KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

Similar documents
KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP33 AIR-TO-AIR HEAT EXCHANGER

KNHX32 SERIES NEMA 4/4X AIR-TO-AIR HEAT EXCHANGERS

ADVANTAGE SERIES KXRP47 AIR-TO-AIR HEAT EXCHANGER

AIR CONDITIONER OPERATOR'S MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRADITIONAL SERIES P47 P52 P59

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE WNP28 SERIES

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner NPT SERIES K_A6C_NPT47L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K2A3C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTEGRITY SERIES K_NA4C4P32L KNA6C4P32L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K_A4C5DP33L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner WATER-COOLED RACK MOUNTED

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner K2A3C8P36LFHN-1

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner ADVANTAGE RP55 SERIES

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTREPID SERIES K2A6C30EP56TR-4

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner SLIMKOOL SERIES K_NA4C4SP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE KA6C4NP28L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. GUARDIAN SERIES K3NA4C3DP24L 480 Volt 1-PHASE

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. DP SERIES KA4C3DP21L with Serial Numbers L18A3965 and above

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES KNA4C9DP47L-1

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C26DP60L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C18DP53L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner. HAZARDOUS LOCATION SERIES K_A6C6HL40LV U.S. Pat. No.

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

M52 3-Phase INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner 480 VOLT GUARDIAN SERIES K3NA6C14DP50L

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Blade Series Heat Exchanger Operation and Installation

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

Panel Mounted Heat Exchangers by Dantherm, Inc.

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL

INSTRUCTION MANUAL. T-SERIES Air Conditioner. T29 Model Pentair Equipment Protection P/N McLean Parts 5736 N. Michigan Rd.

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL. Rev. F 2015 Pentair Equipment Protection P/N

SPECTRACOOL Air Conditioner. N17 Model INSTRUCTION MANUAL. Rev. G 2015 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Equipment Protection P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. D 2015 Pentair Equipment Protection P/N

T-Series Air Conditioner T20 Model

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

T-SERIES Air Conditioner. T53 Model INSTRUCTION MANUAL nvent Rev. G P/N

GENESIS Air Conditioner. M52 3-Phase Model INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

T-Series Air Conditioner T53 Model

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL. Rev. B 2016 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-Series Air Conditioner T15 Model

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-Series Air Conditioner

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

PROAIR Air Conditioner

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-Series Air Conditioner

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

RPI Industries, Inc.

SPECTRACOOL Air Conditioner

SPECTRACOOL Air Conditioner. N16 Model INSTRUCTION MANUAL. Rev. A 2016 Pentair Equipment Protection P/N

RPI Industries, Inc.

GENESIS AIR CONDITIONERS

ClimaGuard Outdoor Heat Exchanger All Models

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

GENESIS Top-Mount Air Conditioner. HB16 Model INSTRUCTION MANUAL. Rev. J 2013 Pentair Equipment Protection P/N

RPI Industries, Inc.

InstructIon Manual KrEs EQuIPMEnt stands

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N

Quality Refrigeration OWNER S MANUAL. Instructions for the installation, operation and maintenance of Traulsen: Heated Banquet & Transport Carts

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

XT Series Thermostats

12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING

Service Parts, Kits and Accessories

Warnings 2. Installation Instructions 3. Wiring Instructions 3. Mounting Instructions 4. Replacement Element Installation 5. Replacement Parts 5

Intelligent Electronic Enclosure Thermal Management Systems

M Series Fan Filter Units

User s Manual and Operating Instructions

MS-600 DESICCANT DEHUMIDIFIER

Intelligent Electronic Enclosure Thermal Management Systems

BX Series. Installation, Operation, Maintenance Instructions & Spare Parts

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

Gen-Air Air Mover. Gen-Air Air Mover. Safety, Operation and Maintenance Manual with Parts List Please read before use! 1/2 HP, 3-Speed Motor

INDUSTRIAL INDUSTRIAL. Installation & Maintenance Instructions. Direct Drive 16 / 20 AIR CURTAIN SERIES IDC16 / IDC20

INSTALLATION AND OPERATING MANUAL

Installation & Maintenance Instructions

MODEL 925W FEATURES: ELECTRICAL DATA: DIMENSIONS: SHIPPING INFORMATION: FOOD WARMING/ MERCHANDISING CABINET

Service Manual Models CPH2 & CPH3

Product Information Packet

Transcription:

Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER OPERATOR'S MANUAL CAUTION BEFORE INSTALLING AND USING THIS HEAT EXCHANGER, IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC, INC. 30 Pennington-Hopewell Road Pennington, NJ 08534 609 466-3400 FAX: 609 466-1114 www.kooltronic.com 900-046-25

TABLE OF CONTENTS Page I. Introduction 2 II. Incoming Inspection 3 III. Product Handling 3 IV. Product Identification and Nameplate 3 V. Principles of Operation 4 VI. Specific Model Data 4-6 Mounting Drawings and Dimensions Technical Data Major Component Replacements Options Wiring Diagram VII. Maintenance 7 VIII. Packing Procedure 7 IX. Warranty 8 I. Introduction Kooltronic Heat Exchangers are designed to provide a cool environment for your electronic or electrical components. There are models to fit virtually all sizes and shapes of electrical or electronic enclosures. Our closed loop design also ensures that your components will not be exposed to hot, dirty operating conditions. This Manual provides you with the necessary general information for properly installing and operating Kooltronic Heat Exchangers. Unit specific technical data and mounting instructions are presented later in the Manual. 2

II. Incoming Inspection Kooltronic Heat Exchangers are designed, built, and packaged to withstand the shock and vibration normally associated with shipment by common carriers. Occasionally improper handling during shipping causes damage. Such handling could include unbanding of palletized shipments, failing to respect any carton handling instructions, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be done upon receipt of all shipments. Any carton tears, dents, scratches, or loose articles should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected for CONCEALED DAMAGE. An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing materials. Kooltronic cannot assume responsibility for Consignee s failure to file a timely freight claim. III. Product Handling Do not attempt to operate your Kooltronic Heat Exchanger until you read and thoroughly understand this Manual. Before operating this unit, all electrical wiring must be checked to assure the proper connections. CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate. IV. Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate. This nameplate provides: Heat Exchanger ➀ ➁ ➂ ➃ Model Number Serial Number Electrical power characteristics Maximum ambient operating temperature MODEL NO. ➀ SERIAL NO. MAX. CABINET VOLTS. FREQ. PH. AMPS TEMP. o F ➂ ➂ ➂ ➂ ➃ ➁ MAX. FUSE SIZE ➂ We recommend you copy this information from your unit. ➀➁ When ordering parts, specify the Model Number and Serial Number. ➂ Before operating, be sure that the power source matches these requirements. UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECTED THIS PRODUCT IS PROTECTED BY ONE OR MORE OF THE FOLLOWING PATENTS: 3,019,965 3,120,166 3,211,360 3,559,728 3,807,493 AND OTHER PATENTS PENDING ➃ Make sure that these parameters are met. Failure to do so may result in permanent damage to the unit. MANUFACTURED BY: KOOLTRONIC, INC. PENNINGTON, NJ 3

V. Principles of Operation If ambient air cannot be utilized directly as a cooling medium, another cost-effective method of cooling is a Water-to-Air system (Figure 1). Water is used to remove heat from the air circulated within the electronics enclosure. Cooling water is circulated through a tubeand-fin coil. As the heat-laden air circulates through the coil, the heat is absorbed by the water and carried away, in a continuous process. Water-to-Air systems are easy to install and usually require minimum maintenance. The water used must be reasonably clean and cold enough to ensure proper operation of the cooling system under the most severe anticipated conditions. In some cases, if sufficiently cold water is available, belowambient-temperature cooling can be achieved. The Heat Exchanger with options -- Automatic Water Flow Control is shown on Figure 2. Figure 1 WATER-TO-AIR Heated Air Cabinet Cooled Air Heat Exchanger Cold Water Blower Water With Heat Load A Water-to-Air Heat Exchanger works by transferring heat of internal air to circulating water, resulting in chilled air which is recirculated throughout the electronics or electrical cabinet. Figure 2 Heat Exchanger Heated Air Solenoid Valve Cooled Air Cold Water Blower Water With Heat Load Water Control Thermostat Water Control Regulator The Adjustable Water Control Thermostat opens and closes a water solenoid valve based on the set point and differential settings. A temperature sensor is located in the airstream of the cabinet. The Adjustable Water Control Thermostat has a factory set point of 75 F. VI. Specific Model Data Mounting The Kooltronic Water-To-Air Heat Exchangers have been engineered to be installed easily. These units utilize double layer gaskets. The first gasket layer is placed on the outside perimeter of the front panel that is sealed against the customer enclosure. The second layer is placed on the two cutouts in the front panel. The first gasket layer will allow a small amount of water between the two layers. The second gasket layer totally protects an enclosure from ambient air, rain or hose down water. This gasket arrangement assures the integrity of the closed loop system and is necessary to maintain the NEMA 4 rating. Prior to mounting, refer to the mounting drawing showing dimensions and locations of mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere with components inside the cabinet. To avoid damaging your air conditioner, please read the following information before installation: 4

