Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

Similar documents
Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

Performance Analysis of Centrifugal Fan by CFD

FLOW AND PERFORMANCE INVESTIGATIONS OF CENTRIFUGAL BLOWERS WITH AEROFOIL BLADED IMPELLERS

Australian Journal of Basic and Applied Sciences

The Role of Computational Fluid Dynamic and Aeroacoustic Simulations in Reducing the Noise of a Forward-Curved Blade Radial Fan

A Novel Approach for the Thermal Management. of PC Power Supply

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Rotodynamic Pumps INTRODUCTION:

Performance Study of Triple Concentric Pipe Heat Exchanger

Ducted Propeller. Airflow Volume

EXPERIMENTAL ANALYSIS OF TIP CLEARANCE AND CHORD LENGTH FOR OPTIMUM DESIGN OF AXIAL FLOW FAN IN AIR COOLED HEAT EXCHANGER

STUDY, ANALYSIS AND DESIGN OF AUTOMOBILE RADIATOR (HEAT EXCHANGER) PROPOSED WITH CAD DRAWINGS AND GEOMETRICAL MODEL OF THE FAN

ICSV14. Cairns Australia 9-12 July, Noise reduction of handheld vacuum cleaners according to geometric optimization of air passages

Effects of Splitter Blades on Centrifugal Pump Performance - A Review

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Introduction to Fans. The Basics of Fan Principles and Terminology

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

EFFECT OF GEOMETRICAL CHANGES OF IMPELLER ON CENTRIFUGAL PUMP PERFORMANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

American International Journal of Research in Science, Technology, Engineering & Mathematics

THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN

Dynamic Response Analysis of Centrifugal Blower with Different Material

Water Pumps. turbo-hydraulic pumps, positive-displacement pumps.

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Selecting the Correct Fan

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

The Advantages of Choosing Centrifugal Fans

SSRG International Journal of Thermal Engineering (SSRG-IJTE) volume 1 Issue1 Jan to April 2015

What is the correct type of fan: Axial, radial, diagonal?

Design And Analysis Of Centrifugal Pump

Optimized fan system design for the one-year cycle of a Heat Pump. Ziehl-Abegg SE Frieder Lörcher

DESIGN AND MANUFACTURING OF CHEMICAL AGITATOR

FAN TYPES CENTRIFUGAL FAN Forward Curve Centrifugal Fan

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

DESIGN AND FABRICATION OF OMNI MULTI AXIS CEILING FAN

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Glossary of Terms Laboratory & Fume Exhaust Fans

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Kerala, India. I. Introduction

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Performance Enhancement of Inclined Bubbling Fluidized Bed Paddy Dryer by Design Modification

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

ABSTRACT I. INTRODUCTION

Analysis of Centrifugal Pump with Closed Type Impeller for Slurry Operations

High Performance Diesel Fueled Cabin Heater. Abstract

CENTRIFUGAL BLOWERS & FANS TM MITTAL ENGINEERING

EXPERIMENTAL ACOUSTIC CHARACTERIZATION OF A WET VACUUM CLEANER

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Fan Performance and Selection. Overview

Faculty of Mechanical and Manufacturing Engineering Universiti Tun Hussein Onn Malaysia Pt. Raja, Batu Pahat, Johor, MALAYSIA

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units

Fan Selection. and Energy Savings

COST REDUCTION OF SECTION CHANNEL BY VALUE ENGINEERING

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Stock Vessels for Improved Quality and Energy Savings

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

DAE Systems. Fan Selection Guide. Section 1: Terminology

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Effect of Impeller Clearance and Multiple Impeller Combinations on Solid Suspension in a Standard Flat Bottom Agitated Vessel

Development of Large Size Hybrid Fan

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Simulation Of Pneumatic Drying: Influence Of Particle Diameter And Solid Loading Ratio

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Main Characteristics of Appliances for Transport and Compression of Air

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

FAN ENGINEERING. Surge, Stall and Instabilities in Fans

Experimental Investigation of Heat Transfer Enhancement from Waveform Pin-Fins

Fans: Features and Analysis

COMPARISON OF SHEAR STRENGTH PARAMETERS OF BLACK COTTON SOIL WITH EFFECT OF RELATIVE COMPACTION

American International Journal of Research in Science, Technology, Engineering & Mathematics

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Water engineers and utilities are often

Effect of Placement of Footing on Stability of Slope

Design, Development and Experimental Investigation of Volumetric Air Receiver

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

USE OF CFD TOOL FOR IMPROVING DESIGN OF CENTRIFUGAL PUMP

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Analysis and Optimization of Centrifugal Blower Using CFD

