Chiller Vs VRF Comparison

Similar documents
APPLICABILITY OF VRV/VRF HVAC SYSTEM A JUDICIOUS AND RATIONAL APPROACH

Variable Refrigerant Flow (VRF) Systems

HVAC 101. H V A C S y s t e m s

HVAC Water chiller selection and optimisation of operation

Product Line Introduction. Karl Zhang Technical support engineer

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

Variable Refrigeration Flow Systems Overview 10/11/2016

High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

Chilled Water system

Leadership, Innovation, Advanced Technology Synergise Here!

Increase your flexibility.

LG VRF Systems. Air Conditioning Technologies

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Appendix 13. Categories of Cooling and Heating systems

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Inverter Ducted Split Air Source Heat Pump. Simply Smart. System with Inverter Drive Technology. boschheatingandcooling.com

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Midea VFD Centrifugal Chiller Technology

High-performance Packaged & Ductable Split Units: Aero, Thermo & Tropico Series

ADVANCED TRAINING INSTITUTE, HYDERABAD PR04/F01

Selection of air conditioning systems

2. CURRICULUM. Sl. No.

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

ECOMax-HE Automatic Tube Cleaning System

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Magnetic Bearing Technology: Achievements in Higher Efficiency

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Efficiency Vermont The American Institute of Architects Continuing Education Systems (AIA/CES) AIA/CES AIA/CES

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

The ultimate fresh air solution.

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Submitted to Reference Approval Construction Unit Designation Schedule #

3 rd Generation of VRV. The professional solution for your professional project

Why to decide on a Rotorcomp compact unit screw compressor

EN aquatech.piovan.com

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

GARCIA GALUSKA DESOUSA Consulting Engineers

Variable refrigerant flow (VRF) systems

Method to test HVAC equipment at part load conditions

VRV LIFE FLEXIBLE / DUAL-FUEL HEATING / INVERTER TECHNOLOGY / QUIET / SPACE-SAVING

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Submitted to Reference Approval Construction Unit Designation Schedule #

ACMVTECH HIGH EFFICIENCY UNITARY AHU

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

ENGINEERING. Edition No. 13 October 2002

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

MECHANICAL SERVICES 101. Ian White

UNIT 4: REFRIGERATION PRINCIPLE

Challenges and Methods of Estimating a Conceptual HVAC Design

Agenda and Objectives

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

Smardt Oil-Free Chillers

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

The Design Flaw in HVAC

YMGI HVAC Line Card VRF Outdoor Units

Transcritical CO2 Bottle Cooler Development

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

b.) Technical Information:

Emad Chen. Head of Qatar Office Midea Commercial Air Conditioner

1.1 This section applies to air handling units for HVAC Systems.

VRF Outdoor Units. YMGI Group 601 Arrow Ln, O Fallon, MO ymgigroup.com Solar Series Mini & Modular

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Vicot Air Conditioning Co., Ltd. CONTENT

Modular Air Cooled Scroll Chillers

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

New and Emerging HVAC Technologies. Rod Rhoads, GDS Associates Dave McCullaugh, Mitsubishi Electric Trane HVAC US Dave Binz, Cambridge Engineering

SMMS-7 VRF. You spoke. We designed.

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Technical Assignment 3 11/15/04. Executive Summary

air systems Roomtop RTC-RTH 15 to 30 - L

Modular Active. Chilled. Beams

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY)

Daikin Blueprint: Delivering Hot Water with a Chiller

APPLICATION GUIDE BEAMS

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Closing the Loop What s best for your system?

