Comfort Ceiling Fan Coil System INDULVENT ec NEW Draught-free ambient air distribution with cooling capacity up to 2600 W Low sound power levels Only electrical, cooling water and condensate connections required Energy-saving EC technology Stepless power regulation Integrated condensate pump Open BUS architecture
Features INDULVENT ec Local ceiling fan coil systems allow the flexible use of available space. For high comfort requirements, INDULVENT ec ensures draught-free ambient air flow with high cooling capacity and low sound power levels. The compact unit employs a fan with energy-saving EC technology. Cooling loads of up to 2600 W can be accommodated. Only electrical, cooling water and condensate connections are required. INDULVENT ec is suitable for the installation in all prevalent modular ceilings. INDULVENT ec performance features Compact design Fan, heat exchanger, dust protection, ambient air temperature sensor and controller are all integrated in a single housing. Up to 2600 W cooling capacity (sensible + latent) per unit for high cooling loads. Only a cold water connection and mains voltage are needed for operation. Draught-free air distribution according to DIN EN 13 779, results from the highinduction, integrated, ceiling air diffuser. Average local air velocities of less than 0.15 m/s can be achieved. Housing with internal insulation using halogen-free closed-cell insulation material. Fire-resistance classification (BKZ) B2. Vent-BUS is an internal communication system which can connect up to 32 subscribers to a common BUS. Any desired combination of individual units and master / slave groups is possible. Comfortable operation, parameterisation and monitoring using a PC or a laptop via the USB socket in the front panel. With the VENT-BUS, any connected unit can be addressed and parameterised from the USB interface of any convenient subscriber. Flexible Because parameterisation is simple, the works control parameters can be changed to individual settings when required. If usage changes, new master / slave groups can be set up at any time. Comprehensive equipment The basic unit includes signal contacts for operation and fault messages. An external control using a 0-10 V DC control voltage is possible. Condensate pump is fitted as standard to ensure the reliable removal of any condensate for construction height 335 mm. Accessories Remote switching point with the functions: OFF STAGE 1 STAGE 2 AUTOMATIC Through valve (¾ ) with thermal actuator to cut off cold water during standstill periods Coupler to incorporate the Vent-BUS in an inhouse BUS system Simple operation and maintenance The folding hinge fitted as standard to the front panel makes servicing easy. Easy to clean (VDI 6022) because all internal parts are easily accessible. Just a few simple operations and the housing, ventilator, heat exchanger, condensate dish etc. are accessible for maintenance and cleaning. Integral cooling regulation adapts the cooling capacity to the load situation in a room by changing the recirculation air flow rate.
Function and Measurement Air flow path Construction Heat exchanger EC motor Fan rotor Outlet recirculation air Inlet ambient air Outlet recirculation air Air guide vane Inlet grille / Filter fleece Condensate dish Simple to operate and easy to maintain The compact unit contains a fan, Cu-Al heat exchanger with hydrophobically-coated vanes, ambient air temperature sensor, filter fleece, condensate pump and an electronic controller. The folding hinge fitted as standard makes installation and servicing especially easy. After undoing the quick-action fastener, the front panel can be swung open. All components are readily accessible, and easy to clean and maintain (VDI 6022). Master-slave operation with Vent-BUS Using the Vent-BUS, it is possible to operate units that belong together in parallel. Up to 32 subscribers can be connected in such a group. Communication is by means of twisted-pair cable that must be installed by the customer. It connects all units that belong to the data BUS in series. Within a hard-wired VENT-BUS, groups can be set up as required at any time and configured to operate in parallel. The parameterisation software is used for this purpose. A special feature of Vent-BUS is that the parameterisation of any subscriber can be carried out from any desired INDULVENT ec connected to the BUS. This offers the advantage that, for example, sensitive rooms do not have to be entered for setting up operations. The temperature of the ambient air entering the unit is recorded by an internal temperature sensor. The integrated electronic controller reacts to this measured temperature or to an external control signal. By changing the speed of rotation, and so changing the recirculation air flow rate, the cooling capacity is continually adapted to the cooling load of a room. Example of parameter setting Two-wire BUS cable INDULVENT ec 1 Master INDULVENT ec 2 Slave INDULVENT ec 32 Slave A USB socket and signal diodes for monitoring and parameterisation of the unit are integrated into the front panel. This allows the current operating state to be read from within the room. In addition the ceiling fan coil has an operation and fault-signal relay.
