAINER REAR VIEW Figure 14 FLUE EXHAUST TERMINAL OF THE HEATER SECTION Installation, Start-Up, Adjustment and Maintenance Manual 33

4.4 SERVICE PLATE DIMENSIONS The connectors for water and gas piping are located on the service plate, situated on the right side of the unit. 11-3 4" 8-1 4" 6-1 2" 11-3 4" 9-1 4" 8-1 4" 6-1 2" 4-1 4" 6-1 2" 7-1 8" 4-1 4" 6-1 2" 7-1 8" 8-1 8" 9-3 4" 2 PIPE VERSION LEGEND A CHILLED/HOT WATER OUTLET 1 ¼ FPT B CHILLED/HOT WATER INLET 1 ¼ FPT E ELECTRICAL KNOCKOUTS 7 / 8 G GAS CONNECTION ½ FPT 4 PIPE VERSION LEGEND A CHILLED WATER OUTLET 1 ¼ FPT B CHILLED WATER INLET 1 ¼ FPT C HOT WATER OUTLET 1 ¼ FPT D HOT WATER INLET 1 ¼ FPT Figure 15 SERVICE PLATE DIMESNSIONS, 2 AND 4 PIPE VERSION. E ELECTRICAL KNOCKOUTS 7 / 8 G GAS CONNECTION ½ FPT 34 Installation, Start-Up, Adjustment and Maintenance Manual

5. ELECTRICAL CONNECTION WARNING IN THE FOLLOWING SECTION PLEASE REFER TO "L" AS "L1" AND TO "N" AS "L2". 5.1 POWER SUPPLY All wiring should be installed in accordance with the latest edition of the National Electrical Codes, ANSI/NFPA No. 70, and with any local codes. The UNIT electrical system is wired for single-phase, 208-230 volt and 60Hz operation. The electrical control box includes a 208 230 to 24 volt transformer to supply low voltage to the control system. The high voltage line connections to be made at the time of installation consists of connecting 208-230 volt, 60 Hz to the high voltage terminal strip of the control panel. A fused disconnect switch should be installed in the 208-230 volt supply line within sight of and not over 50 feet from the unit. NOTE - An error in wiring installation could cause problems during the unit operation and could damage the electrical components of the appliance. - The unit must be electrically grounded in accordance with national requirements. - The power supply line must not be used to turn the unit ON or OFF. The dedicated control switch in the R-W-Y line is for this purpose. - Disconnect the power supply lines only when assured that unit is completely shut off. WARNING DO NOT OPERATE the unit unless the water system is filled with water and, if foreseen, antifreeze. AYF60-119 MODEL Power supply has to be connected inside the unit, to the terminal inside the electric box. The electric box is in the front side of the unit; these are the board terminals: PHASE to terminal L NEUTRAL to terminal N GROUND to terminal In the electric board of the AYF60-119 heating module there are also N. 3 terminals for heating and chilling function activation. In the 230 V 60 Hz electric circuit they are identified as:: R common; W Heater On; Y Chiller On; NOTE When you don t use the DDC (available as accessory), refer to the following indications. Instead, when DDC is used, the indications for the proper electric connections between the unit and its DDC are contained in paragraph 5.3, page 44. It is necessary to provide the following components: AYF 60-119/2 pipe version Unit (see Figure 16, Page 37 and Figure 17, Page 38) Summer/Winter two way switch, cabled with common R terminal and heater on W terminal or chiller on Y terminal; Unit function switch: timer, thermostat, ON/OFF switch, or any switch cabled between common R terminal and Summer/Winter switch (diverted on Y or W terminal); (Possible) R2 relay for pump function. AYF 60-119/4 pipe version (see Figure 19, Page 41 and Figure 20, Page 42) Installation, Start-Up, Adjustment and Maintenance Manual 35

Heating module function switch: timer, thermostat, ON/OFF switch, or any switch cabled between common R terminal and heater on W terminal; Chiller function switch: timer, thermostat, ON/OFF switch, or any switch cabled between common R terminal and chiller on Y terminal; (Possible) R2-R3 relays for pump function. 5.2 ELECTRICAL CONNECTION DIAGRAMS WARNING To connect the water pump for several units installed in the same hydronic system, provide a safety transformer (SELV secondary) and control relays. AYF 60-119/2 PIPE VERSION Water circulation pump could be operated by one of the following methods: Direct control through the electronic control board when pump absorbed power is less than 700 W See diagram at Figure 16. In such a case, make the electric connection to NO-NO terminals of terminal board, placed in the heating module of the unit, and check in the chiller that jumper (J10, placed in the left bottom side of the electronic control board, above the NO circ. Contacts) which should be closed as in details jumper closed. Direct control through the electronic control board when pump absorbed power is more than 700 W. See diagram at Figure 17. In such a case, in the chiller it is necessary to open the jumper (J10, placed in the left bottom side of the electronic control board, above the NO circ. Contacts) as in details Jumper opened. 36 Installation, Start-Up, Adjustment and Maintenance Manual

(CONSENT SWITCH) (GENERAL SWITCH) USE A TIME LAG FUSE ON L WIRE: - 15 AMP FOR 2 PIPE VERSION - 20 AMP FOR 4 PIPE VERSION GROUND CABLE HAS TO BE CONNECTED BY A SUITABLE EYELET TO THE GROUND PIN INTO THE ELECTRICAL BOX, AND FIXED TO IT BY THE PROPER PRESET NUT. L, N WIRING TO THE TERMINAL BOARD MUST BE DONE RESPECTING THE CORRECT POLARITY LEGEND TER - VERTICAL ELECTRIC TERMINALS INSIDE THE HEATER IG - MAIN SWITCH (not supplied) IC - ON / OFF SWITCH (not supplied: timer; progr.; etc.) W-Y - SUMMER / WINTER SWITCH (not supplied) PUMP WATER CIRCULATION PUMP (< 700 W, not supplied) SCH CHILLER ELECTRONIC BOARD (S61) S70 HEATER ELECTRONIC BOARD J10 - JUMPER FOR NO CONTACT (closed, see details) Warning: - CONNECT THE POWER SUPPLY (230 V-60Hz) BY RESPECTING PHASE AND NULL - CONNECT A GROUNDING TO THE CORRECT TERMINAL - MOUNT THE SWITCH WITH APPROPRIATE FUSES AND MINIMUM CONTACTORS OPEN OF 1 /8 - MAKE SURE THAT IN THE Chiller, J10 JUMPER IS CLOSED (see detail Jumper closed ) Jumper J10 TO BE KEPT CLOSE (to be done by Installer) Figure 16 ELECTRICAL CONNECTION FOR SINGLE AYF60-119/2 UNIT, WHEN PUMP ABSORBED POWER IS LESS THAN 700 W Installation, Start-Up, Adjustment and Maintenance Manual 37

LEGEND TER - VERTICAL ELECTRIC TERMINALS INSIDE THE HEATER IG - MAIN SWITCH (not supplied) IC - ON / OFF SWITCH (not supplied: timer; progr.; etc.) W-Y - SUMMER / WINTER SWITCH (not supplied) R2 - RELAY FOR THE PUMP CONTROL (not supplied) (The opening of J10 Jumper on S61 ECB is due to the presence of R2 relay; see detail) PUMP - WATER CIRCULATION PUMP ( 700 W, not supplied) J10 - JUMPER FOR NO CONTACT (Open, see detail) Warning: - CONNECT THE POWER SUPPLY (230 V-60Hz) BY RESPECTING PHASE AND NULL - CONNECT A GROUNDING TO THE CORRECT TERMINAL - MOUNT THE SWITCH WITH APPROPRIATE FUSES AND MINIMUM CONTACTORS OPEN OF 1 /8 - Make sure that in the chiller J10 jumper is opened (see detail Jumper opened ) Jumper J10 to be opened (to be done by Installer) Figure 17 - ELECTRICAL CONNECTION FOR SINGLE AYF 60-119/2 UNIT, WHEN PUMP ABSORBED POWER IS MORE THAN 700 W WARNING For the pump connection to more AYF60-119 /2 pipe version units, installed in the same hydronic system, provide a safety transformer (SELV secondary) and a control relay (KPf); make the connections as shown in diagram of 38 Installation, Start-Up, Adjustment and Maintenance Manual

LEGEND TER ELECTRIC TERMINAL INSIDE THE CHILLER IG SWITCH WITH FUSE FOR GA UNIT (not supplied) TRpump SAFETY TRANSFORMER (SELV secondary) KPf RELAY FOR WATER PUMP CONTROL (not supplied) NO-NO CLEAN CONTACT FOR CONTROL WATER PUMP P WATER CIRCULATION PUMP (not supplied) L / N PHASE / NULL IP SWITCH WITH FUSE FOR WATER PUMP CONTROL (not supplied) J10 JUMPER FOR PUMP (on S61) Jumper J10 to be opened (to be done by Installer) WARNING: - CONNECT THE POWER SUPPLY (230 V-60Hz) BY RESPECTING PHASE AND NULL - CONNECT GROUNDING TO THE CORRECT TERMINAL - MOUNT THE SWITCH WITH APPROPRIATE FUSES AND MINIMUM CONTACTORS OPEN OF 1 /8 - Make sure that Jumper on S70 ECB, on the Heater, is closed as shown in details Jumper closed Figure 18 CONNECTION WITH WATER CIRCULATION PUMP FOR N. 2 AYF 60-119/2. Installation, Start-Up, Adjustment and Maintenance Manual 39

AYF 60-119/4 PIPE VERSION UNIT Cold water circulation pump could be operated by one of the following methods: - Direct control through electronic control board when pump absorbed power is less than 700 W In such a case, make the electric connection to NO-NO terminal of chiller terminal board (TER), placed in the heating module (as shown in Figure 16) and check in the chiller that the Jumper (J10, placed in the left bottom side of the S61 electronic control board) is closed, as in details Jumper closed of Figure 16. - Direct control through electronic control board when pump absorbed power is more than 700 W In such a case, make the electric connection to NO-NO terminals of chiller terminal box (TER) placed in the heating module of the unit, (as shown in Figure 17, using a R2 control relay). In this case, in the chiller it is necessary to open the jumper (J10, placed in the left bottom side of the S61 electronic control board), as in details jumper opened in Figure 17. Hot water circulation pump could be operated by one of the following methods: - Direct control through electronic control board when pump absorbed power is less than 700 W See Figure 19. In such a case, make the electric connection to the S70 electronic control board, placed in the heating module of the unit (as shown in the Figure), and check, on S70 ECB of the heating module itself, that the Jumper (J2, placed in the right bottom side, under the NO Contact ) is closed (as shown in details Jumper closed of the Figure). - Direct control through electronic control board when pump absorbed power is more than 700 W See Figure 20. In such a case, make the electric connection to the S70 ECB, placed in the heating module of the Unit (as shown in the Figure, using a R3 control relay). In this case, on S70 ECB, it is necessary TO OPEN the Jumper (J2, placed in the right bottom side, under the NO Contact ), as shown in details Jumper opened of the Figure. NOTE In Figure 19 and Figure 20, Page 41 and 42 the connection to be made for each AYF60-119 /4 pipe version unit are described, with two examples of water pump (absorbed power more or less than 700 W). For the connection of the pump in the water system, refer to Figure 16 or Figure 17, Page 37 or 38. Warning: when pump connection is to be made for more AYF60-119 /4 units installed in the same hydronic system, provide a safety transformer (SELV secondary) and control relays (KPf; KPc); make the connection following diagram of Figure 21 -, Page 43. 40 Installation, Start-Up, Adjustment and Maintenance Manual

LEGEND TER - ELECTRIC TERMINAL BOARD IG - MAIN SWITCH (not supplied) IC Y - CHILLER ON / OFF SWITCH (not supplied: timer; progr.; etc.) IC W - HEATER ON / OFF SWITCH (not supplied: timer; progr.; etc.) HEATER PUMP - HEATER EXTERNAL WATER CIRCULATION PUMP (< 700 W, not supplied) J2 - JUMPER FOR NO CONTACT (closed, see details) WARNING: - CONNECT THE POWER SUPPLY (230 V-60Hz) BY RESPECTING PHASE AND NULL - CONNECT GROUNDING TO THE CORRECT TERMINAL - MOUNT THE SWITCH WITH APPROPRIATE FUSES AND MINIMUM CONTACTORS OPEN OF 1 /8 - Make sure that Jumper on S70 ECB, on the Heater, is closed as shown in details Jumper closed Jumper J2 to be kept closed (to be done by Installer) Figure 19 ELECTRICAL CONNECTIONS TO BE MADE (ON THE HEATING MODULE) FOR EACH AYF 60-119/4 UNIT, WITH HOT CIRCLULATION PUMPS POWER LESS THAN 700W. Installation, Start-Up, Adjustment and Maintenance Manual 41