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Cold Remedies. SamsungHVAC.com. Product Registration Required Conditions Apply

ASHRAE JOURNAL ON REHEAT

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay

Integrated VarIable refrigerant flow ahu/pau (r410a)

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

General Guidance. The easiest way to establish the amount of refrigerant in the system is to use data supplied by the manufacturer:

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

Transcription:

Chiller Vs VRF Comparison At the time of designing a HVAC project, it is required to understand the project requirements, type of application, duty conditions and compliance to relevant standards. In order to decide which air conditioning system to be used for any particular project, it becomes essential to evaluate different HVAC technologies & systems that will best suit for that project. In today s world, the designer has many choices for designing the HVAC system and it could be very confusing to identify a correct system for a given application. In order to understand which particular system is best suited for any application, the designer has to consider various aspects such as life cycle cost analysis, system architecture, space availability, etc. In today s world, a common confusion is whether to design a system for central plant with chilled water system or to use the Variable Refrigerant Volume System (VRF System). In order to understand the merits and demerits for each system, let us compare Chiller Plant System Vs VRF on different aspects that are generally considered during HVAC designing. Technology Merits & Demerits System Life Cycle Cost analysis System Architecture Reliability Technology Variable Refrigerant Flow (VRF) VRF in refrigeration terminology is termed as Multi Evaporator AC system, a central air conditioning system having capacity modulation. VRF system comprises of one or more number of ODUs (out door units), many IDUs (in door units), which are connected with each other through refrigerant piping network. The ODUs are installed either on the rooftop or in the shaft space or anywhere at the convenient place. Refrigerant is circulated through the pipes, to the evaporator units. Inside spaces are cooled with the help of refrigerant that is circulated through evaporator units. Generally an Electronic Expansion Valve is used as an expansion device. Capacity modulation happens through two fundamental techniques 1) electrical modulation inverter based & 2) mechanical modulation. Merits 1. Different IDU options can be used like Hi-wall unit, cassette unit, concealed unit, ducted type units and so on. This can help in blending the air conditioning system with the appropriate interior design of the space. 2. With the current available options, one can reach up to LEED-Gold rating

3. Operation is very simple, probably as simple as operating a split air conditioning system and hence no separate manpower is required for operating the system. 4. Good option for providing air conditioning to apartments / villas, small installations where in the complexity of the system (a major demerit of this system) can be kept to a minimum. Demerits 1. Complex system architecture, large amount of refrigerant piping running around in conditioned space. 2. If decided to use for larger capacities, more space required to install many number of ODUs. Access to ODUs is necessity as all the maintenance work required will be mostly on the ODUs. 3. Will not be of much benefit where the cooling load has limited diversity, such as in IT / ITES offices, malls, multiplexes, etc. where in the diversity is limited to some conference rooms and / or cafeterias, etc. 4. Can be hazardous for the occupants, being refrigerant circulated through pipes, susceptible to leakages, with the refrigerant possibility of entering the conditioned space. 5. Highly skilled labour required for installation and commissioning and maintenance, especially to identify and correct leakages. 6. Different evaluation standards are referred for performance evaluation 7. Limitation on CFM delivered inside the space, up to 350CFM / TR, can be a serious limitation from indoor air quality as air circulated can be insufficient. Technology Water Cooled Screw Chillers Merits 1. The most matured technology with the history of over 6 decades 2. International standard is referred for performance evaluation AHRI 550/590 3. Highly energy efficient, enables comfortably complying to LEED Platinum requirements 4. With proper system design and installing multiple chillers, even in case of high diversity, chillers become a good option due to their good efficiency even at part load conditions. 5. Project size is not the constraint at all 6. Non-hazardous for the occupants, as water is circulated throughout the refrigeration circuit, no chance of hazardous material entering the conditioned space. 7. Advantage on efficiency can be multiplied by using Thermal storage; and usage of differential tariff.

