SECTION RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES

Similar documents
SECTION RADIANT-HEATING ELECTRIC CABLES / MATS

SECTION ELECTRIC FLOOR HEATING AND SNOW MELTING EQUIPMENT

Union County Vocational - Technical Schools Scotch Plains, New Jersey

100A / 200A. Maximum Heating Load: Enclosure Type: NEMA 4

CATALOG. Toll Free:

Department of General Services Real Estate Services Division Professional Services Branch Additional Detailed Instructions (ADI)

IN2 Lighting Control Devices

Principle of Operation:

STEP Snowmelt. Installation Manual. Low Voltage System

Toll Free:

Self-regulating Roof Heat Cable

A. This Section includes the following lighting control devices:

Self-regulating Roof Heat and Gutter Trace Cable

Toll Free:

A. This Section includes the following lighting control devices:

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

CONTENTS AUTOMATIC TRANSFER SWITCHES

SECTION LIGHTING CONTROL DEVICES

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Above Ground Greasy Waste Disposal Lines

Freezer Frost Heave Prevention

Drexan Energy Systems Inc.

CSI Master Format 2004 Guide Specification for: Snow Melting (Mineral Insulated)

SECTION (15767) - UNIT HEATERS

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM

CATALOG. Toll Free:

PART GENERAL 1.01 SECTION INCLUDES

ComfortTile Floor Heating Systems

ADDITIONAL INFORMATION

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION ENCLOSED CONTROLLERS

Pipe Freeze Protection. Flow Maintenance. Introduction. XL-Trace System

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

COMMERCIAL & RESIDENTIAL SELF-REGULATING HEATING PRODUCTS APPLICATION AND DESIGN GUIDE EUROPE, MIDDLE EAST, AFRICA

SECTION AUTOMATIC TRANSFER SWITCHES

F1202 TRACE HEATING. Road & Ramp

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Contents ATTACHING CONTROLS WARRANTY TOOLS... 5 ELEMENT ELEMENT POWER SUPPLY COVER HEATING ELEMENTS...

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

SECTION ISOLATED POWER SYSTEMS

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

PLSRR Heat Trace Cable Data Sheet

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

XL-Trace System Application and Design Guide

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

ROOF AND GUTTER DE-ICING ICESTOP SYSTEM

DIVISION LOW VOLTAGE DE-ICING / SNOW MELTING SYSTEM IN EXISTING ASPHALT/CONCRETE

Emery County Senior Center Green River 06/07

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

STEP Warmfloor Installation Manual. Step Warmfloor Electric Radiant Floor Heating System

Revitalize Building Mechanical Systems (4619)

MODEL SST 2 40 FREEZE PROTECTION THERMOSTAT MODEL SST FIXED SET POINT THERMOSTAT. Installation and Operation Manual

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Commercial and Residential Self-Regulating Heating Products

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Toll Free:

Electric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada

Model GIT 4 Gutter Snow and Ice Melting Control

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

PYROSELF Innovative Snow Sensor and Controller for 2 x 24A loads outputs. Installation and Operating manual

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Installation and Operation Manual

CSI Master Format 2012 Guide Specification for: Hot Water Temperature Maintenance (HWAT) Systems

Roof and Gutter De-Icing

DS-5C RAIN/SNOW SENSOR CONTROLLER INSTALLATION INSTRUCTIONS

Construction Standards Page

SECTION ROTARY-SCREW WATER CHILLERS

FIRE SPRINKLER SYSTEM FREEZE PROTECTION XL-TRACE SYSTEM

ELEKTRA RadiantFloor Heating

SECTION RADIANT HEATING UNITS

LIGHTING CONTROL DEVICES

A. This Section includes transfer switches rated 600 V and less, including the following:

Keep your home snow and ice free with. WARMUP Outdoor Heating Solutions. From the world s best-selling electric floor heating brand

Heat Tracing Sales Mt. Airy, Maryland Heating Cable. Cut to Length in Field. Description

