GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Similar documents
GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

RK-05 Combustible Gas Transmitter Operator s Manual

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

MGC Dock User s Manual

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

RK Combustible Gas Transmitter Operator s Manual

RK-03 Hydrogen Detector Operator s Manual

RK Transmitter Technical Notice

RK / RK Methane Detector Operator s Manual

MGC Dock User s Manual

Model D12-IR. Digital Gas Transmitter...

RK Multi Point Detector Operator s Manual

QUICK REFERENCE GUIDE

Hydrocarbon Gas Detector

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

RK/ RK Combustible Gas Detector Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

NH 3 RESPONDER Portable Ammonia Leak Detector QUICK REFERENCE GUIDE

GasAlertMicro 5. 1, 2, 3, 4, and 5 Gas Detectors. Quick Reference Guide

SEC Millenium Hydrocarbon Gas Detector

Operation and Maintenance Manual

RK-02 Multi Point Detector Operator s Manual

RK-05 Carbon Monoxide Transmitter Operator s Manual

NH3 RESPONDER PORTABLE AMMONIA LEAK DETECTOR. Quick Reference Guide

RK Carbon Monoxide Transmitter Operator s Manual

Operator s Manual. 1, 2, 3, and 4-Gas Detector

Single Gas Clip and SGC Plus User s Manual Rev 2.1 READ FIRST BEFORE OPERATION WARNING STATEMENTS / AVERTISSEMENT Activating tthe detector for the

RK CO 2 Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

SEC 5000 IREvolution Gas Detector

Operator s Manual. 1, 2, 3, and 4-Gas Detector

Combustible Gas Sample-Draw Detector Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

RK-04 M2 Transmitter Operator s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.3

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

RK / RK CO 2 Detector Operator s Manual

G.O.L.D. GAS OPERATIONS LEAK DETECTION USER MANUAL

RK/ RK Oxygen Detector Operator s Manual

Operation and Maintenance Manual

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

MICROpeL 75 Combustible Gas Sensor Part Number: PM

GasAlertMicro 5 and GasAlertMicro 5 PID O 2, CO, H 2 S, PH 3, SO 2, Cl 2, NH 3, NO 2, HCN, ClO 2, O 3, VOC, and Combustibles

CMF, CMX & CMA series

Combustible Gas/Hydrogen Sulfide Sample-Draw Detector Operator s Manual

SEC Signature Process Gas Analyzer

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

RK/ RK Oxygen Detector Operator s Manual

SGOES Infrared Hydrocarbon Gas Detector Operating Manual

FLAMMABLE GAS DETECTOR DAX 3F-C INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FC_MAN01_EN.indd Ver. V1R2

MODEL GC802 NOVA-SENSOR ELITE COMBUSTIBLE GAS DETECTOR

STAINLESS STEEL FLAMMABLE GAS DETECTOR DAX 3F-I INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FI_MAN01_EN Ver. V1R2

Carbon Dioxide Sample-Draw Detector Operator s Manual

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

RK/ RK Carbon Monoxide Detector Operator s Manual

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

RK-HC-04 M2A Transmitter Operator s Manual

Combustible Gas/Carbon Monoxide Sample-Draw Detector Operator s Manual

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

SEC Millenium Carbon Dioxide Gas Detector

GAS MONITOR Model Model

Vanguard. Toxic & combustible gas detector

VQ500 Series Combustible Gas Detector Elements

Flammable gases Detectors. Model DAX 03F DAX 03F- C DAX 03F- H. Note for installation, use and maintenance. Version 1.2

Controllers. Instruction Manual WARNING

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

Instruction Manual WARNING

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

Combustible Gas Detection and Control System

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

Single Gas Detector. Quick Reference Guide

Macurco HD-11 Hydrogen Gas Detector

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

SEC 2000 Millenium Infrared Gas Detector

GAS PLUS ALARM SYSTEM

Beacon 800 Gas Monitor Operator s Manual

Transcription:

