PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Similar documents
3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Fire Alarm Control Panel. System Maintenance and Log Book

User Operation Manual

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

USER MANUAL & MAINTENANCE GUIDE OG OO

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

Control Panel User Guide

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Control Panel User Guide (TO BE RETAINED BY THE USER)

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

FIRE ALARM CONTROL PANEL FVC01-08

SYSTEM 5000 USER MANUAL

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Application, Installation, Operation & Maintenance Manual

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Installation, Operating and Maintenance Manual

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

The EN54 Part 2 and 4 Fire System

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

USER MANUAL CEF AP28 CONTROL PANEL

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

GAS SUPRESSION CONTROL PANEL:

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. approved document no. DFU Rev 1

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Functional Performance Test

Document No Issue 4 user manual

Control Panel User Guide

Security System. User s Guide for the Text Command Center

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

New Silent Alert Fire Safe System

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Operating instructions Vigilon panel and Network node Fire detection and alarm system

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

SFC-200 SERIES LED FIRE ALARM PANEL

Intelligent Security & Fire Ltd

ZP3 Operator & Maintenance Manual Version 1

Intelligent Security & Fire Ltd

SECURIT 703 USER MANUAL

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

SECURIT 700L USER MANUAL

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

user manual Document No , Revision 03 November 2015

MR-2602 Two Zone Fire Alarm Control Panel

user manual and log book XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

SYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996

System 800 Addressable Fire Detection & Alarm System

Security System. User Guide for the LED Command Center

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire detection and alarm system Operating instructions

NX-148 LCD CODE PAD TABLE OF CONTENTS

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

DYCU-3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL

Control Panel Engineering and Commissioning Instructions

TS400 & TS410. Intruder Alarm Control Panels. Operating Instructions

TS2500. Intruder Alarm Control Panel. SYSTEM OPEN 17:30 01 Jan ENT ESC. Setting the System. Unsetting the System RE SET

ID2000. operating manual

Control/Communicator Installation Manual

Solution Ultima Series Operators Manual ISSUE 1.00

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

OPERATION AND INSTALLATION MANUAL

Contents. Glossary Introduction to the IDS Notes Understanding the Keypad Indicators Operation of the Keypad...

FEC403EN Installation Manual

Fire detection and alarm

Alarm Control Panel WIC-16Z4P WIC-5Z2P. User Instructions

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

Digiplex LED Keypads User s Manual

EXTINGUISHING AGENT RELEASE MODULE

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

IDS800 USER MANUAL. Summary of Operation. + [ ] 2 IDS800 USER MANUAL NO K ISSUED APR 2003 VER 1.44

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES

Transcription:

PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description 2 2. OPERATING INSTRUCTION 2.1. Normal Operating Conditions 3 2.2. Fire Alarm Condition 3 2.1.1. Silencing the Alarm 4 2.1.2. Electrical Manual Activation 4 2.1.3. Resetting the System 4 2.3. Fault Condition 4 2.3.1. Silencing the Fault 4 2.3.2. Resetting the System 4 2.4. Initiating Evacuate Alarm 5 2.4.1. Silencing Evacuate Alarm 5 2.5. Zone/Auxiliary Isolation 5 2.6. Indicators Test 5 2.7. Zone Detection & Extinguishing Control Module 6 2.7.1. Description of Indicators 6 2.7.2. Description of Control Switches 6 2.8. System Front Control Module 7 2.8.1. Description of Indicators 7 2.8.2. Description of Control Switches 7 3. EMERGENCY OPERATING INSTRUCTION 8 4. ROUTINE MAINTENANCE 4.1. Introduction 9 4.2. Maintenance Responsibilities 9 4.3. Operator Duties Log Book Entries 9 4.4. Routine Checks and Tests 9 4.4.1. Daily Checks 9 4.4.2. Weekly Checks 10 4.4.3. Monthly Checks 10 4.4.4. Annual Checks 12

