Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Similar documents
2006 Building Science Press All rights of reproduction in any form reserved.

Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Air Distribution Fan and Outside Air Damper Recycling Control

Unvented Roof Summary Article

Results of Advanced Systems Research: Supplemental Humidity Control Systems

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by

Building America Special Research Project: Space Conditioning Systems for High Performance Homes

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS

Supplement A- Improving Forced Air Heating Systems

2006 Building Science Press All rights of reproduction in any form reserved.

Unvented Roof Assemblies for All Climates by Chris Schumacher

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

FirstEnergy Program Overview

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

RESNET HERS Rater Sample Test Questions 2

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

Ventilation for New Low-Rise Residential Buildings July 20, 2015

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

Dehumidifying with Dedicated Outdoor Air

Residential Heating and Cooling Loads

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships. John Tooley Advanced Energy (919)

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Using a Pressure Pan To Diagnose Duct Leakage

ENERGY STAR Qualified Homes

Effects of Kitchen Ventilation on Residential Dwellings

Don t Turn Active Beams Into Expensive Diffusers

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

In the past, contractors sized heating and cooling systems GETTING HVAC RIGHT

Systems Engineering Approach to Development of Advanced Residential Buildings

Mechanical Ventilation : How much is enough? Can there be Too Much? Subrato Chandra Resnet Meeting 2/20/07

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Executive Summary

Dehumidification: Energy Efficiency Comparisons

When Duct Sealing Kills HVAC Equipment and Efficiency

Managing HVAC in High Performance Buildings

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

100% Outdoor Air Dehumidification Methods

Adding More Fan Power Can Be a Good Thing

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

ACCA Manual J Load Calculations

Insight. Cool Hand Luke Meets Attics. What we ve got here is failure to communicate By Joseph W. Lstiburek, Ph.D., P.Eng.

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II

Energy Impacts of Various Residential Mechanical Ventilation Strategies

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

MF Mechanical Systems. Doug McCleery, PE, CEM March 2, 2016

Relative Humidity in Schools Jim Cummings and Chuck Withers

Design and Operation of a Conditioning Energy Recovery Ventilator (CERV) for Passive Houses

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Insight Duct Dynasty 1

Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Neil A. Moyer James B. Cummings David Chasar Principal Research Engineer Program Manager Research Engineer

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Moisture, Ventilation & Global Weirding NEHERS Webinar Series

Ventilation in Humid Climates: Data from Field Experiments

HOME PERFORMANCE ENERGY ANALYSIS

1 Exam Prep Energy Efficient Building Construction in Florida Questions

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Practical and Effective Approaches to Residential Ventilation for Production Builders

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

ω = (1) Kirby S. Chapman Ph.D.

Cold Storage Warehouse Dock Parametric Study

Building Envelope Air Leakage Failure in Small Commercial Buildings Related to the Use of Suspended Tile Ceilings

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Desiccant Dehumidifier

Museum Archive Dehumidification in Hot & Humid Climates

An Introduction to Energy Efficient and Effective Whole-House Ventilation

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Model 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Basic Building Science insights for Spray Foam, HVAC and Moisture

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

Mold/Moisture Control Case Study

HOW THE FIRST OCCUPANT BEHAVIOR DEHUMIDIFICATION SOLUTION FOR APARTMENT LIVING WAS CREATED

Measured Duct Leakage at Operating Conditions in 48 Homes

Heat pump and energy recovery systems

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Expansion Tank Design (Hydronic Hot Water)

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

ENGINEERING. Edition No. 13 October 2002

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

b.) Technical Information:

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Transcription:

building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 107 Understanding Ventilation in Hot Humid Climates 2006-10-26 by Joseph Lstiburek Abstract: Adding outdoor air in hot humid climates causes moisture problems right? Sometimes. It depends on the condition of the house before you start to add outdoor air. Contrary to popular belief, most houses in hot, humid climates are over ventilated due to duct leakage and induced air change from internal air pressure effects due to unbalanced air flow and door closure. In most houses when HVAC systems are operating, air change rates of between 0.5 and 1.0 ach are common. Between 150 cfm and 200 cfm of outdoor air is typically introduced in this manner when systems are operating. When HVAC systems are not operating, air change rates of between 0.1 ach and 0.2 ach are common due to stack forces and wind. ASHRAE Standard 62.2 recommends adding approximately 40 to 50 cfm of outdoor air. If duct leakage and pressure effects are addressed, no additional latent load is added during full load periods. The uncontrolled air change is dropped to near zero and controlled air change is added in its place. The resultant latent load is typically similar or lower than standard practice again under full load. However, if outdoor air is added to a standard house with duct leakage and internal pressure effects, moisture problems are almost assured - duct leakage and internal air pressure effects must be addressed. Even if duct leakage and internal pressure effects are addressed, the latent loads introduced by ventilation air during part load periods are significant and must be addressed. This can only be done with supplemental dehumidification or ASHRAE Standard 62.2 flow rates should be reduced. 1

