APPLICATION GUIDELINES STEAM MAIN DRAINAGE

Similar documents
Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

WATER HAMMER something that never should occur in a steam system

Steam System Best Practices Document No. 11

How to Trap: Installation and Testing

Steam Trap Selection

Installation and Testing of Inverted Bucket Steam Traps Manual

How to Trap: Steam Tracer Lines

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

How to Trap: Trap Selection and Safety Factors

Hoffman Specialty General Catalog

Why steam trap survey?

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems

Liquid Drainers LIQUID DRAINERS

The. Steam ONE-PIPE STEAM SYSTEMS

Boiler Steam Supply Piping Basics November 18, ) Q: What kind of condensate traps should be used on vacuum condensate return systems?

The. Steam TWO-PIPE STEAM & PUMPED RETURN

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT

How to Trap: Troubleshooting

Efficient Steam System Design

How to Trap: Process Air Heaters

STEAM CONSERVATION GUIDELINES

How to Trap: Conversion Factors

How to Trap: Rotating Dryers Requiring Syphon Drainage

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

Inverted Bucket Steam Traps. for efficient condensate drainage of industrial and HVAC equipment

Economical and simplified solutions that offer quality and optimum steam trap service.

Bringing Energy Down to Earth

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

ANNEX 6. Refinery No. 1 New Area. Problems Existing in the Current Condensate Return System of the New Area of Refinery No.1

What is a Secondary Pressure Drainer?

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

Chapter 2.3: Steam System

Installation and Maintenance "L" and "LS" Series

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

Silhouette. Feedwater Heater. Boiler Feedwater

STAINLESS STEEL TRAP VALVE STATION

BASICS OF STEAM TRAPS BASICS OF STEAM TRAPS

NICHOLSON STEAM TRAP THERMODYNAMIC STEAM TRAPS

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Steam Conservation Guidelines for Condensate Drainage Steam Trap Sizing and Selection.

TEACHER BACKGROUND INFORMATION Water Cycle

A M E M B E R O F T H E K E N D A L L G R O U P

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

Bringing Energy Down to Earth

IMPROVING EFFICIENCY AND QUALITY USING A PERMANENT ORIFICE STEAM TRAPPING SYSTEM

THERMODYNAMIC STEAM TRAPS

Steam Traps and Steam Specialties

Steam Trap Inspection Methods And Steam Cost Analysis

STEAM AND TRAP FUNDAMENTALS

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

APPLICATION DATA SHEET

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS

COOLING / HEATING COILS

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

LIQUIDATOR UMT-TD Series Thermodynamic

THE THERMOSTATIC STEAM TRAP

Impact of Failed Steam Traps on Process Plants - Food and Beverage

10/29/01,2:16 PM TUNNEL WARM-UPPROC4--HIGHLITED REQUIRED ACTIONS.DOC KIRSNER CONSULTING ENGINEERING

Installation and Operation

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

Circuit SolverTM THERMOSTATIC RECIRCULATION VALVE FOR DOMESTIC HOT WATER SYSTEMS.

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass

Bringing Energy Down to Earth

UNIVERSAL STYLE STEAM TRAPS WU450 Series

Steam Conservation Guidelines for. Drainage. Mead O'Brien (800) LP Steam. Condensate. HP Steam RECEIVER TANK HEATER

Armstrong ExpressPack Multi-Tube Steam Dispersion Panel Assembly and Installation Instructions

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

Steam Systems 101. Understanding Your Energy Systems Better. May 5, 2016

PIP PNE00004 Steam Trap Guidelines

INSTALLATION, OPERATION

Landfill & Digester Gas Dryers. Features and Benefits

An Approach to Energy Efficiency: A Focus on an Increased Operational Efficiency, Natural Resource Conservation and Carbon Footprint Reduction

.03 ATMOSPHERIC DEAERATOR

Exceeding Expectations

PRODUCTS. Expansion Joints Fire Fighting. Flexible Metal Hoses. Equipments. Insulation Solutions. Steam. Valves. Level Control.

