Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Similar documents
SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Study on an environmental simulation system of low/high temperature. for great space

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

A Liquid Desiccant System for Solar Cooling and Dehumidification

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Recent Advances in Energy, Environment and Economic Development

Performance Analysis of a Solid Desiccant Air Dehumidifier

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

K.F. Fong *, C.K. Lee, T.T. Chow

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

A study of tea leaves drying using dehumidification process and regeneration of liquid desiccant in a closed-cycle dehumidification-humidification

CFD Analysis of Fire Characteristics on Subway Junction Station

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Development of Bionic Air Cooler Used in High Temperature Coal Mine

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

Compression of Fins pipe and simple Heat pipe Using CFD

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

AR/IA/UP 241 Lecture 5: Psychrometrics

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Analysis of the Design of an HVAC System in a Public Building

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China

14 Drying. I Basic relations and definitions. Oldřich Holeček, Martin Kohout

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

Customers. The core of our innovation. Feeding&Conveying. Drying Dosing Temperature Control Refrigeration Granulation

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Introduction to Material and Energy Balance

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Design, fabrication and testing of Evaporative Desiccant Cooling system


Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Development of a Slope Stability Program for Transmission Towers

Dynamic performance of a novel dew point air conditioning for the UK buildings

EXPERIMENTAL STUDY OF WATER DESALINATION BASED ON HUMIDIFICATION- DEHUMIDIFICATION PROCESS VIA HEAT PUMP

The Use Of Attic Space For Cooling and Dehumidification

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

EXPERIMENTAL STUDY OF COUNTER FLOW AIR DEHUMIDIFIER FOR DIFFERENT PACKING HEIGHTS

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Modelling the Performance of a Diffusion Absorption Refrigeration System

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Australian Solar Cooling Interest Group (ausscig) Conference

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

Next Generation Passivhaus Archives

Variable far infrared radiation (VFIR) technique for cubic carrot drying

Modeling of a regenerative indirect evaporative cooler for a desiccant cooling system

Transcription:

Experimental Investigation of the Padding Tower 1 for Air Dehumidifier Jin Wang Jianhua Liu Cunnan Li Guangli Zhang Shouchao An Associate Associate graduate Engineer Prelector Professor Professor Student College of Urban Construction & Environmental Engineering, University of Shanghai for Science and Technology, Shanghai 200093, PR China Email: wjljh2003@tom.com.cn Abstract: Air conditioning with all fresh air is founded on the principle of dehumidifying by liquid desiccant. It has the characteristics of being clean, power-saving, easy to operate, and requiring low-grade heat. It is suitable for applying waste heat, and solar power as the heat source for regeneration. Hence, this system has a great latent potential for energy savings and environmental protection. The system chooses the padding tower as a dehumidifier and regenerator, which are often used in petrochemical industry. The system chooses a padding tower as a dehumidifier, and LiCl-Water as a liquid desiccant. The vapor in the air is absorbed by the spray of the LiCl solution, and then the absorbed vapor will be released by heating the absorbent. These processes form the circle of absorptive refrigeration operating in atmospheric pressure. This paper describes studies on the theory and experiment of the padding tower of the dehumidifying air conditioning, including selecting different padding and measuring the speed of the air flow and the solution flow and the pressure drop between the layers of the padding. The experimental and computational results indicate that the design parameters of the padding tower significantly influence the characteristics of the liquid desiccant air conditioning. Of these design parameters, the framework of the padding tower, ratio of the air and the concentration of the inlet solution is largest through the tower, the temperature and effects of the dehumidifying capability of the tower. Key words: liquid desiccant, air conditioning with all fresh 1. INTRODUCTION The air conditioning system with all fresh air possesses the characteristics of cleaning, power-saving, easy operating and low grade heat of requiring etc. the system may make use of industry waste heat. solar power and reproducible energy, so it has bigger potential of energy-saving and environment protecting. The system selects padding tower to deal with the supply air of air conditioning system, in the tower the vapor in the air is absorbed by LiCl brine solution to make the air dry. At the same time the thin desiccant solution will be desorbed in the regenerator. In this way an absorption refrigeration circle worked at atmospheric pressure is obtained. The system can get low temperature supply air to meet the need of air conditioning. The dehumidifying process in the padding tower, dehumidifier, is a complex heat and mass transfer process. The impetus of the mass transfer is the vapor pressure difference between handled air and the surface of the desiccant solution. When the vapor pressure of the handled air is higher than the surface vapor pressure of the desiccant solution, the vapor will transfer from gas phase to liquid phase. When the contact time between gas and liquid phases is fully long, the mass transfer process will arrive to poise. In the process the vapor of the air is absorbed to make the air dry and the desiccant solution absorbs the vapor to be diluted. The diluted solution after heated is sent into regenerator, there the vapor pressure of brine solution is higher than the vapor pressure of ambient air imported for regenerating, the vapor transfer from liquid phase to gas phase to realize the desiccant solution regenerate. The regenerated dense solution will be sent back to the dehumidifier to carry out the dehumidification process. Therefore a continuous circle process is formed. 2. PADDING TOWER DEHUMIDIFIER