Pg 2 of 12 1 GENERAL 1.1 Introduction This manual serves to provide only the basis operator s information on the operation of the Fire Extinguishing System. To ensure continuous reliability of the system, it is recommended that an agreement to carry out regular maintenance of the installation be made with a competent and qualified contractor trained to service and maintain this system. Arrangements should be made such that a qualified person is available on call to provide service in the event of any emergency arising at the installation. For more details on maintenance, please refer to the section on routine maintenance covered in this manual. 1.2 System Description This Fire Extinguishing System utilises the System 88 Fire Extinguishing Control Panel. The system comprises a Fire Extinguishing Control Panel, which perform the task of processing the input signals and thereafter transmit the output signals or initiates other auxiliary functions. The panel is usually sited outside the protected room prominent location clearly visible from the entrance. Input devices are used to cause a change in panel status. These devices may be the combination of Remote Electrical Manual Release Call Points, Remote Mechanical Release Control Switches (if provided), Heat/Smoke Detectors or Remote Abort Station. Output devices are used to provide an audio & visual warning. Output devices commonly used are alarm bells, electronic sounders, strobe light, Evacuate flashing sign and Gas Discharged flashing sign. These three components: Input Devices, Control Panel and Output Devices form the backbone of a Fire Extinguishing System. The detection system of Fire Extinguishing Systems operates on a Dual Risk Zone basis. These zones are groups of input devices grouped in accordance to the locality they are protecting. In the event of a Fire/Fault condition, the location where the signal had originated will be defined by the respective indication on the panel. It is therefore important to be familiar with the zoning of the protected area. A zoning diagram (or zone chart) is usually provided for this purpose. The Fire Extinguishing Control Panel is provided with a feature that continuously monitoring the continuity of the input/detection, output/sounder circuits and Electrical actuator circuits to ensure integrity of the system. It is also equipped with a battery back-up supply (lasting at least 24 hours) in the event of an incoming supply failure.

Pg 3 of 12 2 OPERATING INSTRUCTIONS 2.1 Normal Operating Conditions Under normal operating conditions a) The green POWER ON LED lighted b) Countdown timer display indicating the Pre-set time eg : 30 for 30 sec time delay before firing c) No other indicator should be lighted d) The panel should be completely silent e) All alarms should be silent 2.2 Fire Alarm Condition The detection configuration of the Fire Extinguishing System is arranged on a Dual Risk/Cross Zone basis. The 1 st detection will occur when any detector is activated. The 2 nd detection will occur when another detector connected to the other detection circuit of the same grouped zone is activated. 1 st Detection observations a) Twin red FIRE LEDs of the activated detection circuit lighted b) General, red FIRE LED lighted c) Alarm Sounder activated d) Evacuate Sign flashes e) Flashing light activated f) Fire signal to Main Alarm Panel activated g) 1 st detection Aux Relay activated 2 nd Detection observations a) Twin red FIRE LEDs of the other activated detection circuit lighted b) Electronic Sounder activated c) Gas Discharged Sign and red Actuator Fired LED flashes d) 2 nd detection Aux Relay activated e) Delay timer display "30" starts countdown Upon expiry of timer countdown (ie. 00 secs) a) Gas Discharged b) Gas discharged Sign and red Actuator Fired LED becomes steady c) Backlighted Gas Gone wording flashes TO INHIBIT DISCHARGE DURING COUNTDOWN a) Press green FIRING ABORT Switch

Pg 4 of 12 2.2.1 Silencing the Alarm To silence the alarm, carry out the following procedures; a) Press orange SOUNDER SILENCE Switch (After 3 minutes of alarm sounding) b) Built-in LED in switch lighted c) External sounders silenced d) To silence Buzzer, press yellow BUZZER SILENCE Switch e) Remaining intermittent Beep emitted at intervals of about 15 seconds f) Panel remains in alarm state until reset 2.2.2 Electrical Manual Activation To manually discharge the system via the control panel, press MANUAL RELEASE (Red) Gas discharge after time delay. 2.2.3 Resetting the System Before the system is reset, the cause of the alarm must be investigated and duly rectified. In the case of a false alarm, make sure that there is no incident of fire before resetting the system. a) Re-instate the affected devices to normal b) Press brown RESET Switch c) After resetting, the panel will resume to normal operating condition, assuming that there are no other events to cause another alarm and the original cause of the alarm being rectified. 2.3 Fault Conditions The panel is equipped with a self diagnostic feature that checks itself and indicates a wide range of possible faults. In the event of a fault the following will be observed; a) An amber LED of the respective zone fault lighted and/or b) An amber LED of the respective system fault lighted c) General, amber FAULT LED lighted d) Panel buzzer sounding 2.3.1 Silencing the Fault If the fault cannot be rectified, it may be silenced by carrying out the following: a) Press yellow BUZZER SILENCE Switch b) Built-in LED in switch lighted c) Panel buzzer silenced d) Reminding intermittent Beep emitted at intervals of about 15 seconds e) Panel remains in fault state until fault rectified 2.3.2 Resetting the System The cause of the fault should be investigated and rectified. If it is due to a mains supply failure, the system will normalise when the power supply resumes. Some faults are internal to the system and are not covered in this manual. The operator will have to contact the maintenance or service contractor. Once the fault(s) are rectified, the panel will reset itself.

