Technical Paper. Auto tuning and motor protection as part of the pre-setting procedure in a heating system

Similar documents
Hydraulic balance in a district cooling system

Technical paper Hydraulic balance in a district cooling system

ECL Comfort 110, application 116

Technical paper Selection of district heating house stations

ECL Comfort 110, application 130

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

Weather compensated flow temperature control of heating and boiler systems

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

ECL Comfort V a.c. and 24 V a.c.

ECL Comfort V a.c. and 24 V a.c.

The ECL Comfort 110 is a universal 1-circuit controller for use in district heating substations and district heating systems as well as boilerbased

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys

SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL Version 2.1

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

Technical paper Analysis on flat station concept (Preparing DHW decentralised in flats)

Installer Manual KNX Touchscreen Thermostat

Wall-mounted substation PKL-113

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark

TC515 and TC600 Installation Manual. a Winters company

CG Series Digital Temperature Controller OPERATIONS MANUAL

Lecture 4 Power System Protection. Course map

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

Optimal Building Integration of District Heating Substations

Bench-Top Vacuum Oven with 28 segments programmable controller

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

120+ Get your job done swiftly Easy selection of your application is the key. applications.

V3000 KNX. KNX PID control system on water GENERAL DESCRIPTION

Capacity controller for water chiller AK-CH 650

Thermostatic head K. with contact or immersion sensor. Thermostat-Köpfe For medium temperature control

CALEFFI. Solar storage-to-boiler thermostatic connection kit series 01164/09 GB. Function

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR

Optimizing Strategy for Boiler Drum Level Control

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

prestige Control Application Supplement - ACVMax

T6984 A,D,E Electronic Floating Control Thermostats

SP-2400 & 2410 Series Smart Valve Positioner (Linear & Rotary)

prestige Control Application Supplement - TriMax

973 Dew Point Mirror. Portable Industrial Chilled Mirror Hygrometer. Typical applications: REFLECTING YOUR STANDARDS

Home appliances simulator for smart home systems testing

Distribution systems in apartment buildings

Example of Applications and Parameter Functions

Installation Guide. ECL Comfort 210, application A Table of Contents

HydroFlex FLEXIBLE AND RELIABLE MICROPLATE STRIP WASHING AND VACUUM FILTRATION IN A COMPACT, MODULAR PLATFORM. 21 CFR Part 11* 98/79/EC IVD-D*

OVEN INDUSTRIES, INC.

DAWN Electronics, Inc.

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Contact person Date Reference Page Daniel Månsson P07886E-rev2 1 (14) Energy and bioeconomy

CONTROLLING BOILER SWELL AND SHRINK

ROOM THERMOSTAT. with OpenTherm+ communication

R1000 / R1040 / R1080

Service Manual - Series 450/451 IG IGV IG IGV IG IG IG IGV IG

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

HYDROGEN DETECTION INSTRUMENTATION FOR THE SIAC HYDROGEN RECOMBINERS. Summary

Contact person Date Reference Page Björn Folkeson P (14) Energy and bioeconomy

T7984 A,B,C Electronic Modulating Control Thermostats

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES

SX65 and SX75. Electronic process controllers

prestige Control Application Supplement - TriMax

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Rotary Evaporators designed

USER- MANUAL TV7000MKII

"A Case Study of Three Drum Parameter Control in Boiler Using Discrete PID Controller Based on Simulation"

Proceedings Design, Fabrication and Optimization of a Silicon MEMS Natural Gas Sensor

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

product overview ProControl

I/A Series 716C 1/16 DIN Temperature Controller

Intelligent Signature Series Analog Detection

Temperature dependent Components within the Pyroelectric Detector

Control Application. Supplement - ACVMax

Understanding total measurement uncertainty in power meters and detectors

Saving energy with Synco

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

TP970 and TP9600 Series Pneumatic Thermostats

Contact person RISE Date Reference Page Daniel Månsson P (13) Energy and circular economy

Omnisens DITEST TM FIBER OPTIC DISTRIBUTED TEMPERATURE & STRAIN SENSING TECHNIQUE

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand.