Mounting (con t) 1. It is recommended that a lift truck be used for installation. 2. Adjust the lift truck height so that the heat exchanger is located in line with the cutouts and mounting holes. 3. Route the power cord through the air cutout. 4. Move the heat exchanger toward the enclosure panel so that the gap between the heat exchanger and the enclosure is about.05-inch. 5. Install sealing washers and stainless steel nuts on each screw from inside the enclosure and tighten (see mounting drawing). MOUNTING DRAWING ENCLOSURE WALL (15) PLACES BOLT 1/4'' X 1-1/4'' CUSTOMER'S ENCLOSURE RUBBER WASHER BOTTOM SECTION OF H/E UNIT 1/4'' NUT TIGHTEN NUT TO CLOSE GAP GA710048A MOUNTING PLAN 2.75 [70.0] 7.38 [187.4] 7.38 [187.4] (15).312 [7.9] DIA. HOLES 20.26 [514.6] 5.18 [131.5] 1 1 1 2 WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 2 48.02 [1219.7] 5.14 [130.5] 3.49 [88.6] 12.25 [311.1] 1.49 [37.8] 14.10 [358.1] 2 17.28 [438.9] 41.46 [1053.0] 9.32 [236.7].78 [19.8] 5.25 2.25 [57.1] [133.3] 3.30 [83.8] Dimensions, (inches) [metric], are for reference only and are subject to change. Technical Data Performance Approx. Watts/ F Weight Model Volts Amps Watts 1 gpm 2 gpm 3 gpm 4 gpm (lbs.) KNHE48 115 2.2 255 90 135 150 165 89 K2NHE48 230 1.1 255 90 135 150 165 89 Note: The rating Watts/ F is the heat dissipation divided by temperature difference between maximum air temperature in enclosure and water temperature entering the heat exchanger. 5

Major Component Replacements KNHE48 K2NHE48 Part Number Part Number Blower 0194-103 0194-50 Capacitor 0452-32 0452-45 Coil 0667-55 0667-55 Options Automatic Water Flow Control Cooling Effect Detector High Water Level Detector Internal corrosion resistant coatings Low Airflow Detector Other voltages and frequencies Special materials or finishes Special motors, line cords or connectors Wiring Diagram (BLACK) H WE TO BK WE TO RD HEAT AND WATER ALARM EXCESS HEAT ALARM WATER LEVEL ALARM (WHITE) N TO CUSTOMER ALARM SYSTEM WE RD BK TERM. BLOCK HEAT AND WATER ALARM THERMOSTAT BK N.O. LEVEL SWITCH N.C. N.O. COM. 1 2 3 4 5 6 RELAY 7 8 N.C. N.O. COM. CIRCUIT SHOWN WITH LINE POWER OFF NC NO SOLENOID BLOWER MTR WE WE RD BK THERMOSTAT TO CUSTOMER LOW AIRFLOW ALARM SYSTEM BK BRN WD-1379 CAPACITOR 6

VII. Maintenance In general, very little maintenance or repair is required on Water-to-Air Heat Exchangers. CAUTION Disconnect electric power from the Heat Exchanger before servicing unit. Blowers - Removable for Repair or Replacement In Kooltronic Water-to-Air Heat Exchangers, powerful blowers are used. Each is carefully chosen to provide optimum airflow characteristics for component cooling as well as heat transfer within the unit. Each of these air moving devices has been engineered and constructed to provide years of trouble-free operation and thus require no periodic maintenance. In the case of air mover failure, blowers are easily removable with simple tools. Replacement Blower Assemblies and Motors are generally readily available from Kooltronic stock. Please see the listing of Major Component Replacements earlier in this manual. CAUTION Do not handle or carry the blower by inserting fingers into the blower opening where wheels are located. This could cause a wheel misalignment problem and create an out-of-balance condition. Also, the sharp vanes could result in injury. VIII. Packing Procedure Keep Heat Exchanger in proper upright position. Pack Heat Exchanger in an appropriate carton (preferably original carton if possible), with adequate internal protective packaging, making sure carton is marked properly. For local controlled transportation, strap carton where possible, to a secure part of truck to prevent falling or sliding, minimizing vibration, etc. For common carrier shipment, band unit(s) securely to a pallet. Unpalletized shipment risks severe damage which voids the warranty. 7