2 Building Science Digest 107 Introduction Ventilation is an obvious latent load in hot humid climates. What is less obvious is that there are two components to ventilation: the controlled component and the uncontrolled component. The controlled component is of course the outdoor air the designer adds to the building via a controlled ventilation system. The uncontrolled component is defined here as air change created by wind effects, stack effects and the pressure effects from the operation of the HVAC system. The uncontrolled component in most houses is larger than commonly assumed and typically larger than the desired controlled component. Adding an additional controlled component to this large uncontrolled component would only make an already bad situation worse. ASHRAE Standard 62.2 (Ventilation for Acceptable Indoor Air Quality in Low-Rise Residential Buildings) recommends the following ventilation rate: 7.5 cfm/person + 0.01 cfm/ft2 of conditioned floor area Occupancy is defined as the # of bedrooms + 1 For a common single family detached house (3 bedrooms; 2,000 ft 2 ) this works out to 50 cfm of outdoor air. Restated, based on typical house volumes (ceiling heights at 8 ft), this is between 0.2 and 0.3 air changes per hour. The uncontrolled component is dominated by pressure effects created by the operation of the HVAC system. Wind effects and stack effects acting on residential enclosures in hot humid climates are low enough to be almost neglected. This is reflected in ASHRAE Standard 136 (A Method of Determining Air Change in Detached Dwellings) and the tabulated values for W (the weather factor) and an appreciation of residential construction. Most residential enclosures in hot humid climates are low rise (below two storys often one story - therefore only a small stack potential exists even if an appreciable temperature difference is present) and clad with stucco (a tight cladding system that is relatively wind insensitive). Work done by Tooley, Moyer, Cummings and many others in the late 1980 s and early 1990 s showed that the operation of the HVAC system in homes constructed in hot humid climates yielded air change rates of between 0.5 and 1.0 when the systems were operating. When HVAC systems were not operating the same research work showed air change rates of 0.1 to 0.2 ach. Duty cycles (on time) often range between 30 and 70 percent. Assuming a 33 percent duty cycle, the HVAC system induced air change is equal to a continuous ventilation rate of between 50 cfm and 100 cfm. At the time of the work by Tooley, Moyer, Cummings, the typical house envelope leakage characteristics ranged between 2,000 and 3,000 cfm at 50 Pa. In other words, the building envelopes were fairly leaky. One obvious, but often overlooked, truth is that air change does not occur without an air pressure difference even in a leaky

Understanding Ventilation in Hot Humid Climates 3 building enclosure. In the humid south, since stack effects and average wind speeds acting on low rise residential enclosures are small, air change due to these effects is low, and almost independent of envelope leakage area. During the past decade, residential building envelope leakage areas have decreased due to more effective draftstopping. This has resulted in an unintended consequence air pressure differences within houses and between houses and the exterior have increased when HVAC systems are operating. Although the airtightness of the building envelope has increased, the expected air change reduction has not occurred due to the induced air pressure effects. Houses with leaky ductwork and unbalanced air flows continue to have high air change rates despite improvements in building envelope construction. Pressure Effects HVAC system induced air change occurs two ways: leaky ductwork and air handlers located outside of the building pressure boundary (Figure 1) and unbalanced air flows due to door closure and inadequate return flow (Figure 2). A subset of the first type of air change also occurs due to air pressure effects within building cavities (Figure 3). This type of induced infiltration results in serious interstitial moisture problems, but does not always constitute a significant interior latent load. Figure 1: Leakage of HVAC Equipment into Unconditioned Space

4 Building Science Digest 107 Figure 2: Pressure Effect Due to Unbalanced Air Flows Figure 3: Air Pressure Effects within Building Cavities