Temperature Data Logging

EC 160 CO 2. Incubator

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

NATURAL VENTILATION CONTROL SYSTEMS

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

MICRO CONTROLLER S Z SERIES

Optimization of key processes in a refrigeration system. For maximum cooling load there was an EER increase of 18,6% (EER = Energy efficiency Ratio).

4TEMPERATURE CONTROLLER

MODEL-BASED OPTIMIZATION OF AN INFRARED GAS SENSOR

Control solutions Biofloor

ORP (mv) Controller Model: ORP-XP2. UP DOWN ENTER Time & Date Main Menu Alarm Reset

ISO-9001:2008 FURNACES CATALOG. Phone: Fax: Web:

ECL Comfort V a.c. and 24 V a.c.

Temperature Controllers

HydroFlex 3-in-1 microplate strip washing. Flexible and reliable microplate strip washing and vacuum filtration in a compact, modular platform

ThermoMax Steam System Efficient. Reliable. Consistent.

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

Contact person Date Reference Page Björn Folkeson P (15) Energy and bioeconomy

Transcription:

Technical Paper Auto tuning and motor protection as part of the pre-setting procedure in a heating system By Herman Boysen Product Application Manager Auto Tuning inside ECL Comfort The result of Auto Tuning Tap Water Temperature ( C) 80 70 60 50 40 30 20 10 0 Tap Water ( C) Sec. Flow (m3/h) 0.00 5.00 10.00 15.00 20.00 25.00 30.00 Time (min.) 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 Flow Rate (m 3 /h) Published in News from DBDH 3/2000 District Heating Academy

Auto tuning and motor protection as a part of the pre-setting procedure in a heating system B. Sc. Eng. Herman Boysen Product Application Manager Autotuning: Adaptive setting of a domestic hot water service controller. Motorprotection: Automatic setting of a controller during low performance. A precondition for a well functioning heating system is that the correct settings are made before it is put to use. Adjustments are necessary to preset the regulating parameters. This article deals with the way in which the automatic setting of system control parameters is performed and the advantages this gives. Why pre-set a heating system? Pre-setting gives the following benefits: A high degree of comfort Improved protection against lime deposits in domestic hot water heat exchangers Energy saving Long operating life Minimum service Experience shows that the necessary settings are often not made or that they are inadequate. The reasons can be as follows: Ignorance of the importance of pre-setting Lack of instruction in setting No money has been allocated for pre-setting No agreement has been made on system pre-setting The consequence is that the system will not function as intended. Fig. 1. Typical consumer substation in a district heating installation with a heating system and domestic hot water system 2 VF.BB.V1.02 09/2002

Setting a consumer substation in a district heating installation A district heating substation in a large supply installation usually consists of a room heating system and a domestic hot water system (fig. 1). Such stations are often equipped with electronic regulators. Pre-setting includes setting the regulating parameters for both the heating and domestic hot water systems. The heating system is of course not particularly dynamic, in that load changes are usually a result of changes in the outdoor temperature and periodic reductions in the heat output. This is a form of operation that does not impose very high demands on the regulator in order to maintain constant flow temperature in the heating system. Here, the regulator factory settings, based on calculations and experience, are often sufficient to make further adjustments unnecessary. Settings of this type are not dealt with in this article. The opposite is true with the domestic hot water system. In this case the load changes concurrently with the consumption of hot water. Short but considerable load changes are frequent and the demand for high regulating accuracy and domestic hot water temperature stability is high. For several reasons, flow systems such as the one shown in fig. 1 have won approval in district heating systems that incorporate domestic hot water heating. Experience also shows that it is this type of system that imposes the greatest demands on regulating equipment and regulator setting parameters. Setting a regulator for a heating system District heating and domestic hot water systems of the type shown in fig. 1 are normally equipped with PI regulators. To ensure a regulated temperature of satisfactory quality the various parameters of the regulator must be set. The settings involved are as follows: Neutral zone Nz Proportional band Xp Integration time Tn Motor constant Tv The proportional band setting (Xp) affects the extent to which the regulator reacts to a temperature variation. A small Xp gives high amplification and fast reaction to a given temperature variation, but carries with it the risk of unstable temperature. A large Xp gives low amplification and only slight reaction to temperature variation, which means sluggish regulation with high temperature variations when the load changes. The integration time (Tn) affects recovery of the set temperature. A short integration time gives fast recovery, but a risk of instability. A long integration time gives stable regulated temperature, but long recovery time. Setting the valve motor constant (Tv) takes account of the motor running time and the valve stroke. The output signal of the regulator is adjusted accordingly. Setting these parameters requires good knowledge of the heating system parameters and of the regulator, which has to be set. If the technician concerned has little experience of making such settings, it can be a very time-consuming process. Among the parameters of significance to pre-setting are the following: System operating temperatures System load variations Valve motor speed Motorised valve characteristic Heating system time constant Differential pressure across the motorised valve What are the demands on domestic hot water temperature regulation? The demands most often made in connection with the regulation of domestic hot water temperature involve: 1. Set temperature recovery 2. Temperature stability 3. Max. temperature variation on load change 4. Recovery time after a temperature variation on load change. In its requirements and instructions for the installation of district heating consumer stations, the Finnish District Heating Society /1/ gives recommendations on the regulating accuracy of temperature in domestic hot water systems. VF.BB.V1.02 09/2002 3

