DEIF A/S. Operator s Manual. Basic Gen-set Controller. Display readings. Push-button functions. Alarm handling. Log list C (UK)

Similar documents
DEIF A/S. Operator s Manual. Multi-line 2/version 2-GS E (UK) SW version 2.4X.X. Display readings. Push-button functions.

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

Protection and Power Management, PPM-3 Display and push-button functions Alarm handling Log list Failure mode and effect analysis

Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

DEIF A/S. Description of options. Option A4, Loss of mains protection package Automatic Gen-set Controller. Description of option

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control

DELOMATIC 400, DM-400 HYDRO

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list

Option M16.x Configurable I/O extension cards, four multi-inputs (4-20 ma/0-5 V/Pt100) Description of option Functional description

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

TCM-2 Thyristor Control Module DATA SHEET

INSTALLATION INSTRUCTIONS. Anti Knocking System, AKR 3. Document no.: A SW version:

User Manual. Dryer Controller M720

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

Temperature Controller CC24-7 UNIBOX USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Dryer Controller M720

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Guardian II Pipeline Washer B Instruction Supplement

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

Chore-Tronics Load Cell Indicator

Conviron CMP5090 User Guide

Manual# User s Manual

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

REPEATER FS5200R INSTRUCTION MANUAL

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

User Guide IM/SM3000 EN Rev. L. SM3000 Multipoint Videographic Recorder

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Hydro-Pnuematic Tank Contoller. HTC200 and 300 Series. User Manual

Product Data Sheet. Remote Terminals. Features:

Section 9 System Operation

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

SCAN200E USER S MANUAL

ProStar 325 UV-Vis Detector

Memcom Emergency Telephone

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

I/A Series A 2 Software FoxAlert Alarm Manager

REMOTE CONTROL FOR CHILLER MYCHILLER

Quick-Start Guide Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input Models and

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Operation Manual. EGCP-3 Engine Generator Control Package. LS (Load Sharing) Model Manual (Revision E)

QUICK USER GUIDE. Alarm Control Panel

User Operation Manual

Operating Instructions Model: PRT-TS WiFi RF. 01/13 Version 1 Ref: PRT-TSWIFI RF

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

TE809-Ats Instructions Manual

Laptop / PC Programming Manual

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

PowerLogic ION Setup Meter Configuration Software Configuration Guide

User manual for reversible heat pump

CSP-204 CSP-208 CSP-104 CSP-108

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Fire Control Panel FS5100

Configuration wizard WRS-K. Wolf GmbH Postfach 1380 D Mainburg Tel /74-0 Fax / Internet:

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

user manual Document No , Revision 03 November 2015

Discovery 4 Loop Analogue Addressable Control Panel (NVI & NVA series Protocols)

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

OPERATING INSTRUCTIONS

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Xtralis VESDA LCD Programmer Quick Reference Guide

Intelligent Security & Fire Ltd

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

Application description

HERCULES 6 GRAPHICS SYSTEM

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert)

Evolution Environmental Controller. Hired Hand Manufacturing, Inc County Road 68 PO Box 110 Bremen, Alabama 35033

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Accent User. Version. Rheem. PO Box 146, ABN:

THX-DL Data Logger USER & INSTALLATION MANUAL V

Halton SAFE / 7.14 user guide and installation instructions

Operation Manual. EGCP-3 Engine Generator Control Package. MC (Master Control) Model. Manual (Revision C)

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Application Manual Loop Water Controller

Evolution 3000 and 3001

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Lift Station Level Controller

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

725B Configuration Software Manual

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

ZSC100 Gas Detection and Alarm System Controller

ECL Comfort 110, application 116

Oakton TEMP 9500 Advanced Multiparameter Controller

Transcription:

Basic Gen-set Controller 4189340315C (UK) Display readings Push-button functions Alarm handling Log list DEIF A/S DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615 DK-7800 Skive, Denmark E-mail: deif@deif.com, URL: www.deif.com