Pg 5 of 12 2.4 Initiating Evacuate Alarm The operator can raise an evacuate alarm in the event of emergency from the panel by carrying out the following: a) Press red EVACUATE ALARM Switch b) Panel buzzer sounding c) External sounders sounding, Evacuate sign flashes, flashing light activated. 2.4.1 Silencing Evacuate Alarm To cut off the evacuate alarm; a) Release the red EVACUATE ALARM Switch b) External sounders silenced, Evacuate sign and flashing stop operation. 2.5 Zone/Auxiliary Isolations This function is executed when isolation of the respective zone(s) and/or auxiliary functions is intended. Zone isolation will render the respective zone(s) in-operative and will not be affected by the change in condition of the related input device(s). Note : It is not possible to perform a zone isolation when an alarm condition has already occurred in the respective zones. To carry out zone/auxiliary isolation: a) Press green ISOLATE or AUXILIARY ISOLATE Switch b) Built-in LED in switch lighted c) General, amber ISOLATED LED lighted d) Reminding intermittent Beep emitted at intervals of about 15 seconds e) Zone(s)/auxiliary function remains in isolated state until normalised 2.6 Indicators Test This is provided to test the working condition of the visible (LEDs) and audible (Buzzer) indicators a) Press the blue momentary INDICATORS TEST Switch b) Built-in LED in switches as well as all the LED indicators lighted and Buzzer sounds c) Release the switch to normalise Note : Upon activation of any control switches, reminding beeping remains until system normalised and reset.

Pg 6 of 12 2.7 Zone Detection & Extinguishing Control Module 2.7.1 Description of indicators a) Zone Fire (Red Twin) : Zone in fire condition b) Zone Fault (Amber) : Zone in fault condition (Line open / Line short) c) Actuator Fault (Amber) : Actuator fuse blown / actuator line open d) Actuator Fired (Red) : Actuator being fired e) Remote Abort Activated : Remote Abort station being activated (Amber) f) Pressure Low (Amber) : Storage pressure within cylinder is low g) Remote Manual Release : Remote Manual Release station being activated Activated (Red) h) Line Fault (Amber) : Remote Manual Release line / Gas Gone line open / short i) Count Down Timer (2 Digit No.) : Display remaining time for activation of actuator j) Gas Gone (Red Flashing) : System Gas been released 2.7.2 Description of Control Switches a) Zone Isolate Switch (Green) : To isolate zone detection circuit b) Manual Release (Red) : Manual activation for Gas discharge with Timer count down c) Firing Abort (Green) : To abort firing of Actuator, Timer reset to pre-set time d) Auxiliary Isolate (Green) : To isolate 1 st alarm and 2 nd alarm auxiliary control function e) Remote Manual Release : To isolate Remote Manual Release station input Isolate (Green) signal

Pg 7 of 12 2.8 System Front Control Module 2.8.1 Description of Indicators a) Power On (Green) : System energised by Mains and/or Standby Battery b) Fire (Red) : General Fire Indicator, system is in fire condition c) Fault (Amber) : General Fault Indicator, system is in fault condition d) Isolated (Amber) : General Isolated Indicator, system is in isolated condition e) Sounder Line Fault (Amber) : Alarm sounder line open/short (Note : It shall not be suppressed during Fire Alarm condition) f) Earth Fault (Amber) : Field input/output wires shorted to ground g) Mains Fault (Amber) : 230V AC Mains supply failure h) Charger fault (Amber) : Charger Fuse blown / charger voltage low / high i) Battery Fault (Amber) : Battery supply disconnected / battery fuse blown / battery voltage low / high 2.8.2 Description of Control Switches a) Sounder Silence (Orange) : To silence alarm sounder b) Buzzer Silence (Yellow) : To silence fault buzzer c) Spare : Spare control switch for future operation d) Evacuate Alarm (Red) : To raise alarm sounder manually for emergency evacuation e) Indicators Test (Blue) : To test the working condition of all LED indicators and buzzer f) Reset (Brown) : To normalise the system (Note: Silence alarm sounder before RESET)

