Installation and Operation Instructions

Similar documents
ELECTRONIC PARTS - CATALOGUE

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.

OPERATION AND INSTALLATION MANUAL

WARNING FIRE DOOR CLOSING

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

WSC 204 (WSC / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102)

FEC400 Series. Installation Manual

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

FEC403EN Installation Manual

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

Smoke Vent Control Panel RZN 4202 V1

USER MANUAL & MAINTENANCE GUIDE OG OO

Interface and EOL Modules 8

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Installation, Operating and Maintenance Manual

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Application, Installation, Operation & Maintenance Manual

Operation and Maintenance Manual

Installation and user manual for the BiWire / Conventional Repeater Panel

CONTROL DEVICE SLIDETRONIC HD

DICTATOR Hold-Open Systems for Hazardous Areas

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Danfoss gas detection units

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Radio fire warning panel SRC 3000

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

Door Release Power Supply

Conventional Fire Alarm System 2014 V1.2

Fire Control Panel FS4000

Smoke Vent Control Panel PCB4 V4 Installation Manual

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Combi B Alarm box. Mounting instructions

Operating instructions DVC-P / Bedienungsanleitung Druckregler DVC-P

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

MR-2602 Two Zone Fire Alarm Control Panel

PSN-1000 & PSN 1000(E) Installation Manual

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Control Panel Engineering and Commissioning Instructions

SECURIT 700L PLUS ENGINEERING MANUAL

Operating Manual MS220DA

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.

USER MANUAL CEF AP28 CONTROL PANEL

Public Safety DAS Annunciator Panel

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

LC2200 Level Controller Installation and Maintenance Instructions

EXTINGUISHING AGENT RELEASE MODULE

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

Version 3 Controls for smoke and natural ventilation. CompactSmoke WSC 310 / WSC 320 STANDARD Smoke control panel 10-20A

Table of Contents. 1. Mounting Tips... 2

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Beacon 800 Gas Monitor Operator s Manual

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Remote alarm indicator and test combination MK2430

Installation Guide. Disabled Persons Emergency Alarm Kit. Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Model 17A00 Expansion Enclosure

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

KFP-CF Series Operation Manual

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

REPAIR INSTRUCTIONS. TUMBLE DRYER Vented WTA34.. / WTA35..

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Table of Content LT 5165-UL

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

FlexiSmoke WSC 520 / WSC 540 / WSC 560 Modular smoke ventilation panel 20-60A

Kædemotorer. Accessories

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Technical Manual. Level Alarm Unit CARLA & WIDS

Precept Marine Control Panel Application Guide

BX444-Mc Gas Detector

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

XGUARD-10/-5. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

System 800 Addressable Fire Detection & Alarm System

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Transcription:

Smoke and Heat Ventilation Pneumatic - Electronic Control Systems Installation and Operation Instructions Version / SHEVS Control Centre RWZ d K + G Pneumatik GmbH In der Krause 8 9 Eschweiler Deutschland / Germany +9 (0) 0 / 99 0-0 +9 (0) 0 / 0 Info@kg-pneumatik.de Internet: http://www.kg-pneumatik.de GRASL Pneumatic-Mechanik GmbH Europastraße Reidling Österreich / Austria + (0) 7 / 00-0 + (0) 7 / 00-99 Office@graslrwa.at Internet: http://www.graslrwa.at

SHEVS Control Centre RWZ d Contents Page. Concept of Control Centre. Options / accessories. Options / accessories. Installation / putting the equipment into service. Putting the equipment out of service. Functions and operation. Alarm functions.. Activating and resetting the SHE hand-operated fire alarm buttons.. Activating and resetting the automatic fire detectors.. Activating and resetting the alarm by Fire Alarm Control Panel (FACP).. Repetition of OPEN cycle in the case of alarm. Status lights / functions of the SHE hand-operated fire alarm buttons. Status lights / control elements in Control Centre and in enclosure door. DIP switches for setting of functions. Ventilation functions.. Manual ventilation.. Setting / deactivation of ventilation position (stroke limitation).. Setting / deactivation of length of ventilation time (automatic closing upon ventilation) 7.. Indication of position A in ventilation button 7.. Blocking of ventilation 7.. External Wind and Rain Control (WRC) 7..7 Internal Wind and Rain Control (Option WRM) 8. Repetition of CLOSE cycle 8.7 Mains failure 8.8 Potential-free contacts (PFC, option PK) 8.9 Outputs for controlling external warning devices (option WTM) 8. Maintenance 9. Fault finding / troubleshooting 0. General information 0. Displays of Service Display Unit SD. Technical data. Versions. General. Power supply unit. Inputs. Actuator outputs. Line monitoring.7 Fuses.8 Potential-free contacts (option PK).9 Outputs for controlling external warning devices (option WTM).0 Internal Wind and Rain Control (option WRM). EC statement of conformity 7. Terminal and layout diagrams from Please read all information given in these instructions very carefully. Only skilled personnel are permitted to work on the Control Centre! Key to pictograms: = Troublefree operation = = Alarm = Button / travel command OPEN = Warning sound / buzzer Button / travel command CLOSE = Strobe = Malfunction = Position OPEN = Travel control timer Power supply = (mains / accumulator) = Wind = Ventilation position = Rain = Ventilation time = Automatic fire detector = Hand-operated fire alarm = Fire Alarm Control Panel (FACP) RWZdA.doc Errors and omissions excepted Mo Rev. /09 Oct., 009