Table of contents 1. ABOUT THIS DOCUMENT... 3 GENERAL PURPOSE... 3 INTENDED USERS... 3 CONTENTS/OVERALL STRUCTURE... 3 2. WARNINGS AND LEGAL INFORMATION... 4 LEGAL INFORMATION AND RESPONSIBILITY... 4 ELECTROSTATIC DISCHARGE AWARENESS... 4 SAFETY ISSUES... 4 NOTES... 4 3. GENERAL PRODUCT INFORMATION... 5 INTRODUCTION... 5 TYPE OF PRODUCT... 5 4. DISPLAY PUSH-BUTTONS AND LEDS... 6 PUSH-BUTTON FUNCTIONS... 6 LED FUNCTIONS... 8 5. DISPLAY AND MENU STRUCTURE... 10 LCD DISPLAY... 10 MENU STRUCTURE... 10 6. ALARM HANDLING AND LOG LIST... 15 ALARM HANDLING... 15 LOG LIST... 15 DEIF A/S Page 2 of 15

1. About this document This chapter includes general user information about this manual concerning the general purpose, the intended users and the overall contents and structure. General purpose This document is the for DEIF s basic gen-set controller, the BGC. The document mainly includes general product information, display readings, push-button functions, alarm handling descriptions and presentation of the log list. The general purpose is to give the user important information to be used in the daily operation of the unit. Intended users This operator s manual is mainly intended for the daily user. On the basis of this document the daily user will be able to carry out simple procedures such as start/stop and control of the generator set. Contents/overall structure The document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page. The following will outline the contents of each of the chapters. About this document This first chapter includes general information about the Operator s manual as a document, e.g. it deals with the general purpose and the intended users of it. Furthermore, it outlines the overall contents and structure of the document. Warnings and legal information The second chapter includes information about general legal issues and safety precautions relevant in the handling of DEIF products. Furthermore, this chapter will introduce a note symbol, which will be used throughout this document. General product information The third chapter will deal with the BGC unit in general and its place in the DEIF product range. Display push-buttons and LEDs Chapter four provides an overview of the individual push-buttons and LEDs on the front of the BGC. The functionality of these will be presented. Display and menu structure The fifth chapter will provide specific information as to which readings can be made in the display. Alarm handling and log list The sixth chapter will present the handling of alarms and log list. DEIF A/S Page 3 of 15

2. Warnings and legal information This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finally, the highlighted notes, which will be used throughout this document, are presented. Legal information and responsibility DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the generator controlled by the BGC unit, the company responsible for the installation or the operation of the set must be contacted. The BGC units are not to be opened by unauthorized personnel. If opened anyway, the warranty will be lost. Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. Safety issues Installing the BGC unit implies work with dangerous currents and voltages. Therefore, the installation of the BGC should only be carried out by authorized personnel who understand the risks involved in the working with live electrical equipment. Notes Throughout this document a number of notes with helpful user information will be presented. To ensure that these notes are noticed, they will be highlighted in order to separate them from the general text. Xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx DEIF A/S Page 4 of 15

3. General product information This chapter will deal with the BGC unit in general and its place in the DEIF product range. Introduction The BGC is a part of the DEIF multi-line 2 product family. Multi-line 2 is a complete range of multi-function generator protection and control products integrating all the functions you need into one compact and attractive solution. The multi-line 2 product range consists of different basic versions, which can be supplemented with the flexible options needed to provide the optimum solution. The concept of the BGC is to offer a cost-effective solution to gen-set builders who need a simple generator protection and control unit. Being a part of the multi-line product family the standard functions of the BGC can be supplemented with a variety of optional functions. Type of product The BGC is a micro-processor based control unit containing all necessary functions for protection of a gen-set and of mains and generator breaker control. The BGC contains all necessary 3-phase measuring circuits and presents all values and alarms on the LCD display. The design of the BGC allows it to be built directly into the engine side panel or the switchboard door. DEIF A/S Page 5 of 15