2.1 dehumidifier device description The dehumidifier in the experiment system is adiabatic. The desiccant through it is LiCl brine solution. The rule padding in the tower is 350Y ripple metal board and material is 316L stainless steel. The flow mode of the air and solution is countcurrent. In order to ensure the dehumidifying performance of the adiabatic dehumidifier, the device equips a outside circle water cooler to make the solution before entering the dehumidifier be cooled. 2.2 The work condition selection of the dehumidifier The main parameters of the dehumidifier are the ratio of air and solution and the air pressure drop through the device. Based On the mass balance, the reduced vapor quantity of the air should equal to the vapor quantity absorbed by solution. The mass transfer quantity in absorption process shows below. dg = VdY = LdX kmol / s (2-1) V--the air quantity through the parked type tower in unit time, m 3 /s; L--the desiccant solution quantity through the parked type tower in unit time, m 3 /s; dx, dy--the vapor content difference of the air and Solution float point speed(m/s) 6 5.5 5 4.5 4 3.5 3 2.5 2 7 1 2 3 4 5 6 8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 Air flow rate(m/s) solution in the high of dz, kmol/m 3. In the stable and continuous work process, we can have that formula, namely relation operation linearity Equation. V ( Y1 Y2 ) = L( X1 X 2) (2-2) X 2, Y 1 --the vapor content of solution and air at the bottom of the tower, kmol/m 3 ; X 1, Y 2 --the vapor content of solution and air at the top of the tower, kmol/m 3. The operation linearity Equation reflects the vapor content variety relation in any section of the tower. On the above equation, the right design parameters of the system are searched. 2.2.1 Confirming the range of air flow quantity, solution flux and pressure drop in the tower On the least ratio of air and solution, 1.2~2.4m/s the air flow rate range and 0.2m/s variety rhythm are selected. The range of solution flux and the variety rhythm of solution flux respectively choose 4.8 (1~8) m 3 /m 2 /h and 4.8m 3 /m 2 /h. The solution float point speed is calculated by the Bain-Haugen formula. The upper limit of solution flux is related with the wetness rate of padding. When the wetness rate of padding approaching 100%, the flow quantity is the upper limit of solution flux. The calculation result shows at Fig.1 The number of 1~8 represent the variety of solution flux in the range of 4.8 (1~8)m 3 /m 2 /h. The air flow rate is limited by the solution float point speed. From the Fig.1, it is known that the float point speed is related nearly with solution flux. Along with the increase of solution flux, the solution float (a) (b) Fig.1 The variety of solution float point speed and unit height pressure drop with air flow rate under 4.8 (1~8) m 3 /m 2 /h solution flux point speed become gradually small. Usually the air flow when the air flow rate is below 1.8m/s, all of the solution rate is less than 75% of the solution float point speed. As flux ranges satisfy the limit of the float point speed of the the Fig.1(a) shows, when the air flow rate arrives at solution. 2.4m/s, the solution flux shouldn t exceed 4.8 8 m 3 /m 2 /h, Fig. 1(b) reflects unit padding height pressure drop

along with the air flow rate variety under different solution flux. At the 2.2m/s air flow rate, every curve presents an inflexion. It is indicated when the air flow rate is larger than 2.2m/s the unit padding height pressure drop will arise markedly. Otherwise, when the air flow rate keeps constant, along with solution flux increase the unit padding height pressure drop also adds. Moreover the larger the air flow rate is, the more quickly bigger the value of unit padding height pressure drop also adds. So the air flow rate may as well be less than 2.2m/s. 2.2.2 Confirming the padding height The padding height influences both the contact persistence time of air and solution and the balance degrees between air and solution in the dehumidifying process. Owing to the pressure drop in the tower presenting linear variety along with height of padding, so it is necessary to confirm the proper padding height. According to the aforementioned variety rule of pressure drop and liquid float, when the air flow rate of empty tower is set between 1.2~2.2 m/s, the solution flux can vary in the range of 4.8 (1~8) m3/m2/h. Now we set that the selected empty tower air flow rate is 1.6m/s, the total padding height is 0.4~1.6 m. Fig. 2(a) reflects the pressure drop variety in the tower along with the padding filling height variety under different solution flux. Under same solution flux, the total pressure drop of the tower adds lineally along with the increase of padding height. Fig. 2 (b) reflects the air vapor content variety at the tower outlet along with the padding filling height variety under different solution flux. Under same solution spray density, the dehumidification quantity decreases along with the increase of padding height. Arrived at one padding height the air vapor content variety tends to slowness along with padding height increase, namely arriving at the optimal padding height of air dehumidification. The table 1 lists several groups of preferable data relating padding height. (a) (b) Fig.2 The v ariety of total pressure drop of the padding tower and outlet air humidity with padding height under difference solution flux Tab. 1 Several groups of ideal data relating with padding height Solution flux Total padding height in the Total pressure drop of the Air vapor content at outlet (m 3 /m 2 /h) tower(m) tower(pa) of the tower (g/kg) 2 4.8 1 141.7 8.3 3 4.8 0.8 126.7 8.9 4 4.8 0.6 110.0 9.2 Thus the inlet parameters of dehumidification tower are selected. a. The range of the air flow rate is 1.0~ 3.0m/s, the air flow rate increases 0.4m/s in every experiment operation. b. The range of the solution flux variety is 4.8 (1~8)m 3 /m 2 /h, the value of the solution flux increases 4.8m 3 /m 2 /h in every experiment operation. c. The range of the air inlet temperature is 28~40, the air inlet temperature increases 2 in every experiment