SHEVS Control Centre RWZ d. Concept of Control Centre Smoke and Heat Exhaust Ventilation System (SHEVS) Control Centre for connection of V- actuators One or two Smoke and Heat Exhaust groups (SHE groups)(rwz.. / RWZ..), two ventilation groups For each SHE group, two signal lines: Line : automatic fire detectors Line : hand-operated fire alarms RT (non automatic fire detectors) as a) Main alarm point with status lights Operation, Alarm, Malfunction and push-button Reset. Connection of main alarm point with mini buzzer (Alarm / Malfunction) and indication of position OPEN also possible b) Secondary alarm point with status light Alarm Line for connection to a Fire Alarm Control Panel (FACP) Reset of alarm / fire detectors by push-buttons at the main alarm point or at the Control Centre Cycle repetition function in the event of alarm to VdS 8 Monitoring of signal lines, actuator supply line, fuses, accumulators and power line Standby power supply for at least 7 hours with accumulator management to VdS 9 Reverse connection and deep-discharge protection for the accumulators Possibility of connecting ventilation buttons for each ventilation group, also with indication of pos. OPEN Blocking of ventilation function OPEN in the case of insufficient accumulator charge or mains failure Ventilation position can be adjusted for each ventilation group (stroke limitation) Adjustable ventilation time for each ventilation group (automatic closing on ventilation action) Possibility of connecting an external Wind and Rain Control (WRC), e.g. WRS (WRC must have a separate contact for each SHEVS Control Centre to be controlled). Internal Wind and Rain Control at option Functions selectable by DIP switches: Auto Close (closes automatically when an alarm has been reset) Malfunction = Alarm (malfunction in a signal line will trigger an alarm) Thermal Alarm (alarm is triggered when enclosure inside temperature is higher than 70 C) Travelling time min (actuators will stop after minutes travelling time) One ventilation group (both ventilation groups will open / close at the same time) Status lights Operation, Alarm and Malfunction in the enclosure door Use of K+G / Grasl actuators is recommended. When controlling actuators made by others, check them for suitability. For this purpose, please refer to section Technical specifications Connectable actuators: V actuators, travelling time for full stroke at rated load (total travelling time) < minutes or < minutes Actuators must be suitable for cycle repetition functions OPEN or CLOSE (see section... /.) When directly changing the sense of travel, the actuators will stop for about s before the change of sense Driving power for the actuators is obtained from the system s accumulators Sheet steel enclosure, light grey (RAL 70). Options / accessories PK: One potential-free contact (PFC) each for alarm / malfunction WTM: Outputs for controlling external warning devices in the event of alarm or malfunction (e.g. multiple-tone sounder MS and strobe BL) WRM: Internal Wind- and Rain Control All actuators / groups will automatically close on response of WRM. Requires connection of wind sensor WM and / or rain sensor RS (accessories) Direct sensor connection on the module in SHEVS Control Centre. No external WRC required Closing command remains active for at least minutes, or for the time of sensor response Wind speed response point and rain sensor response threshold are adjustable Status LEDs for wind and rain on the module SD : Service display unit for detailed status information (alarms, malfunctions, charging condition) during maintenance and installation. It is advisable to use two to three display units at the same time (RWZ.. / RWZ..) SVM: Battery backed service module for indication of due maintenance action Page

SHEVS Control Centre RWZ d. Putting the equipment into and out of service Only skilled personnel are permitted to work on the Control Centre! Before starting any work, be sure to eliminate any static charges (e.g. by touching the metal of a central heating)! Defects due to faulty connection will not be covered by our warranty or liability. Planning and installation of SHEVS is subject to compliance with the following regulations, as far as applicable: national building codes / model building code and regulations of the local building and fire authorities, VDE codes, esp. VDE 000, 008 and 08, VdS guidelines 098 and, DIN 8 or DIN EN 0, DIN 0, model guidelines for cable and pipe installation, safety guidelines BGI 9 and BGR.. Installation / putting the equipment into service Be sure the Control Centre is deenergised before performing any work! Be sure actuators are not operated by an external power supply (e.g. external accumulators) when already connected to the Control Centre. Otherwise, this may cause defects at the power output of the Control Centre. For wiring the Control Centre, follow the information given in the attached terminal diagrams. Turn on the line voltage. LED Malfunction-Power Supply flashes. Place the accumulators into the enclosure. Connect them as shown in the wiring diagram Line voltage and accumulators. LEDs lights up, LED Malfunction-Power Supply goes out, the equipment is ready for operation. Should a malfunction status continue to be shown, check the wiring. For this purpose, refer to Section (Fault finding / troubleshooting). If necessary, the Control Centre has to be deactivated again (see.). When putting the equipment into service, check all functions and status indications of the Control Centre and its components. The individual functions are described in Section (also simulate malfunctions and check whether they are reliably detected; see.). After about h of continuous operation, the accumulators will be sufficiently charged to ensure the standby time of 7 hours in the event of mains failure.. Putting the equipment out of service Disconnect accumulators from Control Centre (e.g. by removing the connection line to the accumulators). Accumulators can be stored approx. months. If stored longer, they have to be recharged. Turn off the line voltage.. Functions and operation Before operating or touching the control elements within the Control Centre, be sure to have eliminated any static charges (e.g. by touching the case)!. Alarm functions While executing an alarm function, the ventilation functions are blocked. At Control Centres with two RWA groups (RWZ..), the following description is likewise applicable to the second group. Alarm function: When an alarm is detected, the actuators of the SHE group will OPEN, and red LEDs Alarm show the alarm condition. Main alarm points with buzzer (RT --AA) will emit a continuous tone. For further alarm functions ( Malfunction = Alarm, Auto Close etc.) see., potential-free contacts (option PK) see.8, external warning devices (Option WTM) see.9. If upon reset of an alarm a closing action proceeds due to operation of button, manual ventilation will be possible only after up to minutes... Activating and resetting the SHE hand-operated fire alarm buttons When an alarm button is pressed, the LEDs Alarm of the hand operated fire alarms and of the Control Centre will light up. The alarm function will be executed as described in Section.. Page