4. Display push-buttons and LEDs This chapter will present the display push-buttons and LEDs of the unit. Push-button functions The display unit holds a number of push-button functions, which are presented below. INFO: JUMP: VIEW: LOG: Shifts the display 3 lower lines to show the alarm list. Enters a specific menu number selection. All settings have a specific number attached to them. The JUMP button enables the user to select and display any setting without having to navigate through the menus (see later). Shifts the first line displaying in the setup menus. Shifts the display 3 lower lines to show the event and alarm list. The list holds 150 events. These events are deleted, when the BGC is switched off. : Moves the cursor left for manoeuvring in the menus. : Increases the value of the selected set point (in the setup menu). In the daily use display, this button function is used for scrolling the second line displaying of generator values. SEL: Is used to select the underscored entry in the fourth line of the display. : Decreases the value of the selected set point (in the setup menu). In the daily use display, this button function is used for scrolling the second line displaying of generator values. : Moves the cursor right for manoeuvring in the menus. BACK: START: STOP: (GB) ON: (MB) ON: MODE: Jumps one step backwards in the menu (to previous display or to the entry window). Start of the gen-set if SEMI-AUTO is selected. Stop of the gen-set if SEMI-AUTO is selected. Manual activation of close breaker and open breaker sequence if SEMI-AUTO is selected. Manual activation of close breaker and open breaker sequence if SEMI-AUTO is selected. Changes the menu line (line 4) in the display to mode selection. DEIF A/S Page 6 of 15

Push-buttons are placed as follows: INFO: Shifts the display three lower lines to show the alarm list JUMP: Enters a specific menu number selection START: Start of the gen-set if SEMI-AUTO is selected STOP: Stop of the gen-set if SEMI-AUTO is selected Alarm Basic Gen-set Controlle r Power Alarm INFO m ulti- line BGC VIEW Self Check OK Alar m Inh SEL JUMP LOG START STOP Run ON ON Load G ~ BAC K Auto MODE Generator breaker ON/OFF Mains breaker ON/OFF VIEW: Shifts the first line displaying in the setup menus LOG: Shifts the display three lower lines to show the event and alarm list SEL: Selects the underscored entry in the fourth display line BACK: Jumps one step backwards in the menu MODE: Changes the display menu line (line four) to mode selection DEIF A/S Page 7 of 15

LED functions The display unit holds 10 LED functions. The colour is green or red or yellow according to the running situation. ALARM: POWER: Self check OK: ALARM INH.: RUN: (GEN.) OK: (GB) ON: (MB) ON: (MAINS) OK: AUTO: LED flashing indicates that unacknowledged alarms are present. LED fixed light indicates that ALL alarms are acknowledged, but some alarms remain. LED turned off indicates that no alarms are present. LED indicates that the auxiliary supply is switched on. LED indicates that the unit is OK. LED fixed light indicates that the inhibit input is ON. LED indicates that the generator is running. LED green light indicates that the voltage/frequency is present and OK. LED indicates that the generator breaker is closed. LED indicates that the mains breaker is closed. LED is green, if the mains is present and OK. LED is red at a mains failure. LED is flashing green when the mains returns during the Mains OK delay time. LED indicates that auto mode is selected. DEIF A/S Page 8 of 15

The display LEDs are indicating as follows: Alarm: Flashing: Unacknowledged alarm present Steady: Acknowledged, active alarm present Power: Indicates aux. supply ON Self check OK: Indicates self check OK Alarm inh.: Indicates alarm inhibit active Alarm Basic Gen-set Controlle r Power Alarm INFO m ulti- line BGC VIEW Self Check OK Alar m Inh SEL JUMP LOG START STOP Run ON ON Load G ~ BAC K Auto MODE Generator running Generator voltage OK Generator breaker ON Mains breaker ON Mains voltage OK Remote control: ON Local control: OFF DEIF A/S Page 9 of 15

