NFN VESDA-HLI-GW. Programming and Operation Manual. Document: LS NF-E 6/26/12 Rev: A2. P/N: LS NF-E: Rev.

Similar documents
The RPT-485W/RPT-485WF

ONYXWorks. ONYXWorks NOTIFY IP. Installation & Operation Manual. Document /23/11 Rev: A3 P/N: 53620:A3 ECN:

The System 5000 Operating Manual

BACnet Gateway-3. Installation and Operation Manual. Document /6/09 Rev: A P/N: 53372:A ECN:

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

Supplement to the AM2020/AFP1010 Voice Alarm Multiplex Manual Number 15889, Revision F1, dated 12/11/97

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

CHG-120 Battery Charger Instruction Manual. Document /06/2002 Rev: B1 PN 50641: B1 ECN

FCPS-24F/FCPS-24FE. Field Charger/Power Supply D P/N 50079:D ECN Installation, Operation and Application Manual

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

Conventional Fire Alarm Control Panel

ECC-50DA/E ECC-125DA/E ECC-50BDA/E. Distributed Audio Amplifiers. Installation Manual C. Document LS FL-E 1/30/2014 Rev:

PN:51264:A2 ECN Remote Fire Annunciator FDU-80. Document /14/00 Rev: A.

PS-Tools. User s Guide for the 50 Pt Addr Panel

1 UL 864 Compliance. 2 Product Overview. Network Communications Module NCM-W/F Product Installation Document. 1.1 Products Subject to AHJ Approval

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual

SEE DISCLAIMER ON REVERSE

Liquid Crystal Display LCD-160. Manual. Document /16/2013 Rev: D1 P/N 51850:D1 ECN

IndigoVision Alarm Panel. User Guide

Annunciator Control System ACS Series

EXTINGUISHING AGENT RELEASE MODULE

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

The MC-1. Master Clock System

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual

Simplex Panel Interface Guide

FCPS-24/FCPS-24E. Field Charger/Power Supply. Installation, Operation and Application Manual.

Annunciator Modules. for Fire Lite Fire Alarm Control Panels. Document # /30/95 Revision:

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Installation Instructions

Liquid Crystal Display LCD-160. Manual. Document /26/2003 Rev: A P/N 51850:A ECN

PN 50257:E ECN NOTI FIRE NET. Manual. Document 50257:E 7/5/01 Rev: E. Technical Manuals Online! -

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

Lamp Driver Module LDM-32F

Digital Alarm Communicator/Transmitters 411/411UD. Manual. Document LS GE-E 1/29/2014 Rev: A P/N LS GE-E:A ECN

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

Document /14/2012 Rev: A3 P/N :A3 ECN

PN: 51604:A ECN Voice Evacuation Control Panel FIRE COMMAND 25/50X & FIRE COMMAND 25/50XE. Document # /17/02 Rev.

UNC100 Integra Manual

ONYX FirstVision Specification Interactive Firefighters Display

Digital Alarm Communicator/Transmitter. Document # /07/00 Rev. P/N 50921:C ECN

Model SWH-4000 Multi-Technology Mullion 125 KHz and MHz (Flex) Reader Installation Guide. Version A0 Part Number UM-104 September 2005

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Section PERIMETER SECURITY SYSTEMS

Installation, Configuration and User Manual

Monitoring Operator Guide. Access Control Manager Software Version

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

Digital Alarm Communicator/Transmitter 411UD. Document # /07/00 Rev. P/N 50759:C ECN

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

LaserFOCUS VLF-250 Engineering Specification

Model SWH-3000 Proximity Multi-Frequency 125KHz & 13.56MHz (Fixed) Reader Installation Guide. Version A0 Part Number UM-102 September 2005

Laptop / PC Programming Manual

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

4100U City and Relay Cards Installation Instructions

NFS-3030/E. Fire Alarm Control Panel. Programming Manual. Technical Manuals Online! -

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Fire Operator Workstation (Fire OWS) User s Guide

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

Ion Gateway Cellular Gateway and Wireless Sensors

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty...

Model SK Installation and Operations Manual. Fire Control / Communicator. Document Rev: P P/N :P ECN:

Panic. Part Number SYSTEMS, Inc.

