PumpSaver ISS-105 IS Super Cell Installation Guide

Similar documents
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

D SYSTEM CONTROL DWG. APPROVED BY. OrCAD 6 ROSEMOUNT 2410

Notes: Warrick Series 67 Intrinsically Safe Multi-Function Control Installation and Operation Bulletin

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma,

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C

Pioneer-R16 Gas Monitor Operator s Manual

General Specifications

Oxygen (O2) Single-Point Gas Detection System

Mark* VIe and Mark VIeS Control Systems Equipment in Hazardous Locations (HazLoc) Instruction Guide

Single pressure controls for Refrigeration, Air-conditioning and Heatpump applications

Fisher LCP100 Local Control Panel

SECTION AUTOMATIC TRANSFER SWITCHES

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Two-Channel Gas Controller

BA488CF Intrinsically safe Panel mounting Fieldbus Display

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Fire Alarm System Accessories

ESP TECHNOLOGIES LIMITED

Pump-Up Controller MODEL 4062

Analog Room Pressure Monitor RPC Series

Guide Specification Model CTG Automatic Transfer Switch

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

4 & 8-POINT ANNUNCIATORS Instruction Manual

Pump-Down Controller MODEL 4052

Model A1600 Series Annunciator

INSTRUCTION MANUAL. SIL 2 Load Cell/Strain Gauge Bridge Isolating Converter DIN-Rail Power Bus and Termination Board Model D5264S D5264S

AO Annunciator Module

Beacon 800 Gas Monitor Operator s Manual

Certificate of Compliance

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES

DB5 Intrinsically Safe Sounder Type DB-5

2018 PRICING. alderonind.com STANDARD PRODUCTS

AUTOMATIC TANK GAUGES

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

D A R A - 4. Data Aire Relay Auto-Changeover

INSTRUCTION MANUAL. Frequency-Pulse Converter, Repeater and Trip Amplifiers Din-Rail Model D1060S D1060S

Certificate of Compliance

Soft Start Series MP700 Solid State, Reduced Voltage

Continuous Relay Controller LC52 Series Owner s Manual

SET Installation and Operating Instructions. Level switch for one sensor

Tank Gauging System Special Safety Instruction

Custom Pump Controls. The Custom Controls Solution Provider. A New Generation. Complete Management. Page 2

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

User s Manual. EJA Series Differential Pressure and Pressure Transmitters Installation Manual. 1. Introduction. 2. Handling Cautions. 3.

Alarm Panel Operating Instructions

Soft Starter Centrifugal Pump Soft Starter Series

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Installation Instructions

Unipower HPL420. User s Manual. True Motor Power Monitor with... Typical Applications. High Trip Alarm. Low Trip Alarm.

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

ELP21LU3-LF-HLOL THREE CHANNEL

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

Fire Alarm System Accessories

Commercial and Light Industrial Fire Alarm Control Panel

T7984 A,B,C Electronic Modulating Control Thermostats

5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration

Carbon Monoxide Transmitter

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Oakton TEMP 9500 Advanced Multiparameter Controller

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Certificate of Compliance

Certificate of Compliance

MR3CCUHV Temperature/Defrost Control

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

SET-2000 Oil/Sludge 12 VDC

CLEANROOM MONITOR CR3A Network - Installation Instructions

Combustible Gas Detection and Control System

4) Intrinsic Safety Certification

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

705 Emmett Street Bristol, CT DynaLock MODEL 3101C-TJ101 DELAY EGRESS SYSTEM WIRING INSTRUCTIONS

IECEx Certificate of Conformity

SET-2000 Hi Level/Oil

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

ESSEX ENGINEERING CORPORATION

Across-the-Line SERIES MP300 Combined Manual and Automatic

Transcription:

PumpSaver ISS-105 IS Super Cell Installation Guide Visit our website at www.symcom.com for our complete catalog and new product listings! 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605) 348-5685 www.symcom.com