Pg 8 of 12 3 EMERGENCY OPERATING INSTRUCTIONS IN THE EVENT OF AN ALARM Identify the location where the alarm had originated by referring to the zoning diagram. Proceed to the respective location to investigate the cause of the alarm. IF A FIRE IS DISCOVERED a) Call 995 to notify the Singapore Civil Defence Force immediately b) Try to control or extinguish the fire by using the fire hosereel or extinguisher. This should be done only when personal safety is not endangered. IF IT IS A FALSE ALARM a) Be very sure that there is no incident of fire b) Call the respective alarm monitoring company to notify them of the false alarm c) Silence the sounders by pressing the orange SOUNDER SILENCE Switch d) Silence the Buzzer by pressing the yellow BUZZER SILENCE Switch e) Re-instate the respective zone to normal f) Press the brown RESET Switch to re-instate the system to normal TO RAISE AN EVACUATE ALARM a) Press the red EVACUATE ALARM. Sounders will sound, Evacuate Sign flashes and flashing light activated immediately. b) To cut off, de-activate the same switch again IN THE EVENT OF A FAULT CONDITION The panel buzzer will emit a continuous warning with indication of the respective panel faults. a) Press the yellow BUZZER SILENCE Switch to silence the continuous warning. An intermittent Beep at intervals of about 15 seconds will be emitted to reming that a fault has been silenced. Note : This reminding Beep will continue until the panel has been normalised. b) The panel will reset itself when the fault is cleared. c) Notify the maintenance department or the respective maintenance contractor.

Pg 9 of 12 4 ROUTINE MAINTENANCE 4.1 Introduction In order to ensure safe and continuous reliability of the fire alarm system, it should be regularly tested and serviced. Routine testing and maintenance should only be carried out by competent personnel trained in this field and armed with the appropriate equipment to do the job. 4.2 Maintenance Responsibilities The owner of the fire alarm system is responsible for ensuring that it is correctly maintained so that it is in proper working conditions at all times. This will involve arranging for the system to be checked, tested and serviced in accordance with the requirements as described in the Singapore Standard CP 10 : 2005 Code of Practice for the installation and Servicing of Electrical Fire Alarm Systems. The recommendations covered in section 5.4 of this manual may conflict or may require additional tests/checks to be performed as imposed by the local authorities. Where such conflicts occur, the local authority regulation should be followed. 4.3 Operator Duties Log Book Entries The fire alarm system should have a log book associated with it, it is used to record details of all alarm (genuine, practice, test or false), faults, service tests and routine attention given. A format is recommended in CP 10 : 2005. The operator is responsible for recording all events raised by the system into the log book. The log book is an important record of the history of the system and should be kept up to date by the operator and the maintenance personnel. 4.4 Routine Checks and Tests The recommended maintenance procedures can be divided into the following categories : 4.4.1 Daily check 4.4.2 Weekly checks 4.4.3 Monthly checks 4.4.4 Annual checks 4.4.1 Daily Checks The following checks should be made everyday by the panel operator to ensure that the system is operating normally. a) Check that only the green POWER ON LED is lighted. All other indicators should be off and the panel completely silent. If a fault has occurred and the panel buzzer sounding, the appropriate indicator will light up b) Record the fault (s) detected c) Determine the area affected by the fault and decide whether special attention (such as fire patrols) are required in that area