VESDAnet Interface Card Product Guide. Document Number: 10672_05 Part Number: 30071

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN

Advantium 16 System Monitor

RC300 IntelliFire Plus Multifunction Remote Control Installation & Operating Instructions

Static Pressure Control

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788

E3 Series Expandable Emergency Evacuation Installation/Operating Manual. Document: Print Date: 6/6/07 Rev: C

Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

Added password for IP setup page : Password must be in IP format!

ONYXWORKS AND FIRSTVISION. Version 4

Beacon 800 Gas Monitor Operator s Manual

MGC Dock User s Manual

INSTRUCTION MANUAL PC255O

Advisor Advanced Mobile Application User Manual

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

The ADT SLC Signaling Line Circuit Manual

Alarm Client. Installation and User Guide. NEC NEC Corporation. May 2009 NDA-30364, Revision 9

CFP-2410B. Programming, Installation, Maintenance and Operating Manual. Conventional Fire Alarm Control Panel.

AUTOPULSE IQ-636X-2/E ANALOG ADDRESSABLE CONTROL SYSTEM

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual

Avigilon Control Center 5 System Integration Guide

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

FieldServer Driver - Serial FS Notifier NCA

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

Watchguard WGAP864 User Manual

MODEL 5100 BROADBAND ALARM COMMUNICATOR INSTALLATION & USER S GUIDE PRODUCT ID #

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Long Range Radio Alarm Transmitter

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Introduction... 1 System Overview... 1 System Diagram... 2

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

VA301C CONTROLLER WITH BACnet OPTION

Supervisor Standard Edition

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Transcription:

NFN VESDA-HLI-GW Programming and Operation Manual Document: LS10023-000NF-E 6/26/12 Rev: A2 P/N: LS10023-000NF-E: Rev. A2 ECN: 12-0294

Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. These documents can be found at http://www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because: Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets. Smoke particles may be drawn into air returns before reaching the detector. The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo-electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-ofrise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that: Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. 2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0 C to 49 C (32 F to 120 F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32 C ± 2 C (90 F ± 3 F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements: This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. This Class A digital apparatus complies with Canadian ICES-003. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Cet appareil numerique de la classe A est conforme a la norme NMB-003 du Canada. HARSH, NIS and NOTI FIRE NET are all trademarks; and Acclimate Plus, FlashScan, NOTIFIER, ONYX, ONYXWorks, VeriFire and VIEW are all registered trademarks of Honeywell International, Inc. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. 2012 by Honeywell International, Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3

Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or manuals, please e-mail us at FireSystems.TechPubs@honeywell.com. On-Line Help Please include the following information: Product name and version number (if applicable) Topic title The content you think should be corrected/improved Detailed suggestions for correction/improvement Documents Please include the following information: Document part number and title Page number and paragraph The content you think should be corrected/improved Detailed suggestions for correction/improvement Please Note: If you have any technical issues, please contact Technical Services. Manual Usage This manual is written with the understanding that the user has been trained in the proper operations and services for this product. The information provided in this manual is intended to assist the user by describing the configurations and how they affect operations. 4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Table of Contents Table of Contents Section 1 Product Overview...3 1.1: Product Description...3 1.2: Features...3 1.3: Compatibility...4 1.4: System Architecture...4 Figure 1.1 Network Architecture...5 1.5: IP Port Requirements...6 1.6: Installation Overview...6 1.6.1: Required Equipment...6 1.6.2: Power Supply and Communication Connections...7 1.6.3: Board Layout...7 Figure 1.2 VESDA-HLI-GW Board...7 Table 1.1 LED Definitions...8 Section 2 Configuration...9 2.1: Configuration Web Page...9 2.2: Connecting the Configuration Computer...9 2.3: Configuring the VESDA-HLI-GW...9 2.3.1: Logging into the Web Page...9 2.3.2: VESDA-HLI-GW Configuration Menus...10 2.3.3: VESDA-HLI-GW Configuration Settings...10 2.3.4: Zone Mapping and Control by Event...12 Table 2.1 Zone Setting/Alarm State Relationships...12 2.3.5: Error Log...13 Table 2.2 Error Log Message Definition...13 Appendix A: IP Settings...15 A.1: Viewing Existing Settings...15 A.2: Resetting Factory Default Settings...15 Appendix B: Viewing Gateway Configuration... 17 B.1: Required Equipment...17 B.2: Viewing the Configuration...17 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 1