Introduction...3 Quick Start... 4 Model Description... 5 Time Delay...5 Mode Selector... 5 Option Selector...6 1. Pumping Modes... 6 Duplex... 6 Triplex: High/Low Alarm... 6 Quadplex...6 Separate Pump Stop (SPS)... 7 2. IS Super Cell Functions... 7 High Alarm... 7 Low Alarm... 7 Out-of-Sequence Alarm...7 Audible Alarm... 8 Audible Alarm Logic/Fail-Safe...8 Clearing Alarms... 8 Alternation...8 Alternation On...9 Alternation On, Non-Alternating Pump Enabled... 9 Alternation Off...9 Disabling Pumps... 9 External Inputs... 10 External Silence / Alarm Reset... 10 External Power Reset... 10 External Alternation Configuration... 10 3. Wiring Diagrams... 10 4. 5-Channel Relay Mode... 21 Positive/Negative Logic... 21 Latched Output... 21 Time Delay Output... 22 Delay-On-Make... 22 Delay-On-Break... 22 Model ISS-105 Specifications... 23 SymCom warrants its microcontroller-based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document. 2 12/04

Introduction The PumpSaver ISS-105 IS Super Cell is a smart, fivechannel, intrinsically safe relay and pump controller. It has a long list of features that are needed for multiple pump applications. The IS Super Cell can indicate low, high and outof-sequence alarms. It can do alternating pump control, nonalternating pump control, or alternating control with one nonalternating pump. The non-alternating pump can be used as either a jockey or emergency pump and can optionally start the non-alternating pump after every 50 cycles of the lead pump, to keep it working freely. Using the built-in DIP switches, individual pumps can be disabled when taken out of service for repair or maintenance. The IS Super Cell has the following features and capabilities: 4High, Low and Out-Of-Sequence Alarms 4Variable Time Delay/Lag Pump Delay 4Separate Pump Stop 4Pump Alternation w/ or w/o Non-Alternating Pump 4Jockey or Emergency Pump 4Duplex, Triplex or Quadplex Pump Modes 4Pump Up or Pump Down Functions 4External Silence, Reset and Alternation Configuration 4Five-Channel Relay 3 12/04

Quick Start The IS Super Cell can operate as an intrinsically safe pump control for eight different pumping configurations. Duplex, Triplex, Quadplex and Duplex SPS (Separate Pump Stop) pumping modes are possible for either Pump Up or Pump Down applications. Refer to page 21 for the full description of five-channel relay operation. Read 1. Pumping Modes, page 6, for details of the features and mode descriptions of the unit. 1. If the desired pump configuration is known, follow Table 1 to the page showing the typical wiring diagram and setup for each mode. 2. If further description is needed in choosing which mode to use, see Table 2 and Table 3 to view the capabilities of each pumping mode and look at the typical wiring diagrams of the eight different pumping modes starting on page 11. 3. Once the desired configuration is determined, punch out and slide the correct card into the slot on the front of the IS Super Cell to display the input and output connections. Mode Selector Switch Mode Description Page Position 0 5-Channel Relay Mode 0 22 1 Duplex Pump Down Mode 1 11 2 Triplex Pump Down Mode 2 12 3 Quadplex Pump Down Mode 3 13 4 Duplex SPS Pump Down Mode 4 14 5 Duplex Pump Up Mode 5 15 6 Triplex Pump Up Mode 6 16 7 Quadplex Pump Up Mode 7 17 8 Duplex SPS Pump Up Mode 8 18 Table 1. Mode Selector 4 12/04