LEGEND TER - VERTICAL ELECTRIC TERMINALS INSIDE THE HEATER IG - MAIN SWITCH (not supplied) IC Y - CHILLER ON / OFF SWITCH (not supplied: timer; progr.; etc.) IC W - HEATER ON / OFF SWITCH (not supplied: timer; progr.; etc.) HEATER AND CHILLER PUMP EXTERNAL WATER CIRCULATION PUMPS ( 700 W, not supplied) J2 - JUMPER FOR NO CONTACT (open, see details) R3 - RELAY FOR THE HEATERS WATER CIRCULATION PUMP CONTROL (not supplied) (R3 relay opensl Jumper J2 placed on S70 ECB, in the Heater as shown in details Jumper open ) WARNING- - CONNECT THE POWER SUPPLY (230 V-60 Hz) BY RESPECTING PHASE AND NULL - CONNECT A GROUNDING TO THE CORRECT TERMINAL - MOUNT THE SWITCH WITH APPROPRIATE FUSES AND MINIMUM CONTACTORS OPEN OF 1 /8 - Make sure that JUMPER J2, placed on S70 ECB, in the Heater, is open as shown in details Jumper opened Jumper J2 to be opened (to be done by Installer) Figure 20 - ELECTRICAL CONNECTIONS TO BE MADE (ON THE HEATING MODULE) FOR EACH AYF 60-119/4 UNIT, WITH HOT CIRCLULATION PUMPS POWER MORE THAN 700W. 42 Installation, Start-Up, Adjustment and Maintenance Manual

LEGEND IG SWITCH WITH FUSE FOR GA UNIT (not supplied) IP SWITCH WITH FUSE FOR WATER PUMP CONTROL (not supplied) TER ELECTRIC TERMINALS NO circ CLEAN CONTACT (on S70) FOR CONTROL HEATER WATER PUMP (Pc) NO-NO CLEAN CONTACT (on MFR) FOR CONTROL CHILLER WATER PUMP (Pf) KPc RELAY FOR HEATER WATER PUMP (not supplied) CONTROL KPf RELAY FOR CHILLER WATER PUMP (not supplied) CONTROL L / N PHASE / NULL CHILLER AND HEATER PUMP: SAFETY TRANSFORMER (secondary SELV) J2 J10 JUMPER FOR NO CONTACT (on S70); (To be opened by a relay) JUMPER FOR NO CONTACT (on S61); (To be opened by a relay) Figure 21 - WATER CIRCULATION PUMP CONNECTION FOR N. 2 AYF 60-119 /4. Installation, Start-Up, Adjustment and Maintenance Manual 43

5.3 DDC CONNECTION Connection with the unit WARNING For the connection of DDC (available as accessory) with a AYF60-119 unit, consult the instructions, figures and diagrams only contained in this subparagraph. For further details and/or information refer to the specific DDC installation, programming and use manual. To well manage one or more AYF60-119 units connected to the same hydronic system, it is important to use the DDC, available as accessory. In such a case, it is necessary to: - Connect the DDC to the power supply (see DDC: Electric supply wire connection ) - Use a CAN-BUS wire to connect between the units and the DDC (see Connection of DDC to the unit ) DDC: Electric supply wire connection The DDC should be electrically supplied through a safety transformer 230 /24 V.a.c. 60 Hz. With minimum power equal to 20 VA. Use an electric supply wire (min. 2 x 18 AWG) and the 4 terminals connector of the DDC (placed at bottom left, back side) to make the connection as in Figure 22, respecting the following polarity: - terminal 1 = 24 V; - terminal 2 = 0 V; - terminal 3 = ground Warning: in all cases terminal 3 of the DDC terminals connector should be connected to one safety ground ( 0,1Ω). The DDC is also equipped with a plug battery which, in case of black out, stores in its memory the programmed values; the plug battery lasts approximately 7 years, then it should be changed by authorized Service Engineer (TAC). Figure 22 ELECTRICAL SUPPLY WIRE CONNECTION Connection of DDC to the unit The connection between DDC and the unit (or more units) is made through a CAN-BUS wire, in a way to create a parameters communication network, characterized by one series of n nodes (see Figure 23 and Figure 24). The parameters communication network can connect max 3 DDC. NOTE Every single object (AYF60-119 unit or DDC) at its connection to the communication network is intended to be a node. Every network is composed of 2 terminal nodes and of a certain number of intermediate nodes. 44 Installation, Start-Up, Adjustment and Maintenance Manual

2 A 1 DDC 3 B 2nd segment of CAN-BUS wire (available as optional) 2 A 1 DDC CAN-BUS wire AYF 60-119 (available as optional) AYF 60-119 AYF 60-119 1st segment of CAN-BUS wire (available as optional) Figure 23 - EXAMPLE CONNECTION OF DDC TO SINGLE UNIT (2 nodes network) AND TO N.2 UNITS CONNECTED ON THE SAME HYDRONIC SYSTEM (3 nodes network). 4 C 3 segment of CAN-BUS wire (available as optional) 3 B 2 segment of CAN-BUS wire (available as optional) 2 A 1 DDC AYF 60-119 AYF 60-119 AYF 60-119 1 segment of CAN-BUS wire (available as optional) Figure 24 EXAMPLE CONNECTION OF DDC TO N.3 AYF UNITS CONNECTED ON THE SAME HYDRONIC SYSTEM (4 nodes network). CAN-BUS wire connection If the network connection is max 650 ft cable long and has max 6 nodes (e.g.: 5 AYF60-119 + 1 DDC) a simple shielded wire 3 x 18 AWG is required. For major lengths, the CAN-BUS wire should be compatible with Standards Honeywell SDS. The next Table shows some examples of these wires, according to the total length of the wire itself: CABLE TYPE AND MODEL COLOR AND SIGNAL MAX DISTANCE COVERED ft ROBUR NETBUS BLACK = H WHITE = L BROWN = GND 1475 Honeywell SDS 1620 BELDEN 3086A TURCK type 530 DeviceNet Mid Cable BLACK = H WHITE = L BROWN = GND 1475 TURCK type 5711 BLUE = H WHITE = L BLACK = GND 1475 Honeywell SDS 2022 TURCK type 531 BLACK = H WHITE = L BROWN = GND 656 Table 15 EXAMPLE OF TYPES OF WIRES USED FOR CAN-BUS. GND IS THE COMMON SIGNAL WIRE, AND NOT A GROUND CONNECTION. NOTE: GND is the common signal wire, and NOT a ground connection. Take the CAN-BUS wire of suitable length for the connection between DDC and the unit and, for every network or CAN-BUS wire segments (from a node to another) cut sheath of the wire from both terminal for 70/80 mm and connect them to the proper nodes, on the electronic control board (S61) or on DDC. Installation, Start-Up, Adjustment and Maintenance Manual 45

CAN-BUS wire connection to Electronic Control board LEGEND A B F C E INSIDE THE CHILLER NB: Situation with only one CAN-BUS wire (The figure at left, is an example of terminal node connection to electronic control board). A B Isolated adhesive tape CAN-BUS wire shield C Fixing clamp (1 CAN-BUS wire is fixed) D D Connector for CAN-BUS wire conductors (to be removed to ease the conductors connection) E Internal conductors (n. 3) of CAN-BUS wire F Fixing point for eventual 2 segments CAN-BUS wire (intermediate node) Figure 25 EXAMPLE OF CAN-BUS CONNECTION TO ELECTRONIC CONTROL BOARD (EXAMPLE WITH ONLY ONE CAN-BUS WIRE) To connect a CAN bus cable to an appliance: You will need: The appliance (or appliances) positioned in its (or their) final location. Before working on the electrical panel of the appliance, make sure that it is not connected to the power supply. 1. Remove the front panel of the appliance and the cover of the electrical panel. 2. Cut the ideal length of cable for the installation so that it will not undergo bending. 3. Having chosen one end of the length of cable, remove the sheath from a length of approximately 70-80 mm, taking care not to cut the shielding (metallic shield and/or aluminium sheet and, if present, the bare connector in contact with the shield) and the wires contained within. 4. If the diameter of the cable used is not large enough to be blocked inside the cable clamp (letter C of Figure 25 on page 46), make it larger by wrapping electrical tape over the protective outer covering in the area adjacent to the unsheathed part (approximate diameter required: 12-13 mm). 5. Pull back the shielding in the sheathe; apply electrician s tape to the end of the shielding as pulled back (letter A of Figure 25 on page 46). 6. If the appliance is a terminal node of the network connect the three coloured wires to the orange connector, as shown in detail A; of Figure 26 on page 47. Respect the correct indications L, H, GND provided in Table 15 of Page 45, on the figure and on the diagram at the base of the connector. 7. If the appliance is an intermediate node repeat the operations from step 3 to step 6 for the other length of cable required (so to will have two cable lengths everyone without the sheath). To interlace between they the threads with the same color and to connect them to the orange connector, as shown in detail B; of Figure 27 on page 47. 8. Fix the CAN bus cable (or two cables, according to the type of node being connected) to the cable fixing bracket in the upper part of the inside of the electrical panel so that the rolled-back sheathing makes solid contact with the metal bracket. The cables must be held firmly in place by the bracket if pulled.. 46 Installation, Start-Up, Adjustment and Maintenance Manual

To position the jumpers on the board according to the type of node being configured: You will need: access to the electronic board. - If the appliance is a terminal node on the network (i.e. 3 wires are inserted in the orange connector on the board): set the jumpers as shown in detail A of Figure 26. - If the appliance is an intermediate node on the network (i.e. 6 wires are inserted in the orange connector on the board); set the jumpers as shown in detail B of Figure 27. Conductors CAN-BUS wire EXAMPLE OF CLOSED JUMPERS (terminal node with only 1 CAN-BUS wire) GND common cable L LOW signal parameters H HIGH signal parameters P8 CAN PORT / CONNECTOR J1 jumpers (closed position) CHILLER Figure 26 DETAILED EXAMPLE OF THE CONNECTION OF ONLY ONE CAN-BUS WIRE WITH THE ELECTRONIC CONTROL BOARD EXAMPLE OF OPENED JUMPERS (Intermediate node with 2 CAN-BUS wires) GND common cable L LOW signal parameters H HIGH signal parameters P8 CAN PORT / CONNECTOR J1 jumpers (opened position) CHILLER Figure 27 DETAILED EXAMPLE OF THE CONNECTION OF TWO CAN-BUS WIRES WITH THE ELECTRONIC CONTROL BOARD Installation, Start-Up, Adjustment and Maintenance Manual 47

CAN-BUS wire connection to Direct Digital Controller (DDC) WARNING Like the orange connector of the electronic control board, the DDC connector, too, has two different situations of connection (see Figure 29/Figure 30). The Jumpers (J21) are closed in the factory as in 1 st CASE. 1. Take from the supplied bag the orange connector of CAN Port. 2. Connect 3 conductors of CAN-BUS wire (Particular B, Figure 28 ) respecting the signal/color indications as per Table 15 of Page 45 with three inlets H, L, GND of the connector as in Figure 28. 3. If one intermediate node of parameters communication network is under connection, follow the instructions of points 3a, 3b, 3c, 3d; but if one terminal node of parameters communication network is under connection, go directly to point 4. 3a Connect 3 internal conductors of the other segment of CAN- BUS wire (after cutting the sheath from terminals) with 3 inlets H, L, GND of the DDC connector as in Figure 30, Page 49. ORANGE CONNECTOR OF CAN PORT 3b Remove the back cover of the DDC unscrewing the 4 fixing screws. 3c In the electronic control board of DDC, adjust the Jumpers (J21) placed beside the orange connector of CAN Port (P8) as in Figure 30, Page 49. 3d Fix the back cover of the DDC using 4 screws 4. Engage from the back cover hole of DDC the orange connector of CAN Port to the DDC electronic control board. 5a Roll up the cut shield of the above mentioned CAN-BUS wire and connect it with an eyelet terminal of 0.16 (particular C&D, Figure 28 ). 5b (only for intermediate node) roll up the cut shield of the other CAN-BUS wire and connect it with eyelet terminal of 0.16 (particular C&D, Figure 28 ). 6. Unscrew the right bottom screw of the DDC back cover (particular D, Figure 28 ) and insert it to the eyelet terminal (s) and screw it down again. 7 Isolate with suitable adhesive tape the shield part of the wire (particular A, Figure 28 ). DDC B B D P8 A C D LEGEND GND Common cable A Isolated adhesive tape L LOW signal parameters B Conductors CAN wire H HIGH signal parameters C CAN BUS wire shield J21 Jumpers D Eyelet terminal fixed with screw at back cover DDC Figure 28 EXAMPLE OF CAN-BUS WIRE CONNECTION TO DDC (only one entry CAN-BUS wire) 48 Installation, Start-Up, Adjustment and Maintenance Manual