Table of Contents 2 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

1.1 Product Description Section 1 Product Overview The VESDA-HLI-GW provides a communication link between the NFN network and the VESDAnet. This link enables event notification and control of devices on the VESDAnet through the NFN network. Event notifications are displayed on the fire network annunciators. Control can be initiated from these annunciators. 1.2 Features Monitor (NCA-2, LCD-160, ONYXWorks) - Highest Priority event is shown on annunciators. Prealarm Fire Alarms Point Disable Troubles: Detector Fault Scanner Fault Power Fault Low Flow High Flow Filter Fault Field Wiring Fault Auto learn Failure No Answer. NOTE: The trouble categorizations are generic and each encompasses several troubles. Further information can be obtained by referring to XTralis resources. Supervision Troubles: Modbus Communications Fault (Indicates that VESDA-HLI-GW can not talk to VESDA devices.) VESDA Trouble Read Status: Device Type Alarm State - Alert/Action/Fire1/Fiew2/Trouble/Isolated Smoke Level - This is a percentage of obscuration from 0% to 3.1% as defined by VESDA Detector Alarm Thresholds Control (From NCA-2 and ONYXWorks): Reset - Resets all detectors on the VESDAnet Isolate/Enable - Isolates (Disables) and enables single detector on the VESDAnet Silence - Silences all local piezos on detectors Acknowledge VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 3

Product Overview Compatibility Other: Zone Mapping DCC mode is supported for Canadian applications Walk test is not supported by the VESDA gateway History - Rolling history is maintained on the gateway Alarms and Prealarms are latched by the VESDA detectors. Reset is required to unlatch. 1.3 Compatibility Refer to the LS10026-051NF-E VESDA-HLI-GW Listing Document for supported panels and annunciators. Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the VESDA-HLI-GW. 1.4 System Architecture The VESDA-HLI-GW: Uses a Modbus RS-232 interface to VHX-1420-HFS Supervises the communications to the VHX-1420-HFS Monitors 100 detectors Displays VESDA devices as type Aspiration on the display nodes. Multiple events per point are not supported. The detector will be in one of the following states: All Systems Normal Prealarm Fire alarm The following events can be simultaneous with the above events: Disabled Trouble Supported VESDA Detectors: VESDA Laserplus (VLP) VESDA Laserfocus (VLF) VESDA Laserscanner (VLS) VESDA Lasercompact (VLC) 4 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

System Architecture Product Overview RS-485 VESDA VLP VESDA VLF VESDAnet VESDA VLC VESDA VLS VHX-1420-HFS RS-232 VESDA-HLI-GW HS-NCM OR NCM Workstation Embedded Gateway NFN Network Display Node FACP FACP FACP Figure 1.1 Network Architecture VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 5

Product Overview IP Port Requirements 1.5 IP Port Requirements The following IP ports must be available to the VESDA-HLI-GW: Port Type 80 TCP 4016 TCP 62957 TCP The following restrictions apply: Functionality Infrastructure Restriction Must have a Static IP Address, DHCP is not supported. Web Access does not support access through an HTTP Proxy server, because port 62957 is not accessible 1.6 Installation Overview! CAUTION: Multiple VESDA-HLI-GW Installations All VESDA-HLI-GWs must be installed and configured one at a time because all VESDA-HLI-GWs use the same predefined IP address and node number. Install the VESDA-HLI-GW as described in the VESDA-HLI-GW Listing Document (LS10023-051NF-E). 1.6.1 Required Equipment VESDA-HLI-GW Assembly: The following components are shipped with the VESDA-HLI-GW: VESDA-HLI-GW printed circuit board NUP-to-NUP Cable (P/N 75556) - Used to connect the VESDA-HLI-GW board to a standard NCM and supported panel USB Cable (P/N 75665) - Used to connect the VESDA-HLI-GW board an HS-NCM board:. Wire Leads to NUP Network Communications Module power cable (P/N 75583) Network Components: RJ45 to RJ45 standard Ethernet network cable - Customer s internet or intranet connection NFN Network, version 5.0 or later Cables - P/N 50110140-001 Serial cable between the HS-NCM and the VHS-1420-HFS High-Speed Network Communication Module: HS-NCM-W HS-NCM-MF HS-NCM-WMF HS-NCM-SF HS-NCM-WSF HS-NCM-MFSF Standard Network Communication Module NCM-W NCM-F Customer-Supplied Equipment: A computer to run Internet Explorer and configure the VESDA Gateway 6 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Installation Overview Product Overview VESDA Required Equipment (not including power supplies) VHS-1420-HFS 1.6.2 Power Supply and Communication Connections The VESDA-HLI-GW must be correctly connected to a power source meeting applicable requirements and other equipment in the system in order to function properly. For detailed connection information, refer to the VESDA-HLI-GW Listing Document (LS10023-051NF-E). 1.6.3 Board Layout USB A Host (J13) USB B Device (J14) D15 D19 D20 D33 D45 D14 D9 LED (See Table 1.1) Ethernet Connector (J8) Mounting Hole (1 of 12) D12 D10 D13 D11 NUP A Serial Data Connector (J6) NUP B Serial Data Connector (J7) Trouble Relay (TB6) TB1: -24 V Out +24 V Out -24 V In +24 V In D7 D8 D25 D18 Figure 1.2 VESDA-HLI-GW Board VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 7