Model Description The ISS-105 has three adjustable controls to set the mode of operation: 1. Mode Selector 2. Option Selector 3. Time Delay WARNING! Time Delay To ensure proper initialization and operation, set the mode and option selectors before applying power to the unit. The Time Delay can be set from 2 255 seconds and is the Lag Pump delay in each of the pumping modes. When the Lead Float opens/closes, the Time Delay starts and once it expires, the Lag Pump is ready to turn on. After the Lag Pump turns on, any necessary pumps will turn on successively after a two-second time delay each. Mode Selector This dial is used to select the operation mode. A description of each mode is shown in Table 1. The capabilities of each pumping mode and the Non-Alternating Pump designations are shown in Table 2 below. Duplex Triplex Quadplex Duplex SPS # Pumps 2 3 4 2 High Alarm Yes *Yes No **Yes Low Alarm Yes *Yes No **Yes Out-of-Sequence Alarm Yes Yes Yes Yes # Stop Floats 1 1 1 2 Pump Direction Up/Down Up/Down Up/Down Up/Down Non-Alternating Start Float Lag 1 Lag 2 Lag 3 N/A Non-Alternation Pump Pump 2 Pump 3 Pump 4 N/A Alternator Yes Yes Yes Yes Table 2. Mode Capabilities * On a Triplex pump system, either a High or Low Alarm is available, but not both. See Triplex Mode description for more details. ** On a Duplex SPS system, a High Alarm is typical on a Pump Down application and a Low Alarm is typical on a Pump Up. 5 12/04

Option Selector Position Option Selector Table 2 describes the Option Selector for all pumping modes. ( Indicates the function is available for the pump mode) Function Description Duplex Triplex Quadplex Duplex SPS (Separate Pump Stop) 1 High Alarm * 2 Low Alarm * 3 Pump 1 4 Pump 2 5 Pump 3 6 Pump 4 7 Audible Alarm Relay State/Fail Safe 8 Alternator Select 0, (ALS-0, see Table 4) 9 Alternator Select 1, (ALS-1, see Table 4) 10 Alternator Select 2, (ALS-2, see Table 4) Table 3. Option Selector * On a Triplex pump system, either a High or Low Alarm is available, but not both. See Triplex Mode description for more details. 1. Pumping Modes Duplex In a Duplex mode, two pumps are used with one Stop Float and High and Low Alarms. Triplex: High/Low Alarm In a Triplex mode, three pumps are used with one Stop Float. In a Triplex Pump Down mode, a High Alarm is the typical configuration with the Option Selector switches 1=ON (High Alarm) and 2=OFF (Low Alarm). If a Low Alarm is desired, the alarm float must be moved to the position in the tank below the Stop Float and Option Selector switches must be 1=OFF and 2=ON. In a Triplex Pump Up mode, a Low Alarm is the typical configuration with the Option Selector switches 1=OFF (High Alarm) and 2=ON (Low Alarm). If a High Alarm is desired, the alarm float must be moved to the position in the tank above the Stop Float and Option Selector switches must be 1=ON and 2=OFF Quadplex In a Quadplex mode, four pumps are used with one Stop Float and no alarms floats. 6 12/04

Separate Pump Stop (SPS) In the Duplex SPS mode, both the Lead and Lag pumps have their own stop floats. In an SPS Pump Down mode, a High Alarm is the typical configuration with Option Selector switches 1=ON (High Alarm) and 2=OFF (Low Alarm). If a Low Alarm is desired, the alarm float must be moved to the position in the tank below the Lead Stop Float, and Option Selector switches must be 1=OFF, and 2=ON. In an SPS Pump Up mode, a Low Alarm is the typical configuration with Option Selector switches 1=OFF (High Alarm) and 2=ON (Low Alarm). If a High Alarm is desired, the alarm float must be moved to the position in the tank above the Lead Stop Float, and Option Selector switches must be 1=ON and 2=OFF. 2. IS Super Cell Functions High Alarm The High Alarm is activated when the High Alarm Float closes, indicating the pumps are unable to keep the water level down on a Pump Down application. If the High Alarm Float closes at any time, all pumps will turn on, bypassing the 10-second out-of-sequence trip delay, and the adjustable Time Delay. If a High Alarm is used on a Pump Up application, the alarm will be activated when the High Alarm Float closes indicating the water level has been pumped too high, possibly due to a defective Stop Float, and will turn off all pumps. During a High or Low Alarm, the Alarm LED and Audible Alarm LED will be on. If the High or Low Alarm condition ends, the Audible Alarm will turn off and the Alarm LED will flash indicating the alarm had occurred, but is not present now. If the High or Low Alarm occurs again, the Audible Alarm LED will turn on again, but the Alarm LED will remain flashing. The unit must be silenced or reset to clear the flashing alarm LEDs. Low Alarm The Low Alarm is activated when the Low Alarm Float opens indicating the pumps are unable to keep the water level up on a Pump Up application. If the Pump Up Low Alarm Float opens at any time, except if a High Alarm is activated, all pumps will turn on. If a Low Alarm is used on a Pump Down application, the alarm will be activated when the Low Alarm Float opens indicating the water level has been pumped too low. This may be a result of a defective stop float. The Low Alarm will not turn off the pumps though, but will activate the low alarm relay; another form of pump-dry protection such as the SymCom Model 777 may be required. Out-of-Sequence Alarm When a float in the series does not open or close in sequence, the Audible Alarm will be activated and input LED(s) will flash until the unit 7 12/04