The IceFree Eave System

SECTION DOMESTIC WATER HEATERS

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

1.3 REFERENCES A. ANSI/NFPA 70 - National Electrical Code. B. ARI Commercial and Industrial Humidifiers.

SECTION FAN COIL UNITS

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Technology for human beings that is, compatible with nature, creating permanent HEAT TRACING Dreams that can greatly improve the quality of life,

Low Voltage System. STEP Warmfloor Installation Manual. Step Warmfloor Electric Radiant Floor Heating System

SECTION LIGHTING CONTROLS

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Radiant Edge LT TM Ice Melt System Installation and Operation Guide Version 1.4

Transcription:

SECTION 238313 - RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES A. Low-voltage Electric Snow and ice heating elements "under" finished roof materials (shingles or metal), gutters, and downspouts. This pertains to the following electric heating mat and cable: Self-regulating, parallel resistance, RoofHeat deicing heating elements. B. Controls, Accessories C. Associated installation materials. 1.2 Related Requirements: A. Section 15770 Floor Heating and Snow Melting Equipment B. Section 15773 Electric Heating Cables, Mats, Modules, Panels and Controls C. Section 16855 Heating Cables (Electrical) D. Section 260520 Heating Cables E. Section 260523 Electric Cables F. Section 260620.16 Electrical G. Section 260620.23 Electrical H. Section 262200 Low Voltage I. Section 268313 Radiant Heating Electric Cables J. Section 268313 Radiant Heating Electric Mats 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include rated capacities, operating characteristics, and furnished specialties and accessories. 2. Schedule heating capacity, length of cable, spacing, and electrical power requirement for each electric heating cable required. B. Shop Drawings: For electric heating cable. 1. Include scaled plans, sections, details, and attachments to other work. 2. Include diagrams for power, signal, and control wiring. 3. Include electrical panel schedules for load centers. 1.4 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For electric heating cable/mat to include in operation and maintenance manuals. RADIANT-HEATING ELECTRIC CABLES 238313-1

1.5 WARRANTY A. Special Warranty: Manufacturer agrees to repair or replace electric heating cable that fails in materials or workmanship within specified warranty period. 1. Warranty Period, STEP RoofHeat Deicing Heating Elements and Transformer Power Supplies (excluding circuit breakers): 10 years from date of Substantial Completion, and 2 years on internal electronics provided that resistance readings are taken before, during, and after installation; and sent to Manufacturer. PART 2 - PRODUCTS 2.1 GENERAL REQUIREMENTS FOR ELECTRIC HEATING CABLE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.2 PLASTIC, SELF-REGULATING FLEXIBLE SHEET HEATING ELEMENT - STEP ROOFHEAT FLEXIBLE DEICING HEATING ELEMENT A. Basis-of-Design Product: Subject to compliance with requirements, provide STEP RoofHeat Snowmelt / Deicing Heating Element by: Warmzone 12637 S. 265 W., Suite 100, Draper, UT 84020 Phone: 888-488-9276 / Fax: 801-948-7599 Web: www.warmzone.com B. Compliance: UL 1693, ETL Listed, having CE marking, and conforming to ANSI/UL. C. Heating Element: [12 inch (305 mm)] [9 inch (229 mm)][3 inch (76mm)] wide, 3/64 inch (1.2 mm) thick heating element made from a homogenous semi-conductor self-regulating polymer, utilizing PTC Nano-Technology allowing elements to heat at maximum power in cold environments. D. Electrical Insulating Jacket: Mylar. E. Maximum Survival Temperature: 380 deg F (193 deg C). F. Maximum Operating Temperature: 248 deg F (120 deg C). G. Maximum Obtainable Operating Temperature: 86 deg F (30 deg C). H. Capabilities and Characteristics: 1. Heating Element Construction: [12 inch (305 mm)] [9 inch (229 mm)][3 inch (76mm)] wide, parallel-resistive, self-regulating conductive polymer. 2. Heating Element Thickness: 3/64 inch (1.2 mm). 3. Heating Element: PTC (positive temperature coefficient) semi-conductive polymer. RADIANT-HEATING ELECTRIC CABLES 238313-2