Technical data Dimensions Side view cold water connections Soffit from room (front plate) Side view electrical connections Side view cold water and condensate connections Section *335 mm with condensate pump *375 mm with free condensate drain All dimensions in mm
Technical data - Dimensions (size 600) 598 58 569 84,5 400 84,5 ~85 156 598 335 (375)* ~43 Side view cold water connections 12 Soffit from room (front plate) 571 85 400 85 184 43 282 233 Attachement point Attachement point Heat exchanger Side view electrical connections Cold water connection Fan unit Controller / Electrical connection box 569 84,5 400 84,5 40 166 Ceiling panel Front panel Condensate dish 253 170 50 56 Ø3/4" Ø3/4" 57 110 86 70 179 VL RL Temperature sensor Filter fleece Section Siede view cold water and condensate connections *335 mm with condensate pump *375 mm with free condensate drain All dimensions in mm
Technical data Operating range and properties Overview Operating temperature range as indoor unit C + 5 bis + 40 Recirculation air flow rate m 3 / h 100-470 Power supply V / Hz 230 / 50 Degree of protection Nominal electrical power requirement of fan 1 Watt 39 Standby power consumption Watt 4 Operating medium IP X0 Water Operating limits for water temperature C + 5 bis + 65 C Heat exchanger test pressure bar 10 Nominal heat exchanger water requirement l / h 450 Nominal pressure loss kpa 9 Water connection, supply / return Zoll ¾ External thread Water volume l 1.8 Electrical power requirement of condensate pump Watt 11 Condensate connection (free discharge) mm 10 x 1.0 Condensate connection (pressure line) mm 6 x 1.5 Condensate pump, delivery head / flow rate m / l / h 3,5 / 2 Dimensions of housing without front panel Height / Width / Depth mm 335 / 596 / 594 Dimensions of front panel Height / Width / Depth mm 12 / 623 / 623 Operating weight kg 31 1 Power requirement V max = 470 m³ / h. Cooling capacity 2 Recirculation air flow rate [m 3 / h] Cold water supply temperature 6 C 8 C 10 C 12 C 14 C Total cooling capacity [Watt] 150 1270 1050 840 650 490 200 1480 1220 980 760 570 250 1690 1390 1110 870 650 300 1890 1560 1250 980 740 350 2080 1720 1380 1080 820 400 2290 18880 1510 1190 890 450 2470 2040 1650 1280 970 470 2600 2100 1690 1330 1000 2 Ambient air conditions: 26 C / 60 % rel. humidity, dew point: 17,6 C
Technical data - Operating range an properties (size 600) Overview Operating temperature range as indoor unit C +5 to +40 Recirculation air flow rate m³/h 100-470 Power supply V/ Hz 230/50 Degree of protection IP X0 Nominal electrical power requirement of fan 1 Watt 39 Standby power consumption Watt 4 Operating medium Water Operating limits for water temperature C +5 to +65 C Heat exchanger test pressure bar 10 Nominal heat exchanger water requirement l/h 450 Nominal pressure loss kpa 9 Water connection, supply / return Zoll 3/4" External thread Water volume l 1,8 Electrical power requirement of condensate pump Watt 11 Condensate connection (free discharge) mm 10 x 1,0 Condensate connection (pressure line) mm 6 x 1,5 Condensate pump, delivery head / flow rate m / l/h 3,5 / 2 Dimensions of housing without front panel Height mm 375 Width mm 571 Depth mm 569 Dimensions of front panel Height mm 12 Width mm 598 Depth mm 598 Operating weight kg 31 1 Power requirement V max = 470m³/h Cooling capacity 2 Recirculation air flow rate [m³/h] Cold water supply temperature 6 C 8 C 10 C 12 C 14 C Total cooling capacity [Watt] 150 1270 1050 840 650 490 200 1480 1220 980 760 570 250 1690 1390 1110 870 650 300 1890 1560 1250 980 740 350 2080 1720 1380 1080 820 400 2290 1880 1510 1190 890 450 2470 2040 1650 1280 970 470 2600 2100 1690 1330 1000 2 Ambient air conditions: 26 C / 60 % rel. humidity, dew point: 17.6 C
Technical data Sound power level and requirement Sound power levels and electrical power requirements Recirculation air flow rate [m³/h] Sound power level [db (A)] Electrical power requirement [Watt] 150 29 8 200 33 10 250 37 13 300 41 17 350 45 23 400 48 29 450 51 37 470 (max.) 52 39 Water side pressure loss Water volume [l / h] Pressure loss [kpa] 300 (minimum water volume) 3.9 350 5.3 400 7.0 450 (nominal water volume) 8.8 500 10.9 550 13.2 The cooling capacity depends principally on: Parameter settings Fan speed selected by the control system or manually Ambient air temperature and humidity Cold water supply temperature and cold water mass flow Determination of the cooling capacity using graphs or formulas is therefore laborious and prone to error. The speed of rotation of the fan changes continually according to the ambient air temperature, as does the cooling capacity during condensing operation. We recommend: Due to the numerous parameters, please contact our Technical Sales for a concrete design proposal.