Demerits 1. Availability of water is a must 2. Requires additional space for plant room for chillers, AHU rooms and space for mounting the cooling towers. 3. Trained manpower is required for operating the central chiller plant. Life Cycle Cost Analysis Life Cycle Cost = Initial CapEx + Operational Cost + Maintenance Cost Case study for 1000TR capacity system No Parameter Unit VRF W/C Screw Chiller 1 Initial CapEx, average cost Rs / TR 50,000 ~ 65,000 50,000 ~ 55,000 1a Total CapEx Rs 57,500,000 52,500,000 2 Operational Cost ikw / TR Equipment (Weighted Avg. Power IPLV) ikw / TR 0.900 0.500 Condenser Water Pumps ikw / TR NA 0.050 Chilled Water Pumps ikw / TR NA 0.06 AHUs ikw / TR NA 0.100 Cooling Tower ikw / TR NA 0.020 Total ikw/tr ikw / TR 0.90 0.73 2a Total operational cost @Rs. 8.75/kW Rs / Yr 35,437,500 28,743,750 3 Cost of make up water @Rs. 20/m 3 Rs / Yr NIL 557,000 4 Maintenance Cost (CAMC) Rs / TR / Yr 1800 ~ 2000 1200 ~ 1500 5 Operational maintenance Man-hours Rs / Yr NIL 300,000 5a Total maintenance cost Rs / Yr 1,800,000 1,500,000 6 Total O & M Cost / Yr (2a+3+5a) Rs / Yr 37,237,500 30,800,750 7 O & M Cost for 15 Years Rs 558,562,500 462,011,250 8 Life Cycle Cost (1a+7) Rs 616,062,500 514,511,250 Calculation References: 1. Total CapEx: Average cost/tr 2. Total operating cost: Lowest figure for ikw/tr; Running hours 15 Hrs/day x 300 Days 3. Total maintenance cost: Lowest cost/tr/yr

System Architecture In order to achieve capacity modulation, VRF system essentially requires lot of electrical & electronic controls. Most of the controls are fitted in the ODUs panel board. Apart from electrical-electronic controls, each outdoor unit consists of refrigeration components like compressor, condenser, fan, refrigeration components & controls, and quite a lot copper piping. Fig-1 & Fig-2 speak all about the complexities. The system also needs communication cable to run all the way through from outdoor boxes till each & every indoor unit to exchange electronic signals between ODUs and each IDU. Having copper piping, electrical cabling, communication cables, makes the refrigeration network bit complex. On the other hand, water cooled screw chiller system architecture & its functioning is quite simple. It does not require complex electrical electronic controls, refrigeration network for the system to operate and for the capacity modulation too. Further, circulation of water to the AHUs is also a very simple system and all the designer needs to adhere to is simple piping rules. We all know simpler the system architecture, better reliable it will be & better from the serviceability standpoint too. Figure 1 Figure 2

Reliability Oil Management VRF In VRF, refrigerant is circulated throughout the refrigeration circuit. Oil along with the refrigerant leaves the compressor through every compressor discharge, which then is circulated throughout the refrigeration circuits. It is very essential that whatever oil that has left out of compressor, should be returned to a compressor, to facilitate lubrication. At low part load conditions, velocity of the refrigerant & oil is not adequate enough to bring both (oil & refrigerant) back to the compressor. In order to bring the oil back to the compressors, it becomes most essential to run the entire system at high load, for few minutes, after every certain hours. Many times because of the application requirements, the liquid line distances are quite long, to the tune of 400 ~ 450+ feet. The longer liquid lines further create more challenges on account of oil recovery. Also, longer the refrigerant lines, less efficient the system would be. Chillers All chillers have an in-built oil management system, thereby eliminating any issues of oil recovery. Refrigerant flood back VRF Since there is a large quantity of refrigerant available in the system, during part load conditions when only few compressors (matching to % part load) are in operation, the entire refrigerant mass is handled by those few compressors. In such duty conditions, many a times, system may run into issues if due care is not taken. In that case the compressors see flooding of liquid refrigerant that eventually leads to compressor motor burn out, mechanical breakage of the compressors, etc. Chillers Liquid flooding is not an issue at all, as the system is properly designed and only the amount of refrigerant required is circulated, rest stays in the condenser.

Conclusion For smaller systems, up to 100 ~ 200 TR, with limited ODUs and IDUs, VRF system can be a good solution, as for smaller central plant system, space availability for chillers, AHUs may not be available. Also, for such small systems, the VRF system can remain simple with limited refrigerant piping and without much complexities. However, when the installation size starts increasing, VRF systems, as seen above, start becoming complex and in such cases, planning the installation for a central plant is always beneficial. The life cycle cost of such a system is not only lower than the VRF system, but it also avoids safety related issues such as leakage of refrigerant in conditioned space, better air circulation, better indoor air quality, etc.