GG-LEL2 COMBUSTIBLE GAS SENSOR Installation and Operation Manual

2 GG-LEL2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel.

GG-LEL2 3 Table of Contents General description....6 Installation....6 Locating the sensor....6 Installation guidelines....7 Wiring...8 Operation....9 Start-up...9 Calibration....9 Maintenance...12 Specifications....13 Warranty....14 For technical support, contact: Calibration Technologies 920 N Trade Winds Pkwy Columbia, MO 65201 866-394-5861 sales@ctiengineering.com www.ctiengineering.com

4 GG-LEL2 General Description The GG-LEL2 sensor is a +24 VDC, three-wire, 4/20 ma sensor for combustible gases. It is designed to detect and monitor potentially explosive levels combustible vapors in air over the range of 0-100% LEL. It provides an industry standard linear 4/20 ma output signal compatible with most gas detection systems and PLCs. The GG-LEL2 provides real-time continuous monitoring of high concentrations of combustible gases utilizing catalytic bead sensor technology housed in a corrosion resistant stainless steel shell with a sintered metal flame arrestor isolating the sensing element from the ambient air. A ¾ NPT thread on the sensor housing mates with the threaded entry on the explosion-proof transmitter enclosure. Most codes specify an alarm notification at a level not higher than 25% LEL to remove potential ignition sources in the event of a gas leak. Catalytic-bead gas sensors respond to and measure concentrations of a vast majority of flammable gases, with the notable exception of gases which poison catalytic oxidation catalysts, such as silicones and many sulfur bearing chemicals. More frequent calibrations may be necessary if operating in these conditions. Installation Locating the sensor One of the most important considerations when installing GG-LEL2 sensors is that they should be easily accessible for calibration and maintenance. When installing only one GG-LEL2 sensor in a room or area, centrally locate the sensor in the center of all potential leak sources. If the target gas is lighter than air, mount sensor closer to the ceiling where the gas will likely accumulate. If the target gas is heavier than air, mount sensor closer to the floor. As a general rule of thumb, mount sensors within 30 feet of potential leak sources.

GG-LEL2 Installation Guidelines: Mount sensor enclosure through the mounting holes as shown in Figure 1. If mounting on a wall with studs, the mounting screws should be screwed into the studs. Must be easily accessible for calibration and maintenance. Mount the sensor vertically with the sensor pointing down. Mount the sensor within 30 feet of the potential leak source. Take air movement and ventilation patterns into account. To prevent electrical interference, keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters. If mounting sensor outdoors, consider prevailing wind direction and proximity to the most likely source of leaks. Protect the sensor from sun and rain. 5 Figure 1: Mounting Dimensions

6 GG-LEL2 Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 80 ma. Output: Linear 4/20 ma output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet. Monitoring: Monitoring equipment must be configured to indicate a fault if the signal is below 1 ma. All signals over 20 ma must be considered high gas concentrations. Alarm setpoints should not be lower than 10% of full-scale range. Wiring Guidelines: Always disconnect power at the controller before performing any wiring at the sensor. Always use three conductor, insulated, stranded, shielded copper cable. Do not pull sensor wiring with AC power cables. This can cause electrical interference. If cable runs cannot be made without a splice, all splice connections should be soldered. Ground the shield at the main control panel. Tape the exposed shield wire at the sensor to insulate it from the enclosure. To maintain certification rating of the enclosure, conduit fittings of the same rating or better must be used. Terminal Block Plug (Field Wiring): SHLD: To case (earth) ground of monitoring equipment GND: To ground terminal of power supply +24V: To +24V terminal of power supply SIG: To signal input of monitoring equipment