4. Heating Element Bus Braid: Two-tinned-copper, 15 AWG. 5. Heating Element Insulation: Mylar. 6. Heating Element Outer Jacket: Mylar. 7. Cold Lead: 10 AWG MTW, insulation provided my manufacturer. 8. Splice: Field connected to cold lead. 9. Maximum Heat Output (flexible sheet): [11.3 W/ft. (37.1 W/m), 21.3 W/ft. (69 W/m), 24 W/ft. (78.7 W/m), 9 W/ ft. (29.5 W/m) at 68 deg F (20 deg C)]. 10. Minimum Installation Temperature: N/A. 11. Minimum Spacing: 0 inch (0 mm). 12. Electrical Characteristics: a. Volts: [12] [24] Volts AC b. Phase: Single-phase c. Hertz: 0-60 Hz I. Power Supply (Power Pack): [Model EPI-LX] [Model EPI-LX-R], Class I Power Supply with metal enclosure, line and load terminal blocks with line and load circuit-breakers. 1. Power Supply Characteristics: a. [500 W] [1000 W] [1500 W]. b. Transformer Type: Toroidal (low noise) transformer. c. Transformer Winding: Isolated primary and secondary winding. d. Primary Voltage: [120] [208] [230] [240] [277]. e. Secondary Voltage: [12 V] [24 V]. f. Each primary input protected by metal oxide varistor. g. Each output having a load active LED indicator. h. Enclosure: NEMA I rated, aluminum. 2. Control Board Characteristics: For LX-R Series: a. Soft Starts Transformer(s): For elimination of inrush. b. Multiple Power Pack Staging: To allow more wattage per unit. c. Allows single controller to operate multiple power packs. 2.3 CONTROLS A. Comply with requirements in Section 230900 "Instrumentation and Control for HVAC" and Section 230993 "Sequence of Operations for HVAC Controls" for control devices and sequence of operations for radiant-heating electric cables. 1. System activation shall be controlled by WS Snowmelt controller with external temperature and/or moisture sensors. Control of the system shall be achieved by the use of one or two remote mounted sensors which will collectively sense the outdoor temperature and the presence of falling snow. a. System shall be capable of responding to the input from both a temperature and moisture sensor. b. Controller will be capable of controlling one zone. c. Control device shall be CSA, ETL, UL or equivalent Approved. RADIANT-HEATING ELECTRIC CABLES 238313-3

2. WS-2C, WS-5 or WS-8C Aerial mounted sensors with integral or remote temperature and moisture sensors. Appropriate contactor / relay enclosures shall be NEMA 3R minimum rated, suitable for outdoor mounting. Control of the system shall be achieved by the use of an Aerial Controller with integrated snow and temperature sensors which will collectively sense the outdoor temperature and the presence of falling snow. a. System shall be capable of responding to the input from both a temperature and moisture sensor. b. Controller will be capable of controlling one zone. c. Controller will remain energized for an adjustable duration following the end of snowfall, so that slush and ice formation are prevented or evaporated. d. Controller shall feature a device to permit Manual Override. The manual feature shall self-disconnect after a time delay to prevent system run-away. e. Controller shall have remote auxiliary control unit (WS-AUX) that mimics Aerial Sensor for easy visibility and ground access. f. The control device shall be CSA, ETL, UL or equivalent Approved. 2.4 ACCESSORIES A. WS Interconnect Cable: To go between Aerial Snow Sensor and the remote auxiliary (WS- AUX) control unit. Cable should be stranded, shielded 6 conductor, 22 AWG. 1. Length: [50 ft. (15.2 m)] [100 ft. (30.5 m)] [200 ft. (61 m)]. PART 3 - EXECUTION 3.1 EXAMINATION A. For all products, examine surfaces and substrates to receive electric heating cables or cableheated mats for compliance with requirements for installation tolerances and other conditions affecting performance. 1. Ensure surfaces in contact with electric heating cables or cable-heated mats are free of burrs and sharp protrusions. 2. Measure and verify square footages (square meters) for areas to be heated. 3. Verify available supply voltages for project. 4. Identify location of any required junction box(s). Ensure that the maximum cold lead distance for each product is not exceeded. 5. Ensure that environmental requirements for required controls are not violated. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 APPLICATIONS A. Install the following types of electric heating cable for the applications described: RADIANT-HEATING ELECTRIC CABLES 238313-4