EXAMPLE OF CLOSED JUMPERS (Terminal node with N. 1 CAN-BUS wire) GND common cable L LOW parameters signals H High parameters signals P8 CAN PORT / CONNECTOR J21 jumpers (closed position) conductors CAN-BUS Wire Figure 29 DETAILED EXAMPLE OF ONE CAN-BUS WIRE CONNECTION TO DDC EXAMPLE OF OPENED JUMPERS (Intermediate node with N. 2 CAN-BUS wires ) conductors CAN-BUS Wire GND common cable L LOW parameters signals H High parameters signals P8 CAN PORT / CONNECTOR J21 jumpers (opened position) conductors CAN-BUS Wire another segment Figure 30 DETAILED EXAMPLE OF TWO CAN-BUS WIRES CONNECTION TO DDC Installation, Start-Up, Adjustment and Maintenance Manual 49

LEGEND DDC TR DIRECT DIGITAL CONTROLLER (SUPPLIED AS OPTIONAL) SAFETY TRANSORMER 230/24 Vac 60 Hz (>20 VA, not supplied) Components inside chiller J1 JUMPERS FOR CAN-BUS ON ECB (SCH) TER ELECTRICAL TERMINAL BOX Components inside heater L / N LINE/ NEUTRAL (Electrical supply) Figure 31 CONNECTION OF DDC TO N. 1 AYF 60-119 (2 e 4 PIPES) 50 Installation, Start-Up, Adjustment and Maintenance Manual

LEGEND DDC DIRECT DIGITAL CONTROLLER (SUPPLIED AS OPTIONAL) TR SAFETY TRANSORMER 230/24 Vac 50/60 Hz GND/L/H COMMON (HIGH/LOW) (OF CONNECTOR P8) J21 JUMPERS FOR CAN-BUS ON ECB (SCH) TER J1 IG TER TER L / N ELECTRICAL TERMINAL BOX (chiller) JUMPER for CAN-BUS on ECB (SCH) GENERAL SWITCH WITH FUSE (not supplied) VERTICAL TERMINAL BOX (heater) HORIZONTAL TERMINAL BOX (chiller) LINE/ NEUTRAL (Electrical supply) Figure 32 - CONNECTION OF DDC TO N. 2 AYF 60-119 (2 e 4 PIPES) Installation, Start-Up, Adjustment and Maintenance Manual 51

CHILLER SECTION LEGEND: CNT BOX FLAME CONTROL BOX GV ELECTRIC GAS VALVE BLW FLUE FAN C1 FLUE FAN CONDENSER IGT IGNITOR ELECTRODE FLS FLAME SENSOR TR TRANSFORMER 230/24 V (AC) FAN FAN MOTOR THRF RETURN WATER TEMP. PROBE C1 FAN MOTOR CONDENSER THMF OUTLET WATER TEMP. PROBE LS SIGNAL GAS VALVE OPENING TG GENERATORE TEMPERATURE PROBE TL HIGH TEMPERATURE LIMIT SWITCH TCN CONDENSER TEMPERATURE PROBE TF HIGH TEMPERATURE EXHAUSTED GAS LIMIT SWITCH TA AMBIENT TEMPERATURE PROBE SW AIR PRESSURE SWITCH SRT1 SOLUTION PUMP ROTATION PROBE L PHASE SUPPLY IGN TR IGNITER TRANSFORMER N NEUTRA SUPPLY TER INTERNAL ELECTRIC TERMINAL (9 POLES) FL WATER FLOW SWITCH PUMP HYDRODYNAMIC PUMP MOTOR Figure 33 ELECTRIC WIRING CHILLER section AYF60-119 UNITS (2 AND 4 PIPES) 52 Installation, Start-Up, Adjustment and Maintenance Manual

HEATER SECTION LEGEND WDP DIFFERENTIAL WATER PRESSURE SWITCH GV ELECTRIC GAS VALVE TF HIGH TEMPERATURE LIMIT SWITCH CONT. BOX FLAME CONTROL BOX PSW DIFFERENTIAL AIR PRESSURE SWITCH TL HIGH TEMPERATURE LIMIT SWITCH IGT IGNITOR ELECTRODE TER Vertical ELECTRIC TERMINALS FLS FLAME SENSOR BLW FLUE FAN DV 3 WAY ELECTRO VALVE IGT TR IGNITER TRANSFORMER Figure 34 ELECTRIC WIRING HEATER SECTION AYF60-119 /2 UNITS (2 PIPES) Installation, Start-Up, Adjustment and Maintenance Manual 53

HEATER SECTION LEGEND WDP DIFFERENTIAL WATER PRESSURE SWITCH GV ELECTRIC GAS VALVE TF HIGH TEMPERATURE LIMIT SWITCH CONT.BOX FLAME CONTROL BOX PSW DIFFERENTIAL AIR PRESSURE SWITCH TL HIGH TEMPERATURE LIMIT SWITCH IGT IGNITOR ELECTRODE TER Horizontal ELECTRIC TERMINALS FLS FLAME SENSOR BLW FLUE FAN LS SIGNAL GAS VALVE OPENING IGT TR IGNITER TRANSFORMER Figure 35 ELECTRIC WIRING HEATER SECTION AYF60-119 /4 UNITS (4 PIPES) 54 Installation, Start-Up, Adjustment and Maintenance Manual

6. START-UP AND ADJUSTMENT WARNING This unit should be started-up by Authorized Engineers (TAC) according to the manufacturer s instructions. The end-user is not authorized to perform start-up and adjustment operations. Immediately after placing the boiler in operation, the ignition system safety shutoff device must be tested: proceed as follows: With unit switched off, close gas valve. Start the unit by closing the consent switch (see section 5, on page 35) Check for the presence of a flame control box error (see IGNITION CONTROL BOX, on page 90) Shut-off the unit by opening the consent switch Open gas valve Start the unit by closing the consent switch and check unit proper operation If during the first start-up (in site) a DANGEROUS or ANOMALOUS situation is met due to non-conform system, the start-up operations won t be completed. The user/installer must perform the proper adjustments indicated by authorized engineers (TAC), who will carry out the start-up. The positive result of the first start-up (in site) is only reflecting the good operation of the unit and DDC (if used), but doesn t involve any responsibility concerning the correct execution of the system. The length of the warranty is dependent upon the installation and START-UP of the unit by Authorized Technicians (TAC). See warranty card for complete details. DANGEROUS SITUATIONS FOR THE UNIT AND/OR PERSONS If up on performing the 1 st start-up one of the following conditions is found don t proceed with the start-up: - Unit installed indoors, or in position unsafe for servicing and maintenance. - The unit turned on and off by using the main electrical switch (not using control switch). - Antifreeze mono-ethylene glycol not added to the water - Unit damaged or defective due to transport and/or installation ANOMALOUS INSTALLATION CONDITIONS FOR THE UNIT AND/OR PERSONS The authorized Robur service (TAC) can carry out the 1st start-up, but the unit will be kept switched off until the user/installer fully follows the manufacturer s directions/instructions when these anomalous conditions occur: - Installations which show situations in contradiction to the directions/instructions of the manufacturer in part or fully; - Installations which show situations which result or may result as a defective unit operation. Installation, Start-Up, Adjustment and Maintenance Manual 55

6.1 INSTRUCTIONS ON HOW TO START AND SHUT-OFF THE UNIT OPERATING INSTRUCTIONS 1. STOP! Read the safety information on the label For your safety read before operating on the electric panel of the unit. 2. Set the control switch to OFF position. 3. Turn off all electric power to appliance. 4. This appliance is equipped with an ignition device with automatically lights the burner. Do not try to light the burner by hand. INLET OUTLET 5. Remove control access panel. 6. Push in gas control knob slightly and turn clockwise to OFF. NOTE: Knob cannot be turned to OFF unless knob is pushed in slightly. Do not force. 7. Wait (5) minutes to clear out any gas. If you then smell gas, STOP! Follow B in the safety information above on this label. If you don t smell gas, go to the next step. 8. Turn gas control knob counterclockwise to ON. 9. Replace control access panel. 10. Turn on all electric power to the appliance. 11. Set thermostat to desired setting. 12. If the application will not operate, follow the instructions To Turn Off Gas Of Appliance GAS CONTROL KNOB SHOWN IN ON POSITION INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE 1. Set the control switch to OFF position. 2. Turn off all electric power to the appliance if service is to be performed. 3. Remove control access panel. 4. Push in gas control knob slightly and turn clockwise to OFF. Do not force. 5. Replace control access panel. 6.2 FILLING THE WATER PIPING WARNING When pressurizing the system, make sure that water pressure is not below 14.5 PSIg. WARNING To ensure correct operation of the unit and to avoid the water freezing, add 10% by volume of inhibited mono-ethylene glycol (antifreeze) to the circulation water. Add more mono-ethylene glycol as needed for the minimum external temperature of the installation zone. The method described below is only one of several ways that can be used to fill the hydronic circuit. A container to mix water and mono-ethylene glycol and a water pump to drive the mixture into the hydronic system is required; 2 valves are placed on the circuit as shown in Figure 36. 56 Installation, Start-Up, Adjustment and Maintenance Manual

1. Open air bleed(s) located at the highest point in the system. Connect a hose between the charging pump and Valve A. Connect a hose to Valve C and place the other end of this hose into the mixing container (See Figure 21). 2. Mix the desired concentration and volume of water/monoethylene glycol antifreeze in the container. If the container will not hold the volume required to fill hydronic circuit, multiple batches must be made. 3. Close Valve B. Open Valve A and Valve C. Start charging pump to push the water/antifreeze mixture into the hydronic system. Air will be removed through the hose on Valve C as the hydronic system fills. Continue to fill the system until the water/antifreeze mixture returns to the mixing container via the hose on Valve C. 4. If the volume in the mixing container is adequate to fill the hydronic system, skip to Step 14. If the volume in the mixing container is inadequate to fill the hydronic system, close Valve A prior to air entering the charging pump and shut the charging pump off. 5. Make a new container of water/antifreeze mixture. 6. Start the charging pump and open Valve A to continue filling hydronic system. Repeat Steps 4 through 6 as needed until hydronic system is filled or until charging pump is incapable of adding any additional mixture due to pump discharge head limitations. 7. If the system is filled, skip to Step 14. If the system is not full, turn on the hydronic system s pump but do not start the unit. Jumping the N.O. CIRC. contacts on the electronic control board can start the hydronic system s pump. 8. Throttle Valve B, if necessary to continue filling the hydronic system if the system does not start filling after the hydronic system pump was started. 9. If the volume in the mixing container is not sufficient to fill the hydronic system, close Valve A prior to air entering the charging pump and shut both pumps off. 10. Mix new container of water/antifreeze mixture. 11. Start both pumps and open Valve A. 12. Repeat Steps 9 through 11 until the system is filled and all air is removed from the hydronic system. 13. Close Valve A and Valve C. Shut off all pumps. Open Valve B. 14. Close any manual air bleed valves. 15. Start pumps and open Valve A. 16. Add additional inhibited antifreeze/water mixture until the hydronic system has a total pressure of at least 20 psig or sufficient pressure in the system to allow a positive pressure at pump suction at all times. 17. Close Valve A and shut down both pumps. 18. Disconnect the charging pump and the mixing container. 19. The hydronic system is now charged. CHARGING PUMP MIXING CONTAINER VALVE A VALVE C HYDRONIC SYSTEM S WATER PUMP VALVE B Figure 36 COMPONENTS USED IN FILLING THE HYDRONIC SYSTEM Installation, Start-Up, Adjustment and Maintenance Manual 57