Pg 10 of 12 d) Determine the reason for the cause of the fault or note the activities immediately prior to the cause of the fault in the area affected e) Silence the fault buzzer f) Inform the maintenance contractor responsible for servicing and arrange for repair 4.4.2 Weekly Checks Weekly checks may be made by the operator or by the maintenance or contractor responsible for servicing the installation. The following checks are recommended. a) Check that all LEDs/indicators are operational by carrying out a LAMP TEST as described in section 2.6 b) Isolate auxiliary functions as described in section 2.5 so as to prevent the initiation of the auxiliary functions c) Carry out a simulated fire alarm condition by activating any detector. Always activate a different zone each week to ensure a more uniform test on of the system. Note : It may be necessary to contact the alarm monitoring company prior to activating the alarm to warn them of the simulated fire condition being tested and also to check with the monitoring company after completion of test to ensure that the fire alarm signal was received and the system reset. d) Check that all sounders are working and the panel conditions as described in section 2.2 are observed e) Silence and reset the panel as described in section 2.2.1 and 2.2.4 f) Initiate the evacuate alarm as described in section 2.4 and normalise as described in section 2.4.1 g) Check the battery condition and the voltage reading by the use of a multimeter h) On completion of the above tests, ensure that all switches are in the correct operating position i) Rectify all faults (if any) immediately j) Record in the log book that the above tests has been conducted 4.4.3 Monthly Checks In addition to the weekly checks, the following inspection and testing procedures are to be carried out each month. Any corrective action that has not yet been taken should be noted and carried out. a) Simulate fire condition in all zones one by one. Silence and reset one zone followed by the next (similar to that as described in section 5.4.2.c). Check that all auxiliary functions are executed as according to that as intended during a fire situation. Reset system after this test.

Pg 11 of 12 b) Simulate fire condition in all alarm zones one by one. This time silence the activated zone followed by the simulation of a fire condition of the next zone. The alarm should resound whenever a new zone is set into alarm. Reset the system after this test. c) Remove the detector fuse. The buzzer should sound together with FAULT and amber LO indications lighted in all zones. The panel should be silenced when BUZZER SILENCE is activated. Replace detector fuse. System should normalise d) Short the detector line of all zones one by one. The buzzer should sound together with FAULT and red LS indications lighted at the respective zone. The buzzer should sound whenever a new zone is shorted. The buzzer should be silenced when the short is removed. e) Remove the bell line fuse. The buzzer should sound together with SOUNDER FAULT and both amber LO indications lighted. The panel should be silenced when BUZZER SILENCE is activated. Replace bell line fuse. System should normalise f) Isolate a zone in accordance to the procedures as described in section 2.5. Trigger a device in that respective zone. It should have no alarm effect on the panel. Normalise the isolated zone g) Check battery and terminals condition. If a wet type battery is used, check the specific gravity and level of the electrolyte. h) Disconnect the battery supply. The POWER ON and BATTERY FAULT indicators should be lighted and the buzzer sounding. Connect back the battery and system should normalise itself i) Switch off incoming mains supply. The POWER ON, MAINS FAULT and CHARGER FAULT indicators should be lighted and the buzzer sounding. The standby battery should take over the supply to the system. Resume the mains supply and system should normalise itself j) Check earth leakage function by applying a short between the positive leg of the detector line and earth (chassis). The buzzer should sound together with EARTH FAULT and red + indications lighted. Repeat, using the negative leg of the detector line. The buzzer should sound together with EARTH FAULT and amber - indications lighted. k) Check that the panel is in a clean and operative condition l) Visually inspect the condition of the components, terminations and cables m) Ensure that all faulty components are properly replaced n) Record in the log book any circuit that require repair and arrange accordingly o) Ensure that all switches are in the correct operation position p) Record in the log book that the above tests has been conducted

Pg 12 of 12 4.4.4 Annual Checks The annual checks should include all the inspections and testing as described in sections 5.4.1, 5.4.2 and 5.4.3. In addition, the following should be carried out. a) The maintenance/servicing personnel should arrange to check the operation of at least 20 percent of the detectors in an installation each year. The selection of detectors to be tested should be spread over as many zones as possible and should be made in such a way that all detectors in an installation should have been checked at least once in 5 years. The checking of the detectors should take the form of either : (i) The testing of a detector in site or (ii) The removal of a detector and its replacement by a detector which has been checked and calibrated by the supplier. b) Circuits requiring automatic voltage regulated supplies should be checked to ensure correct operation and voltage output c) Where the heat-sensitive element of thermal detectors or the enclosure of other detectors are found to be coated with paint or any material likely to affect the operation of the detectors, such material should be cleaned off or if necessary have the detector replaced. Note : In certain environments it may be necessary to clean and adjust smoke detectors at more frequent intervals d) Record in the log book any fault (s) identified and that the above tests had been conducted.