1. Snow and Ice Melt for metal/shingle roofs, gutters and downspouts: Mylar-insulated, parallel-resistance heating element. 3.3 INSTALLATION A. Low-Voltage and Self-Regulating STEP RoofHeat Snow Melting Systems Installation Guidelines. 1. Comply with manufacturer's product data, including product technical bulletins, installation instructions, and design drawings. Complete installation must conform to manufacturer's installation instructions, NEC Code, and any appropriate local electric codes. a. Choose qualified personnel who are either trained or are willing to be trained by Warmzone. b. This is an electric heating system and requires personnel trained in the National Electric Code that understands the importance of preventing mistakes that can cause an electrical fire. c. Make sure that all materials used are approved for the specific application and have no adverse compatibility with the heating elements. d. Use only components supplied by or recommended by the manufacturer. e. STEP RoofHeat elements should not touch, cross, or overlap at any point. f. Do not energize rolled up heating elements. g. Make sure to note and identify the locations of the electrical bus braid wires for each heating element, to avoid fastening (nail) through bus braids. h. Installation shall be made in accordance with NEC 424.90 through 424.99 with the following exceptions on 424.93 and 424.99 described in (a) and (b) respectively: 1) PTC Polymer Heating Panel Sets: Nailing or stapling of PTC polymer heating panel shall be done through the polymer material but at least 1 inch from the bus braid conductors. Nails, staples or other fasteners shall not penetrate the current-carrying bus braid conductor wires. 2) Fault Protection: A current limiting device is provided by the manufacturer to protect the un-grounded conductors supplying the heating panel sets. The device shall function when a short circuit occurs such as a result of penetration of both bus conductors or extension wires with a metal device. 2. Fixed Outdoor Electric Roof Deicing and Snow Melting Equipment. Installation shall be made in accordance with NEC Article 426 with the exceptions of grounding and groundfault protection requirements described under 426.22, 426.27 and 426.28. Secondary circuit shall not be grounded according to grounding requirements. 3.4 CONNECTIONS A. Ground the transformer housing and primary according to NFPA 70 (NEC) Class 1 wiring. B. The secondary circuit is ungrounded and floating. RADIANT-HEATING ELECTRIC CABLES 238313-5

3.5 FIELD QUALITY CONTROL A. Testing: Owner will engage a qualified electrician to perform tests and inspections. B. Manufacturer's Field Service: Engage a qualified service representative to test and inspect components, assemblies, and equipment installations, including connections. C. Perform the following tests and inspections [with the assistance of a qualified service representative]: 1. Perform tests before, during, and after heating element installation - before application of coverings such as roofing material. 2. Test heating element for electrical continuity and insulation integrity before energizing. 3. Test heating element to verify rating and power input. Energize and measure voltage and current simultaneously according to instructions. D. Repeat tests for continuity, insulation resistance, and input power after applying finished surface on heating element. E. Radiant-heating electric elements will be considered defective if they do not pass tests and inspections. F. Prepare test and inspection reports for warranty purposes, and send to manufacturer. 3.6 PROTECTION A. Protect installed heating elements, including non-heating leads, from damage during construction. B. Remove and replace damaged heating elements according to instructions. END OF SECTION 238313 RADIANT-HEATING ELECTRIC CABLES 238313-6