Specification Text Comfort Ceiling fan coil system INDULVENT ec A square form with the following functions: Room cooling and dehumidification in recirculation mode with a highly inductive, swirl air diffuser for the greatest possible comfort in accordance with DIN EN 13779 and DIN ISO 7730 Suitable for installation in all popular modular ceilings Unit is easy to clean according to VDI 6022 Speed regulation or control of fan unit depending on ambient air temperature, an external control voltage, a remote switch or Vent-BUS Potential-free changeover contacts for operation and fault signals Operation, monitoring and parameterisation using a laptop (customer to supply) via a USB socket in the front panel Type: INDULVENT ec consisting of: Housing made from zinc-plated steel sheet, thermally insulated, with 8 attachment points Ø 9 mm Front panel, finish colour RAL 9010, with black or light grey (similar to RAL 7035) air guide vanes Front panel with folding hinge is easy to open for servicing and cleaning EC radial fan with backwards-curved guide vanes, stable characteristic, low noise level and electrical power requirement Heat exchanger with high thermal performance made of copper tubing with press-fitted, hydrophobically-coated, aluminium lamellae for optimum condensate removal. Water connections: ¾ male threads. Electronic controller with ambient air temperature sensor and USB socket Condensate dish made from flame-retarded ABS with external condensate-discharge nozzle Condensate pump with float control and safety cut-off integrated into the unit Easy-to-change G 2 filter fleece Plug 3-pole for power supply consisting of plug fitting and cable housing Operating weight: ca. 31 kg External dimensions: Nominal size of front panel: 623 mm x 623 mm Housing dimensions: 596 mm x 594 mm x 335 mm (without front panel) Type INDULVENT ec / Manufacturer: Kiefer Luft- und Klimatechnik Pos. Quantity Type Price per piece Additional charge front panel coated in RAL colour of your choice, air guide vanes black or light grey (similar to RAL 7035) Pos. Quantity RAL Price per piece Additional charge remote switch for operating a unit from the room Surface mounting Pos. Quantity Price per piece Flush-mounting Pos. Quantity Price per piece Additional charge through valve (¾ ) with thermal actuator to cut off cold water during standstill periods (supplied loose) Pos. Quantity Price per piece Additional charge for plug fitting consisting of: 1 x plug 3-pole for fault message 1 x plug 3-pole for operation notification 1 x plug 12-pole for connection for remote switch, external control voltage and Vent-BUS Pos. Quantity Price per piece Additional charge for parameterisation of the offered INDULVENT units on site by Kiefer according to our installation charge rates Pos. Quantity Estimated price
Specification Text (size 600) Comfort Ceiling fan coil system INDULVENT ec A square form with the following functions: Room cooling and dehumidification in recirculation mode with a highly inductive, swirl air diffuser for the greatest possible comfort in accordance with DIN EN 13779 and DIN ISO 7730 Suitable for installation in all popular modular ceilings. Unit is easy to clean according to VDI 6022 Speed regulation or control of fan unit depending on ambient air temperature, an external control voltage, a remote switch or Vent-BUS Potential-free changeover contacts for operation and fault signals Operation, monitoring and parameterisation using a laptop (customer to supply) via a USB socket in the front panel Type: INDULVENT ec consisting of: Housing made from zinc-plated steel sheet, thermally insulated, with 8 attachment points Ø 9 mm Front panel, finish colour RAL 9010, with black or light grey (similar to RAL 7035) air guide vanes Front panel with folding hinge is easy to open for servicing and cleaning EC radial fan with backwards-curved guide vanes, stable characteristic, low noise level and electrical power requirement Heat exchanger with high thermal performance made of copper tubing with press-fitted, hydrophobically-coated, aluminium lamellae for optimum condensate removal (water connections: ¾ male threads). Electronic controller with ambient air temperature sensor and USB socket Condensate dish made from flame-retarded ABS with external condensate-discharge nozzle Condensate pump with float control and safety cut-off integrated into the unit Easy-to-change G 2 filter fleece Plug 3-pole for power supply consisting of plug fitting and cable housing Operating weight: ca. 31 kg External dimensions: Nominal size of front panel: 598 mm x 598 mm Housing dimensions: 571 mm x 569 mm x 335 mm (without front panel) Height: 335 mm (with condensate pump) 375 mm (without condensate pump) Type: INDULVENT ec / Manufacturer: Kiefer Luft- und Klimatechnik Pos. Quantity Type Price per piece Additional charge front panel coated in RAL colour of your choice, air guide vanes black or light grey (similar to RAL 7035) Pos. Quantity RAL Price per piece Additional charge remote switch for operating a unit from the room Surface mounting Pos. Quantity Price per piece Flush-mounting Pos. Quantity Price per piece Additional charge through valve (¾ ) with thermal actuator to cut off cold water during standstill periods (supplied loose) Pos. Quantity Price per piece Additional charge for plug fitting consisting of: 1 x plug 3-pole for fault message 1 x plug 3-pole for operation notification 1 x plug 12-pole for connection for remote switch, external control voltage and Vent-BUS Pos. Quantity Costs Additional charge for parameterisation of the offered INDULVENT units on site by Kiefer according to our installation charge rates. Pos. Quantity Estimated price
Experts for air conditioning Development and testing laboratory Consulting and planning for ventilation and air conditioning systems Linear diffusers Chilled ceilings Concrete core cooling with air System construction comfort air conditioning System construction industrial air conditioning Building management Maintenance service Asbestos decontamination E3042-04/12 Maschinenfabrik Gg. Kiefer GmbH Tel.: +49 (0)711 8109-0 Fax: -205 Heilbronner Straße 380 396 E-Mail: info@kieferklima.de 70469 Stuttgart, Germany Internet: www.kieferklima.de You will find further information about our products and services on our website: www.kieferklima.de