TYPE OF APPROXIMATE PERCENTAGE OF ANTIFREEZE BY VOLUME ANTIFREEZE 20 30 40 50 MONO-ETHYLENE GLYCOL 16 F 4 F -12 F -35 F Table 16 FREEZING POINTS OBTAINED BY VARIOUS CONCENTRATIONS OF MONO-ETHYLENE GLYCOL ANTIFREEZE As other hydronic appliances, Robur heating and cooling systems operate with grid-water of good quality. In order to prevent any possible problem of operation or reliability caused by filling or top-up water, please refer to codes and norms about water treatment for thermo-hydraulic installations in civil or industrial applications. Parameters indicated in Table 17 must be complied with. CHEMICAL AND PHYSICAL PARAMETERS OF WATER IN HAETING/COOLING SYSTEMS PARAMETER UNIT OF MEASUREMENT ALLOWABLE RANGE ph \ > 7 (1) CHLORIDES ppm < 125 TOTAL HARDNESS (CaCO 3 ) f < 15 IRON ppm < 0.5 (1) COPPER ppm < 0.1 (1) ALUMINIUM ppm < 1 LANGELIER S INDEX \ 0 0.4 HARMFUL SUBSTANCES FREE CHLORINE ppm < 0.2 (1) FLUORIDES ppm < 1 SULPHIDES ABSENT (1) In accordance and respecting current and local regulation Table 17 CHEMICAL AND PHYSICAL PARAMETERS OF WATER. Water quality can be measured through parameters like acidity, hardness, conductivity, chlorides content, chlorine content, iron content and the like. WARNING!!! The presence of active chlorine in the water, in particular, can jeopardize parts of the installation and Robur units. Therefore, please make sure that active chlorine content and total hardness are compliant with the allowable ranges reported in Table 17. The way the installation is operated can be the cause of possible degradation of water quality. Moreover, abnormally massive water top-up or reintegration can cause a drift of chemical or physical abovementioned parameters. Reintegration should not exceed 5% per year of the total amount of water. It is advised to check regularly the water quality, especially in case of automatic or periodic top-up. In case water treatment is needed, this operation should be carried out by a professional or competent person, following strictly the instructions by the manufacturer or supplier of the chemical substances for the treatment, since dangers could arise for health, for the environment and for Robur appliances. Several products for water treatment are available on the market. In case washing of the pipes is needed, this operation should be carried out by a professional or competent person, following strictly the instructions by the manufacturer or supplier of the chemical substances for the washing, avoiding the use of substances aggressive for stainless steel or containing/releasing active chlorine. Please make sure the pipes are properly rinsed in order to remove any residue of chemical substances from the pipes. Robur is not liable for ensuring that water quality is always compliant with what reported in Table 17 is not s. Non-compliance with indications above may jeopardize the proper operation, integrity and reliability of Robur appliances, invalidating the warranty. For any further detail, please contact directly Robur Corporation Evansville, IN Phone (812) 424-1800; Fax (812) 422-5117. 58 Installation, Start-Up, Adjustment and Maintenance Manual

6.3 GAS PRESSURE ADJUSTMENT The manufacturer supplies the units already adjusted for a particular type of gas. The type of gas can be checked and easily identified by looking at the marking label inside the unit. Nevertheless, before starting the unit it is necessary to check and if necessary adjust the Gas Input (HHV) to the burner. Using Table 18, Table 19, Table 20 and Table 21 arrange the proper manifold pressure according to the local gas heating value (BTU content per cubic foot) and specific gravity following the successive procedure. These tables are based on the correct natural Gas Input (HHV) for the model by manifold pressure in inches of water column (in WC). CHILLER SIDE MJ CONTENT PER CU.Meter BTU CONTENT SPECIFIC GRAVITY OF NATURAL GAS PER CU.FT. 0,55 0,6 0,65 0,7 35,40 950 2,81 3,07 3,33 3,58 36,33 975 2,67 2,91 3,16 3,40 37,26 1000 2,54 2,77 3,00 3,23 38,19 1025 2,42 2,64 2,86 3,08 39,12 1050 2,30 2,51 2,72 2,93 40,05 1075 2,20 2,40 2,60 2,80 40,98 1100 2,10 2,29 2,48 2,67 41,92 1125 2,01 2,19 2,37 2,55 MJ CONTENT PER CU.Meter Our reference: BTU CONTENT SPECIFIC GRAVITY OF NATURAL GAS PER CU.FT. 0,555 37,78 1014 2,5 Table 18 - MANIFOLD PRESSURE in WC inches BASED ON GAS INPUT (HHV) OF 94,900 Btu/hr USING 0.21 ORIFICE. The conditions referred to by the table above are for the guidance of the installer and the CSA design certification does not cover the conditions described therein. Note: For Propane Gas Models, follow the same instructions as given for natural gas. The manifold pressure for propane gas should be 4.8 W.C. and adjustment is made at the gas valve regulator. Manifold pressure at 94,900 Btu/hr. input using 0.14 orifice. GAS TYPE NATURAL GAS LP GAS MANIFOLD PRESSURE 2.5 WC Inches 4.8 WC Inches NOZZLE DIAMETER 0.21 0.14 Table 19 MANIFOLD PRESSURE AND NOZZLE DIAMETER- CHILLER SIDE Installation, Start-Up, Adjustment and Maintenance Manual 59

HEATER SIDE MJ CONTENT PER CU.Meter BTU CONTENT SPECIFIC GRAVITY OF NATURAL GAS PER CU.FT. 0,55 0,6 0,65 0,7 35,40 950 3,05 3,32 3,60 3,88 36,33 975 2,89 3,16 3,42 3,68 37,26 1000 2,75 3,00 3,25 3,50 38,19 1025 2,62 2,86 3,09 3,33 39,12 1050 2,49 2,72 2,95 3,17 40,05 1075 2,38 2,60 2,81 3,03 40,98 1100 2,27 2,48 2,69 2,89 41,92 1125 2,17 2,37 2,57 2,77 MJ CONTENT PER CU.Meter Our reference: BTU CONTENT SPECIFIC GRAVITY OF NATURAL GAS PER CU.FT. 0,555 37,78 1014 2,7 Table 20 - MANIFOLD PRESSURE in WC inches BASED ON GAS INPUT (HHV) OF 129,000 Btu/hr USING 0.25 ORIFICE. The conditions referred to by the table above are for the guidance of the installer and the CSA design certification does not cover the conditions described therein. Note: For Propane Gas Models, follow the same instructions as given for natural gas. The manifold pressure for propane gas should be 4.8 W.C. and adjustment is made at the gas valve regulator. Manifold pressure at 129,000 Btu/hr. input using 0.17 orifice. GAS TYPE NATURAL GAS LP GAS MANIFOLD PRESSURE 2.7 W.C. Inches 4.8 W.C. Inches NOZZLE DIAMETER 0.25 0.17 Table 21 - MANIFOLD PRESSURE AND NOZZLE DIAMETER- HEATER SIDE PRESSURE ADJUSTMENT PROCEDURE 1. Turn main gas valve knob to the OFF position. 2. Remove the plug on outlet end of gas valve and attach pressure tap and manometer. 3. Turn power ON, and close control switch. 4. Wait for the burner to start up. Due to the presence of air inside the piping, it may be that the burner does not start at the first three attempts and failing to do so the ignition system is locked out. If this happens reset the ignition system (see dedicated procedure, end of Appendix). Repeat until all the air is purged from the piping and the burner ignites. 5. When the burner ignites read the manometer and compare to the required pressure in Table 18 for chiller, Figure 37 for heater. 6. If necessary change the manifold pressure using the gas valve regulator. The regulator is built into the gas valve. Remove the seal screw and turn adjusting screw clockwise to increase pressure or counter clockwise to reduce pressure. Replace seal screw after adjustment. 7. Open control switch and make sure unit is off. 8. Turn gas valve knob to the off position. 9. Remove manometer and pressure tap. Replace plug in gas valve and turn gas valve to the on position. 10. Turn unit on by closing control switch. Check all gas connections with soap for leaks. 60 Installation, Start-Up, Adjustment and Maintenance Manual

PRESSURE REGULATOR ADJUSTMENT INLET PRESSURE TAP REMOVE CAP SCREW FOR PRESSURE ADJUSTMENT OUTLET PRESSURE TAP INLET OFF ON OUTLET GAS CONTROL KNOB Figure 37 GAS VALVE Installation, Start-Up, Adjustment and Maintenance Manual 61

6.4 CHILLED WATER TEMPERATURE REGULATION WARNING When DDC is used, the following menu3 set-up is not to be done. It s necessary to consult Installation and Programming manual of DDC - Direct Digital Controller. If the unit isn t connected to a DDC, chilled water temperature regulation can be set up from menu 3 of the S61 card (see APPENDIX: S61 electronic card). MENU SIGNALS Thermostat action Cold water set point MENU 3 End User Adjustment DESCRIPTION OF MENU SIGNALS Cold water temperature difference T Exit Table 22 MENU 3 PARAMETERS The thermostat action parameter can assume 2 values: 0 and 1. When 0 is set, temperature to drive the unit is read by the INLET probe; when 1 is set, the temperature is read by the OUTLET probe. The set-point is intended to be the pre adjusted water temperature (in/out), when being achieved, the unit will start the switching off cycle as (since) the conditioning request is met. This parameter can assume values from a factory set minimum value up to 77 F. The temperature difference is intended to be a value, which should be summed up by the pre adjusted set point temperatures. This parameter can assume values from 1.8 F up to 14.4 F. The obtained value represents the water temperature. According to this temperature, the conditioning request will be re activated and then the unit will start up again. For example, let us suppose the following adjustments : - Thermostat action: unit operation with outlet temperature - set-point +44 F; - Temp. difference 2 ; The unit behaves as follows : - One time during the unit operation, the water of HYDRONIC system is getting cold until the outlet water temperature reaches +44 F (set-point temperature); - Up on achieving that temperature, the unit will be switched off automatically. - When the water temperature starts getting high, reaches +46 F (that is +44 F plus the temp difference of 2) the unit will start-up again to cool the water once more until reaching +44 F, and so on. Then, according to these adjustments the unit switches off at +44 F and starts-up at +46 F. To set up the parameters use the encoder knob: - To select a menu, a parameter or a value rotate the knob. - To enter a value press the knob (see APPENDIX: Electronic system of the AYF60-119 unit). 62 Installation, Start-Up, Adjustment and Maintenance Manual

6.5 HOT WATER TEMPERATURE REGULATION When DDC is used, the following menu3 set-up is not to be done. It s necessary to consult Installation and Programming manual of DDC - Direct Digital Controller. If the unit isn t connected to a DDC, chilled water temperature regulation can be set up from menu 3 of the S61 card (see APPENDIX: S61 electronic card). MENU 3 End User Adjustment MENU SIGNALS 3. 1 6 0 3. 1 6 1 3. 1 6 2 3. E Hot water thermostat action Hot water set point Hot water temperature difference T Exit DESCRIPTION OF MENU SIGNALS Table 23 HOT WATER REGULATION PARAMETERS The thermostat action parameter can assume 2 values: 0 and 1. When 0 is set, temperature to drive the unit is read by the INLET probe; when 1 is set, the temperature is read by the OUTLET probe. The set-point is intended to be the pre adjusted water temperature (in/out), when being achieved, the unit will start the switching off cycle as (since) the heating request is met. This parameter can assume values from a minimum value of 104 F to a factory set value. The temperature difference is intended to be a value, which should be summed up by the pre adjusted set point temperatures. This parameter can assume values from -36 F up to -1.8 F. The obtained value represents the water temperature. According to which, the heating request will be re activated and then the unit will start up again. For example, let us suppose the following adjustments : - Thermostat action: unit operation with outlet temperature - set-point +122 F (suggested value for residential and commercial use plants); - Temp. difference -3.6 F ; The unit behaves as follows : - One time during the unit operation, the water of HYDRONIC system is getting hot until the outlet water temperature reaches +122 F (set-point temperature); - Up on achieving that temperature, the unit will be switched off automatically. - When the water temperature starts getting low, reaches +118.4 F (that is +122 F plus the temp difference of -3.6) the unit will start-up again to heat the water once more until reaching +122 F, and so on. Then, according to these adjustments the unit switches off at +122 F and starts-up at +118.4 F. To set up the parameters use the encoder knob: - To select a menu, a parameter or a value rotate the knob. - To enter a value press the knob (see APPENDIX: Electronic system of the AY00-119 unit). Installation, Start-Up, Adjustment and Maintenance Manual 63