SHEVS Control Centre RWZ d For reset, press the button Reset in a main alarm point or in the Control Centre. When releasing the button, the LEDs Alarm go out and the buzzer will be deactivated... Activating and resetting the automatic fire detectors When an automatic fire detector responds, the LEDs Alarm of the fire alarm buttons, of the Control Centre and of the active detector will light up. The alarm function will be executed as described in Section.. For reset, press the button Reset in a main alarm point or in the Control Centre. When releasing the button, the LEDs Alarm will go out and the buzzer will be deactivated. Should an automatic fire detector respond again, repeat the reset procedure (response may be due to smoke particles still remaining in the detector)... Activating and resetting the alarm by Fire Alarm Control Panel (FACP) If an alarm is given by the FACP, it will be released in all groups of the Control Centre. The LEDs Alarm of all fire alarm buttons and of the Control Centre will light up. The alarm function will be executed as described in Section.. Resetting the alarm will be done at the FACP. If no more alarm is present (if necessary, press the button Reset ), the LEDs Alarm will go out and the buzzer will be deactivated... Repetition of OPEN cycle in the case of alarm To ensure reliable opening of the actuators when an alarm has been activated, even in adverse circumstances (e.g. when seals are icy), the OPEN command will remain in the following repetition cycle for a period of 0 minutes: actuators move for minutes in OPEN direction, briefly in CLOSE direction and then for minutes again in OPEN direction, and so forth.. Status lights / functions of the SHE hand-operated fire alarm buttons For activating and resetting an alarm, see... Status light (green LED, main alarm point RT --BS) indicates: Troublefree operation. As soon as a malfunction is detected, this light will go out. Status light (red LED, all RT ) indicates: Alarm. Status light (yellow LED, main alarm point RT --BS) indicates: Malfunction (see also.). Red button Reset at main alarm points RT --BS serves to reset the alarm function. Main alarm points with indication of position OPEN (RT --BS-A): Status light (yellow LED) lights up, as soon as a travelling command in direction OPEN has been activated. If a travelling command in direction CLOSE has been active for the same length of time, the light will extinguish. Main alarm points with buzzer for indication of alarm and malfunction (RT --BS-AA): In the case of an alarm, the buzzer will emit a steady tone, while in the case of malfunction, an intermittent tone will be given. Yellow button Reset serves to deactivate the warning tone.. Status lights / control elements in Control Centre and in enclosure door Status lights in the enclosure door: Status lights, and in the enclosure door have the same function as the lights of the main alarm point (see.). Status lights on main board: Status light indicates: Troublefree Operation. When a fault is detected, this light will go out. Status light indicates: Malfunction-Power Supply (see also.). Status light indicates: Alarm (in RWZ.. provided separately for both SHE groups). Status light indicates: Malfunction Actuator / Signal Line (see also.). In RWZ.. light is provided separately for both RWA groups. Status lights / indicate active travelling commands in OPEN or CLOSE direction; they are provided separately for both ventilation groups. Page

SHEVS Control Centre RWZ d Button Reset (reset alarm): Red button Reset serves to reset the alarm function (see.). At Control Centres with two SHE groups (RWZ..), button will control both groups at the same time. Button Reset / (Reset Warning Tone / Timer): Yellow button Reset serves to deactivate the warning tone. Function Reset has been provided for installation and maintenance purposes only (see.). Potentiometer (ventilation position): see.. Potentiometer (ventilation time): see... DIP switches for setting of functions Auto Close DIP switch S- (first ventilation group) and S- (second ventilation group): In position ON, the actuators will be automatically closed upon reset of a present alarm. Once this function has responded, indoor ventilation will not be possible for up to. Factory setting: ON (automatic closing activated). Malfunction = Alarm DIP switch S- (first SHE group) und S- (second SHE group): In position ON, the alarm function proceeds as described in Section. if a malfunction is present in a signal line. After clearance of the fault, the alarm will be reset by pressing the button Reset at a main alarm point or at the Control Centre. Factory setting: OFF (no alarm in the case of malfunction). Thermal Alarm DIP switch S-: In position ON, an alarm will be triggered as soon as the enclosure inside temperature rises over 70 C. Factory setting: OFF (no triggering of alarm at temperature rise over 70 C). One ventilation group DIP switch S- and S-: In position ON, both ventilation groups will be controlled at the same time when pressing the ventilation buttons. Stroke limitation and Auto Close remain adjustable separately. Factory setting: OFF (ventilation functions separated for both groups). Travelling time min DIP switch S- (first ventilation group ) and S- (second ventilation group): In position ON, travelling commands for the actuators will be deactivated after minutes only. Factory setting: OFF (deactivation after minutes).. Ventilation functions When executing the ventilation functions, be sure not to exceed the rated duty cycle of the actuators. The two ventilation groups can be controlled either separately, or at the same time by activation of the function One ventilation group (see.)... Manual ventilation After briefly pressing a ventilation button ( / ), the actuators will travel up to their end positions or to the selected ventilation position (see..). If the button is pressed again, the actuators will stop. If the button is pressed for reverse sense of travel, the actuators will briefly stop and then reverse. If the button is pressed for a longer time (> s), the actuators will be travelling as long as the button remains pressed. This likewise permits actuator travel up to the end position or to the selected ventilation position (see..)... Setting / deactivation of ventilation position (stroke limitation) When stroke limitation is activated, the actuators operating in ventilation mode will not open beyond the desired ventilation position, determined by adjusting the travelling time in OPEN direction. Travelling times from to 0s or to 0s can be adjusted for this purpose (depending on total travelling time, see below). When the adjusted ventilation position is reached, there will be no response to pressing button. Actuators will fully open only in the case of alarm or deactivated function. Factory setting: stroke limitation is activated and set to approx. s. Page