5. Display and menu structure In this chapter the display and the unit menu structure will be presented. LCD display The BGC display is a backlit LCD text display containing 4 lines with 20 characters in each line. There is no control of the light intensity of the display (no dimmer). Basically, all measured and calculated values can be read in the display. These may be selected via the PC utility software (USW). For selection of values see the Designer s reference handbook. Menu structure The BGC display includes two menu systems, which can be used without password entry: View menu system This is the daily use menu system designed for the operator. 15 windows are configurable and can be entered by using the arrow push-buttons. Setup menu system (not commonly used by the operator) This menu system is used for setting up the unit, and if the operator needs detailed information which is not available in the view menu system. Changing of parameter settings is password protected. Entry window When the unit is powered up, an entry window appears. The entry window is the turning point in the menu structure and as such the gateway to the other menus. It can always be reached by pressing the BACK push-button 3 times. The event and alarm list will appear at power up, if an alarm is present. DEIF A/S Page 10 of 15

View menu The view menus (V1, V2 and V3) are the daily use menus designed for the operator. First display line Operational status Second and third display lines Measurements relating to operational status Fourth display line Selection of setup, view and mode menus In the view menus various measured values are on display. Selection of views in the display The readings etc. are all selected by moving the cursor (fourth display line (note the underscore on V1 - this is the cursor)): The cursor is moved using the and push-buttons on the right side of the display. View window 1 Display of measured values according to the selections made during configuration. For detailed info about configuration see the Designer s reference handbook. V1 contains 15 different windows, which can be selected using the and push-buttons on the right side of the display. View window 2 Display of measured values according to the selections made during configuration. Display V2 follows the selection in V1 as follows: 1: Window 1: (Start prepare) 2: Window 2: (Synchronising) 3: Window 3: (Ramp up/down) 4: Window 4: 5: Window 5: (Default (when none of the above are in operation)) DEIF A/S Page 11 of 15

View window 3 Display of measured values according to the selections made during configuration. The V3 display changes with running modes: First display line indicates running status of the unit. Statuses are: - Manual: No regulation, protections are active. - AMF: Automatic start/stop according to Automatic Mains Failure selected functionality. - Island: Island (stand alone) generator or island load sharing with other generators (option G3). - Peak shaving (option G3): Parallel with mains (grid) cutting the top load off the mains supply according to selected values. - Fixed power (option G3): Delivering a predefined amount of power to the mains (grid). Second and third display lines display measured values. Fourth display line displays the selection line. Display V3 follows the selection in V1 as follows: 1: Window 1: (Start prepare) 2: Window 2: (Synchronising) 3: Window 3: (Ramp up/down) 4: Window 4: 5: Window 5: (Default* (when none of the above are in operation)) View window overview Windows View 1 View 2 View 3 Window 1 (used in V2, V3) Window 2 (used in V2, V3) Window 3 (used in V2, V3) Window 4 (used in V2, V3) Window 5 (used in V2, V3) Window 6 Window 7 Manual selection with UP or DOWN pushbuttons Changes automatically between the 5 first windows: 1. Window 1 (Start prepare) 2. Window 2 (Sync.) 3. Window 3 (Ramp up/down) 4. Window 4 5. Window 5 (Default*) Window 8 Window 9 No manual selection. Window 10 All three lines show Window 11 measurements Window 12 Window 13 Window 14 Window 15 Changes automatically between the 5 first windows: 1. Window 1 (Start prepare) 2. Window 2 (Sync.) 3. Window 3 (Ramp up/down) 4. Window 4 5. Window 5 (Default*) No manual selection. Line 1 shows the text 1 5. Line 2 and line 3 show measurements * The default window is automatically selected after the ramping up, when the gen-set is in normal operation, e.g. fixed power mode. DEIF A/S Page 12 of 15