Pamphlet A2404. Mechanical Pump & Pump/ Trap. GP Series GT Series

Kirsner Consulting Engineering, Inc. for BP 4/19/2010. Chapter 10. Water in Steam Lines (This is the BP title in existing Manual)

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

LIQUIDATOR 450 SERIES

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS

THERMODYNAMIC STEAM TRAPS

ANAEROBIC DIGESTERS HEATED BY DIRECT STEAM INJECTION: EXPERIENCE AND LESSONS LEARNED

Technical Data CONDENSATE COMMANDER PUMP SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 9902D

Blowdown Separator & Aftercoolers Installation, Operation, & Maintenance

HEAT EXCHANGER FORMULAS & EXAMPLE

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

.005 ATMOSPHERIC DEAERATOR

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Function of the FENIX Hydrodynamic Trap working on Variable Load Applications

Transcription:

APPLICATION GUIDELINES STEAM MAIN DRAINAGE

1) Steam Main Drip Leg Dimensions 2) Types of Warm-Up a) Supervised b) Automatic 3) Spacing of Drip Legs 4) Low Pressure Drainage-- Sizing Traps for Automatic Warm Up 5) Trap Types 1) Steam Main Drip Leg Dimensions In order to trap your system mains, some important dimensions should be considered when designing the system. Drip legs are the key to successful, water hammer free, system start-up. Drip Legs: a) Let condensate escape by gravity from the fast moving steam. The properly sized drip leg acts as a separator by providing an increase in flow area, which slows the steam flow down allowing the condensate to drop out. This is important during operation as well as start-up. During operation steam velocities can approach 150 miles (241 kilometers) per hour. Condensate that is carried along at this velocity will not be drained easily unless the velocity is reduced. Therefore, drip leg diameter must be large enough to create the separator effect by reducing velocity. Once the system is up to pressure the large drip leg keeps the condensate from being sucked out of the drip leg. This can happen when high velocity steam moves across the opening to a small drip leg causing a piccolo effect. The high velocity gas experiences a pressure drop, which will cause condensate to be sucked out of a small pipe. A large drip leg does not experience this pressure drop and therefore able to collect and discharge condensate. b) Store the condensate until the pressure differential is great enough for the steam trap to discharge it. On start-up cold piping causes steam to collapse and pressure to drop. This causes a very high condensate load for the trap to handle, but with virtually no pressure for the trap to use in discharging the condensate. This is compounded when the condensate line is located above the steam line. So, rather than flood the steam main, a large drip leg gives the water a place to accumulate until the pressure is sufficient for the trap to handle the accumulation. 2 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

General: The selection of drip leg sizes to drain steam mains depends on the warm-up method that will be used: Figure 1 Steam Mains Steam Main M Steam Main M D Drip Leg H D Drip Leg Drain Valve Steam Trap Drain Valve Steam Trap Table 1 Recommended Drip Leg Sizing M D Drip Leg Length Steam Main Size Drip Leg Diameter Supervised Warm-Up Automatic Warm-Up in mm in mm in mm in mm 1/2 12.7 1/2 12.7 10 254 28 711.2 3/4 19.05 3/4 19.05 10 254 28 711.2 1 25.40 1 25.40 10 254 28 711.2 2 50.8 2 50.8 10 254 28 711.2 3 76.2 3 76.2 10 254 28 711.2 4 101.6 4 101.6 10 254 28 711.2 5 127 4 101.6 10 254 28 711.2 6 152.4 4 101.6 10 254 28 711.2 8 203.2 4 101.6 12 304.8 28 711.2 10 254 5 127 15 381 28 711.2 12 304.8 6 152.4 18 457.2 28 711.2 14 355.6 8 203.2 21 533.4 28 711.2 NOTES: 1. Drain valve is required for supervised start-up only. Drain valve needs heat tracing or insulation on outdoor installations where freezing is possible. 2. Steam traps are shown in the piping set-ups: side-in, side-out or bottom-in, top-out. On supervised start-up, the H dimensions is to the top of the trap or the top of the drain piping, whichever is higher. Either trap type can be used. 3. Drip leg piping should always follow the D dimension. The take-off to the trap can be the same connection as the trap. We are constantly asked for a 3 (80 mm) trap to drain a 3 (80 mm) line. A 3 (80 mm) trap is grossly oversized, and a 3/4 (20 mm) trap will work better, because it is sized for the load. 4) Static pressure head H must always be positive on automatic warm-up. 16 406.4 8 203.2 24 609.6 28 711.2 18 457.2 10 254 27 685.8 28 711.2 20 508 10 254 30 762 30 762 24 609.6 12 304.8 36 914.4 36 914.4 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 3