GG-LEL2 Operation Start-Up It is usually best to disconnect external alarms and other equipment from the sensor until the initial start-up procedures are completed. Because sensors are normally located at a distance from the main unit, the test time required and accuracy of the response checks will be improved if two people perform the start-up procedures and use radio contact. Start-Up Test: 1. One person exposes each sensor to calibration gas or gas sample such as propane or butane. 2. The second person stays at the control unit to determine that each sensor, when exposed to the gas, is connected to the proper input and responds, causing appropriate alarm functions. Relative Response Table (with 2.5% Methane) Gas Voltage (mvdc) Methane 120 Propane 163 n-butane 163 n-pentane 183 n-hexane 200 Hydrogen 111 Ethane 139 Ethylene 168 Ethanol 152 7 Calibration The combustible gas sensor has a slightly different response to each combustible gas or vapor. Because of these factors, a combustible transmitter must be adjusted differently if the system is meant to detect a gas or vapor other than methane. 2.5% methane gas can be used for calibration of the combustible transmitter when used for other gases. The voltage that you set at the transmitter test point will be different for each gas. The table below provides the voltage setting for various gases. Note: Ensure area is free from explosive gases before removing cover while sensor is energized. The GG-LEL2 sensor comes factory calibrated and should require only minimal adjustments after installation. There are two pots on the preamp that are used for calibration. (see Figure 2)

8 GG-LEL2 Note: Never measure sensor output in ma. Always use mvdc or VDC voltmeter settings. Calibration Mode: Cal mode is required for calibrating the sensor. It clears the deadband (factory set at 4.8 ma) and averaging. Pressing the CAL switch enables cal mode and the green LED will flash. To exit out of cal mode, press the CAL switch or after 6 minutes it will automatically time out. Zero Calibration: After the unit is installed and has been powered up for a minimum of 1 hour, the unit can be zero calibrated by the following: Press the CAL switch once to enter cal mode. Do not adjust the zero pot if the green LED is not flashing. Be sure the unit is in clean air. If unsure, apply zero air gas to the sensor to properly zero calibrate. Adjust the zero pot until the sensor outputs 40 mv from Test [-] to Test [+] (see Figure 2). Span Calibration: If span adjustment is required, the following procedure will span the unit: Apply 2.5% CH4 span gas at 0.5 to 0.8 L/min (span gas must be in air, not nitrogen or other carrier). Sensor should react to gas within 15 seconds. Once the output signal has peaked (or 2 minutes maximum) adjust the span pot until the correct output is achieved (see Relative Response Table and Figure 2). Calibration is now complete. 4mA Adjustment: Sometimes a fine adjustment of the 4mA signal may be desired to compensate for a slight positive or negative zero-signal reading on the control panel. Make sure the sensor is NOT in calibration mode. Adjust the 4mA pot until the control panel reads zero. Sensor replacement: If sensor replacement is required, follow the procedure below. Note: Ensure area is free from explosive gases before proceeding. Unscrew the sensor cover. Unplug 3-position sensor plug from transmitter. Unscrew sensor head from enclosure and discard. Carefully install new sensor and plug into transmitter. Refer to calibration section on page 7 to calibrate new sensor. Note: Below are a few response characteristics which may be an indication that the gas sensor is at or near the end of its useful life. If any of these are observed, the sensor may need to be replaced: Slow response to / recovery from calibration gas. Failure of the output to reach 50% of the calibration gas value prior to span adjustment if last calibration was 6 months ago or less. Unable to achieve correct output during calibration.

GG-LEL2 9 Green LED indicates power Red LED indicates hardware fault Calibration switch Span adjustment Zero adjustment 4mA adjustment Sensor head plugs in here Sensor head Figure 2: Sensor output and zero/span adjustment

