MIXING RATIO AND ABSOLUTE HUMIDITY

Similar documents
Chapter 14, Problem 27.

Thermo-physical properties found on most psychrometric charts

Atmospheric Moisture: Relative Humidity and Dew Point

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

Thermodynamics II Chapter 6 Mixtures & Psychrometry

There are (at least) four reasons why you need to understand moisture and humidity in building physics:

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Session 3 Humidity definitions & units

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Moisture in the Atmosphere. GEOG/ENST 2331 Lecture 9 Ahrens: Chapter 4

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

TEACHER BACKGROUND INFORMATION Water Cycle

More heat energy means more of what type of energy? Does the mass change? So, what must change? What is the same in both containers?

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Use this Construction/HVAC Glossary to answer the questions below.

Last exam / sista tent

What Will Happen? If you leave a hot drink on the table and wait for a while, does the drink heat up or cool off?

Psychrometric Engineering Applications

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

HVAC (Heating, Ventilating, and Air Conditioning)

Air Conditioning Clinic

Unit THE NATURE OF HEAT

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

EVAPORATION NEEDS ENERGY

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Water in the Atmosphere

ENGINEERING LETTER 4

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

R07. Answer any FIVE Questions All Questions carry equal marks *****

SIR C.R.REDDY COLLEGE OF ENGINEERING, ELURU DEPARTMENT OF MECHANICAL ENGINEERING ETD-II. Model Short Answer Questions And Answers

ω = (1) Kirby S. Chapman Ph.D.

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

Humidity An excuse for the 80s

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Chapter 5: Atmospheric Moisture

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

2. In areas of the world where outdoor temperatures are low enough to drop the interior building temperature below setpoint.

The Refrigeration Cycle

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

The Refrigeration Cycle

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Humidity Generation and Humidity Measurement The Complete Guide

Armstrong Cool-Fog Systems

Heat pump and energy recovery systems

Principles of Cold Insulation

HUMIDITY IN INCUBATION

6. Within an internal combustion engine, the can-shaped component that moves up and down the cylinder

Wavelength-of-Light Compensation

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Separation Processes: Drying

Lecture 7 Water in the Atmosphere

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

EqUIPMENT LAYOUT MANUAL


3.4 Humidity. Types of instruments

Solar Still - Improved Distillation

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems

PRINCIPLES OF REFRIGERATION ~ CHILLER EFFICIENCY & CONDENSATION by PM Husband

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

L14 ENVIRONMENTAL CONTROL TECHNICAL DATA

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Drying principles and general considerations

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Working under relative and absolute humidity with DSC, calorimetry, TGA and TMA techniques

PHYSICS OF FOIL HEAT GAIN/LOSS IN BUILDINGS

Meteorology 432. Hygrometry Spring 2013

(Refer Slide Time: 00:00:40 min)

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Hygrometry. The art or science of humidity observation

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

A Review of Hydronic Balancing of Cooling Water Circuit

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

LESSON CLUSTER 9 Explaining Condensation and the Water Cycle

Psychrometric chart (Temperatures and humidities within the yellow box are comfortable.)

SECTION THIRTEEN HEATING, VENTILATION, AND AIR CONDITIONING

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

Pressure Enthalpy Charts

LOW ENERGY CLIMATE CONTROL FOR MUSEUM STORES

1. What are the scales of temperature? What are the formulas to convert among them? Fahrenheit, Celsius, Kelvin

ICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

HRU ECO 4. System 4 Continuous Mechanical Supply and Extract Ventilation with Heat Recovery Appendix Q Eligible

USING THE P-T CARD AS A SERVICE TOOL

Changes of phase usually involve a transfer of energy Evaporation

Heat Recovery Units. Heat Recovery 1

3. Turn on the electrical power supply to the dryer, and move the safety disconnect handle mounted on the dryer s upper power box to on.

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Transcription:

MIXING RATIO AND ABSOLUTE HUMIDITY The units used for describing water vapour in air are many, and confusing. This chapter is about Mixing Ratio (MR) and Absolute Humidity (AH). The Mixing ratio (also called specific humidity) is a strange phrase but comes nearest to our intuitive understanding of concentration - the amount of one component in a mixture. The mixing ratio of water vapour in air is the weight of water vapour mixed into a given weight of dry air. The unit is kg/kg. This is the vertical axis of the psychrometric chart. There are two common uses for the mixing ratio. In meteorology the mixing ratio is useful for tracing the properties of vast air masses as they rise or fall in the atmosphere. The mixing ratio of a discrete blob of moist air does not change with varying atmospheric pressure and temperature as it moves in the atmosphere. In the more down to earth science of air conditioning, the mixing ratio is useful in calculations involving air as the transporter of water vapour through ducts to control the room humidity. Air is also the transporter of heat to control the room temperature. Calculations of the energy used in air conditioning have to combine the thermal properties of both air and water vapour.