Understanding Ventilation in Hot Humid Climates 5 Addressing the uncontrolled HVAC system induced air change requires tight ductwork, sealed air handlers, and balancing the flow between rooms. With tight ductwork, sealed air handlers and balanced air flow, uncontrolled air change can be reduced to near zero. Ductwork and air handler leakage can be addressed using many techniques that will not be addressed here (except to say that standard duct tape is not one of them). Leakage values of approximately 5 percent (as tested by pressurization at 25 Pa) of total flow or less appear to result in negligible air change when HVAC systems are operating and return system flows are balanced (Lstiburek & Rudd). Numerous federal, state and utility construction programs have promoted duct system and air handler leakage performance specifications in the 5 percent range a range of duct leakage that appears to be justified based on the field experience to date. Pressurization effects due to door closure can cause significant air change and comfort problems. Bedroom pressurization relative to hallway/common areas of 10 to 20 Pa is common with single return systems (Tooley & Moyer). These effects can be mitigated using transfer grilles (Figure 4) or jump ducts (Figure 5). Figure 4: Transfer Grille

6 Building Science Digest 107 Figure 5: Jump Duct The New Moisture Balance If the uncontrolled air change is reduced to near zero and replaced with a continuous flow roughly equal to the uncontrolled air change, it can be argued that the net moisture balance should remain unaffected. Adding controlled ventilation does not increase latent loads under this condition. However, this is only true during the time of year when HVAC systems regularly operate. During the spring and fall months during the part load seasons - HVAC systems do not regularly operate. Air change drops to between 0.1 and 0.2 ach. The typical house has a very low latent load due to air change during this time. This is fortunate since there is also almost no provision for moisture removal during this time by the HVAC system. Adding controlled ventilation to this condition does constitute a significant increase in the latent load. In fact, the load during this time is almost completely latent because the outdoor dry-bulb temperature is very near to the indoor dry-bulb temperature and this latent load is effectively doubled in the typical house by adding a ventilation rate of 0.15 and 0.2 ach (the typical ASHRAE Standard 62.2 rate). Gatley notes that the process of air conditioning consists of approximately 70 percent sensible cooling in the form of temperature reduction accompanied by approximately 30 percent latent cooling in the form of water vapor removal. According to Gatley, at partial load operating conditions which occur for a majority of system operating hours many dwellings in hot humid climates require higher ratios of latent cooling 40 to 50 percent. This is not possible with standard residential air conditioning equipment. The latent load problem under part load conditions during the spring and the fall in humid climates is progressively becoming more serious as the typical residential

Understanding Ventilation in Hot Humid Climates 7 building envelope and its mechanical equipment evolve. The use of high performance window systems (spectrally selective windows high visible light transmittance, low solar heat gain coefficient) is significantly increasing the time period of part load conditions during the year. This is coupled with equipment with higher SEER and EER ratings with no latent load control. And as a final insult to the house and its occupants, the equipment is typically oversized (on the order of 150 percent or more of total load). Adding controlled ventilation with untreated outdoor air to a house under these conditions almost assures problems even with tight ductwork, sealed air handlers and balanced air flows. Gatley, citing work done by The Trane Company, shows the effect of oversizing. Systems oversized by 20 percent achieve latent heat removal of approximately 15 percent of the total cooling load under the assumed part load conditions. Whereas, correctly sized systems achieve moisture removal of up to approximately 30 percent under part load conditions. The same work shows that in correctly sized systems with variable speed fans with constant speed refrigeration compressors achieve 35 percent moisture removal under part load conditions. With variable refrigeration compression this moisture removal is even greater. Sizing of equipment will not be addressed here except to note that it is a major residential HVAC industry problem. Even with correctly sized standard HVAC systems, the part load problem associated with the latent load remains albeit not to the same extent. The author s experience with newly constructed houses in hot humid climates has led him to conclude that supplemental dehumidification during part load periods is necessary especially in houses with controlled ventilation. Three general approaches to supplemental dehumidification in residences are recommended: stand-alone dehumidifiers (Figure 6); enhanced air conditioning systems (variable speed blowers and compressors); and ventilating dehumidifiers. Each approach has advantages and disadvantages.