2) Types of Warm-Up: a) Supervised Warm-Up: is widely used for initial heating of large diameter above 8 (20 cm) or long more than 1000 ft (304 m) mains. Such mains may be warmed up only once in a lifetime. The drain valves for free flow to the atmosphere are opened wide before steam is admitted to the main. These drip valves are not closed until after all or most of the warm-up condensate has been discharged. The the trap is opened and can take over the job. A supervised warm-up will not need such a long drip leg, because only operating load condensate will be removed automatically by traps, and the condensate load will stay about the same. (Warm-up of principal piping in a power plant will follow the same procedure.) b) Automatic Warm-Up: In this case, the boiler is fired, letting the mains and some or all equipment come up to pressure and temperature without manual help. This kind of warm-up is used more for occasional steam use or steam system shutdown every night, weekend, or seasonally. In this case, you will need a bigger drip leg because the condensate load handled by the trap will be much greater, due to the start-up load. At start-up a high condensate load occurs at low pressure. Once up to temperature there will be less condensate at high pressure. In this type of warm-up, the steam trap will discharge all the condensate, because there are no manual drain valves. 3) Spacing of Drip Legs: Drip legs and drain traps should be provided at intervals no longer than 500 ft (75 m) because steam main condensate should be drained while it is a heavy dew rather than a dangerous slug. 4) Low Pressure Drainage -- Sizing Traps for Automatic Warm-up: A static head dimension is used only on automatic warm-up because we have two pressure conditions. Start-up low pressure and operating high pressure. During start-up the trap is discharging condensate because of the static head dimension. Condensate can be discharged during the warm-up only because the static head pushes condensate through the trap. Generally, a trap that can handle the line s running load can also handle the start-up load as long as the line is heated no faster than 200 F (93 C) per hour. The traps s capacity is actually quite high at cold start-up conditions because: 1. Cold condensate does not flash when discharged. The flashing causes flow to be choked off when being discharged from the orifice. 2. Cold water is more dense than hot (by more than 10%) so more pounds per hour are able to pass through the fixed orifice in the trap. To check trap capacity you must know: 1. The total warming up load (see Armstrong Conservation Guidelines, Table CG-1: Warming Up Load). 2. The time period over which warm-up takes place. 3. The static head dimension H. 4 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

Divide the head dimension by 28(H/28) to get psi. Then divide the warming up load by the start-up time (in hours) to get lbs. per hour. Table 2 lists orifice capacities at these very low pressures. If your pressure is not listed, do not interpolate. Capacities can be approximated using this equation: C 1 = C 2 x P 1 P 2 Where: C1 = Unknown capacity (#/hr) at actual pressure (P1) P1 = Actual pressure in psi P2 = Pressure from chart C2 = Capacity from chart Table 2 Orifice Capacities at Low Pressures. Use only for sizing traps for automatic warm-up. Pressure Orifice 0.5 0.07 1 1.014 2 0.28 psig barg psig barg psig barg Pounds (kg) per hour 5/64 37 16.78 52 23.59 71 32.21 No. 38 49 22.23 69 31.30 121 54.89 7/64 73 33.11 103 46.72 140 63.50 1/8 94 42.64 134 60.78 182 82.56 5/32 148 67.13 209 94.80 284 128.82 3/16 214 97.07 302 136.99 410 185.98 7/32 291 132.00 411 186.43 559 253.56 1/4 379 171.91 535 242.68 728 330.22 9/32 482 218.64 680 308.45 925 419.58 5/16 595 269.89 841 381.48 1145 519.37 11/32 715 324.32 1010 458.14 1370 621.43 3/8 851 386.01 1205 546.59 1640 743.90 7/16 1160 526.18 1640 743.90 2230 1011.53 1/2 1515 687.20 2140 970.70 2910 1319.98 9/16 1875 850.50 2650 1202.04 3600 1632.96 5/8 2375 1077.30 3350 1519.56 4550 2063.88 3/4 3100 1406.16 4160 1886.98 5400 2449.44 7/8 4225 1916.46 5700 2585.52 7250 3288.60 1 1/16 6240 2830.46 8400 3810.24 10700 4853.52 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 5

5) Trap Types We recommend the use of inverted bucket steam traps because this kind of trap works on the density principle thereby discharging condensate as soon as it reaches the trap. Another advantage of the inverted bucket traps is that they fail open, so, incase of trap failure, the main won t flood. 6 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

Notes 7

INTELLIGENT SOLUTIONS IN STEAM, AIR AND HOT WATER Armstrong International Armstrong Steam and Condensate Group, 816 Maple St., Three Rivers, MI 49093 USA Phone: (269) 273-1415 Fax: (269) 278-6555 2017 Armstrong International, Inc. APP-504-EN Printed in USA - 5/17