In forensic studies of the microclimate in historic structures the mixing ratio is used to study the effects of infiltration, because its value is a much more sensitive way of differentiating between air streams than the relative humidity, which is the customary environmental measurement in museum conservation. On a cold day the outside air often has a high relative humidity but its mixing ratio is always quite small, because of the low saturation water vapour content at low temperature, and the relatively high density of cold air. At zero degrees and 85% RH the mixing ratio is just 0.0032 (kg/kg). Inside the steamy kitchen shown in the figure below, the RH is the same, but the temperature is higher. The air density is lower than outside but the water vapour is much more abundant, because the same RH at a higher temperature is represented by a higher water vapour concentration. The mixing ratio is 0.014. The kitchen has a broken window, so outside air is pouring in and flowing over the floor, because it is denser. Gradually it warms and mixes with the kitchen air as well as extracting moisture from absorbent furnishings. This process can be followed by watching the increase in mixing ratio as one traverses the room from the outside wall inwards.

The mixing ratio requires knowing the total air pressure. In practice, the mixing ratio is calculated from measurement of the relative humidity and the temperature, assuming a typical air pressure of 101 kpa, at sea level. Air moving into a room loses its identity rather quickly, as it mixes and warms. In the author's front room there is a horizontal sash window, which ensures a good air flow to the wood burning stove but also ensures a crisp chill in the room when the stove is unlit. On a cold winter morning most of the glass panes are fogged because they are the coldest surface in the room, so vapour from the furnishings and the ever-damp walls of the ancient house condenses there. However, the outside air, of equally high RH on this drizzly day, keeps the column of panes below the arrow well scrubbed with outside air flowing parallel to the glass through the vertical gap between the two halves of the window.

These glass surfaces are actually cooler than the other panes, being exposed on both sides to outside air, However, there is no condensation because the stream of incoming air is above the dew point and quickly warms up as it enters the room, so the RH reduces further. The effect is very small scale - the panes of the leftmost column are just as fogged as those on the right side. The mixing ratio changes rapidly as the invading air merges with the room air. Use of the mixing ratio is therefore best confined to air masses so large that their water vapour exchange with the surroundings is very slow. Indoors, such isolation is only achieved within air conditioning ducts.

In the free space of a room the mixing ratio quickly loses its identity. So I will next explain a near relative of the mixing ratio which is numerically very similar but gives a more direct insight into the vapour concentration in space. The Absolute humidity of the air is the concentration of water vapour expressed as the weight of water in unit volume of space. In an isolated space this does change with pressure. because the space shrinks under pressure, pushing the water molecules closer together. However, in most situations relevant to conservation, except air transport and picture relining, the total atmospheric pressure remains nearly constant. The absolute humidity of a packet of air also changes slightly as it expands with temperature - proportionately to the kelvin temperature, meaning about one part in 300 per degree change in temperature. Analysis of the consequences of air exchange Analysis of the effect of air infiltration on the relative humidity in a room begins with a measurement of the air exchange rate. This is usually calculated from the fall in concentration of a trace gas as it exits the room, at the room temperature. The rate is expressed as room volumes per hour. (An alternative technique is to slightly pressurise the room with a fan mounted in a temporary, close fitting door. One measures the air passing through the fan at a given pressure difference, then looks up the equivalent air exchange rate.)

If the outside air is colder, the air coming in will initially have a smaller volume than the air going out, because it will expand to match the outgoing volume as it warms up. During the warming process the mixing ratio does not change, so it can be directly compared with the mixing ratio of the room air as a first step towards calculating the change of room RH resulting from the mixing process. If after one hour, the room has acquired 0.1 volumes of outside air, the mixing ratio is one tenth of the outside ratio plus nine tenths of the inside ratio. To find out if this matters to the room contents, the mixed up mixing ratio has to be converted to RH. Remembering that air has no influence on the RH, one first converts the mixing ratio to the absolute humidity in the interior space, which is then converted into the vapour pressure and finally into RH. Here is an example calculation: at 20 C the density of dry air is 1.2041 kg/m 3. If the mixing ratio is 0.007 (kg/kg) the concentration (absolute humidity) of water vapour is 0.007 x 1.2041 = 0.0084 kg/m 3. The vapour pressure is obtained from the gas law P = nrt. n is the mass of water vapour expressed in moles, which is 0.0084 divided by 0.018 kg which is the molar mass of water. This is = 0.47 mol. R is the gas constant: 8.31 Joules/mol/m 3. This mysterious factor is just there to reconcile the units of the real participants.

Remembering that T is in degrees kelvin, the partial pressure of water vapour is 0.47 x 8.31 x 293 = 1144 Pa. The saturation vapour pressure, taken from tables or formula, is 2326 Pa, so the RH is 1133/2326 = 49%. Atmospheric water vapour is usually measured and recorded as RH, so to understand how RH changes with infiltration and other processes that mix two portions of air at different water content and temperature, one has to flip back and forth between four definitions for moisture in air: the mixing ratio, the absolute humidity, the vapour pressure and the relative humidity. However, in practice one can bypass the mixing ratio stage by calculating the absolute humidities of the air masses, if the temperatures are not vastly different. This is not strictly correct, but remember that all these quantities are in practice calculated from measurements of temperature, pressure, which is usually assumed, and relative humidity, which is difficult to measure with better than 2 % accuracy. Source: http://www.conservationphysics.org/teabag/ah_mr.php