Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015

Similar documents
2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

BEST PRACTICE RECOMMENDATIONS

Why ventilate? Dilute contaminants Control or aggravate humidity Comfort or lack of cooling Odors Provide oxygen

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

A highly efficient Enclosure is Key. The Building is always the sum of ALL it s parts

Common Building Code Misinterpretations

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

Sprinklers in Wood-Frame Construction:

The V in HVAC: Mechanical Ventilation in ENERGY STAR Certified Homes

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

Moisture, Ventilation & Global Weirding NEHERS Webinar Series

Indoor Environmental Quality

Building Codes, Ventilation Rates, and Certified Performance. Ventilation Track Comfortech 2007 St Louis, MO September 27, 2007

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

2012 International Mechanical Code Significant Changes. About the Significant Changes

LEED for Homes Points

Put the V back in HVAC

2006 Building Science Press All rights of reproduction in any form reserved.

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Design Architect s/applicant s Certification Of Threshold Criteria

Ventilation BCBC & Richard Kadulski Architect

Ventilation BCBC 9.32 & Richard Kadulski Architect

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

18. Mechanical Ventilation

InspirAIR Compact Heat and Energy Recovery. Multi-Family HRV/ERV

An Introduction to Energy Efficient and Effective Whole-House Ventilation

(A) ft 3. cfm. cfm (Q

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

Integrating Emerging Technologies and Codes & Standards

Residential Makeup Air Systems & Requirements

INTERNATIONAL MECHANICAL CODE

Discover how much Water You re Using and Use that Information to Optimize Your Facility

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

ROOM-BY-ROOM DEMAND CONTROLLED HEAT RECOVERY VENTILATION

High Performance or Hype Performance? Marc Rosenbaum, Some Real World Data. Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

IMC Significant Changes Summary Tier I

SMART ERV Energy Recovery Ventilator. Build It Tight / Ventilate It Right!

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

Steven Winter Associates, Inc. J827

Technical Information

2013 innovation. Room-by-room demand controlled heat recovery ventilation

The 2018 Ventilation Extravaganza. Rick Karg Residential Energy Dynamics 2018

50% 80% 7 Years. Filter. Ventilation Solutions IAQ Canada. Ventilate. of our time is spend indoors. Limited warranty on motors

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

State of MN Energy Code Ventilation Review for 2017 Energy Design Conference. By 1. Mike D. Wilson Dakota Supply Group

QUALITY CONTROL Passive House Checklist

Guidelines for Integrated, Heat Pump Water Heaters in Multifamily Buildings. Rev. July 18, 2018

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

CHAPTER 4 VENTILATION AIR SUPPLY

WHOLE-HOUSE VENTILATION SYSTEMS

Limited Lifetime core warranty. 5-year warranty on balance of unit.

Multifamily Central Ventilation Assessment and Retrofit Techniques

GARCIA GALUSKA DESOUSA Consulting Engineers

Outside Air Requirements... SOLVED!

2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Mechanical System Description

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (6)

AirCycler g2-k Installation & User s Guide

Applying the latest version of the National Ventilation Standard Heyoka Solutions, LLC Paul H. Raymer

Heat Recovery Ventilation

Mechanical Ventilation for Kansas Weatherization Programs

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (2)

HEAT RECOVERY VENTILATION For healthy, energy efficient ventilation

Introduction. Products conforming with a European Council Directive. CE marked construction products. Other regulations

Designing Thoughtful Green Performance - On-Demand Venting and Exhaust Systems

BIGGEST BANG FOR YOUR BUCK- Part Deux

Convergence: The Integration of Lighting and Micro Sensor Technology

Building Regulations Approved Document F1 Means of Ventilation April 2006

Uniform Dwelling Code 2017 Updates SPS 323

on-demand Minimizing Energy Loss through order to meet Sustainable Design Standards

EARTH ADVANTAGE HVAC REQUIREMENTS

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

Notable Changes in the Mechanical Codes

MECHANICAL VENTILATION

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

4. OVERVIEW OF MECHANICAL SYSTEM

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

Transcription:

Passive House Northwest AIA CEU Provider Multifamily Ventilation Strategies Workshop AIA Course # phnw082 Aubrey Gewehr March 27, 2015

Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-aia members are available upon request. This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is prohibited. Aubrey Gewehr

Course Description In an increasing market for multifamily - energy efficient - high performance building shells, efficient ventilations strategies become paramount in maintaining human health and comfort without sacrificing high level project such as Passivhaus Certification. So what is the best approach to creating a well-ventilated multifamily building? As with most issues in design, it depends This workshop will discuss ventilation approaches to be considered from large central air handlers, to individual systems in each dwelling, to options in between. The pros and cons of several strategies will be presented with ample time to pose questions and debate methods. How important is distribution? Is heat recovery necessary? Should occupants have control? How much air is enough? These questions and more will be addressed through outlining general concepts and presenting case studies. Bring your own questions or a specific problem you are struggling with for discussion.

Learning Objectives At the end of the this course, participants will be able to: 1. 2. 3. 4. Participants will be able to calculate the ventilation rates for multifamily dwellings based on International Mechanical Code and Passive House requirements. Participants will know the optimal distribution of supply and exhaust locations within a dwelling. Participants will be able to assess the different equipment strategies for providing multifamily ventilation and weigh the pros and cons of each. Participants will evaluate the ventilation needs of the non-dwelling ancillary spaces of a multifamily building and apply appropriate ventilation strategies.

Why Multifamily? Population growth Growth of households More people in urban areas limited land Housing expense Ecologically efficient Energy efficient PHNW 2015 6

Why Ventilate? Air Humidity CO ² Concentration VOC s Smells Allergens Temperature PHNW 2015 7

Learning Objective One 1. Calculating Passive House and Mechanical Code airflow rates PHNW 2015 8

Ventilation: How much air do we need? Depends upon who you ask International Mechanical Code (IMC) 2012 ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings 2010 Version and 2013 Version Passive House Institute (PHI) Passive House Institute U.S. (PHIUS) PHNW 2015 9

Example Apartment for Ventilation 1,200 SF TFA 8.2 FT Ceilings 3 bedrooms 2 Bathrooms PHNW 2015 10

IMC 2012 Airflow Referenced by the International Residential Code (IRC) Adopted by all the Northwest States 0.35 Air Changes per Hour (ACH) - But not less than 15 CFM per person Kitchen exhaust: 25 CFM continuous* Bathroom exhaust: 20 CFM continuous Toilet room exhaust: 20 CFM continuous *Some local states have adopted additional requirements 1,200SF * 8.2FT = 9,840 CF at 0.35 ACH BUT 3 Bedrooms = 4 People so Kitchen + 2 Bathrooms 57 CFM 60 CFM 65 CFM PHNW 2015 11

Passive House Airflow Airflows required for a certifying Passive House project 18 CFM Per Person 0.30 Air Changes per Hour (ACH) of TFA Kitchen exhaust: 35 CFM continuous Bathroom exhaust: 24 CFM continuous Toilet room exhaust: 12 CFM continuous Laundry room exhaust: 12 CFM continuous 1,200SF * 8.2FT = 9,840 CF at 0.30 ACH (*1.3) 49 CFM (64 CFM) 4 People * 18 CFM/P 72 CFM Kitchen + 2 Bathrooms 83 CFM PHNW 2015 12

Example Apartment for Ventilation 1,200 SF TFA 8.2 FT Ceilings 3 bedrooms 2 Bathrooms Standard Supply Exhaust IMC 60 CFM 65 CFM PHI 49 CFM 83 CFM 62.2-2010 42 CFM 40 CFM* 62.2-2013 66 CFM 40 CFM* * With Intermittent range hood or additional 5 ACH airflow out of the kitchen (+82 CFM for a 10x12 kitchen) PHNW 2015 13

Learning Objective Two 1. Calculating Passive House and Mechanical Code airflow rates 2. Optimal distribution of supply and exhaust locations PHNW 2015 14