Product Overview Installation Overview Table 1.1 LED Definitions Reference Designator Label Description D7 WDT Active/Lit indicates the system has undergone a reset due to a Watchdog circuit firing. D8 PWR FAIL TBD D9 ACTIVE Active/Lit indicates that WinCE is running. D10 NUPA RX Toggles on when data is received at the NUP A port. D11 NUPB RX Toggles on when data is received at the NUP B port. D12 NUPA TX Toggles on when data is sent on the NUP A port. D13 NUPB TX Toggles on when data is sent on the NUP B port D14 NFN A TBD D15 NFN B TBD D18 PROGRAM Not Used D19 USB A Active/Lit indicates a device is connected to the USB A port. D20 USB B Active/Lit indicates a device is connected to the USB B port. D33 LINK Active/Lit indicates an Ethernet connection. D45 DATA Blinks to indicate data transmission to or from the Ethernet port. 8 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

2.1 Configuration Web Page Section 2 Configuration The VESDA-HLI-GW is configured through a dedicated web page running on the embedded gateway itself. Microsoft Internet Explorer version 8 or later with the latest version of JAVA is required to configure the VESDA-HLI-GW. 2.2 Connecting the Configuration Computer The computer used to configure the VESDA-HLI-GW must be able to establish an IP connection to the VESDA-HLI-GW. The default IP address of the VESDA-HLI-GW is 192.168.1.2. Consult your network administrator if unsure how to make this connection. Refer to Appendix A, IP Settings for instructions on resetting and reviewing the IP settings for the VESDA-HLI-GW. 2.3 Configuring the VESDA-HLI-GW 2.3.1 Logging into the Web Page 1. Start Microsoft Internet Explorer. 2. Navigate to the IP address of the VESDA-HLI-GW (default is http://192.168.1.2). 3. Depending on the version of Java installed on the configuration computer, a security prompt may appear. If it does, click NO to proceed to the configuration web page. 4. If prompted, click Run to enable the applet. 5. When the login dialog box displays, enter the password (default is eight zero characters) and then click Login. VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 9

Configuration Configuring the VESDA-HLI-GW 2.3.2 VESDA-HLI-GW Configuration Menus Menu Sub-Menu Description File Reboot Displays a dialog box allowing the user to reboot the VESDA-HLI-GW. Tools History Displays an events log with date, time, type of event, and description. Set Gateway Password Displays a dialog box allowing the user to change the current password. Default: 00000000 (eight zeros) Passwords are case sensitive. Alpha and numeric characters are supported. One character minimum and 8 characters maximum. Backup... Restore... Delete Objects Database Browse to the folder where you would like to store current VESDA-HLI-GW configuration settings, and then click Save. Displays a dialog box allowing that allows the user to restore the VESDA- HLI-GW configuration settings to a previously saved state. Displays a dialog box allowing the user to choose to delete the objects database and reboot. Upgrade Firmware In the Look In drop down menu, select the file name that begins, #VGNUW and has the extension.ar. Then click Open. An on-screen dialog indicates a successful upgrade. Language Displays a dialog box from which the user can navigate to and select the desired language file. 2.3.3 VESDA-HLI-GW Configuration Settings Navigation Pane Item Sub-Item Property/ Node Description VESDA Gateway (read only) Type Displays the gateway type by name. Version Displays the gateway version number. Board Type Displays the hardware model type. Kernel Version Displays additional software version information. Boot Version Displays additional software version information. Current Time/ Date Displays the current date/time information. Additional Properties IP Address Settings IP Address Click the value to change the IP address. (Default is 192.168.1.2) Refer to Appendix A:, "IP Settings" for additional information. Subnet Mask Click the value to change the subnet address. (Default is 255.255.255.0) IP Gateway Click the value and enter the IP address of the IP Gateway for the host network. (Default is 0.0.0.0) MAC Address This is the Media Access Control (MAC) address of the gateway Ethernet port and is not configurable. NFN Settings Node Click value to assign the NFN node number of the VESDA-HLI-GW. (Default is 0) 10 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