operation. d. The range of the air inlet absolute humidity is 12~24g/kg, the air inlet absolute humidity increases 2g/kg in every experiment operation. e. The range of the solution temperature is 25~40, the solution temperature increases about 1 in every experiment operation. In experiment process each parameter among the parameter of a~e is adjusted from the minimum to the maximum, other parameter keep constant. After the system running steadily, the data of the dehumidifier operating are collected and tracked recorded. A team of curves concerned in inlet parameter of dehumidifier effecting dehumidification efficiency are obtained after analysing and clearing up the data. 3. EXPERIMENT RESULTS ANALYSIS In the research of experiment, the test element of the air temperature, relative and absolute humidity, and solution temperature are adopted by T type thermocouple. The test device of the air flow rate adopts Y type pitot tube and micromanometer. LZB-40 type glass rotameter is used to measure solution s flowing speed. All parameter values are real time data collected by ADAM-4018+ collection module and ADAM-4520 type diversion module, and transferred to computer through RS-232 serial port. 3.1 The affection of inlet solution flux to outlet air humidity and temperature Fig.3 and Fig.4 respectively describe the affection of every inlet parameter to the outlet parameter of air and solution or to the change of dehumidification capacity. These figures reflect the variety direction of effecting outlet parameters and dehumidifying efficiency along with the change of inlet parameters of solution and air with difference solution concentration. Fig.3(a), (b), (c) reflect that the outlet humidity and temperature of air and solution outlet temperature will fall if solution flux increases. The increasing of solution flux makes heat and mass transfer more sufficient, but to unit solution flux, the sensible heat and potential heat absorbed by liquid desiccant also decrease, so solution outlet temperature shows a falling current when inlet solution. outle t a ir hi umidity (g/kg D A ) 16 14 12 10 8 6 1 2 3 4 solution flux ( 1.68kg/m 2 /s) 5 ( ) Outlet air temperature 34.0 33.0 32.0 31.0 30.0 29.0 30 1 2 3 4 5 solution flux( 1.68kg/m 2 /s) (a) the variety of outlet air humidity (b) the variety of outlet air temperature 44 outlet solution temperature 41 38 35 32 1.0 2.0 3.0 4.0 5.0 solution flux( 1.68kg/m 2 /s) (c) the variety of outlet solution temperature Fig. 3 the variety of outlet parameters with inlet solution flux dihumidity efficiency % 90% 70% 50% 1.0 2.0 3.0 4.0 5.0 solution flux ( 1.68kg/m 2 /s) (d) the variety ofdehumidifying efficiency flux increasing. As the lower the solution temperature is, the less the vapour pressure of solution is, so that the impetus of mass transfer is larger, and mass transfer factor is higher. So when the solution flux augments, the heat and mass transfer gets enhanced. When the solution flux becomes less, the curve in the