is reset or power is cycled. An out-of-sequence condition has to exist for 10 seconds before the ISS-105 will alarm. When the stop float fails open in pump down mode or closed in pump up mode, an Out-of-Sequence Alarm will NOT occur and pumps will not turn on with floats. In this case, all pumps will turn on when the High/Low Alarm is activated. Thus, in Quadplex mode, pumps will never turn on if the Stop Float malfunctions. Audible Alarm The Audible Alarm is activated when a High, Low or Out-of Sequence Alarm occurs. The Audible Alarm will turn off when there is no longer high or low alarms or if the unit is silenced. Audible Alarm Logic/Fail-Safe The Audible Alarm relay can be configured to operate in either a Fail- Safe mode (position 7=ON), or a Non Fail-Safe mode (position 7=OFF). In Fail-Safe mode, the NC (Normally Closed) contacts will be open during normal operation and closed during an alarm. In Non Fail-Safe mode, the NC contacts will be closed during normal operation and open during an alarm. Clearing Alarms The external Silence / Alarm Reset button will clear the Audible Alarm. The Reset button or cycling power will clear Out-of-Sequence Alarms. Alternation The ISS-105 is equipped with a built-in alternator that determines which pump will start each pumping cycle. This alternator is configured using switches ALS-0, ALS-1 and ALS-2 of the Option Selector. ALS-0 ALS-1 ALS-2 Function Position 8 Position 9 Position 10 Alternation On ON ON ON Alternation On OFF ON ON Alternation On, Non- Alternating Pump Enabled (1) *ON OFF OFF Alternation On, Non- Alternating Pump Enabled (1) **OFF OFF OFF Alternation Off, Force Pump 1 as Lead OFF ON OFF Alternation Off, Force Pump 2 as Lead OFF OFF ON Alternation Off, Force Pump 3 as Lead (2) ON ON OFF Alternation Off, Force Pump 4 as Lead (3) ON OFF ON Table 4. Alternator Options Note (1) In Duplex Mode, this setting is the same as Alternation On. Note (2) In Duplex Mode, this will force Pump 1 as lead and will cycle Pump 2 every 50 cycles of the lead pump Note (3) In Duplex Mode, this will force Pump 2 as lead and will cycle Pump 1 every 50 cycles of the lead pump * If ALS-0 is ON in this mode, the Non-Alternating Pump will cycle when the Non- Alternating Float changes state, or after 50 cycles of the Lead Float. ** If ALS-0 is OFF the Non-Alternating Pump will cycle only when the Non-Alternating Float changes state. 8 12/04