Configuring the VESDA-HLI-GW Configuration Navigation Pane Item Sub-Item Property/ Node Description Additional Properties (Cont d) NFN Settings (Cont d) Panel Label Click value to enter panel label. (Default is Vesda Gateway) DCC Enable Check the box for DCC (Display and Control Center) participation. This network function ensures that one location at a time is in command of the Acknowledge, System Reset, Signal Silence, and Drill functions. Channel A Threshold Select High for a high-noise NFN network. Set to Low for a low-noise NFN network. Channel B Threshold Select High for a high-noise NFN network. Set to Low for a low-noise NFN network. NFN Information (Read Only) Style 7 Check the box for a Style 7 SLC (Signaling Line Circuit) configured NFN network. Uncheck the box for a Style 4 SLC configured NFN network. Connection Port Connection Type NCM Version Displays Serial when the VESDA-HLI-GW connects to an NCM through the serial port or if there is no NFN connection. Displays USB when the VESDA-HLI-GW connects to an HS-NCM via USB. Describes how the gateway is connected to the NFN. Displays the NCM version number. Note: NCM Version does not appear when there is no NFN connection. NCM Status Bits Displays the NCM status, which can be: Piezo, UPS Failure, Network Fail Port A, Network Fail Port B, High Speed Audio, NCM Sniffer Mode Active, Local Connection Limit Exceeded, or None. Mapping Zone Label Configuration Fire Network Time Policy Label Note: NCM Status Bits does not appear if when there is no NFN connection. Always displays Accept Time since VESDA-HLI-GW accepts the time from the network, but does not broadcast time to the network. Check the box next to each detector with which the gateway will communicate. Once mapped, the gateway is able to access detector information. Double-click to display a list of zone labels. Click on the zone to display its property screen. Click on the value to change the zone label. Click Save to save the change. Monitored Zone List Label Extended Label Zone Configuration Click the value to enter the label for the detector. Read only. Displays a list of the ten general zones supported by the gateway and their settings. Click on the zone number or <Enter Zone> label to enter/change the zone to be monitored. Click the value and select the Cooperative Control By Event (CCBE) level from the drop-down menu. Click Save to save the changes. Error Log Refer to 2.3.4, "Zone Mapping and Control by Event" for details. Label text is red when there is an error. Click to display date, time, and error description information. Refer to 2.3.5, "Error Log" for details. VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 11

Configuration Configuring the VESDA-HLI-GW 2.3.4 Zone Mapping and Control by Event The VESDA-HLI-GW can be configured for 10 general zones per VESDA device. Zones 0 to 999 are supported with Zone 0 being a general alarm zone that is active if any detectors are in the FIRE1 or FIRE2 state. The zones have the following characteristics: All Zones activated by the gateway remain active until there is a reset issued from the NFN. At that time, all the zones related to detectors being reset are cleared. A zone remains active as long as any detectors assigned to that zone are active. A zone goes into trouble state when any of its detectors become disabled or in trouble. The zone remains in a troubled state until all of its detectors are enabled and not in trouble. When the detector is disabled, zones can go off (if the point goes off), but cannot go on (if the point goes on). Note that enabling a point may also result in zones going active, if the point went active while it was disabled. Disabling of zones is not supported by the VESDA-HLI-GW. Zone disables are ignored. Points must be disabled individually. Force On/Off of zones is not supported. Read Status of zones is supported. The Table 2.1, Zone Setting/Alarm State Relationships describes when zones are activated for each zone setting for each alarm state. An X indicates that the zone will be activated. There are two labels, the 20-byte standard label and the 12-byte custom label. The Network Control Annunciator (NCA) displays them along with the events. There are 10 slots for Cooperative Control By Event (CCBE) per detector. Each slot can be set to one of the zones 1-999. In the Value column of the slot there is a selection for what type of event will cause the one to go active. The possible types of events are Alert, Action, Fire1, Fire2 and Any. Zones are cumulative in the given order. For example, an Action event triggers the Action and Alert zones. A Fire1 event triggers the Fire1, Action and Alert zones. A Fire 2 event triggers all zones. Table 2.1 Zone Setting/Alarm State Relationships Alarm State Alert Action Fire1 Fire2 Zone State Setting Alert X X X X Action X X X Fire1 X X Fire2 X Any X X X X 12 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