SHEVS Control Centre RWZ d Activation / setting: Turn potentiometer P. (group ) or P. (group ) to adjust the ventilation position: Turning clockwise will increase the opening angle or deactivate the function. Turning counterclockwise will reduce the opening angle. Every time the setting has been changed, fully close the actuators using button. For precise setting, measure the opening time from the closed position to the desired ventilation position. Of a meter having a DC measuring range (V) up to V, connect (+) pole with measuring point MP. (group ) or MP. (group ) and the (-) pole with measuring point GND. Carefully turn potentiometer P. (group ) or P. (group ) for setting the appropriate value (see table): a) Actuators with total travelling time min (DIP switch S- / S- in position OFF) Opening time s 0s s 0s s 0s s 0s s 0s s 0s Setting P 0,V 0,V,0V,V,80V,9V,8V,97V,V,7V,V,V (Calculation of values: U = (t s) 0,078V/s) b) Actuators with total travelling time min (DIP switch S- / S- in position ON) Opening time 0s 0s 0s 0s 0s 0s 70s 80s 90s 00s 0s 0s Setting P 0,V 0,V,00V,8V,77V,V,,9V,0V,9V,07V,V (Calculation of values: U = (t s) 0,08V/s) Deactivation: Turn potentiometer P. (group ) or P. (group ) up to the right-hand end position to deactivate the function. After deactivating the function, fully close the actuators using button... Setting / deactivation of length of ventilation time (automatic closing upon ventilation) The function ventilation time has been factory deactivated. With this function activated, the actuators operating in ventilation mode will automatically close when the adjusted time ( to 0 minutes) has elapsed. Activation / setting: Turn potentiometer P. (group ) or P. (group ) to set the ventilation time: Turning clockwise will increase or deactivate the ventilation time. Turning counterclockwise will reduce the ventilation time. For precise setting, proceed as follows: Of a meter having a DC measuring range (V) up to V, connect the (+) pole with measuring point MP. (group ) or MP. (group ) and the (-) pole with measuring point GND. Carefully turn potentiometer P. (group ) or P. (group ) for setting the appropriate value (see table): Ventilation time min min 7min 8min 0min min min min min 7min 8min 0min Setting P 0,00V 0,V 0,V 0,9V,V,9V,8V,V,V,7V,0V,9V (Calculation of values: U = (t min) 0,V/min) Deactivation: Turn potentiometer P. (group ) or P. (grooup ) up to the right-hand end position to deactivate the ventilation time... Indication of position in ventilation button Status light lights up as soon as a travelling command in direction OPEN has been activated. If a travelling command in CLOSE direction has been active for the same time, the status light will go out... Blocking of ventilation If due to insufficient power reserves the accumulators are not likely to ensure the standby time of 7 hours, there will be no response to pressing the ventilation button. Closing by pressing ventilation button (or by an active WRC) is still possible. Indoor ventilation is possible again as soon as the accumulators have been sufficiently recharged. Blocking of ventilation does not affect an alarm... External Wind and Rain Control (WRC) Response of the Wind and Rain Control causes the equipment to automatically close. The ventilation functions remain disabled until enabled by the WRC again. An alarm will have priority. Page 7

SHEVS Control Centre RWZ d..7 Internal Wind and Rain Control (Option WRM) Response of the wind or rain sensor causes the equipment to close automatically. The yellow LED Wind or Rain on the module lights up. The ventilation functions remain disabled until enabled again by the wind and rain module. An alarm will have priority. The response thresholds of the sensors can be adjusted at the potentiometers for wind and rain on the module by means of a screwdriver: Turning clockwise will increase the sensitivity. Turning counterclockwise will reduce the sensitivity. Factory setting for both sensors is maximum sensitivity. Too low sensitivity settings may result in damage due to wind and rain, which will not be covered by our liability. The rain sensor, after having responded, will be heated. This enables the sensor surface to dry up more quickly once the rainfall is over, so that indoor ventilation may be resumed. Reduced sensitivity to wind DIP switch W:S-: In position ON, the Control will be less sensitive to gusts of wind. This setting does not affect the sensitivity to steady wind. This setting should only be used for sufficiently sturdy and rugged structures! Factory setting: OFF (normal sensitivity). Continuous heating of rain sensor DIP switch W:S-: In position ON, the rain sensor will be continuously heated at reduced power. This will prevent, for example, formation of dew in the morning, which would result in an activation of the sensor. If the sensor is activated by rain, the heating will operate at full power until the sensor is dry. Factory setting: OFF (heating is active only when sensor has responded).. Repetition of CLOSE cycle If an actuator overload protective function responds (e.g. due to gust of wind) during an automatic closing command (WRC, Auto Close, mains failure), the cycle can be repeated by briefly pressing ventilation button. The actuators will open for a short time; thereafter, the closing command will be activated again..7 Mains failure In the case of mains power failure the accumulators cannot be charged, but will supply the necessary power for a standby time of 7 hours. Mains power failure does not affect the alarm functions. Actuators in ventilation position will close, and there will be no response to ventilation button if pressed. Mains failure has to be cleared without delay, to avoid activation of the deep-discharge protection of the accumulators, to recharge them and thus ensure reliable operation of the equipment. Deep-discharge protection: In the case of critical condition of the accumulators, the complete Control Centre including status indications will be switched off. Please note that a low rest current (in addition to natural self-discharge) will still be flowing. Therefore the accumulators, if not recharged, are already in danger of being permanently damaged after a few days only..8 Potential-free contacts (PFC, option PK) PFC (PFC Alarm): The contact is activated when an alarm is detected. When the alarm has been reset, the contact will switch back into neutral position. PFC (PFC Malfunction): PFC Malfunction will be activated upon detection of a malfunction (see.). After clearance of the fault, the contact will switch back into neutral position..9 Outputs for controlling external warning devices (option WTM) The outputs for controlling external warning devices (such as multiple-tone sounder MS and strobe BL) will be activated as soon as an alarm has been detected. An early deactivation of output MS is possible by pressing an external reset button or pressing the yellow button Reset at the Control Centre or at main alarm points with buzzer. Resetting the alarm will automatically switch off the two outputs. Page 8

