ICC CODE CORNER 2015 International Fire Code

Similar documents
IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

CHAPTER 5: EXHAUST SYSTEMS

ICC CODE CORNER 2015 International Fire Code

COMMERCIAL KITCHEN FIRE SAFETY

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

MOBILE FOOD VENDING Food Trucks & Trailers

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

Laboratories and Hazardous Materials. Company Overview

GUIDELINES FOR MOBILE FOOD FACILITIES

Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS. A. Regulations, Standards and References 2. B. Scope 3. C. Approvals and Listings 3

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

SEMICONDUCTOR FABRICATION FACILITIES

JADE RANGE LOG BROILER MODELS: JLB SERIES

Standard for tests for flammability of plastic materials for parts in devices and appliances

Above Ground Fuel Tank Requirements

CORE Protection Fire System Specification

SEMICONDUCTOR FABRICATION FACILITIES

Note: The event coordinator is responsible for compliance of all regulations.

UNDER CABINET RANGE HOOD

SEMICONDUCTOR FABRICATION FACILITIES

MOBILE FOOD VENDOR DEFINITION & FIRE INSPECTION INFORMATION

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

SafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

Note: The event coordinator is responsible for compliance of all regulations.

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

UNDER CABINET RANGE HOOD. This manual is made with 100 % recycled paper.

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

SEMICONDUCTOR FABRICATION FACILITIES

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

Safe Schools: A Health and Safety Check

Integrated Hood Liner

CLEANING & MAINTENANCE For performance, appearance, and health reasons, clean filter, fan and grease-laden surfaces. Use only a clean cloth and mild d

Revolving Oven Gas Wood Model 140

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Department of Public Safety

Integrated Hood Liner

Safety Tips for the Office

READ AND SAVE THESE INSTRUCTIONS

2012 International Mechanical Code Significant Changes. About the Significant Changes

Operation Manual RANGE HOOD

Structural Guidelines. Food Service Establishments. Retail Food Stores

ICC CODE CORNER 2015 International Fire Code

Special Occupancy Requirements

APPUZO RANGE HOOD INSTALLATION

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

UNIFIED FACILITIES GUIDE SPECIFICATIONS

GASEOUS HYDROGEN SYSTEMS

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

Level I Chapter 1 Worksheet

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights

Low Wall Back Shelf Exhaust Canopy

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

INSTALLATION AND OPERATION MANUAL GAS SKILLETS MODELS: GTS-30 GTS-40

GENERAL FIRE REQUIREMENTS SELF INSPECTION CHECKLIST

FUEL. Fire & Flammable Liquids Properties. Flammable & Combustible Liquid Safety. Safety. Practice. Laws: OSHA & NFPA. Safety.

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems

ICC CODE CORNER 2015 International Fire Code

Tents and Temporary Membrane Structures Permit Procedure

Models. Options. Standard Features. LoH 2 O

Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien

SECTION COMMERCIAL-KITCHEN HOODS

CONTENTS DESCRIPTION UNPACKING DIMENSIONS

ICC CODE CORNER 2012 IFC Code & Commentary

NFPA 96, 2017 REVIEW SUMMARY

IMC Significant Changes Summary Tier I

User s Manual WS-69TB30 / WS-69TB36 (22 ) WS-69TB42 / WS-69TB48 (22 ) WS-69TS30 / WS-69TS36 (18 ) WS-69TS42 / WS-69TS48 (18 )

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

The D1000. Typical Specifications: activate the mechanical fire suppression system. (pressurized potassium citrate / potassium acetate mix)

Dear Concessionaire,

Defend In Place 2012 IFC Overview of Institutional Occupancies

RL Series Commercial/Residential Ventilation Fan Installation Instructions Please Read And Save These Instructions.

INSTALLATION & OPERATION MANUAL GAS CHARBROILERS

Chapter One Commercial Kitchen Fires

Tents and Temporary Membrane Structures Packet

READ AND SAVE THESE INSTRUCTIONS Installer: Leave this manual with homeowner.

AerFlow at ::rangehoods.com is a division of kitchen::accessories U N L I M I T E D

FOOD PREPARATION WITHIN EXHIBITS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

JOINT CODE INTERPRETATION

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

Ventilating Fan FV-05VFL2 FV-08VFL2 FV-11VFL

READ AND SAVE THESE INSTRUCTIONS WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:

2015 ICC Commercial Cooking Systems

JFT Flight Machine. JFT Flight Machine. Models. Options. Standard Features. JFT Flight Machine

Flammable Liquids!!!!!