R. K. Engg. Works Private Limited

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

ARI 260 Standard: Sound Rating of Ducted Air Moving and Conditioning Equipment

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Experimental Study and Analysis of Flat Plate Solar Water Heater with Different Flow Rates using of Circulating Pump

Transcription:

2016 IJSRSET Volume 2 Issue 4 Print ISSN : 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil Mechanical Engineering Department, AISSMS COE, SPPU, Pune, Maharashtra, India ABSTRACT In this paper, an experimental study has been carried out to study the effects of volute tongue clearance and rotational speed on performance of backward curved blades centrifugal blower. The experiments are performed in the wide range of rotational speeds varying from 1500, 2000, 2500 and 2800 rpm with different volute tongue clearance blowers of 6%, 8%, 10% and 12.5 % of impeller diameter are used for experimentations. The experiments are performed with respective Indian standard IS4894:1987. To study the performance parameters flow rate, total pressure, shaft power and efficiency of the blowers. The aim of many different experimental tests is to validate whether the effects of different volute tongue clearance modifications and impeller speed to blower performance and to find a good volute tongue clearance and impeller speed matching to increase the performance of centrifugal blower. The results show that the volute tongue clearance and impeller speed has a significant effect on the performance of centrifugal blower. Keywords: Centrifugal Blower, Impeller Speed, Performance, Volute Tongue Clearance I. INTRODUCTION Centrifugal blowers are frequently used in many applications to produce high pressure. It correspondingly develops high-pressure ratios in small axial distance related to axial fans. They are commonly used in heating, ventilation, air conditioning systems and various other applications. Depending on the blade shape, centrifugal blowers can be classified into forward-curved, backward-curved, radial, and airfoil types. A blower is a device for moving air which utilizes a power driven the rotating impeller. A blower has at least one inlet opening and at least one outlet opening. The rotating impeller was transfers mechanical energy from the shaft toward the air stream. The energy in air appears in the form of air velocity and air pressure. It is important to note that all of the energy added to the air is added to power driven rotating impeller. When the air moves into the suction side of the impeller, the shape of the casing provides the necessary pressure to the flowing air. In centrifugal blower, the air was forced to the periphery and discharged into the volute [1]. The variations of the volute tongue clearance in order to decrease the pressure deviations in this region. Decreasing impeller-tongue clearance is mostly used method for centrifugal blower performance improvement [2]. Increase the gap between the tongue and the impeller, thus charge the tongue out of the region with reduce nonuniform flows [3].The volute tongues position has a significant effect on the performance. Large pressure variation is observed in the vicinity of volute tongue region and it decreases with increase in distance from the tongue [4-5]. The effect of volute tongue position on the circumferential pressure distribution was observed. The differences in flow pattern and flow reversal are larger when the radial gap is smaller and the blockage effect is reduced with increasing radial gap. Thus, the volute tongues position has a significant effect on the performance [6-7]. The modified tongue positions have affected to power consumption and the total efficiency of the fan [8-9]. The volute tongue clearance had a substantial effect on the performance of centrifugal fan [10-12]. In the work reported here, an experimental study on the backward curved blades centrifugal blower performance has been performed and then, some different volute tongue IJSRSET162431 Received : 11 July 2016 Accepted : 20 July 2016 July-August 2016 [(2)4: 261-266] 261

clearances, different impeller speed and their coupling effect to the performance of the backward curved blades centrifugal blower. The fundamental object of the present work is to offer a case study on the backward curved blades centrifugal blower performance. The second object is to appreciate whether the effects of different volute tongue clearance modifications to centrifugal blower performance are additive. And the additional object is to find a good matching between impeller speed and volute tongue clearance to increasing the performance of centrifugal blower. II. METHODS AND MATERIAL 1. Centrifugal Blower Details The four centrifugal blowers are used for the experimental measurement. The difference between the all this blower is only the casings with different volute tongue clearances the impeller is similar. Fig.1 shows the test centrifugal blower and Table I demonstration all dimensions of the test centrifugal blower. The different volute tongue clearance blowers are shown in Fig.2. For experimentation all four blower volute tongue clearance are 12.5%, 10%, 8% and 6% of impeller diameter and different speed of impeller are used. The blower is driving by an electric motor at different speed. Figure 2. Casings with Different Volute Tongue Clearances TABLE. I CENTRIFUGAL BLOWER PARAMETER Sr. No Parameter Unit Values 1 Impeller Outlet Diameter mm 280 2 Impeller Inlet Diameter mm 140 3 Impeller Blade Number - 12 4 Impeller Width mm 20 5 Impeller Blade Angle deg 30 6 Casing Width mm 65 7 Volute Tongue Radius mm 14 8 Casing Inlet Diameter mm 125 9 Casing Outlet B L mm 65 185 2. Experimentation Figure 1. Test centrifugal blower In this study, four centrifugal blowers were tested according to Indian standard IS4894:1987. The test setup contains of a centrifugal blower of backward curved type, a test inlet duct and delivery duct. The blower is driven by an AC three-phase electric motor. The inlet duct has 125 mm in diameter and 552 mm in length and delivery duct has 200 mm in length. The flow rate can be varied by orifice plate in the inlet duct during experiments. The test setup is assembled and the experiments conducted in accordance with IS4894:1987. Fig.3 shows a test setup equipped with the measuring devices. The flow rate over the blower is calculated by the static pressure measured by the U-tube manometer at section A of the inlet duct. The static pressures at the blower inlet are measured over four taps equally distributed on the circumference of the inlet duct at section B and the outlet total pressure measured at the outlet of the blower for calculating the blower total 262