SHEVS Control Centre RWZ d Output MS upon malfunction DIP switch WT:S-: In position ON, the output for the multiple-tone sounder is activated on detection of a malfunction. When the fault has been cleared, the output will be automatically deactivated again. Factory setting: OFF (activation in case of alarm). Output BL upon malfunction DIP switch WT:S-: In position ON, the output for the strobe is activated on detection of a malfunction. When the fault has been cleared, the output will be automatically deactivated again. Factory setting: OFF (activation in case of alarm). Auto Reset DIP switches WT:S- and WT:S-: The output for the multiple-tone sounder will be automatically deactivated when the selected time has elapsed, even in the case of the alarm / malfunction still being present. For setting, please refer to the table beside. Factory setting: Both OFF (no automatic deactivation). Auto Reset DIP DIP deactivated OFF OFF after min OFF ON after min ON OFF after min ON ON Reset BL DIP switch WT:S-: In position ON, the output for the strobe will also be deactivated when Reset is pressed, or automatically deactivated according to the setting of the Auto Reset table. Factory setting: OFF (deactivation only after reset of alarm / clearance of fault).. Maintenance If no other relevant codes and regulations prevail, check all functions and indications of the Control Centre and its components at least once a year. This will also include checking the terminal points, connecting lines, indicators and fuses as well as cleaning various components where necessary. Check mounting brackets etc. for firm seating. Grease actuators and SHE Units (windows, domelights etc.) where necessary. For the individual functions of the Control Centre please refer to Section. Simulate malfunctions as well, and check whether they are reliably detected; see. Information about accumulators: Check the accumulators for proper function once a year and replace them every four years latest (observe date of installation / manufacture)! Instant method for checking the accumulators: Remove line fuse F. Voltage at the accumulator contacts will then be approx. - 7V. Activate the alarm function (open actuators). During opening, the voltage at the accumulator contacts should not fall below V. Reinsert line fuse F! The end user as last possessor is obliged to return waste batteries / accumulators to a distributor or to the public waste management authorities. This obligation to return batteries / accumulators concerns any end user, private and commercial. When putting the equipment out of service or deactivating it temporarily, accumulators must be unplugged and the line voltage turned off! Charged accumulators that are not connected can be stored for about months. If stored longer, they have to be recharged. Reset of travel control timers: Double click yellow button Reset in the Control Centre to reset the travel time control timers. This feature serves the sole purpose of shortening the time required for installation and maintenance work, it being not necessary to wait for timers to have elapsed before checking other functions. Within s after double-clicking, non-retracted actuators can be retracted by briefly pressing a ventilation button. In this case, the closing command will remain activated for or minutes depending on the setting of DIP switches S- / S- (see.) Caution when ventilation position is active: Double-clicking the button makes the Control Centre assume that all actuators are closed. If this is not the case, a selected ventilation position may be overridden by a subsequent opening action. Therefore, be sure all actuators have closed upon completion of the installation / maintenance work (if necessary, press button again)! When directly operating actuators, e.g. by external accumulators in the course of installation and maintenance work, be sure actuators are disconnected from the Control Centre! Otherwise, damage to the Control Centre power output may occur. Page 9

SHEVS Control Centre RWZ d Equipment with integrated Wind and Rain Module: The following work / checks have to be performed at least once a year: Clean the rain sensor with a damp cloth, using a mild detergent if necessary. Do not scour the sensor surface! Check the wind sensor for free movement Check the sensor functions Check all SHE Units / Ventilation Units for proper closing action. Fault finding / troubleshooting. General information Presence of a malfunction will be shown by yellow LEDs in the Control Centre door and at the main alarm points. As soon as a malfunction is detected, LED will go out. Owing to the separately arranged LEDs Malfunction-Power Supply (mains, accumulator, earth fault, service display module) and Malfunction (signal lines, actuators, accumulators) on the main board, causes of the malfunctions can be located. Detailed indication / analysis of faults using the Service Display Unit SD (see.). Detected malfunctions are: Accumulator or mains failure Failure of fuses F to F Wire-break or short-circuit of signal lines Wire-break or short-circuit of actuator supply lines Service module SVM (optional) is active, or has been removed In the event of malfunction, contact Maintenance Services, if necessary. Spare material: A bag with spare fuses and resistors is available in the Control Centre. Checking the signal lines: If a fault is thought to have originated here, the signal lines should be disconnected one after another in the Control Centre. Next the resistance can be measured at the ends of each signal line in the Control Centre:. Measure the two wires against each other: ~ 0kΩ Signal line is OK ~ 0Ω Short-circuit > 0kΩ Wire-break. Measure the two wires against the PE terminal: ~ 0Ω Earth fault For further measurement the respective terminating resistor (taken from the spares bag or from the last firedetector) may be connected in the Control Centre again (delivery condition). If a fault is not detectable any longer, the malfunction is probably due to a line or wiring fault or to a defective fire detector. Page 0