IX. Standard Warranty KOOLTRONIC products are warranted to be free of defects in workmanship, materials and components. The following warranty periods apply from date of shipment: Air moving devices/components and hermetic system components: One year Non-operating parts, except filters: 5 years The above warranty applies when the equipment is operated under the following conditions: Ambient temperature not in excess of 125 F (52 C) in normal atmosphere or as stated on product nameplate Voltage variation no greater than ± 10% from nameplate rating Frequency variation no greater than ± 3Hz from nameplate rating Maximum cooling load no higher than air conditioner nameplate rating Waiting five minutes before restarting air conditioner after intentional or accidental shutoff Compliance to all other installation, maintenance and operating instructions, as supplied The purchaser assumes the responsibility of grounding the unit and installing it in accordance with local electrical and safety codes, as well as the National Electric Code (NEC) and OSHA KOOLTRONIC cannot assume responsibility for mis-application of its products or the erroneous selection of an inappropriate product by a nonauthorized KOOLTRONIC representative. Our applications engineers will gladly assist in the selection of the proper product, provided all required details of the application are furnished. KOOLTRONIC assumes no liability beyond the repair or replacement of its own product. This Warranty does not cover: Labor or reimbursement of labor for evaluation, removal, installation, repair, or cost of any warranted part, unless authorized in writing by KOOLTRONIC Use of equipment for other than its designed purpose or operating conditions Operation in harsh, oily, corrosive or other abnormal environmental conditions, without the proper filtration, sealing, protective coatings and/or weather protection Damage to hermetic system resulting from continuous operation with dirty or clogged air filters or improper or negligent maintenance Use of refrigerant other than designated Customer modification or abuse Shipping damage or other accident (Claims for shipping damage are the responsibility of the customer. Timely claims must be filed by the customer with the freight carrier) Cracked or broken hermetic tubing, brazed joints or other internal damage caused by shipping or mishandling Damage caused by shipping units attached to an enclosure Any and all conditions resulting from noncompliance with the preceding operating conditions Returned freight must be paid by customer This standard warranty does not apply to custom products. Consult your KOOLTRONIC representative for limitations THIS WARRANTY CONSTITUTES THE ENTIRE WARRANTY WITH RESPECT TO THE PRODUCT AND IS IN LIEU OF ALL OTHERS, EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY AND WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT IS KOOLTRONIC RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER. RETURN AUTHORIZATION (RA) PROCEDURE All returns require a Return Authorization number whether the return is for warranty or non-warranty repair, rotation of stock, damage or any other reason. Returns without an RA number will be refused. Customer must call KOOLTRONIC After Sale Kare (ASK), Pennington, New Jersey (609 466 3400) to obtain an RA number, or email ask@kooltronic.com. The following information is required when an RA is requested: - Original customer Purchase Order number and date - Date product was received by customer - Number of parts to be returned - Product description, model and serial number - Reason for return - Action requested - Contact name, telephone, FAX numbers and e-mail address Pack unit in a suitable container for shipment, preferably the 8 original packaging if available. All Heat Exchangers must be returned in an upright position properly secured to a pallet. Improper packaging may void warranty claim. If a Heat Exchanger is received laying down or shipped via UPS or similar small parcel service the warranty will be void. Mark carton prominently with KOOLTRONIC s Return Authorization Number. Enclose all pertinent documents. Freight charges on all products returned to KOOLTRONIC shall be paid by the customer. Unauthorized collect shipments will be refused. If a unit is repaired under Warranty, KOOLTRONIC will pay the freight charges both ways within the Continental USA at KOOLTRONIC s negotiated rates. Warranty repaired units will be returned to customer at KOOLTRONIC expense only within the Continental USA. All authorized returns are subject to a restocking fee.