10 GG-LEL2 Maintenance The GG-LEL2 was designed for long life and minimal maintenance. For proper operation, it is essential that the test and calibration schedule be adhered to. Calibration Technologies recommends the following maintenance schedule: Maintenance Guidelines: The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from purchase date. Calibrate the detector at least once every 6 months. Calibration should be performed with certified calibration gas. Calibration kits and replacement cylinders are available from Calibration Technologies. In highly critical areas or where poisoning from silicones or sulfur compounds may be present, a response test should be performed between calibrations to verify proper sensor response and alarm functions. This can be done with calibration gas or a gas sample such as propane or butane. All tests and calibrations must be logged. Always disconnect power at the controller before performing any wiring at the sensor. Sensor Life: Typical sensor life of the GG-LEL2 sensor is five years. Although extremely reliable, a few things can cause the sensor to become depleted including: a long period of time continuous exposure to high concentrations of silicon vapors and lead compounds When the sensor reaches the end of its useful life, the unit will give no indication of failure other than that the sensor will not respond. Therefore, it is absolutely essential that these sensors be calibrated on a regular basis. Sensor Replacement: Replacement sensors can be obtained from Calibration Technologies. Disconnect the sensor from the transmitter, unscrew the sensor from the enclosure, discard the old sensor and replace it with the new one. The sensor can be calibrated after a 1-hour warm-up period. Replacement cell order# GG-LEL2-RS

GG-LEL2 11 Specifications Detection Principle: Catalytic Bead Detection Method: Diffusion Gas: Combustible Gases Range: 0-100% LEL (lower explosive limit) Output Signal: Linear 4/20 ma (max input impedance: 700 Ohms) Power Supply: +24 VDC, 80 ma Response Time: T 50 = less than 30 seconds T 90 = less than 60 seconds Accuracy: +/- 3% of full-scale Zero Drift: Less than 0.1% of full-scale per month Span Drift: Application dependent, but generally less than 3% per month Linearity: +/- 0.5% of full-scale Repeatability: +/- 1% of full-scale Sensitivity: 1% LEL Wiring Connections: 3-conductor, shielded, stranded, 20 AWG cable (General Cable C2525A or equivalent) up to 1500 ft. Temperature Range: -40 F to +140 F (-40 C to +60 C) Dimensions: 6.75 high x 5.25 wide x 4.5 deep Weight: 3.75 lbs Sensor Head: Stainless steel flameproof enclosure constructed with an integral stainless-steel sinter filter for the safe entry of the atmosphere being detected. ATEX Certificate CESI 01 ATEX 066 U Enclosure: Copper-free aluminum body, epoxy powder coat finish, neoprene gasket, for hazardous areas. NEC/CEC: Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class II, Division 2, Groups F, G Class III NEMA/EEMAC: 3, 4, 4X, 7BCD, 9EFG UL Standard: 1203 CSA Standard: C22.2 No. 30 FM Classification No.: 3615 ATEX Certificate KEMA 02 ATEX 2265U IEC Standards EN:60079-0, EN:60079-1, EN:60529

12 GG-LEL2 Limited Warranty & Limitation of Liability Calibration Technologies, Inc. (CTI) warrants this product to be free from defects in material and workmanship under normal use and service for a period of two years (including the sensor element), beginning on the date of shipment to the buyer. This warranty extends only to the sale of new and unused products to the original buyer. CTI s warranty obligation is limited, at CTI s option, to refund of the purchase price, repair, or replacement of a defective product that is returned to a CTI authorized service center within the warranty period. In no event shall CTI s liability hereunder exceed the purchase price actually paid by the buyer for the Product. This warranty does not include: a) routine replacement of parts due to the normal wear and tear of the product arising from use; b) any product which in CTI s opinion, has been misused, altered, neglected or damaged by accident or abnormal conditions of operation, handling or use; c) any damage or defects attributable to repair of the product by any person other than an authorized dealer or contractor, or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on: a) proper storage, installation, calibration, use, maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI; b) the buyer promptly notifying CTI of any defect and, if required, promptly making the product available for correction. No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period. THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CTI SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY

GG-LEL2 13

14 GG-LEL2

GG-LEL2 15

ctiengineering.com 866-394-5861 GG-LEL2-DOC1-2 20180221