SHEVS Control Centre RWZ d. Displays of Service Display Unit SD Using the optional Service Display Unit SD the operating conditions can be shown precisely. For this purpose, insert a display unit into slot Service Display for controller µc, µc (SHE group ) or µc (SHE group, RWZ.. only): Slot for Service-Display Unit SD The following tables give an overview of different operating conditions of the Control Centre. The character shown in the Service Display Unit indicates normal condition. Displays of controller µc: Display Cause Mains failure or fuse F / F blown Accumulator failure or fuse F blown Blocking of ventilation active Service module SVM (optional) active or has been removed Charge with constant current (no fault) Charge with constant voltage (no fault) Abbreviations: SC = short-circuit WB = wire-break Displays of controller µc (SHE group ): Display Cause in alarm state Cause in malfunction state Line : alarm Line : wire-break Line : alarm Line : short-circuit Line : alarm Line : wire-break Alarm activated by internal thermal sensor Line : short-circuit Line : wire-break, Malfunction = Alarm activated Line : wire-break Line : short-circuit, Malfunction = Alarm activated Line : short-circuit Line : wire-break, Malfunction = Alarm activated Fuse F. blown Line : short-circuit, Malfunction = Alarm activated WB / SC actuator supply line group Line : wire-break, Malfunction = Alarm activated Fuse F. blown (RWZ..) Line : short-circuit, Malfunction = Alarm activated WB / SC actuator supply line group (RWZ..) Displays of Controller µc (SHE group ): Display Cause in alarm state Cause in malfunction state Line : alarm Line : wire-break Line : alarm Line : short-circuit Line : alarm Line : wire-break Alarm activated by internal thermal sensor Line : short-circuit Line : wire-break, Malfunction = Alarm activated - Line : short-circuit, Malfunction = Alarm activated - Line : wire-break, Malfunction = Alarm activated - Line : short-circuit, Malfunction = Alarm activated - - Fuse F. blown - WB / SC actuator supply line group Page

SHEVS Control Centre RWZ d. Technical data. Versions SHE- Ventilation- Type Ident No. groups groups Output current RWZ..-8d 800 0 8D00 8A (V / 9W) RWZ..-8d 800 0 8D00 8A (V / 9W) RWZ..-d 800 D00 x8a (V / 8W) RWZ..-d 800 D00 x8a (V / 8W). General Dimensions in mm (W x H x D): 00 x 00 x Cable entry through membrane grommets (from above): x M, x M Environmental class III (to VdS 8): Relative humidity: Degree of protection provided by enclosure (to DIN EN 09): - to +0 C 0 to 80%, no condensation IP0 Not to be used outdoors. To be protected from direct exposure to sun rays, moisture and excessive formation of dust! To be installed preferably at dry and heated indoor location.. Power supply unit Line voltage supply: 0V~ / 0Hz Current input: 0,A Internal voltage supply: V / 7 hours for line failure RWZ..-8d: Sealed lead-acid accumulators: x V / 7Ah, VdS approved I / U - charge: max. 70mA (9,V) / 7,V RWZ..-d: Sealed lead-acid accumulators: x V / Ah, VdS approved I / U - charge: max.,a (9,V) / 7,V. Inputs Automatic fire detectors: (Line ): Smoke detector / heat detector (RM / TM or RM / TM ): Hand operated fire alarms (non automatic fire-detectors): (Line ) Secondary alarm point (RT -) Main alarm point (RT --BS) Main alarm point (RT --BS-A, with indication of position OPEN ) Main alarm point (RT --BS-AA, with buzzer ) Fire Alarm Control Panel: (Line ) Terminating resistor: Release resistor: 0 pieces per SHE group total of 0 pieces per SHE group, max. of these with buzzer NO contact with 0kΩ ±0% ¼W kω..,kω ±0% ½W Other: Ventilation button (LT): unlimited for each ventilation group Ventilation button with indication of position OPEN (LT-A): 0 pieces per ventilation group Wind and Rain Control (WRC): NC contact (WRC must have a separate contact for each SHEVS Control Centre to be controlled) Page

SHEVS Control Centre RWZ d. Actuator outputs Rated voltage: Maximum cross section of supply cable: Admissible voltage drop from Control Centre to actuator: V (+V / -V) x 0mm² (rigid) per output V at full load Max. total output current: RWZ..-8d ( outputs) 8A (e.g. A + A or A + A) RWZ..-d ( outputs) A (each max. 8A) If actuator arrangement is simple (no complex branching), the following cable lengths per output are admissible: Current Cross section,0a,0a,0a,0a,0a,0a 7,0A 8,0A x,mm² m m m m 9m 7m m m x,mm² 7m m m 8m m m 0m 9m x,0mm² m 8m 9m 9m m 9m 7m m x,0mm² 7m 87m 8m m m 9m m m x 0,0mm² 90m m 97m 7m 8m 8m m m x,mm² 87m m 9m m 7m m m m x,mm² m 7m 8m m 9m m m 8m x,0mm² m m 77m 8m m 9m m 9m x,0mm² 8m 7m m 87m 70m 8m 0m m x 0,0mm² 80m 90m 9m m m 97m 8m 7m When cores are used, connect cores each in parallel.. Line monitoring Signal lines: Actuators (unbranched common line): wire-break, short-circuit wire-break, short-circuit.7 Fuses Mains primary (G fuse link x0mm): F: T A Mains secondary (G fuse link x0mm): F: T,A Actuators (G fuse link x0mm): F., F.: T 8A Accumulators (flat car fuse 9mm): RWZ..-8d: F: 0A RWZ..-d: F: 0A.8 Potential-free contacts (option PK) Contact load rating PFC-, PFC- (change-over contacts): A / 0V / 0V~ Fuses PK-, PK- (G fuse links x0mm): P:F, P:F: F A.9 Outputs for controlling external warning devices (option WTM) Multiple-tone sounder MS: Strobe BL: V / max. 00mA V / max. 0mA.0 Internal Wind and Rain Control (option WRM) Wind sensor WM: Heated rain sensor RS: Response threshold setting range for wind : Response threshold setting range for rain : piece piece approx. - m/s or 0-0km/h (approx. wind force - 7) drizzle - stronger rainfall. EC statement of conformity The Control Centre meets the demands concerning emission to DIN EN 000-- and DIN EN 0, concerning immunity to DIN EN 000-- and DIN EN 00-. Page