pressure. The distance from the static taps at blower inlet duct is 130 mm. The three phase variable autotransformer is used to varying the speed of blower. The rotation speed of the blower is measured by a hand-held tachometer. The input power required to drive the impeller is measured using an ammeter and voltmeter. From experimental calculation data the blower total efficiency is calculated by using following equation, volume flow rate and the y-axes is total pressure. The modifications of volute tongue clearance have affected on the total pressure, efficiency and shaft power of centrifugal blower. For different volute tongue clearances, the increasing volume flow rate the variation in total pressure is shown in Fig.4 at 2800 rpm. Total = 2.725 10-3 Q P t Where, P t the blower total pressure, Q is the blower volume flow rate. In this study, the uncertainty in the flow rate and the pressure measurements is ±2.5%. Moreover, the fan input power obtained is within ±2%. The rotational speed variation during the test is controlled within ±1%. The maximum uncertainties for different instruments are as follows, Tachometer: ± 0.05 % (± 10 rpm) Ammeter: ± 0.01 % (± 0.01 Amp) U-tube manometer: ± 1 mm of H 2 O Figure 4. Effect of volume flow rate on total pressure at 2800 rpm Figure 3. Actual test setup III. RESULTS AND DISCUSSION In the present study, the effects of modifications of volute tongue clearance were studied on the entire four blowers i.e. 12.5%, 10%, 8% and 6% volute tongue clearance blowers at four different speeds e.g. 2800, 2500, 2000 and 1500 rpm. The experimental measured results are shown in two plots, where the x-axes are Figure 5. Effect of volume flow rate on total pressure at 2500 rpm For different volute tongue clearances, the increasing volume flow rate the variation in total pressure was shown in Fig.5at 2500 rpm. The total pressure is increased when the volute tongue clearance is decreased. For different volute tongue clearances, the increasing volume flow rate the variation in total pressure was shown in Fig.6 at 2000 rpm. For different volute tongue clearances, the increasing volume flow rate the variation in total pressure was shown in Fig.7at 1500 rpm. The 263

total pressure is increased when the volute tongue clearance is decreased. Figure 6. Effect of volume flow rate on total pressure at 2000 rpm Figure 7. Effect of volume flow rate on total pressure at 1500 rpm Figure 9. Effect of volume flow rate on efficiency at 2500 rpm For different volute tongue clearances, the increasing volume flow rate the variation in efficiency is shown in Fig.8 to Fig.11 at different impeller speed, 2800, 2500, 2000 and 1500 rpm. As volume flow rate is greater than Q 1 = 420 m 3 /h the efficiency is increased when the volute tongue clearance is decreased the total pressure, volume flow rate and efficiency were increased as the volute tongues clearance was decreases. The operating point of the blower was shifted as the impeller speed varied. The impeller speed is varied from 2800 rpm to 1500 rpm the total pressure, volume flow rate and shaft power are decreases. The efficiency remains same only the operating point of the blower was shifted as the impeller speed varied. Figure 8. Effect of volume flow rate on efficiency at 2800 rpm Figure 10. Effect of volume flow rate on efficiency at 2000 rpm 264