figure changes sharply; with the solution flux increasing the variety direction of the curve becomes smooth. When the solution flux is too small to moist the padding surface, The heat and mass transfer reduces at that time. With solution flux increasing, the wet ratio of padding goes up which makes the effective area of heat and mass transfer augment and the heat and mass transfer boost up quickly. When the solution flux arrives at one value, the effective area of heat and mass transfer does not increase continuously and the process of heat and mass transfer goes to stabilization. So the variety directions of the performance curves of the parameter also achieve smooth. 3.2 The affection of inlet air humidity to outlet air and solution parameter Fig. 4 describes the outlet parameters variation quantity of air and solution with the variation of inlet air absolute humidity, in the condition that air dry bulb temperature is 34, solution flux is 5.04kg/m 2 s, solution temperature is 30, solution concentration are 30 %, and. Fig. 4(a).(b) show the variation of inlet air absolute humidity hardly affects the outlet air humidity, and the outlet air and solution temperature will rise along with the augmentation of inlet air absolute humidity. According to the experiment results, the difference between the maximum and minimum of outlet air temperature is less than 2.3% of the maximum. Fig. 4(c).(d) respectively describes the augment current of solution outlet temperature and dehumidifying efficiency with the increasing in inlet air absolute humidity. The larger the dehumidification quantity is, the more the potential heat released by the vapour dehumidified, so the solution temperature will rise correspondently. Usually the range of temperature rise does not exceed over 6 and affect hardly the average mass transfer efficiency. ) DA outlet air hiumidity (g/kg 17 14 11 8 5 14 16 18 20 22 24 26 inlet air hiumidity (g/kgda) outlet air temperature 30.4 30.3 30.2 30.1 30.0 14 16 18 20 22 24 26 inlet air humidity(g/kgda) (a) the variety of outlet air humidity (b) the variety of outlet air temperature outlet solution temperature 38.0 36.0 34.0 32.0 30.0 outle t air humidify(g/kgda) 14 16 18 20 22 24 (c) the variety of outlet solution temperature 23 19 15 11 7 inlet air humidity(g/kgda) 3 21 24 27 30 33 36 39 42 45 26 fficiency% dehumitify e 80% 60% 20% 0% 25.0 14 16 18 20 22 24 inlet air humidify(g/kgda) (d) the variety of dehumidifying efficiency Fig.4 the variety of outlet parameters with inlet air humidity Proceedings of the Sixth International Conference for Enhanced Building Operations, 28.0 Shenzhen, China, November 6-9, 2006 Inlet solution temperature outlet air temperature 43.0 40.0 37.0 34.0 31.0 25 28 31 34 37 40 26

(a) the variey t of outlet air humidity (b) the variety of outlet air temperature outlet solu tion tempera ture 43,0 40,0 37,0 34,0 31,0 28,0 25 28 31 34 37 40 dehumidifyin g eff icienc y 80,0% 60,0% 40,0% 20,0% 0,0% 25 28 31 34 37 40 inlet solution temperature (c) the variety of outlet solution temperature inlet solution temperature (d) the variety of dehumidifying efficiency Fig.5 the variety of outlet parameters with inlet solution temperature 3.3 The affection of solution temperature to outlet air and solution parameter It is known from Fig. 5 that the experiment values of outlet air humidity and temperature rise obviously with value are obtained by changing the inlet air and solution parameter of the dehumidifier. The inlet air parameter such as air flow rate, dry bulb temperature, humidity etc hardly affects to the outlet air parameter, but the solution inlet solution temperature rise. This denotes that along with the increase of inlet solution temperature the vapour temperature, ratio of the air and solution, solution concentration have biggish affection to the outlet air pressure of solution augment, the impetus of mass transfer parameter. So as the outlet air temperature and humidity falls and the mass transfer efficiency follows to debase. have larger dependence to the desiccant solution, the When the solution inlet temperature arrives at one value, selection of parameter work point in the moment of the solution dehumidifying efficiency gradually wanes till dehumidifying tower design must pay enough attention. zero. For example, when solution temperature is 25, the dehumidifying efficiency to air exceeds over 60%; when REFERENCES solution temperature is 40, the dehumidifying [1] Bohua Fen etc. Handbook of chemistry project[m]. efficiency to air approach to zero. If the temperature of Beijing: Publishing company of chemistry industry, solution rose any higher, the dehumidifier would change 1989, (In Chinese) into a regenerator. [2] Adnan A. Kinsara, Parametric study of an energy efficient air conditioning system using liquid 4. CONCLUSION desiccant[j]. Applied Thermal Engineering,1997, The experime ntal system constructed and operated in t his study has yielded valuable information of dehumidifier. These ar e some quantitative data about its 18(5):327-335. [3] Shuyin Wang. Technique enchiridion of padding tower for modern times[m]. Publishing company of performance. The dehumidification system is studied by experiment in changing operating conditions. The affection currents to the variation of each outlet parameter [4] petrifaction of China, 1998, (In Chinese) was studied with the liquid-desiccant [5] Guangli Zhang. The dehumidification equipment air-conditioning system[d]. Shanghai: University of

Shanghai for Science and Technology s master paper2005 (In Chinese) [6] Arshad Y.Khan and Jorge L.Martinez.Modelling and parametric analysis of heat and mass transfer performance of a hybrid liquid desiccant absorber[j]. Energy Conversion, 1998, (39):1095-1112, [7] A.Rahaman, M.M.Elsayed and N.M.Al-Najem. a numerical solution for cooling and dehumidification of air by a falling desiccant film in parallel flow[j]. Renewable Energy, 1998, 13 (3):305-322.