Alternation On When the alternator is on, each pump will be alternated as the Lead Pump (see Table 5). Cycle 1 Cycle 2 Cycle 3 Cycle 4 Cycle 5 Pump 1 Lead Lag 3 Lag 2 Lag 1 Lead Pump 2 Lag 1 Lead Lag 3 Lag 2 Lag 1 Pump 3 Lag 2 Lag 1 Lead Lag 3 Lag 2 Pump 4 Lag 3 Lag 2 Lag 1 Lead Lag 3 Table 5. Pump Sequence Alternation On, Non-Alternating Pump Enabled The Triplex and Quadplex pump modes are equipped with an optional Non-Alternating Pump. This pump will not be included in the normal pump alternation sequence when ALS-1 and ALS-2 (positions 9 and 10) are both OFF. If ALS-0 (position 8) is ON, the Non-Alternating Pump will cycle when the Non-Alternating Float changes state or after every 50 cycles of the Lead Float. If ALS-0 is OFF, the Non-Alternating Pump will only cycle if the Non- Alternating Float changes state. The last pump in the float sequence (highest #) is the Non- Alternating Pump and can be used as either a jockey or emergency pump. (See Table 2, page 5 for Non-Alternating Pump and Float details for each pumping mode.) A Jockey Pump is typically a smaller pump that will always be used first in the pump sequence. In order to implement a jockey pump; the Non-Alternating Pump Float must be moved in the tank to just above the Stop Float in a Pump Down system, and to just below the Stop Float in a Pump Up system. See Figure 9 (page 19), an example wiring diagram using a Jockey Pump in a Duplex Pump Down system. An Emergency Pump is usually a larger pump that is always used last. In order to implement an emergency pump; the Non-Alternating Pump is already the last pump in the sequence so there is no need to move the float. See Figure 10 (page 20), an example wiring diagram using an Emergency Pump in a Duplex Pump Down system. Alternation Off When the alternator is off, a Lead Pump can be forced by setting ALS-0, 1 & 2 (see Table 4). The remaining pumps will start in a sequential order as each float opens/closes. Disabling Pumps Using the built-in DIP switches, individual pumps can be disabled, when taken out of service for repair or maintenance. 9 12/04

External Inputs A five-pin connector is provided for optional external inputs. External Silence / Alarm Reset This input allows for an external NO (Normally Open) pushbutton that will silence audible alarms and clear flashing alarm lights. External Power Reset This input allows for an external NO pushbutton to reset the IS Super Cell, causing the same effect as a power cycle. External Alternation Configuration For Duplex Mode, a SPDT (Single Pole Double Throw) switch can be connected to close RTCL1 or RTCL2 (remote controls) to force Pump 1 or 2 as the Lead Pump. Option Selector Positions 8, 9 & 10 must be OFF. If the switch is in the middle position, pumps will be in alternation mode. For Triplex and Quadplex Modes two SPST (Single Pole Single Throw) switches can be connected to force Pump 1,2,3 or 4 to be the Lead Pump. Option Selector Positions 9 & 10 must be OFF. To force Pump 1 or 2 as Lead, Position 8 must be OFF. To force Pump 3 or 4 as Lead, Position 8 must be ON. For alternation mode, close both RTCL1 and RTCL2. 3. Wiring Diagrams The following Figures 1-10, show typical wiring diagrams for all pumping modes available for the IS Super Cell. 10 12/04

Figure 1. Typical Wiring for Duplex Pump Down - Mode 1 Switch State Mode Selector Switch 1 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 6. Typical Duplex Pump Down Setup 11 12/04

Figure 2. Typical Wiring for Triplex Pump Down - Mode 2 Switch State Mode Selector Switch 2 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm OFF 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 ON 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 7. Typical Triplex Pump Down Setup 12 12/04

Figure 3. Typical Wiring for Quadplex Pump Down - Mode 3 Switch State Mode Selector Switch 3 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm NA 2 Low Alarm NA 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 ON 6 Pump 4 ON 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 8. Typical Quadplex Pump Down Setup 13 12/04

Figure 4. Typical Wiring for Duplex SPS Pump Down - Mode 4 Switch State Mode Selector Switch 4 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm OFF 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 9. Typical Duplex SPS Pump Down Setup 14 12/04

Figure 5. Typical Wiring for Duplex Pump Up - Mode 5 Switch State Mode Selector Switch 5 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 10. Typical Duplex Pump Up Setup 15 12/04

Figure 6. Typical Wiring for Triplex Pump Up - Mode 6 Switch State Mode Selector Switch 6 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm OFF 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 ON 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 11. Typical Triplex Pump Up Setup 16 12/04