View menu example The following is an example of a configured view menu system. In this example 4 of 15 windows have been configured in view 1. ML 2- BGC V. 1.00 2003-06-01 09.35.54 SETUP V3 V2 V1 MANUEL B 440 438 440V G 439 438 440V SETUP V3 V2 V1 G 150 140 150A B 440 438 440V G 440 438 440V SETUP V3 V2 V1 G 440 438 440V G-L1 50Hz 440V B-L1 50Hz 440V SETUP V3 V2 V1 SEL BACK G 439 440 440V f-l1 50.02Hz PROTECTION SETUP PROT CTRL PWR SYST GOV BASELOAD int AVR FIXED PF int SETUP V3 V2 V1 G 150 140 150A G 0.90PF 103KW SETUP V3 V2 V1 U-SUPPLY 24V SETUP V3 V2 V1...ETC. (max. 15) DEIF A/S Page 13 of 15

Mode menu If the MODE push-button is pushed, a selection of possible running modes appears in the fourth display line. Using the and push-buttons moves the cursor, and the mode can be selected by pressing the SEL button: SEMI: - The display push-buttons (START, STOP, GB ON, GB OFF) are active and can be used by the operator. - The regulators are also active, i.e. the speed control will bring the generator to nominal speed upon start (only if option G2/G3 (sync.) is present). - When pushing a breaker button for closing, the BGC will synchronise (if allowed) the breaker. When the breaker closes, the controls stop. TEST: - The BGC will start the generator, carry out the test sequence (predefined time period) and stop the generator again. Hereafter the generator will return to AUTO mode. The mains breaker will remain closed, and the generator breaker will remain open. NB: If option G2/G3 (sync.) is selected, the test running can be selected to be parallel to the mains and take load to a predefined value. AUTO: - The BGC will automatically carry out the control type selected (AMF, fixed power etc.). - The display control push-buttons (START, STOP, GB ON, GB OFF) are disabled. - If the selected running mode is fixed power or island, timer start/stop (week watch) or binary input, then start/stop can be used. MAN: - The display push-buttons (START, STOP, GB ON, GB OFF) are active and can be used by the operator. - The regulators are not active, i.e. speed (and voltage) control has to take place using binary inputs for UP and DOWN control (only if option G2/G3 is present). - When pushing a breaker button for closing, the BGC will be a check synchroniser (if allowed) for the breaker. When the breaker closes, the speed/load/voltage/power factor can be controlled using the binary control inputs. To return to the other display functions from MODE selection, press the BACK push-button. DEIF A/S Page 14 of 15

6. Alarm handling and log list Alarm handling When an alarm occurs, the BGC will automatically go to the alarm list for display of the alarm. If reading of the alarms is not desired, use the BACK push-button to exit the alarm list. If you decide to enter the alarm list later, use the INFO push-button to jump directly to the alarm list reading. The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active meaning that the alarm condition is still present. Once an alarm is acknowledged and the condition has disappeared, the alarm will no longer be displayed in the alarm list. This means that if there are no alarms, the alarm list will be empty. G 0 0 0 V 1230 Gen low-volt 1 UN-ACK 2 Alarm(s) ACK FIRST LAST This display example indicates an unacknowledged alarm. The display can display only one alarm at a time. Therefore, all other alarms are hidden. To see the other alarms use the and push-buttons to scroll in the display. To acknowledge an alarm, place the cursor (underscore) under ACK and then press SEL. To jump to the first (oldest) or the last (youngest) alarm, place the cursor under the selection (FIRST or LAST) and press SEL. Log list The log list in the BGC contains up to 150 events and/or historical alarms. An event is e.g. closing of breaker and starting of engine. An alarm is e.g. overcurrent or high cooling water temperature. To enter the log list, press LOG. To scroll up and down in the list, use the and push-buttons. It is also possible to go to the first (oldest) logging or the last (youngest) logging by placing the cursor (underscore) under the selection (move the cursor using the and push-buttons) and press the SEL push-button. DEIF A/S reserves the right to change any of the above DEIF A/S Page 15 of 15