7. SERVICING AND MAINTENANCE This manual is an integral and essential part of the product and must be given to the owner. Performing correct preventive service and maintenance will help to guarantee long life of the unit with high efficiency and low maintenance costs. WARNING ONLY Authorized Technicians (TAC) strictly complying with the manufacturer s instructions and the local standards should perform maintenance and service on the UNIT internal components. Lubrication of condenser fan motor, hydraulic pump, chiller motor and pre-mixer motor is not recommended. The operations described below must be performed once a year. If the unit is installed on a heavy-duty installation (industrial plants, 24hr operation etc.), it is necessary to increase the frequency of checks and services. MAINTENANCE TO BE PERFORMED ON THE CHILLER SIDE OF THE UNIT: - Cleaning of the condenser /absorber coils - Check condenser fan height NOTE Before any type of service is performed, ALWAYS shut-off the power supply at the main switch. CLEANING THE CONDENSER / ABSORBER COILS It is recommended to clean the condenser / absorber coils regularly since the UNIT cooling capacity can be greatly reduced by dirt on the coils. The user, installer or service technician can perform this operation. To clean condenser / absorber coil proceed as follows: 1. Shut off the power and gas supply. 2. Remove the covering panels. 3. Use a brush to remove dirt from the outside and inside of the condenser/absorber coils. 4. Using water pressure, wash the coils from in to out and from top to bottom. Care should be taken not to spray electrical components or to damage the aluminum fins. 5. Check that all dirt is removed. 6. Replace the panels. 7. Turn on the power and gas supply. 8. Start unit to check for correct operation. NOTE Do not use solvents for cleaning the condenser/absorber coils; this could cause damage to the aluminum fins. 64 Installation, Start-Up, Adjustment and Maintenance Manual

CHECK CONDENSER FAN HEIGHT For proper air flow, the distance between the top edge of the fan blade and the top panel must be 1 1/4. If the fan is at an improper height, adjust the location of the mounting strap around the fan motor. 1 1/4 FAN BLADE EDGE TOP PANEL MOUNTING STRAP SECTION VIEW NOTE: SOME DETAIL HAS BEEN REMOVED FOR CLARITY Figure 38 SECTION VIEW SHOWING PROPER FAN HEIGHT MAINTENANCE TO BE PERFORMED ON THE HEATER SIDE OF THE UNIT: - Venting system and vent terminal have to be periodically examinated and cleaned - Check functioning of combustion and thermal exchange circuit: - burner and exhaust gas flue - igniter and flame sensor system - Check functioning of regulation and safety devices - Analysis of combustion products, according to in-force standards and laws. - Flue gas inspection and cleaning - Cleaning of the burner FLUE GAS PASSAGE INSPECTION AND CLEANING Early in the year before operating the unit, complete the following instructions: 1. Turn off gas and electric supply to the unit. 2. Remove front panel. 3. Remove top panel. 4. Clean the base pan around the generator housing of any debris. 5. Look down the flue opening at the back of the generator housing and clear any debris that may be obstructing the opening (see Figure 23). 6. Look down the air intake chute for combustion air and clear any debris that may be obstructing the opening. 7. Reinstall top panel. 8. Reinstall front door. 9. Turn on gas and electric supply to the unit. 10. Start unit to check for correct operation. It is recommended that at least once a year a qualified service technician perform routine maintenance on the equipment. Installation, Start-Up, Adjustment and Maintenance Manual 65

CLEANING OF THE BURNER Tools Needed: Fiber Bristle Brush Dust Mask (3M #8710 or equal) Safety Goggles Hand Tools WARNING ALWAYS wear safety goggles! 1. Shut off gas and electric supply to unit. 2. Remove front panel. 3. Remove bolts and nuts securing pre-mixer blower housing to burner tube flange. 4. Remove screws holding burner and insulation retaining straps. Note: Wear a dust mask (3M #8710 or equal NOISH/MSHA TC-21C mask) during burner removal, cleaning, and assembly operations. 5. Pry bottom of burner tube out to clear bottom of generator housing. Pull burner down and out to remove from generator housing. Note: Be careful not to distort or damage the burner tube or the igniter and sensor assemblies in the generator housing. 6. Position burner tube with open end down. 7. Clean burner tube ports with fiber bristle brush and shake any debris out of the tube. 8. Inspect burner tube gasket that seals the burner tube to the generator housing and the burner flange gasket that seals burner to pre-mixer blower housing. Replace either gasket if damaged during burner removal process. (Burner tube gaskets Kit No. 16009-716) 9. Replace burner tube in reverse order of removal. Note: Make sure the two gaskets are positioned correctly and that generator housing is properly sealed. 10. Turn on gas and electric supply to unit. 11. Start unit and check for correct operation. Before any type of service is performed, ALWAYS shut-off the power supply at the main switch. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. NOTE 66 Installation, Start-Up, Adjustment and Maintenance Manual

8. ADAPTING TO ANOTHER GAS ONLY an Authorized Technician can perform the operation described in this section. If the type of gas indicated does not correspond to the type to be used (natural or propane gas) by unit, it must be converted and adapted to the type of gas to be used. The gas orifice (nozzle) must be changed and the gas valve must be converted. CHILLER SIDE For this operation proceed as follows: NOTE 1. Turn off the gas and electrical supply, remove front and left panel. 2. Remove the wires from the gas valve. 3. Remove the ring nut from the threaded gas nozzle. 4. Remove the gas nozzle from gas valve by removing the 4 screws from the valve flange (use 9/64 hex key wrench). Put the o-ring in a safe place, to be re-used with the new nozzle. 5. Attach the new gas nozzle to the gas valve using the 4 screws to secure valve flange: be sure to put the o-ring in the proper site. 6. Tighten the ring nut and re-attach wires to the valve. 7. Turn on the gas and electrical supply. 8. Adjust the gas pressure for the gas to be used following the instructions reported in SECTION 6.3 "GAS PRESSURE ADJUSTMENT. 9. Replace the stickers indicating the type of gas for which the unit is preset with the new one, which indicates the type actually being used. GAS VALVE Figure 39 CHILLER GAS VALVE HEATER SIDE 1. Turn off the gas and electrical supply, unscrew front panel screws and remove it. 2. Remove the ring nut from the threaded gas nozzle. 3. Remove the gas nozzle. Put the o-ring and the gasket in a safe place, to be re-used with the new nozzle. Installation, Start-Up, Adjustment and Maintenance Manual 67

4. Place the new gas nozzle. Be sure to put the o-ring and the gasket in the proper site. 5. Tighten the ring nut. 6. Turn on the gas and electrical supply. 7. Adjust the gas pressure for the gas to be used following the instructions reported in SECTION 6.3 "GAS PRESSURE ADJUSTMENT. 8. Replace the stickers indicating the type of gas for which the unit is preset with the new one, which indicates the type actually being used. GAS VALVE Figure 40 HEATER GAS VALVE INLET FOR COMBURANT AIR AIR DIAPHRAGM Figure 41 DETAILS OF ADAPTING GAS PROCEDURE-HEATING SECTION 68 Installation, Start-Up, Adjustment and Maintenance Manual

9. SPARE PARTS Each AYF unit is composed by both a chiller module (ACF60-00) and a heater module (AY00-119). Below are the lists of the spare parts for ACF and AY00-119/2 - AY00-119/4 modules, and for AY00-119. Each list comes after the respective exploded drawing, which pictures each part in the list with its progressive number. Spare parts can be ordered from Robur Corporation. CHILLER MODULE SPARE PARTS Exploded drawing n.1: INSULATING, WATER PIPES AND ACCESSORIES Figure 42 EXPLODED DRAWING N.1 SEE Table 28, PAGE 78 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 69

Rif. Codice Descrizione Q.tà 1 J-TBO358 PUMP HIGH PRESSURE PIPE 1 2 N-RND016 D.3/8"x1,5 COPPER WASHER 2 3 N-BLL000 PUMP GAS SCREW 3/8 1 4 J-FLS009 WATER FLOWSWICH FOR S61 1 5 C-CBN091 ABSORBER FRONT-SIDE INSULATING 1 6 C-CBN092 ABSORBER REAR-SIDE INSULATING 1 7 R-TBO418 WATER DELIVERY PIPE 1 8 R-TBO420 WATER RETURN PIPE 1 9 K-MNM002 DIFFERENTIAL MANOMETER KIT 1 10 J-TRS007 IGNITER TRANSFORMER 1 11 E-LMP013 SIGNAL LIGHT 230V WITH FAST-ON 1 12 G-VLV032 PRESSURE RELIEF VALVE 1 13 R-GFS001 FLOWSWICH CLAMPING RING NUT 1 14 L-STF189 AIR BREATHER VALVE BRACKET 1 15 H-VLV000 AUTOMATIC AIR BREATHER VALVE 1 Table 24 SPARE PARTS PICTURED IN Figure 42: INSULATING, WATER PIPES AND ACCESSORIES 70 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.2: ELECTRICAL BOX AND PUMP Figure 43 EXPLODED DRAWING N.2 SEE Table 29, PAGE 80 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 71

Rif. Codice Descrizione Q.tà 1 R-PMP009 60 Hz OIL PUMP 1 2 J-NTV000/B MX20/15 VIBRATION DAMPING 2 3 J-CRT003 PUMP CARTER 1 4 L-BQD018 ELECTRIC PANEL BASE 1 5 E-TRS013 60 Hz 208-240/24V/40VA ELECTRICAL TRANSFORMER 2 6 L-STF149 GROUND CONNECTION BRACKET 1 7 E-CNT031 24 Vac, 60Hz, MICROPROCESSOR BASED HSI CONTROL 1 8 J-TLT020 COMBUSTION CHAMBER THERMOSTAT 1 9 E-SLT040 S61CF24 ELECTRICAL BOARD 1 10 E-CND011 CONDENSER 12.5 µf 450 V 1 11 G-PRS000 AIR PRESSURE SWITCH ACF60.2 60 Hz 1 12 E-MRS020 9 STUD TERMINAL BOARD WITH REED 1 13 L-CQD011 ELECTRIC BOX COVER 1 14 C-12100960 INSPECTION HOLE GLASS 1 15 N-TPP019 D.25 PROTECTION CAP 1 16 N-CRN000 ELECTRIC BOX HINGE 2 17 J-TLT015 LIMIT THERMOSTAT FOR GENERATOR 1 Table 25 SPARE PARTS PICTURED IN Figure 43: ELECTRICAL BOX AND PUMP 72 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.3: COMBUSTION CHAMBER AND GAS SYSTEM Figure 44 EXPLODED DRAWING N.3 SEE Table 30, PAGE 82 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 73

Rif. Codice Descrizione Q.tà 1 J-CCM026 FRONT COMBUSTION CHAMBER ASSY 1 2 S-CMR000 REAR COMBUSTION CHAMBER ASSY 1 3 H-CMR002 COMB. CHAMBER INTERNAL CONVEYOR 1 4 L-STF120 RETAINER BURNER 2 5 L-MFS000 BURNER TUBE CLIP 2 6 C-CBN040 FRONT BOTTOM INSULATION 1 7 C-CBN038 REAR UPPER INSULATION 1 8 C-CBN037 FRONT-TOP INSULATION 1 9 C-CBN042 COMBUST. CHAMBER BASE INSULATION 2 10 C-CBN080 RIGHT COMBUST. CHAMBER INSULATION 1 11 C-CBN081 LEFT COMBUST. CHAMBER INSULATION 1 12 C-CBN039 COMB. CHAMBER REAR-SIDE INSULATION 2 13 C-CBN041 COMB. CHAMBER/GENERATOR INSULATION 1 14 J-CBN029 BURNER INSULATION 1 15 J-BRC017 BOILER BURNER 1 16 J-GRN028 BURNER UNION TRIMMING 2 17 R-DFF009 INCLINED AIR-GAS MIXER 1 18 J-LTT047 SPARKLING ELECTRODE 1 19 C-GRN086 SENSOR FLAME ELECTRODE GASKET 1 20 J-LTT046 SENSOR FLAME ELECTRODE 1 21 N-GRG006 2075 NB 70 O-RING 1 22 J-CSL000 D.11/16 x 50 CERAMIC INSULATION 1 23 G-VLV052 24 VAC GAS CONTROL VALVE 1 24 B-GLL150 Ø 5.3 METHANE NOZZLE 1 B-GLL153 Ø 3.6 GPL NOZZLE 1 25 C-GRN041 24x24 GAS PIPE GASKET 1 26 C-GRN040 1 GASKET 1 27 N-GRG000 3087 NBR NT 70 O-RING 1 28 R-TBO645 GAS TUBE COMPONENT 1 29 G-FLN019 90 ½ NPT GAS VALVE FLANGE 1 30 C-GRN057 CENTELLEN 200 ¾ GASKET 1 31 K-SFF038 BLOWER KIT 1 Table 26 SPARE PARTS PICTURED IN Figure 44: COMBUSTION CHAMBER AND GAS SYSTEM 74 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.4: PANELS KIT Figure 45 EXPLODED DRAWING N.4 SEE Table 31, PAGE 84 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 75