Configuring the VESDA-HLI-GW Configuration 2.3.5 Error Log The error log displays specific information when the VESDA-HLI-GW detects a trouble condition. When a trouble condition is present, the output relay also de-energizes. The following table defines the possible errors displayed in the log: Table 2.2 Error Log Message Definition Error VESDA Trouble Connection Not Supported Modbus Communication Fault Missing Detector # Description The VESDAnet has encountered a condition such as a break or open condition. A VSC from Xtralis is necessary to interpret the error code. Device has an invalid wiring configuration on the NUP port, for example, trying to attach an HSNCM with a serial cable. Cannot communicate with HLI. For example, HLI is unplugged. Indicates a detector programmed into the system is offline (for example # is a numeric value which is the detector number). VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 13

Configuration Configuring the VESDA-HLI-GW 14 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 : 6/26/12

Viewing Existing Settings IP Settings Appendix A: IP Settings NOTE: The procedures in this appendix require the use of a USB flash memory drive. A.1 Viewing Existing Settings 1. Connect the flash drive to the VESDA-HLI-GW. 2. Reboot the gateway. A file is created that matches the configured IP address of the gateway, followed by the extension.txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered to match the Gateway configuration. The file contains additional information such as the MAC address of the gateway. 3. Connect the drive to a PC and view the files. The flash drive should contain a file that matches the configured IP address of the gateway, followed by the extension.txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it has been altered to match the gateway configuration. The file contains additional information such as the MAC address of the gateway. A.2 Resetting Factory Default Settings 1. Connect the flash drive to a PC and create a file named default.ldc. The contents of the file is not significant; however, ensure that the file does not have an additional hidden file extension. This file will be automatically deleted from the flash drive. 2. Eject the flash drive from the PC. 3. Disconnect power from the gateway. 4. Disconnect the communication cable to the Gateway USB port (if present) and connect the flash drive. 5. Reconnect the 24 VDC power supply to the gateway. 6. After approximately one minute, disconnect the flash drive from the USB port and (if necessary) reconnect the cable removed in Step 4. 7. Connect the flash drive to the PC and verify that the file named 192.168.12.txt is on the drive. If the file is on the flash drive, the reset has been accomplished. If the file is not on the flash drive The flash drive may not have been connected during the reboot period or was removed early. The flash drive is not seen as a valid drive by the hardware. A software error has occurred and technical support may need to be contacted. VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12 15

IP Settings Resetting Factory Default Settings 16 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev. A2 6/26/12

Required Equipment Viewing Gateway Configuration Appendix B: Viewing Gateway Configuration B.1 Required Equipment VESDA-HLI-GW USB flash memory drive PC B.2 Viewing the Configuration 1. Connect the flash drive to the VESDA-HLI-GW. 2. Reboot the Gateway. A file is created that matches the configured IP address of the gateway, followed by the extension.txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it will be altered to match the Gateway configuration. The file contains additional information such as the MAC address of the Gateway. 3. Connect the drive to a PC and view the files. The flash drive should contain a file that matches the configured IP address of the gateway, followed by the extension.txt (e.g., 192.168.1.2.txt). If the file already exists on the drive, it has been altered to match the Gateway configuration. The file contains additional information such as the MAC address of the Gateway. VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12 17

Viewing Gateway Configuration Viewing the Configuration 18 VESDA-HLI-GW Programming and Operation Manual - P/N: LS10023-000NF-E: Rev: A2 6/26/12

Limited Warranty Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by Honeywell International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL INTERNATIONAL INC. S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. BACNET-GW-3 Operation and Programming Manual - P/N: LS10014-000NF-E: Rev. A2 6/26/12 25

World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com