SHEVS Control Centre RWZ d System diagram (please consider local conditions / components) st SHE / ventilation group Example of connection on page, detailed examples on following pages. Option PK Page 9 Option WTM Page 9 st SHE group Page MS x0,8 RM / TM RM / TM x, (0V~) / x0,8 (0V-) x, (0V~) / x0,8 (0V-) BL External warning devices PK- PK- x0,8 (max. 00m) (x0,8 with external reset button) x0,8 Page 7 F FACP x0,8 SHEVS Control RWZ x, x0,8 for WRC or Page 0 L/N/PE x0,8 for option WRM Page Mains x, For max. admissible lengths of cable, please refer to section "Technical Data". When using cores ( cores each in parallel) greater lengths can be achieved. Max. 0mm² can be clamped. L/N/PE Wind- and Rain Control (WRC) WRC x0,8 Page 8 Option WRM WM / RS st ventilation group x0,8 Page 7 LT x0,8 for LT-A LT x0,8 0x0,8 Smoke Exhaust Smoke Exhaust x0,8 x0,8 st SHE group Smoke Exhaust WM / RS Number of wires depends on type and order of connection of the hand operated fire alarms. Other groups: Components in the second SHE- or ventilation group will be connected in accordance with the examples given for the first group. See also RT --BS-AA-A RT --BS RT - Pages + General: length of cable max. 00m, if not specified otherwise. RWZdA.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /08 Mo Jan. 8, 008 Page / 0

SHEVS Control Centre RWZ d Example of connection X0 Mains PE N L Rend (x0k) X. Actuators When connecting fire detectors, remove terminating resistor Rab from Control Centre and connect it to the last detector. X. Line Rab (0k) Rab (0k) Line When attaching a FACP, remove terminating resistor Rab from Control Centre and connect it as shown. Ventilation button 7 8 9 0 7 8 When conecting an external WRC, remove shorting bridge. Rab (0k) X Line 9 0 WRC 0V~ / 0Hz Open +, Close - Open -, Close + RM+ RT+ LED Alarm Reset Alarm LED OK LED Malfunction RT-SA+ RT-LED Open Warning tone Reset warning tone LT-Close LT-C LT-Open LT-LED-Open FACP+ Rab (0k) RT- RM- FACP- Ral (k) WRC-C WRC-NC RM / TM RM / TM L L out L in 7 9 9 P + - br bl 8 0 Rend (x0k) Alarm Reset Sound Smoke Exhaust bl br F NO C 0 LT-A FACP WRC WRS WM / RS When connecting actuators, remove end resistors Rend from the Control Centre and connect them to the last actuator. In case of wrong travelling sense, reverse polarity of actuator cable. Terminal blocks of the groups: group group Actuators X. X. Signal lines X. X. Main alarm point RT --BS-AA-A (with buzzer and indication of position open) Colour code for resistors: 0k = brown/black/black/red k = brown/green/black/brown RWZdA.sch When attaching a FACP, connect release resistor Ral (k / 0,W) as shown. It is taped to the Control Centre door when delivered. PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /09 Mo Oct., 009 Page / 0

SHEVS Control Centre RWZ d V- actuators In case of wrong travelling sense, reverse polarity of actuator cable. bl br st actuator st SHE / ventilation group X. Rend (x0k) Open +, Close - Open -, Close + br bl nd actuator monitored common line When connecting actuators, remove final resistors Rend from the Control Centre and connect them as shown. Rend (x0k) br bl rd actuator nd SHE / ventilation group X. Rend (x0k) Open +, Close - Open -, Close + The nd group will be connected as shown for the st group, but using terminal strip X.. Colour code for resistors: 0k = brown/black/black/red RWZdA.sch! When directly operating actuators, e.g. by external accumulators in the course of installation and maintenance work, be sure actuators are disconnected from the Control Centre! PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /08 Mo Jan. 8, 008 Page / 0

SHEVS Control Centre RWZ d Automatic fire detectors st SHE group Automatic fire detectors RM / TM (terminals L in, L out and L) or RM / TM (terminals, and ) X. Line RM+ L L...... RM - Rab (0k)... Lin Lout...... Lin... Lout... Lin... L When connecting fire detectors, remove terminating resistor Rab from Control Centre and connect it to the last detector. Lout... Rab (0k) nd SHE group X. Line Rab (0k) RM+ RM - The nd group will be connected as shown for the st group, but using terminal strip X.. Colour code for resistors: 0k = brown/black/black/red RWZdA.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /07 Mo Mar., 007 Page / 0