Rif. Codice Descrizione Q.tà 1 P-MNS035 PAINTED FRONT-LEFT COLUMN 1 2 P-MDS004 PAINTED BACK RIGHT-LEFT COLUMN 2 3 P-MND020 PAINTED FRONT-RIGHT COLUMN 1 4 P-PNF063 COMPLETE PAINTED FRONT PANEL 1 5 C-12100960 INSPECTION HOLE GLASS 1 6 L-PST068 SILK SCREENED SERVICE PLATE 1 7 N-MNG000 PANELS HANDLE 1 8 E-MTR056 60 Hz FAN MOTOR 1 9 V-PRT000 60 Hz MOTOR RAIN SHIELD 1 10 L-STF210 60 Hz FAN MOTOR BRACKET 4 11 V-VNT025 BLADE ASSEMBLY FAN 26 Ø 60 Hz 1 12 P-CPR048 PAINTED SUPERIOR PANEL 1 13 N-TPP061 Ø33.4 H.25 VINYL CAP 1 14 C-CBN028 380X840 SUPERIOR PANEL INSULATION 1 15 J-GPR000 FAN GRID 1 Table 27 - SPARE PARTS PICTURED IN Figure 45: PANELS KIT 76 Installation, Start-Up, Adjustment and Maintenance Manual

HEATER MODULE SPARE PARTS Exploded drawing n.5: COMBUSTION CHAMBER ASSY Figure 46 EXPLODED DRAWING N.5 SEE Table 28, PAGE 78 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 77

Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà J-CMB140 Complete combustion chamber 1 L-BSM012 L-BSM012 L-BSM012 Combustion chamber base 1 2 C-CBN044 C-CBN044 C-CBN044 Rigid upper/lower insulation 2 3 C-CBN043 C-CBN043 C-CBN043 Upper/lower insulation 2 4 C-CBN078 C-CBN078 C-CBN078 Right lateral insulation assembly 1 5 C-CBN123 C-CBN123 C-CBN123 Left lateral insulation assembly 1 6 P-CPR051 P-CPR051 P-CPR051 Combustion chamber cover 1 7 L-PNN083 L-PNN083 L-PNN083 Complete left panel 1 8 L-PNN084 L-PNN084 L-PNN084 Complete right panel 1 10 J-SCM006 J-SCM006 J-SCM006 Heat exchanger assembly 1 12 C-CBN047 C-CBN047 C-CBN047 AY00-119 intercooler collectors insulation 2 13 L-GRG000 L-GRG000 L-GRG000 Flow Grid 1 15 J-BRC000A J-BRC000A J-BRC000A AY00-119 burner 1 16 L-MFS000 L-MFS000 L-MFS000 Clip burner tube 3 17 L-STF120 L-STF120 L-STF120 Retainer burner 2 18 J-CBN029 J-CBN029 J-CBN029 Burner insulation gasket 1 19 J-LTT047 J-LTT047 J-LTT047 Sparkling electrode 1 20 J-LTT035 J-LTT035 J-LTT035 Ignitor/sensor 1 23 J-GRN054 J-GRN054 J-GRN054 Sparkling electrode gasket 1 9 N-BCC009 N-BCC009 N-BCC009 Bush 1 11 L-MSC002 L-MSC002 L-MSC002 Mixer spring 1 14 J-CSL000 J-CSL000 J-CSL000 Ceramic insulation 1 21 J-CVO199 J-CVO199 J-CVO199 AY00-119 FLS cable 1 22 J-CVO124 J-CVO124 J-CVO124 Transformer sparkling cable 2 24 J-TLT017 J-TLT017 J-TLT017 Module AY00-119 limit thermostat 1 Table 28 SPARE PARTS PICTURED IN Figure 46 on page 77: COMBUSTION CHAMBER ASSY 78 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.6: EXHAUSTED GASES ASSY Figure 47 EXPLODED DRAWING N.6 SEE Table 29, PAGE 80 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 79

Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà 1 L-CMN004 L-CMN004 L-CMN004 Chimney 1 J-SCR002 Kit exhausted gases flue 2 R-TBO413 R-TBO413 R-TBO413 Flue gas pipe 1 3 J-CBN048 J-CBN048 J-CBN048 Flue gas hood insulation 1 4 J-GRN072 J-GRN072 J-GRN072 Nosepiece gasket 1 J-FMI002 Kit exhausted gases 5 R-TBO417 R-TBO417 R-TBO417 T pipe M/F/M 1 6 L-DFL024 L-DFL024 L-DFL024 Chimney baffle plate 1 7 J-TBO271 J-TBO271 J-TBO271 Gas pipe Ø130 1 8 O-FSC001 O-FSC001 O-FSC001 Closing clamp Ø130 3 9 N-SPP005 N-SPP005 N-SPP005 Wall bearing racket for pipe Ø130 2 10 J-SCR000 J-SCR000 J-SCR000 Condensate drain for Ø130 pipe 1 11 J-TRM000C J-TRM000C J-TRM000C Ø130 pipe terminal for AY00-119 1 12 J-TLT015 J-TLT015 J-TLT015 Limit thermostat for generator 1 13 J-CVO198 J-CVO198 J-CVO198 AY00-119 TF cable 1 Table 29 SPARE PARTS PICTURED IN Figure 47 on page 79: EXHAUSTED GASES ASSY 80 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.7: BLOWER AND GAS SYSTEM ASSY Figure 48 EXPLODED DRAWING N.7 SEE Table 30, PAGE 82 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 81

Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà 1 R-DFF006 R-DFF006 R-DFF006 Air gas mixer 1 J-SFF047 AY00-119 blower assembly 2 J-GRN028 J-GRN028 J-GRN028 Burner union trimming 2 3 E-MTR054 E-MTR054 E-MTR054 Blower motor 60 Hz 1/50 HP 1 4 V-CCL017 V-CCL017 V-CCL017 Scroll housing 1 5 V-VNT010 V-VNT010 V-VNT010 Blower wheel 1 6 L-DFR057 L-DFR057 L-DFR057 Air diaphragm 36.5 mm 1 7 L-BCC020 L-BCC020 L-BCC020 Air intake 1 8 J-SND018 J-SND018 J-SND018 Air probe 1 J-SPA001 Air pressure switch baking 9 L-CPR007 L-CPR007 L-CPR007 Air pressure switch cover 1 10 L-STF132 L-STF132 L-STF132 Air pressure switch bracket 1 11 J-PRA016 J-PRA016 J-PRA016 193 Pa air pressure switch 1 12 J-GLL156 J-GLL156 J-GLL156 Nozzle Ø6,30 (Nat.) 1 J-GLL107 J-GLL107 J-GLL107 Nozzle Ø4,30 (LP) 1 13 J-GRN040 J-GRN040 J-GRN040 Gasket for nut 1 1 14 R-NPP032 R-NPP032 R-NPP032 ½ NPT gas nipple 1 15 J-VLV052 J-VLV052 J-VLV052 Gas control valve 1 K-GAS 281 K-GAS282 Gas tube 16 G-FLN019 G-FLN019 G-FLN019 Gas valve flange 1 17 R-TBO703 R-TBO703 R-TBO703 Gas tube vertical component 1 18 R-TBO702 R-TBO702 R-TBO702 Gas tube horizontal component 1 19 R-RCC102 R-RCC102 R-RCC102 ½ T connection 1 20 N-TPP069 Galvanized steel NPT ½ plug 1 21 R-NPP033 R-NPP033 NPT/G nipple 1 Table 30 SPARE PARTS PICTURED IN Figure 48 on page 81: BLOWER AND GAS SYSTEM ASSY 82 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.8: PANELS KIT Figure 49 EXPLODED DRAWING N.8 SEE Table 31, PAGE 84 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 83

Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà 1 L-PST129 L-PST085 L-PST086 Silk-screened service plate 1 2 L-PNN087 L-PNN087 L-PNN087 Painted front panel 1 3 L-PNN093 L-PNN093 L-PNN093 Painted right panel 1 4 L-PNN026 L-PNN026 L-PNN026 Painted rear panel 1 5 P-PSP069 P-PSP069 P-PSP069 Painted superior panel 1 6 L-DFL041 L-DFL041 L-DFL041 Baffle protecting nozzle 1 7 L-PNN090 Painted left panel 1 8 L-BSM011 L-BSM011 L-BSM011 Complete base 1 Table 31 - SPARE PARTS PICTURED IN Figure 49 on page 83: PANELS KIT 84 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.9: WATER PIPING Figure 50 EXPLODED DRAWING N.9 SEE Table 31, PAGE 84 FOR THE RELATIVE PARTS LIST. Installation, Start-Up, Adjustment and Maintenance Manual 85

Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà 1 R-TBO267 Water heat exchanger output pipe 1 2 R-TBO526 Water 3 ways valve output pipe 1 3 R-TBO264 Water 3 ways valve input pipe 1 4 K-TBI046 Water inlet pipe AY00-119/2 1 5 J-VDV000 3 ways valve 1 6 N-RND028 N-RND028 N-RND028 Teflon washer 8 mm 1 7 J-RND017 J-RND017 J-RND017 Teflon washer 1 1/4 1 8 R-TBO538 R-TBO538 Water outlet pipe 1 9 K-TBI045 K-TBI045 Water inlet pipe 1 10 R-TBO542 Chiller water inlet/outlet piping 2 11 J-FLS007 J-FLS007 J-FLS007 H2O differential flow switch 1 12 J-VLV000 J-VLV000 J-VLV000 Automatic leak air valve 1 13 J-VLV010 J-VLV010 J-VLV010 ASME overpressure valve 1 14 J-MNM003 Pressure Gauge 1 Table 32 - SPARE PARTS PICTURED IN Figure 49 on page 83: WATER PIPING 86 Installation, Start-Up, Adjustment and Maintenance Manual

Exploded drawing n.10: ELECTRIC BOX 6 7 8 9 Figure 51 EXPLODED DRAWING N.10 SEE Table 33 on PAGE 87 FOR THE RELATIVE PARTS LIST. Code Ref. AY00-119 AY00-119/2 AY00-119/4 Description Q.tà J-QLT218 J-QLT219 Electric box 1 L-BQD022 L-BQD022 L-BQD022 Electric box basement 1 2 J-CQD012 J-CQD012 J-CQD012 AY00-119 box cover kit 1 3 N12913046 N12913046 N12913046 Electric box hinge 2 5 J-TRS015 J-TRS015 J-TRS015 Ignition transformer 1 6 J-TRS013 J-TRS013 J-TRS013 Transformer 208-240/24V 1 7 J-CNT031 J-CNT031 J-CNT031 24 VAC ignition control box 1 8 J-SLT032 J-SLT032 J-SLT032 Electronic card S70CF24 1 9 J-SLT028 Electronic card AY10 1 4 L-SPP016 L-SPP016 L-SPP016 Electric box support 1 Table 33 - SPARE PARTS PICTURED IN Figure 51 on page 87: ELECTRIC BOX Installation, Start-Up, Adjustment and Maintenance Manual 87