Traditional System Layout Exhaust Air Locations Bathrooms Kitchen Supply Air Locations Corridors PHNW 2015 15

Traditional System Layout Exhaust Air Locations Bathrooms Kitchen Supply Air Locations Corridors?????? What s the ACH in the Bedrooms? PHNW 2015 16

Unventilated Bedrooms Get Stale House is 5.0 ACH At 50 PA Bedroom occupied at 11:15 pm with door closed Exhaust fan turned on at 1:30 am at 88 CFM (ASHRAE 62.2 Rate for house is 62 CFM Exhaust fan off at 6:00 am Door open at 6:30 am PHNW 2015 17

Typical Balanced System Layout Exhaust Air Locations Bathrooms Kitchen Laundry Moisture/Odor Laden Areas Supply Air Locations Bedrooms Offices Living/Family Rooms* Remote Rooms * Depending upon layout PHNW 2015 18

Learning Objective Three 1. Calculating Passive House and Mechanical Code airflow rates 2. Optimal distribution of supply and exhaust locations 3. Multifamily equipment strategies PHNW 2015 19

Exhaust Fan vs. HRV Energy Usage Exhaust Fan case, 60 CFM continuous: Energy Usage = (1.085)(60 CFM)(70 F - 30 F)(24 hours) = 62,496 Btu/Day Exhaust Fan Case, 120 CFM intermittent (2 hours per day): Energy Usage = (1.085)(120 CFM)(70 F - 30 F)(2 hours) = 10,416 Btu/Day Ventilation Thermal Energy Usage Make-up Air Temperature Daily Energy Usage [btu/day] 70,000 60,000 50,000 40,000 30,000 20,000 10,000 0 62,496 Continuous Bath Fan 10,416 Intermittant Bath Fan PHNW 2015 20 Make-up Air Temperature [ F] 70 60 50 40 30 20 10 0 Continuous Bath Fan 30 30 Intermittant Bath Fan

Exhaust Fan vs. HRV Energy Usage 75% Efficient HRV case, 60 CFM continuous: Energy Usage = (1.085)(60 CFM)(70 F - 30 F)(24 hours)(1 0.75) = 15,624 Btu/Day Make-up air temperature = 30 F + (70 F - 30 F)*(0.75) = 60 F Ventilation Thermal Energy Usage Make-up Air Temperature Daily Energy Usage [btu/day] 70,000 60,000 50,000 40,000 30,000 20,000 10,000 62,496 10,416 15,624 Make-up Air Temperature [ F] 70 60 50 40 30 20 10 30 30 60 0 Continuous Bath Fan Intermittant Bath Fan 75% Efficient HRV 0 Continuous Bath Fan Intermittant Bath Fan 75% Efficient HRV PHNW 2015 21

Exhaust Fan vs. HRV Energy Usage 90% Efficient HRV case, 60 CFM continuous: Energy Usage = (1.085)(60 CFM)(70 F - 30 F)(24 hours)(1 0.90) = 6,250 Btu/Day Make-up air temperature = 30 F + (70 F - 30 F)*(0.90) = 66 F Ventilation Thermal Energy Usage Make-up Air Temperature Daily Energy Usage [btu/day] 70,000 60,000 50,000 40,000 30,000 20,000 10,000 62,496 10,416 15,624 6,250 Make-up Air Temperature [ F] 70 60 50 40 30 20 10 30 30 60 66 0 Continuous Bath Fan Intermittant Bath Fan 75% Efficient HRV 90% Efficient HRV 0 Continuous Bath Fan Intermittant Bath Fan 75% Efficient HRV 90% Efficient HRV PHNW 2015 22

Multi-Family Options Individual Apartment Units With Individual Intake/Exhaust Pros Better Compartmentalization Individual Control Boost Capacity Good for Condominiums Minimize Duct Runs Minimize energy usage Energy paid by occupant Cons Multiple Wall Penetrations Dispersed Maintenance May be more expensive PHNW 2015 23