SHEVS Control Centre RWZ d Hand-operated fire alarms (non-automatic fire detectors) st example: Main alarm point last (secondary alarm point last: see page ) st SHE group Rab (0k) Line X. 7 8 9 0 RT+ RT- LED Alarm Reset Alarm LED OK LED Malfunction RT-SA+ RT-LED Open Warning tone Reset warning tone Alarm Reset Sound 7 9 9 8 0 0 Smoke Exhaust Terminals and in the last main alarm point with indication of position open to be linked as shown.! A B C D E F G H Smoke Exhaust A B C D E F G H Smoke Exhaust When connecting fire detectors, remove terminating resistor Rab from Control Centre and connect it to the last detector. Alarm Reset 7 9 8 0 Smoke Exhaust! Rab (0k) Terminals, 0 and in the last main alarm point to be linked as shown. nd SHE group Main alarm point RT --BS-AA-A (with buzzer and indication of position open) Secondary alarm point RT - Secondary alarm point RT - Main alarm point RT --BS-AA-SA X. Rab (0k) 7. RT+ RT- LED Alarm The nd group will be connected as shown for the st group, but using terminal strip X.. Terminals A - H of the secondary alarm points are provided only for looping-through the signals to following main alarm points. Colour code for resistors: 0k = brown/black/black/red RWZdA.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /0 Mo Oct. 7, 00 Page / 0

SHEVS Control Centre RWZ d Hand-operated fire alarms (non-automatic fire detectors) nd example: Secondary alarm point last (main alarm point last: see page ) st SHE group When connecting fire detectors, remove terminating resistor Rab from Control Centre and connect it to the last detector. X. Rab (0k) Line 7 8 9 0 RT+ RT- LED Alarm Reset Alarm LED OK LED Malfunction RT-SA+ RT-LED Open A B C D E F 7 9 8 0 7 9 8 0! A B C D E F Rab (0k) Warning tone Reset warning tone G H 9 0 9 0 G H Smoke Exhaust Alarm Reset Sound Smoke Exhaust Alarm Reset Sound Smoke Exhaust Smoke Exhaust nd SHE group X. Rab (0k) 7. RT+ RT- LED Alarm Secondary alarm point RT - The nd group will be connected as shown for the st group, but using terminal strip X.. Main alarm point RT --BS-AA-A (with buzzer and indication of position open) Terminals A - H of the secondary alarm points are provided only for looping-through the signals to following main alarm points. Main alarm point RT --BS-AA-A (with buzzer and indication of position open) Colour code for resistors: 0k = brown/black/black/red RWZdA7.sch Secondary alarm point RT - Terminals, 0 and in the last main alarm point to be linked as shown. Terminals and in the last main alarm point with indicationof position open to be linked as shown. PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA.sch Rev. /0 Mo Oct. 7, 00 Page / 0

SHEVS Control Centre RWZ d Ventilation buttons, Fire Alarm Control Panel (FACP) Ventilation buttons X. st ventilation group 7 8 LT-Close LT-C LT-Open LT-LED Open - P + P P P P - +! nd ventilation group X. 7 8 LT-Close LT-C LT-Open LT-LED Open LT-A LT The nd group will be connected as shown for the st group, but using terminal strip X.. LT-A LT LT Terminals + and P in the last ventilation button with indication of position open to be linked as shown. Fire Alarm Control Panel (FACP) When attaching a FACP, remove terminating resistor Rab from Control Centre and connect it as shown. Line Rab (0k) X 9 0 FACP+ FACP- FACP FACP NOcontact Rab (0k) When attaching a FACP, connect release resistor Ral (k / 0,W) as shown. It is taped to the Control Centre door when delivered. Ral (k) Colour code for resistors: 0k = brown/black/black/red k = brown/green/black/brown RWZdA8.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA7.sch Rev. /09 Mo Oct., 009 Page 7 / 0

SHEVS Control Centre RWZ d Wind- and Rain Control (WRS / option WRM) External Wind and Rain Control (WRS ) X Terminals WRS Rain sensor RS WRC-C WRC-NC When connecting an external Windand Rain Control, remove shorting bridge between these terminals. 7 WRS Internal relay contact WM Heating RS RS GND r bl bk Surface of sensor br bl Wind sensor WM or Depending on the system the following contacts of WRS can be used: NC C Internal Wind and Rain Control (option WRM) 8 9 contact contact contact contact Option WRM W: Rain sensor RS Use a separate contact for each SHEVS Control Centre to be controlled! WM Heating RS RS GND r bl bk br Wind sensor WM Surface of sensor bl RWZdA9.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA8.sch Rev. /0 Mo Oct. 7, 00 Page 8 / 0

SHEVS Control Centre RWZ d Potential-free contacts (option PK), multiple-tone sounder and strobe (option WTM) Potential-free contacts Option PK P: P:F Internal PFC relay PFC-A-NC PFC-A-C PFC-A-NO PFC- (PFC Alarm) Caution! External voltage! P:F Internal PFC relay PFC-M-NO PFC-M-C PFC-M-NC PFC- (PFC Malfunction) Multiple-tone sounder and strobe Option WTM WT: MS+ MS- + - Multiple-tone sounder MS BL+ BL- + - Strobe BL External reset button for reset of option WTM (reset also possible by push-button in Control Centre or main alarm points RT --BS-AA) RWZdAA.sch PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdA9.sch Rev. /09 Mo Oct., 009 Page 9 / 0

SHEVS Control Centre RWZ d Line voltage and accumulators Line voltage: X0 L N PE L N PE 0V~ / 0Hz Accumulators: Main board RWZ (-) Accu (+) bl r - + + bk - V Accu V Accu Place accumulators into enclosure as shown and connect them. Important: When putting the Control Centre into and out of service, observe the operating instructions! Be sure to disconnect the accumulators if mains voltage supply is cut out for a longer time. PNEUMATIK R:\RWZ\d\Doku\RWZd.ddb - En\RWZdAA.sch Rev. /0 Mo Oct. 7, 00 Page 0 / 0