TABLE.IV 2000 RPM 12.5 444.9192 248.7590 0.0560 54.8968 10 461.6914 282.9865 0.05919 61.3145 8 461.9453 282.9865 0.0570 63.5577 6 493.4948 292.5811 0.0581 69.9906 Figure 11. Effect of volume flow rate on efficiency at 1500 rpm Table II to Table V summarized the change in blower performance when the volute tongues clearance was varied from12.5 % to 6% of impeller diameter. At different impeller speed, 2800, 2500, 2000 and 1500 rpm, the blower was operating at full discharge condition. TABLE.II 2800 RPM 12.5 630.4469 472.7425 0.1536 53.8735 10 632.5968 522.0660 0.1576 59.3010 8 654.7344 558.6915 0.1583 64.1811 6 673.8414 591.2284 0.1595 69.3729 TABLE.III 2500 RPM 12.5 551.8543 390.2524 0.1093 54.6924 10 578.7608 419.4676 0.1122 60.0786 8 578.9030 434.9731 0.1106 63.2537 6 617.0228 463.2954 0.1135 69.9343 TABLE.V 1500 RPM 12.5 344.0233 136.4810 0.0240 54.2846 10 346.0059 156.1010 0.0252 59.9458 8 349.9710 165.9111 0.0250 64.2261 6 370.3988 170.7084 0.0248 70.7500 IV. CONCLUSION The present paper experimentally studies the effect of modification of volute tongues clearance and different rotational speed of impeller on centrifugal blower performance. Experiments of the original blower and modified blowers are conducted and the results are compared. As the volute tongues clearance decreases from 12.5% to 6% of impeller diameter, the total pressure, volume flow rate and efficiency has significantly increased at full discharge condition. The operating point of the blower was shifted as the impeller speed varied. The impeller speed is varied from 2800 rpm to 1500 rpm the total pressure, volume flow rate, shaft power and efficiency are decreases. Therefore all the modified blowers satisfy the fan law and it gives higher level of performance at 2800 rpm. The modified volute tongues clearances, increases the total pressure and efficiency of blower because the reverse airflow at the region near blower volute tongue are effectively reduced. 265

NOMENCLATURE P t t c d Total pressure (Pa) Volute tongue clearance (mm) Impeller diameter (mm) Shaft power (kw) Efficiency V. REFERENCES [1]. Fan handbook, Selection, Application and Design. Frank P. Bleier. (1998). Chapter no.7. pp. 7.1-7.45. [2]. Sheam-Chyun Lin, Ming-Lun Tsai, An integrated performance analysis for a backward-inclined centrifugal fan, Computers & fluids. (2012, Dec). 56. pp. 24 38. [3]. Qi Datong, Mao Yijun, Liu Xiaoliang, Yuan Minjian, Experimental study on the noise reduction of an industrial forward curved blade centrifugal fan, Applied acoustic, 2009, pp. 1042-1050. [4]. R. Dong, S. Chu, J. Katz, Effect of modification of tongue and impeller geometry on unsteady flow, pressure fluctuations, and noise in a centrifugal pump, The international gas turbine institute, 1997, Vol. 119. [5]. Yew-Wah Wong, Weng-Kong Chan, and Wei Hu, Effects of tongue position and base circle diameter on the performance of a centrifugal blood pump, International center for artificial organs and transplantation, (2007, Dec), Vol.31, pp.639-645. [6]. Chen-Kang Huang, Mu-En Hsieh, Performance Analysis and Optimized Design of Backward- Curved Airfoil Centrifugal Blowers, American Society of Heating, Refrigerating and Air- Conditioning Engineers, (2009, May), Volume 1, Number 3. [7]. O. P. Singh, Rakesh Khilwani, T. Sreenivasulu, M. Kannan, Parametric study of centrifugal fan performance: experiments and numerical simulation, International Journal of Advances in Engineering & Technology, (2011, May). Vol. 1,Issue 2,pp.33-50 [8]. Sandra Velarde-suarez, Rafael ballsteros- Tajadura, Carlos Santo aria-morros, Reduction of aerodynamic tonal noise of a forward curved centrifugal fan by modification of the volute tongue geometry, Applied acoustics, 2006, pp. 225-232. [9]. W. Neise, Noise reduction in centrifugal fan: A literature survey, Journal of sound and vibration, 1975, pp. 375-405. [19]. W. Neise, Review of noise reduction methods for centrifugal fans, Journal of engineering for industry, 1982, Vol.104. pp. 151-160. [20]. William A. Smith, James K. O Malley, Reducing blade passage noise in centrifugal fans, American society of heating, refrigeration, and air conditioning engineers transactions, 1974, Part II. Vol. 80. pp. 45-51. [21]. K. H. Shah, unified design and comparative performance evaluation of forward and backward curved Radial tipped centrifugal fan, (ICME2003) 26-28 December 2003. 266