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Barcelona Collection. Use and handling instructions Mode d emploi et d entretien Instrucciones de uso y mantenimiento

EXCELSIOR FIRE DISTRICT

The D1000. Typical Specifications: Standard Options*: Model: D1030-I_-DF Spec & Submittal Version 2.3 D1000-I_-DF D1000-I_-DF-NFPA101

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

FIRE DEPARTMENT PERMIT GUIDELINES

ICC CODE CORNER 2015 International Fire Code

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

NFPA 101 Life Safety Code Culture change 2012

Transcription:

SECTION 609 COMMERCIAL KITCHEN HOODS [M] 609.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. [M] 609.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Exception: A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with UL 710B. 609.3 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with Sections 609.3.1 through 609.3.4. 609.3.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. 609.3.2 Grease extractors. Where grease extractors are installed, they shall be operated when the commercialtype cooking equipment is used. 609.3.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3. 609.3.3.1 Inspection. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 609.3.3.1 or as approved by the fire code official. Inspections shall be completed by qualified individuals.

609.3.3.3.1 Tags. When a commercial kitchen hood or duct system is inspected, a tag containing the service provider name, address, telephone number and date of service shall be provided in a conspicuous location. Prior tags shall be covered or removed. TABLE 609.3.3.1 COMMERCIAL COOKING SYSTEM INSPECTION FREQUENCY 609.3.3.2 Grease accumulation. If during the inspection it is found that hoods, greaseremoval devices, fans, ducts or other appurtenances have an accumulation of grease, such components shall be cleaned in accordance with ANSI/IKECA C 10. 609.3.3.3 Records. Records for inspections shall state the individual and company performing the inspection, a description of the inspection and when the inspection took place. Records for cleanings shall state the individual and company performing the cleaning and when the cleaning took place. Such records shall be completed after each inspection or cleaning and maintained. 609.3.4 Extinguishing system service. Automatic fire extinguishing systems protecting commercial cooking systems shall be serviced as required in Section 904.12.6. 609.4 Appliance connection to building piping. Gas-fired commercial cooking appliances installed on casters and appliances that are moved for

cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.69. The commercial cooking appliance connector installation shall be configured in accordance with the installation instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer's instructions. SECTION 610 COMMERCIAL KITCHEN COOKING OIL STORAGE 610.1 General. Storage of cooking oil (grease) in commercial cooking operations utilizing above-ground tanks with a capacity greater than 60 gal (227 L) installed within a building shall comply with Sections 610.2 through 610.7 and NFPA 30. For purposes of this section, cooking oil shall be classified as a Class IIIB liquid unless otherwise determined by testing. 610.2 Metallic storage tanks. Metallic cooking oil storage tanks shall be listed in accordance with UL 142 or UL 80, and shall be installed in accordance with the tank instructions. 610.3 Nonmetallic storage tanks. Nonmetallic cooking oil storage tanks shall be installed in accordance with the tank instructions and shall also comply with all of the following: 1. Tanks shall be listed for use with cooking oil, including maximum temperature to which the tank will be exposed during use. 2. Tank capacity shall not exceed 200 gallons (757 L) per tank. 610.4 Cooking oil storage system components. Cooking oil storage system components shall include but are not limited to piping, connections, fittings, valves, tubing, hose, pumps, vents and other related components used for the transfer of cooking oil, and are permitted to be of either metallic or nonmetallic construction.

610.4.1 Design standards. The design, fabrication and assembly of system components shall be suitable for the working pressures, temperatures and structural stresses to be encountered by the components. 610.4.2 Components in contact with heated oil. System components that come in contact with heated cooking oil shall be rated for the maximum operating temperatures expected in the system. 610.5 Tank venting. Normal and emergency venting shall be provided for cooking oil storage tanks. 610.5.1 Normal vents. Normal vents shall be located above the maximum normal liquid line, and shall have a minimum effective area not smaller than the largest filling or withdrawal connection. Normal vents shall be permitted to vent inside the building. 610.5.2 Emergency vents. Emergency relief vents shall be located above the maximum normal liquid line, and shall be in the form of a device or devices that will relieve excessive internal pressure caused by an exposure fire. For nonmetallic tanks, the emergency relief vent shall be allowed to be in the form of construction. Emergency vents shall be permitted to vent inside the building. 610.6 Heating of cooking oil. Electrical equipment used for heating cooking oil in cooking oil storage systems shall be listed to UL 499 and shall comply with NFPA 70. Use of electrical immersion heaters shall be prohibited in nonmetallic tanks. 610.7 Electrical equipment. Electrical equipment used for the operation of cooking oil storage systems shall comply with NFPA 70. Next Month SECTION 611 HYPERBARIC FACILITIES Page 1788

The International Code Council, a membership association dedicated to building safety and fire prevention, develops the codes used to construct residential and commercial buildings, including homes and schools. Most U.S. cities, counties and states that adopt codes choose the International Codes developed by the International Code Council. The Center for Campus Fire Safety 978.961.0410 SupportTeam@campusfiresafety.org