Figure 7. Typical Wiring for Quadplex Pump Up - Mode 7 Mode Selector Switch 7 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm NA 2 Low Alarm NA 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 ON 6 Pump 4 ON 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 12. Typical Quadplex Pump Up Setup 17 12/04

Figure 8. Typical Wiring for Duplex SPS Pump Up - Mode 8 Switch State Mode Selector Switch 8 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm OFF 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 ON 9 ALS-1 ON 10 ALS-2 ON Table 13. Typical Duplex SPS Pump Up Setup 18 12/04

Figure 9. Typical Wiring for Duplex Pump Down with a Jockey Pump - Mode 1 Switch State Mode Selector Switch 1 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 OFF 9 ALS-1 ON 10 ALS-2 OFF Table 14. Typical Duplex Pump Down w/ Jockey Setup 19 12/04

Figure 10. Typical Wiring for Duplex Pump Down with an Emergency Pump - Mode 1 Switch State Mode Selector Switch 1 Time Delay Adjustment MIN Option Selector Switch 1 High Alarm ON 2 Low Alarm ON 3 Pump 1 ON 4 Pump 2 ON 5 Pump 3 NA 6 Pump 4 NA 7 Fail-Safe OFF 8 ALS-0 OFF 9 ALS-1 OFF 10 ALS-2 ON Table 15. Typical Duplex Pump Down Setup 20 12/04

4. Five-Channel Relay Mode Some unique features of the Five-Channel Relay mode are described below. To use the IS Super Cell in this mode, the Mode Selector dial must be set to position 0. Option Selector Position Function Description ON Function OFF Function 1 Enables Channel 2 Latch Channel 1 and 2 function normally Channel 1 Latches Channel 2 2 Enables Channel 4 Latch Channel 3 and 4 function normally Channel 3 Latches Channel 4 3 Relay 1 Logic Positive Negative 4 Relay 2 Logic Positive Negative 5 Relay 3 Logic Positive Negative 6 Relay 4 Logic Positive Negative 7 Relay 5 Logic Positive Negative 8 9 Selects Make/Break Enables Delay-On- Make/Break Timer Delay-On-Break Make/Break Timer Disabled Delay-On-Make Make/Break Timer Enabled 10 Not Used ----- ----- Table 16. Five-Channel Relay Options Positive/Negative Logic Using positive logic will give the same output as input if the input is closed, the corresponding output relay will also be closed. If using negative logic, the output will be the opposite of the input if the input is closed, the output relay will be open. Latched Output Relays 2 and 4 can be configured as latched relays. Input 2 will cause relay 2 to close, but this relay will not open until input 1 opens. Relay 4 will close when input 4 closes, but will not open until input 3 opens. 21 12/04

Time Delay Output Relay 5 can be configured as a Delay-On-Make or a Delay-On-Break time delay output. All timing starts when the input switch opens or closes. The time base for this output is adjustable using the Time Delay knob and ranges from 2-255 seconds. Delay-On-Make If Input 5 closes, the Time Delay will start and LED 5 will flash. Once the Time Delay has expired, Output Relay 5 will close and the LED will be on. If Input 5 opens at any point during the timing cycle, the Time Delay stops and Output Relay 5 remains open. Delay-On-Break If Input 5 opens, the Time Delay will start and LED 5 will flash. Once the Time Delay has expired, Output Relay 5 will open and the LED will be off. If Input 5 closes at any point during the timing cycle, the Time Delay stops and Output Relay 5 remains closed. Figure 11. Typical Wiring for 5-channel Relay - Mode 0 22 12/04