Multi-Family Options Individual Apartment Units With Ganged Intake/Exhaust Pros Good Compartmentalization Individual Control Boost Capacity Minimize Penetrations Potentially easier maintenance Energy paid by occupant Cons Central Ductwork & Fire Dampers Loss of Floor Space for Shafts Dispersed Maintenance May be more expensive PHNW 2015 24

Multi-Family Options Individual Apartment Units With Central Mechanical Room Pros Good Compartmentalization Individual Control Boost Capacity Minimize Penetrations Centralized Maintenance Cons Central Ductwork & Fire Dampers Loss of Floor Space for Shafts May be more expensive Energy paid by building owner PHNW 2015 25

Multi-Family Options Central Ventilation Units Pros Central Maintenance May be less expensive Minimize Penetrations Cons Central Ductwork & Fire Dampers Loss of Floor Space for Shafts No Individual Control / Boost Harder to Balance Higher energy usage Energy paid by building owner PHNW 2015 26

Central vs Dispersed Airflow Rates Passive House max airflow: 83 CFM Individual unit per apartment = Controllability High speed (boost mode) operation: 83 CFM Normal Speed operation (77% max): 64 CFM Low speed operation (0.3 ACH): 49 CFM Absent mode operation: 20 CFM Central System = One Speed Full Time operation: 83 CFM More Air = More Energy Higher thermal load to heat it Higher electrical load to move it PHNW 2015 27

Learning Objective Four 1. Calculating Passive House and Mechanical Code airflow rates 2. Optimal distribution of supply and exhaust locations 3. Multifamily equipment strategies 4. Addressing non-dwelling ancillary spaces PHNW 2015 28

Non-dwelling Ancillary Spaces Variety of other occupancies possible in a multifamily project: Corridors Trash rooms Janitor s closets Gathering rooms Bathrooms Storage areas Laundry Gym IMC and ASHRAE 62.1 Standards are appropriate to follow And (mostly) parallel with each other. PHNW 2015 29

Non-dwelling Ancillary Spaces Corridors: 0.06 CFM / SF Trash Rooms: 1.00 CFM / SF Exhaust Janitor s Closets: 1.00 CFM / SF Exhaust A good strategy to supply into the corridors and exhaust from the trash rooms & janitors closets. Dedicated HRV for this purpose at continuous rate. PHNW 2015 30

Non-dwelling Ancillary Spaces Gathering Rooms: 5 CFM/Person + 0.06 CFM/SF Public Bathrooms: 25 CFM/unit Exhaust single occupant 50 CFM/unit Exhaust multi occupant A good strategy to supply into gathering room and exhaust from the adjoining bathrooms. Dedicated HRV(s) for this purpose Good occupancy for CO 2 control low rate to meet bathroom requirements and ramp up with increased occupancy. PHNW 2015 31

Non-dwelling Ancillary Spaces Laundry Rooms: 7.5 CFM/Person + 0.06 CFM/SF Likely can be tied into an HRV system with other spaces. Per IMC, dryer exhaust over 200 CFM must have make-up air! Possible strategy to build dryer bank into a make-up air plenum behind the machines. Interconnect make-up air dampers to open with dryer operation PHNW 2015 32

Non-dwelling Ancillary Spaces Gyms: 20 CFM/Person + 0.06 CFM/SF Storage Rooms: 0.12 CFM/SF Office Spaces: 5 CFM/Person + 0.06 CFM/SF Can likely be tied into HRV with other spaces Gym may utilize dedicated HRV with CO 2 control since high rates and intermittent usage likely. PHNW 2015 33

In Summary Design airflows to Passive house rates but check for compliance with local building code. Fully distributed systems of balance ventilation are key for good indoor air quality and a healthy dwelling. Heat recovery ventilation saves substantial energy. Individual systems in each dwelling are best practice but may not fit into every project s particular constraints. Ancillary spaces must be addressed and incorporated into overall ventilation strategy. When in doubt, hire an engineer WITH Passive House training PHNW 2015 34

This concludes The American Institute of Architects Continuing Education Systems Course Passive House Northwest education@phnw.org

? Questions???????????