8 Building Science Digest 107 Figure 6: Air Handler Schematic with Stand-Alone Dehumidifier Air handler located and accessed within interior conditioned space. Dehumidifier and condensate overflow pan supported by metal stand. Dehumidifier drain plumbed to air handler condensate system. Outside air provided to return side of system with motorized damper control. Flow controller for outside air should not allow air handler to run with motorized damper open for 15 minutes after cooling is de-energized to prevent re-evaporation of condensate from coils and drain pan. Outside air is controlled by a motorized damper. Closing the outside air damper during unoccupied periods will allow the flow controller to periodically mix the interior air without bringing in outside air helping the dehumidifier control interior RH humid air is brought to the dehumidifier. The cooling function of the A/C can also be shut down during this time (i.e. A/C on blower only operation). Pressure relief grille provided to bleed accidental/incidental pressure field created by duct leakage.

Understanding Ventilation in Hot Humid Climates 9 The use of a stand-alone dehumidifier plumbed/drained to a condensate drain has the advantage of low cost (adds approximately $300 to the typical house). The disadvantage is the heat generated by the dehumidifier and it s effect on comfort. Additionally, operating costs are the highest of the three general approaches. However, it is a simple to implement solution and typically compensates for oversizing of equipment. The use of enhanced air conditioning systems has the advantage of not having to install a separate piece of equipment. The disadvantage is a substantial increase in cost (adds approximately $1,000 or more to the typical house). Additionally, equipment sizing is critical. However, implementation is the easiest of the three systems and costs are likely to drop the most as these systems become commodity items as opposed to special order. The use of ventilating dehumidifiers has the advantage of the lowest operating cost (since these dehumidifiers have been optimized for humidity removal). The chief disadvantage is their current cost (adds approximately $2,000 to the typical house). Conclusions In order to provide controlled ventilation in new houses constructed in hot humid climates without creating latent load problems it is necessary to take the following measures: Install tight ductwork and air handlers Balance interior air flows Size equipment correctly Provide supplemental dehumidification References ASHRAE Standard 136-1993 (RA 2001); A Method of Determining Air Change Rates in Detached Dwellings, ASHRAE, Atlanta, GA, 2001. ASHRAE Standard 62.2P; Ventilation for Acceptable Indoor Air Quality in Low-Rise Residential Buildings, ASHRAE, Atlanta, GA, 2002. Cummings, J.B. and Tooley, J.J.; Infiltration Rates and Pressure Differences in Florida Homes Caused by Closed Interior Doors When the Central Air Handler is On, Passive Solar Conference, Cambridge, MA, 1988.

10 Building Science Digest 107 Cummings, J.B. and Tooley, J.J.; Infiltration and Pressure Differences Induced by Forced Air Systems in Florida Residences, ASHRAE Transactions, June, 1989. Gatley, D.P.; Energy Efficient Dehumidification Technology, Workshop Proceedings: Bugs, Mold & Rot II, Building Environment and Thermal Envelope Council, Washington, DC, November 16-17, 1993. Lstiburek, J.W.; Humidity Control in the Humid South, Workshop Proceedings: Bugs, Mold & Rot II, Building Environment and Thermal Envelope Council, Washington, DC, November 16-17, 1993. Lstiburek, J.W. and Rudd, A.; Controlled Ventilation in Building America Houses, Building Science Corporation, Westford, MA, 2002. Tooley, J.J. and Moyer, N.A.; Mechanical Air Distribution and Interacting Relationships, Florida Home Energy Reviews of Orlando, Orlando, Florida, February, 1988. Joseph Lstiburek, Ph.D., P.Eng., is a principal of Building Science Corporation in Westford, Massachusetts. He has twenty-five years of experience in design, construction, investigation, and building science research. Joe is an ASHRAE Fellow and an internationally recognized authority on indoor air quality, moisture, and condensation in buildings. More information about Joseph Lstiburek can be found at www.buildingsciencecorp.com Limits of Liability and Disclaimer of Warranty: Building Science Digests are information articles intended for professionals. The author and the publisher of this article have used their best efforts to provide accurate and authoritative information in regard to the subject matter covered. The author and publisher make no warranty of any kind, expressed or implied, with regard to the information contained in this article. The information presented in this article must be used with care by professionals who understand the implications of what they are doing. If professional advice or other expert assistance is required, the services of a competent professional shall be sought. The author and publisher shall not be liable in the event of incidental or consequential damages in connection with, or arising from, the use of the information contained within this Building Science Digest.