APPENDIX ELECTRONIC SYSTEM OF THE AYF60-00 UNITS The electronic system of the AYF60-119 units is composed by two different electronic boards: the main control board (S61) and the S70 control board. The S61 electronic control board is placed inside the electrical box and is equipped with a 4 digits display, a regulating knob (encoder) and a terminal set (CAN PORT) for the remote connection. The DISPLAY (particular A) shows the operation data (example: chilled water temperature) and possible anomalies, through the visualization of the unit codes. Besides, It is possible to visualize all relative available information (data, parameters, values, etc.). A C LEGEND A 4 digits DISPLAY for visualizing operational and unit codes B REGULATING KNOB (Encoder) for scrolling/selection of data C CAN PORT for the connection to DDC B Electronic Control Board S 61 Figure 52 ELECTRONIC CONTROL BOARD DETAIL Rotating and pressing the REGULATING KNOB (particular B) allows the scrolling and selection of the information on the display. Through the regulating knob and Display, operation management and control take place. The CAN PORT (particular C) allows the connection, by one can-bus wire, between the electronic control board and DDC (available as accessory). When such connection is made, the operation management and control of the unit takes place only through the DDC. NOTE The S61 electronic control board is placed inside the electrical box of the unit and is visible from the front panel. To interact with the regulating knob (encoder) of the electronic control board, it is necessary to remove the front panel of the unit and, without opening the electrical box, to act on the encoder by the supplied tube of about 4-3 /4. The S70 electronic control board is placed inside the control box of the heater module. S 70 ECB Figure 53 Particular ECB S70 placed in the heating module 88 Installation, Start-Up, Adjustment and Maintenance Manual

Operation and management control The display of the electronic control board S61, during normal operation, keeps visualizing, alternatively the following information (in 2 pipe version, only the information on the functioning module are alternatively shown: or Chiller or Heater): Cold water inlet temperature (after the symbol ) Cold water outlet temperature (after the symbol ) Cold water temperature difference (after the symbol ) Hot water outlet temperature (after the symbol ) Hot water inlet temperature (after the symbol ) Hot water temperature difference (after symbol ) For example, the information ( ), indicates that the cold water outlet temperature is equal to 44,6 F). If anomalies are found, the electronic control board will show them on the display and will visualize the relative flashing unit codes. (i.e. ). Until the unit code is not deactivated, display will show the unit code 0 flashing. When there are more than one unit code deactivated, they will be visualized in alternative mode and flashing. To enter the menu of electronic control board (visualization menu) it is sufficient pushing once its ENCODER: on the display the 1st Menu Item wiill be visualized (Menu 0, that is ). NOTE If any information (Menu, Menu Item, parameters and/or values, etc.) is visualized on the display in flashing mode, it means that this information is available or, to the contrary, this information couldn t be entered. When an information is not available, the display visualizes:. By rotating the encoder all the other menu will be visualized on the display. To exit and return to the precedent level, it is necessary to select the letter E ( ) by pressing the encoder. To enter in menu and visualize menu entries it s necessary to stop on the desired menu and press the encoder: on the display the first menu entry of the same menu will be visualized. NOTE The menu entries will be identified on the display of the electronic control board through a number, where its maximum value is 3 digits (lined up at right). The visualization is characterized by the presence (on the 1st digit of display) of the menu identification number (example : indicates entry 0, menu 0; indicates menu entry 2, menu 0). By rotating the encoder, all the other menu entries of the same menu will be visualized on the display. To exit and return to the precedent level (default visualization), it is necessary to select the letter E ( ) by pressing the encoder. Installation, Start-Up, Adjustment and Maintenance Manual 89

MENU DESCRIPTION The electronic control board presents nine menu (from 0 to 8), as follows: Menu 0: Data Visualization Menu 1: Menu 2: Menu 3: Menu 4: Menu 5: Menu 6: Menu 7: Menu 8: Parameter Visualization Actions End User Adjustment Adjustment (by Installer) Adjustment (by Assistance Centers) Unit Type Adjustment (by Assistance Centers) Digital Inlet Visualization Set Password (not manageable) E : Exit Table 34 S61 MENUS MENU 0, 1 and 7 are Visualization Menu (data and parameters are read-only). In menu 0 it s possible to visualize the unit operation data detected from the electronic control board; In menu 1 it s possible to realtime visualize the unit operation data and the unit management. In menu 7 a number will represent the state of digital Inlet. MENU 2 is an Execution Menu ; through this menu it s possible execute actions like reset ignition control box and reset errors, as consequence of anomalies detected by the unit. The code will be visualized on the display of the electronic control board. MENU 3, 4, 5 e 6 are Adjustment Menu, to adjust the contained information. Menu 3 is relative to the enduser, who can eventually (if allowed) modify the value of parameters; an example are cold water set point and the water temperature difference setup. MENU 4, 5 e 6 are only to be managed by Robur Technical Assistance authorized Centers (TAC). NOTE The electronic control board has three fuses for circuit protection. If the electronic control board does not start up or the condenser fan does not run, remove power from the unit and check the condition of the fuses. The S61 board requires a 10A (condenser fan) and two 2A fuses (electrical board). The size of the fuse is labeled on the electronic control board next to the respective fuse holder. WARNING The maximum current carrying capacity of the N.O. Contact is 4A. Refer to Section 5.2, Pump Wiring. 90 An isolation relay MUST be used to separate the UNIT transformer from additional equipment having a transformer or damage to the S61 board will occur. Refer to Section 5.3, Control Switch Wiring. IGNITION CONTROL BOX WARNING When power is supplied to the unit (to the R terminal on the ignition control box), ignition control will reset, perform a self check routine, flash the diagnostic LED, and enter thermostat scan state. When the control switch is closed, the electronic control board will energize the ignition control box starting the ignition sequence (24 volts applied to the W terminal on the ignition box). Installation, Start-Up, Adjustment and Maintenance Manual

The ignition control box will check the differential air pressure switch for open contacts. - If the differential air pressure switch contacts are closed and stay closed for 30 seconds, an air flow fault will be appear The diagnostic LED on the ignition control box indicates this fault. In this mode, the ignition control box pre-mixer blower will not start. If the pressure switch contacts are open, the ignition control box pre-mixer blower will instead start. - An air flow fault will occur if the air pressure switch contacts remain opened for 30 seconds after the pre-mixer blower start. The diagnostic LED on the ignition control box indicates this fault. In this mode, the ignition control box will keep the pre-mixer blower energized. If the air pressure switch contacts close after the pre-mixer blower starts (normal operation), a pre-purge delay begins and the ignition sequence continues. Next, the ignition control box energizes an ignition transformer that generates a high intensity spark at the igniter to ignite the gas/air mixture. Simultaneously, the gas valve is energized, allowing the flow of gas to the burner. As soon as the ignition period ends, the flame sensor checks for flame presence. If the flame is detected, the gas valve and pre-mixer blower remain energized. Should the burner fail to light, flame is not detected during the first trial for ignition: the gas valve and ignition transformer are de-energized and the ignition control box begins an inter-purge delay before another ignition attempt. The control will attempt two additional ignition trials (total of 3 ignition trials) before going into lockout. In lockout, the gas valve will de-energize immediately and the pre-mixer blower will turn off. Ignition control box requests a reset operation to restart. The thermostat ( W terminal), air pressure switch and burner flame are constantly monitored to assure proper system operation. When the call for heat has ended (24 volts removed from W terminal on ignition control), the gas valve is de-energized immediately. The ignition control then senses loss of flame and de-energizes the pre-mixer blower. To reset the CHILLER SIDE ignition box from menu2: - To enter menu2, proceed as indicated above. - In menu2, push the encoder on menu signal 0 to enter the reset ignition control box option, visualized by the flashing code res0 ( ); push the encoder to confirm the reset operation. - After confirmation, the display visualizes again the menu signal. - To exit, select the letter E ( ) and push the encoder. To reset the HEATER SIDE ignition box from menu2: - To enter menu2, proceed as indicated above. - In menu2, push the encoder on menu signal 0 to enter the reset ignition control box option, visualized by the flashing code res0 ( ); push the encoder to confirm the reset operation. - After confirmation, the display visualizes again the menu signal. - To exit, select the letter E ( ) and push the encoder. FC± DIAGNOSTIC LED R TERMINAL W TERMINAL Figure 54 - IGNITION CONTROL BOX Installation, Start-Up, Adjustment and Maintenance Manual 91

TABLE OF OPERATING CODES GENERATED BY ELECTRONIC BOARD (firmware version 3.027) COLD MODULE U 1 GENERATOR THERMOSTAT LIMIT TEMPERATURE CODE GENERATED BY: CODE GENERATED WHEN: HIGH temperature detected by limit thermostat on body of generator. Reset limit thermostat manually: AYF operation will be restored automatically when the cause ceases. E 1 GENERATOR THERMOSTAT LIMIT TEMPERATURE Code U 1 is active for 1 hour, or U 1 intervenes 3 times in 2 hours of operation. Contact ROBUR TAC. U 2 CODE GENERATED BY: EXHAUST FUMES THERMOSTAT HIGH temperature detected by exhaust fumes thermostat. Reset occurs automatically when the condition that generated the code ceases. E 2 EXHAUST FUMES THERMOSTAT CODE GENERATED WHEN: code U 2 is active for 1 hour, or generated 3 times in 2 hours of operation. Reset may be performed via DDC (or via S61 board via menu 2, menu item 1). If codes U 2 and/or E 2 occur again, contact ROBUR TAC. U 3 COLD WATER ANTIFREEZE THERMOSTAT CODE GENERATED BY: LOW temperature detected by cold outlet water sensor. Reset occurs automatically when the condition that generated the code ceases. U 4 INADEQUATE VENTILATION / CONDENSER OVERHEATING CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED BY: (TCN - TA) values > limit set. Reset occurs automatically 20 minutes after the code is generated. E 4 INADEQUATE VENTILATION / CONDENSER OVERHEATING Code U 4 is generated twice in 2 hours of operation. Carry out appropriate checks. Reset may be performed via DDC (or via S61 board, menu 2, menu item 1). If the code persists, contact ROBUR TAC. E 5 HIGH AMBIENT TEMPERATURE HIGH temperature detected by ambient temperature sensor. Reset occurs automatically when the condition that generated the code ceases. E 6 LOW AMBIENT TEMPERATURE LOW temperature detected by ambient temperature sensor. Reset occurs automatically when the condition that generated the code ceases. 92 Installation, Start-Up, Adjustment and Maintenance Manual

U 7 HIGH CONDENSER INLET TEMPERATURE CODE GENERATED BY: HIGH temperature detected by condenser inlet temperature sensor (T> limit set: menu 1, menu item 66) Reset occurs automatically when the condition that generated the code ceases. CODE GENERATED WHEN: E 7 HIGH CONSENSER INLET TEMPERATURE Code U 7 is active for 1 hour, or U 7 code is generated 12 times in 2 hours of operation. (with central flame control unit on) E 8 FLAME CONTROL UNIT ERROR CODE GENERATED BY: Code E12 on cold module and condenser inlet temperature increasing by over 18 F (10 C) within 1 hour. Carry out appropriate checks. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED BY: U 10 COLD WATER FLOW SWITCH: insufficient chilled water flow Insufficient cold water flow rate (circulator on and flow switch open). Reset occurs automatically when correct flow rate is restored. E 10 COLD WATER FLOW SWITCH: insufficient chilled water flow Code U 10 is generated 5 times since appliance was powered, or code U 10 is active for two hours. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. U 11 INSUFFICIENT ROTATION OF OIL HYDRAULIC PUMP Insufficient rotation of oil hydraulic pump. Reset occurs automatically 20 minutes after the code is generated. E 11 INSUFFICIENT ROTATION OF OIL HYDRAULIC PUMP code U 11 is generated twice in 2 hours of operation. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. Failure of burner to ignite. U 12 FLAME CONTROL UNIT ARREST Reset occurs automatically when the electrovalve opens again (new attempt at ignition) or after code is active for 5 minutes. Flame arrest signal. E 12 FLAME CONTROL UNIT ARREST Reset may be performed via DDC (or S61 board via menu 2, parameter 0). If the code persists, contact ROBUR TAC. Installation, Start-Up, Adjustment and Maintenance Manual 93

CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED WHEN: E 16 OUTLET WATER TEMPERATURE SENSOR DEFECTIVE Fault (interruption or short circuit) on outlet water temperature sensor. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. E 17 COLD INLET WATER TEMPERATURE SENSOR DEFECTIVE Fault (interruption or short circuit) on condenser inlet water temperature sensor. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. E 18 CONDENSER OUTLET TEMPERATURE SENSOR DEFECTIVE Fault (interruption or short circuit) on condenser outlet temperature sensor. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. E 20 CONDENSER INLET TEMPERATURE SENSOR DEFECTIVE Fault (interruption or short circuit) on condenser inlet temperature sensor. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. E 28 GAS SOLENOID VALVE EXCITED WHEN THE FLAME CONTROL BOX IS LOCKED The flame control box is locked (E 12) but the gas solenoid valve is excited. In this case the flame control box is reset (E 12 resets) Reset may be performed from the DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised ROBUR TAC. U 29 GAS ELECTROVALVE WITHOUT ELECTRICAL POWER Gas electrovalve is off for 5 seconds (with central flame control unit on). Reset occurs automatically if the gas electrovalve switches on again within 10 minutes (with central flame control unit on). E 29 GAS ELECTROVALVE WITHOUT ELECTRICAL POWER CODE GENERATED WHEN: Code U 29 is active for more than 10 minutes (with central flame control unit on). Carry out appropriate checks. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. CODE GENERATED BY: U 32 WATER TEMPERATURE TOO LOW The warning appears when the water temperature is lower than the operational limits (cooling). Reset occurs automatically with 3.6 F hysteresis for all the units. 94 Installation, Start-Up, Adjustment and Maintenance Manual

U 51 ANTIFREEZE FUNCTION ACTIVATED COOLING MODULE Activation takes place only if the cold module is off and the antifreeze function is enabled (see menu 1, parameter 77). CODE GENERATED WHEN: Inlet or outlet water temperature of the cold module falls below 39.2 F (4 C - the code generated signals that the antifreeze function has been activated). In this case the antifreeze function activates the plant water circulator. Reset (deactivation of antifreeze function) occurs automatically when, with only the circulator on, the inlet and outlet water temperatures return to over 41 F (5 C - in this case the circulator switches off), or if the function itself is disabled. CODE GENERATED BY: CODE GENERATED: ELECTRONIC BOARD CODE GENERATED BY: U 77 COLD MODULE FLOW SWITCH "ON" (AYF/4 only) The flow switch of the cold module detects that water is present in the plant, when (and only in this situation) the appliance is configured as a 2-pipe cold-hot plant and the plant is operating in hot mode at that moment. The code (U 77) is disabled when the antifreeze function is active. Reset occurs automatically when the condition that generated the code ceases. E 78 HOT MODULE DIFFERENTIAL PRESSURE SWITCH "ON" (on AYF/2 only) If the plant is operating in cooling mode and the differential water pressure switch of the hot module is closed. Reset occurs automatically when the condition that generated the code ceases. Incomplete parameters. U 80 INCOMPLETE PARAMETERS The code remains active until operating parameters have been entered and completed. Contact ROBUR TAC. NB: If the board is replaced, code E80 may appear: this means that AY/AYF characterisation data has not been entered. CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED BY: E 80 INVALID PARAMETERS Invalid parameters or damage to parameter memory. Reset is automatic when the correct parameters are entered. If the code persists, contact the ROBUR TAC: if the parameters are incorrect, it is necessary to enter and complete the AY/AYF operating and characterisation parameters; if the memory is damaged it is necessary to replace the board. U 81 - U 82 INVALID BANK 1 DATA - INVALID BANK 2 DATA Invalid Bank 1 data - Invalid Bank 2 data. Reset occurs automatically 5 seconds after the code is generated. E 81 - E 82 INVALID BANK 1 DATA - INVALID BANK 2 DATA Invalid Bank 1 data - Invalid Bank 2 data. Reset may be performed via the S61/AY10 board via menu 2, parameter 1 or 21. If the code persists, contact ROBUR TAC. Installation, Start-Up, Adjustment and Maintenance Manual 95

U 83 SIMULTANEOUS ACTIVATION OF RY and RW CONTACTS (AYF/2 only) CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED WHEN: HOT MODULE CODE GENERATED BY: CODE GENERATED BY: Contacts RY and RW (of an AYF/2) are closed at the same time. Reset occurs automatically when at least one of the two contacts opens. If the code persists or occurs again, contact ROBUR TAC. E 84 FAULTY CONNECTIONS OF 24 Vac TRANSFORMER OR FUSES Damage to 1 of the 2 24-0-24 Vac input fuses or one of 24-0-24 Vac wires to the board not supplying current. Check 24-0-24 Vac fuses and electrical power connections on the board. Reset may be carried out via DDC (or via S61/AY10 board via menu 2, menu item 1 or 21). If the code persists or occurs again, contact ROBUR TAC. E 85 INCORRECT MODULE TYPES (from menu 6) The module type set (from menu 6) does not correspond to the one managed by the board. Reset occurs automatically when the correct parameters are entered. If the code persists, contact ROBUR TAC. Processor error. Contact ROBUR TAC. E 86 - E 87 - E 88 - E 89 MEMORY TEST UNSUCCESSFUL E 90 AMBIENT TEMPERATURE SENSOR DEFECTIVE Interruption or short circuit of ambient temperature sensor. Reset may be performed via DDC (or S61/AY10 board via menu 2, menu item 1 or 21). If the code persists, contact ROBUR TAC. E 91 BOARD DEFECTIVE One of the following is absent: serial number of board, hardware version code or encryption key written during board test. Contact ROBUR TAC. E 100 FAULT ON RESET CIRCUIT OF FLAME CONTROL UNIT Fault on reset circuit of flame control unit. Contact ROBUR TAC. E 101 MANUAL RESET LIMIT TEMPERATURE THERMOSTAT HIGH temperature detected by limit thermostat on body of generator. The event is detected only when the central flame control unit is on and the gas electrovalve is receiving power (the thermostat is connected in series with the electrovalve power supply). Contact ROBUR TAC. 96 Installation, Start-Up, Adjustment and Maintenance Manual

CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED WHEN: CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED: CODE GENERATED: CODE GENERATED BY: CODE GENERATED BY: U 102 EXHAUST FUMES THERMOSTAT HIGH temperature detected by exhaust fumes limit thermostat. Reset the exhaust fumes thermostat manually: reset of AY/AYF occurs automatically when the condition generating the code ceases E 102 EXHAUST FUMES THERMOSTAT Code U 102 persists for 1 hour, or is generated 3 times in 2 hours of operation. Contact ROBUR TAC. The S70 board is not present. E 103 ELECTRONIC BOARD FOR HEATING (S70) Reset is automatic and occurs when the condition that generated the code ceases to apply. If the code persists, contact ROBUR TAC. E 105 HIGH AMBIENT TEMPERATURE HIGH temperature detected by ambient sensor. Reset is automatic and occurs when the condition that generated the code ceases to apply. E 106 LOW AMBIENT TEMPERATURE LOW temperature detected by ambient sensor. Reset is automatic and occurs when the condition that generated the code ceases to apply. U 107 WATER PRESSURE SWITCH OF HOT CIRCUIT (AY and AYF 4-PIPE TYPE ONLY) If the plant is operating in cooling mode and the water differential pressure switch of the hot module (of an AY or AYF/4 unit ) is closed. Reset is automatic and occurs when the condition that generated the code ceases to apply. E 108 FLOW SWITCH OF COOLING MODULE (AYF 2-PIPE TYPE ONLY) If the plant is operating in heating mode and the water flow switch of the cold module (of an AYF/2) is closed. Reset is automatic and occurs when the condition that generated the code ceases to apply. If the code persists, contact ROBUR TAC. Failure of burner to ignite. U 112 CENTRAL FLAME CONTROL UNIT ARREST Reset is automatic and occurs when the electrovalve is opened again (when a new attempt to ignite the burner is made), or after the code is active for 5 minutes. Flame arrest signal. E 112 CENTRAL FLAME CONTROL UNIT ARREST Reset can be performed via DDC (or S61/AY10 electronic board via menu 2, parameter 20). If the code persists, contact ROBUR TAC. Installation, Start-Up, Adjustment and Maintenance Manual 97

CODE GENERATED BY: CODE GENERATED WHEN: E 128 GAS SOLENOID VALVE EXCITED WHEN THE FLAME CONTROL BOX IS LOCKED The flame control box is locked (E 12) but the gas solenoid valve is excited. In this case the flame control box is reset (E 12 resets). Reset may be performed from the DDC (or from the S61 board via menu 2, parameter 21). If the code persists, contact authorised ROBUR TAC. U 129 GAS ELECTROVALVE WITHOUT ELECTRICAL POWER Gas electrovalve is off for 5 seconds (with central flame control unit on). Reset occurs automatically if the gas electrovalve switches on again within 10 minutes (with central flame control unit on). E 129 GAS ELECTROVALVE WITHOUT ELECTRICAL POWER CODE GENERATED WHEN: Code U 129 is active for more than 10 minutes (with central flame control unit on). Carry out appropriate checks. Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact ROBUR TAC. CODE GENERATED BY: CODE GENERATED BY: CODE GENERATED WHEN: CODE GENERATED BY: U 131 WATER TEMPERATURE TOO HIGH The warning appears when the water temperature is higher than the operational limits (heating). Reset occurs automatically with 3.6 F hysteresis U 175 WATER DIFFERENTIAL PRESSURE SWITCH insufficient hot water flow rate Insufficient hot water flow rate. The code is generated if, on the hot module, the circulator is on and the water differential pressure switch is open. Reset occurs automatically when the correct water flow rate is restored or if the circulator switches off. E 175 WATER DIFFERENTIAL PRESSURE SWITCH - insufficient hot water flow rate Code U 175 occurs 5 times since appliance was powered, or code U 175 is active for 2 hours. Reset can be performed via DDC (or S61/AY10 electronic board via menu 2, parameter 21). If the code persists, contact ROBUR TAC. E 176 HOT OUTLET WATER TEMPERATURE SENSOR DEFECTIVE Fault (interruption or short circuit) on hot outlet water temperature sensor. Reset may be performed via DDC (or S61/AY10 board via menu 2, parameter 21). If the code persists, contact ROBUR TAC. E 177 HOT INLET WATER TEMPERATURE SENSOR DEFECTIVE CODE GENERATED BY: Fault (interruption or short circuit) on inlet water temperature sensor. Reset may be performed via DDC (or S61/AY10 board via menu 2, parameter 21). CODE GENERATED BY: U 178 HIGH HOT OUTLET WATER TEMPERATURE High hot outlet water temperature. Reset is automatic and occurs when the condition that generated the code ceases to apply. 98 Installation, Start-Up, Adjustment and Maintenance Manual

U 179 ANTIFREEZE FUNCTION ACTIVATED HEATING MODULE The antifreeze function is activated only if the hot module is off and the antifreeze function is enabled (see menu 1, parameter 163) CODE GENERATED WHEN: The temperature of inlet water to the hot module falls below 39.2 F (4 C - the code generated indicates that the antifreeze function has been activated). In this case the antifreeze function activates the plant water circulator. If the same temperature falls further to below 37.4 F (3 C - the antifreeze function also switches on the central flame control unit. Reset (deactivation of the antifreeze function) is automatic and occurs if, with only the circulator on, the temperatures of hot inlet and outlet water return to over 41 F (5 C - in this case the circulator switches off), or, if also the flame control unit has been switched on, the same temperature reaches 64.4 F (18 C - in this case the flame control unit and then the circulator switch off). Table 35 - Operating codes generated by S61/AY10 electronic board (codes may also be visualised by DDC display). IN TABLE, TAC = TECHNICAL ASSISTANCE CENTRE (the manufacturer s authorized Service Technicians or authorized Service Engineer). Installation, Start-Up, Adjustment and Maintenance Manual 99

LEFT SIDE OF COMBUSTION CHAMBER 1 NOTE: SOME DETAIL HAS BEEN REMOVED FOR CLARITY 1 2 IGNITION TRANSFORMER IGNITION CABLES 3 3 FLAME SENSOR 2 4 5 4 ANTI-SPARK INSULATORS 5 IGNITER 6 6 IGNITER GASKET FIGURE 55 CHILLER SIDE: IGNITION TRANSFORMER, IGNITER ASSEMBLY AND FLAME SENSOR 100 Installation, Start-Up, Adjustment and Maintenance Manual

1 3 5 4 2 6 1 IGNITION TRANSFORMER 2 IGNITION CABLES 3 FLAME SENSOR 4 ANTI-SPARK INSULATOR 5 IGNITER 6 IGNITER GASKET FIGURE 56 HEATER SIDE: IGNITION TRANSFORMER, IGNITER ASSEMBLY AND FLAME SENSOR Installation, Start-Up, Adjustment and Maintenance Manual 101