Model ISS-105 Specifications Control Voltage 108 132VAC Frequency 50/60 Hz Power 4 Watts (max.) Adjustments Time Delay/Lag Pump Delay 2 255 sec. Mode Selector 0 8 (9 F: force mode 0) Option Selector 1 10, ON/OFF Silence Button dry input only / non IS Reset Button dry input only / non IS External Alternation Configuration ALS-1 External Alternation Configuration ALS-2 Pumping Modes Available Duplex Pump Down 2 pumps w/ high and low alarms Triplex Pump Down 3 pumps w/ high alarm (typical) Quadplex Pump Down 4 pumps Duplex Pump Down SPS 2 pumps w/ high alarm (typical) (Separate Pump Stop) 2 stop floats Duplex Pump Up 2 pumps w/ high and low alarms Triplex Pump Up 3 pumps w/ low alarm (typical) Quadplex Pump Up 4 pumps Duplex Pump Up SPS 2 pumps w/ low alarm (typical) (Separate Pump Stop) 2 stop floats 5-Channel Relay Mode 5-Channel 1 relay latched / time delay output Operating Temperature -20 to 55 C Terminals Wire AWG 12 20 AWG Torque 6 in.-lbs. Relay Contacts B 300 or 480VA @ 240VAC, Pilot Duty 240 VAC, 7A (max.), General Purpose Pump Inrush Delay 2 sec. Entity Parameters Voc=16.8 V Isc=1.2 ma La=100mH Ca=0.39µF Po = Voc * Isc 4 Class I, Divisions I & II, Groups A, B, C & D; Provides Intrinsically Safe Circuits in Class II, Divisions I & II, Groups E, F & G; the Following Locations: and Class III locations Standards Passed Electrostatic Discharge (ESD) Radio Frequency Immunity (RFI) Fast Transients IEC 61000-4-2, Level 3, 6 kv contact, 8 kv air IEC 61000-4-2, Level 3, 10V/m IEC 61000-4-4, Level 3, 4 kv input power 2 kv inputs/outputs 23 12/04

Load 1 RELAY #1 Load 2 RELAY #2 CONTROL DRAWING ISS-105 ASSOCIATED APPARATUS / APPAREILLAGE CONNEXE Non-Hazardous Location Load 3 RELAY #3 RELAY #4 Load 4 RELAY #5 ISSuper Cell Load 5 INPUT 120 VAC 11 5 VAC Supply Voltage 120VAC Relay Output Rating 7 Amps @ 240VAC General Purpose Pilot Duty 480VA @ 240VAC, B300 Maximum Ambient Temperature Rating 55 C DEVICE MUST BE INSTALLED IN A SUITABLE ENCLOSURE WARNING! TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTABLE ATMOSPHERES, DISCONNECT POWER BEFORE SERVICING. MODEL ISS-105 I1 I2 I3 I4 I5 IC DEVICE MAY ONLY BE REPAIRED BY THE MANUFACTURER WARNING! SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY. AVERTISSEMENT! LA SUBSTITUTION DE COMPOSANTS PEUT COMPROMETTRE LA SÉCURITÉ INTRINSÈQUE. See Notes 1 & 2 See Note 3 Hazardous Location Class I, Divisions I & II, Groups A, B, C & D; Class II, Divisions I & II, Groups E, F & G; and Class III locations NOTES: 1. Maximum distance between unit and switch contact is 10,000 feet. 2. All non-intrinsically safe wiring shall be separated from intrinsically safe wiring. Description of special wiring methods can be found in the National Electrical Code ANSI/NFPA 70, Article 504 Intrinsically Safe Systems. Check your state and local codes for additional requirements. 3. All switch contacts shall be non-energy storing, containing no inductance or capacitance. 4. Entity Parameters: Voc = 16.8V Ca = 0.39µF Isc = 1.2mA Po = Voc * Isc La = 100mH 4 5. Entity Parameter Relationships: IS Equipment Associated Apparatus Vmax (or Ui) Voc or Vt (or Uo) Imax (or Ii) Isc or It (or Io) Pmax, Pi Po Ci + Ccable Ca (or Co) Li + Lcable La (or Lo) Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown in the table above. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci, must be less than the marked capacitance, Ca (or Co), shown on any associated apparatus used. The same applies for inductance (Lcable, Li and La or Lo, respectively). Where the cable capacitance and inductance per foot are not known, the following values shall be used: Ccable = 60pF/ft., Lcable = 0.2µH/ft. 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605) 348-5685 www.symcom.com