Requirement Temperature variations Settings Effects Max. constant permanent deviation from set point after a temperature change, +/-2 K Nz Neutral zone Small Nz setting improves recovery accuracy with risk of unstable flow temperature. Max. permanent temperature hunting, +/-2 K Xp Proportional band Tn Integration time Small Xp gives fast-acting system with risk of hunting. Short Tn gives fast system with risk of hunting. Max. temperature variation during operation, 10 K Xp Proportional band Small Xp gives small variations, but with risk of hunting. Recovery time after a temperature change, <+/-2 K within 120 seconds Tn Integration time Long Tn gives long recovery time of set temperature. Table 1. Recommendations on the regulating accuracy of temperature in domestic hot water systems. Table 1 shows the requirements contained in the recommendations on the regulating accuracy of temperature in domestic hot water systems issued by the Finnish District Heating Society /1/. The requirements in table 1 relate to domestic hot water temperature accuracy in connection with load change and constant operation. The requirements are as follows: 1. Max. constant temperature variation from set point after a temperature change, +/-2 K. 2. Max. permanent temperature hunting, +/-2 K. 3. Max. temperature deviation during operation, 10 K. 4. Recovery time after a temperature change, <+/-2 K within 120 seconds. Testing the domestic hot water system To test these parameters it is necessary to run a tapping programme in which the system is loaded in steps of 25% up to 100% load and then down again to 0%. During 0% load the test is run with a consumption corresponding to the circulation of domestic hot water in the system. A typical example of this procedure is shown in fig. 3. The problems in fulfilling the requirements of the recommendations can be seen in the changes of flow from 0%-25% and from 25%-0%. The test parameters shown in the simulation, fig. 3, and the tests, fig. 4 and fig. 5 are: T11 District heating flow T12 District heating return T21 Domestic cold water temperature T22 Domestic hot water temperature ml District heating flow m2 Domestic hot water flowcirculation of domestic hot water in the system. 4 VF.BB.V1.02 09/2002

Fig. 2. Simulation of typical test in accordance with the recommendations of the Finnish District Heating Society/1/ Temperature stability, recovery capability and settling time show no particular problems during testing under the given conditions. However, it can be seen that the deviation in domestic hot water temperature exceeds the recommended max. 10 K from the setting. Furthermore, there are problems with temperature stability during no-load operation where the load corresponds to the heat loss in the circulation lines. During no-load conditions, the motorised valve operates with a very small degree of opening and the valve characteristic is very steep. The consequence is high amplification. /2/, /3/, /4/. The hunting during no-load operation shown in fig. 2 is seen very often in domestic hot water systems. Hunting imposes high demands on the quality of the motor and regulator; the motor is cut in and out very frequently and is thus subjected to much wear. If the regulator is equipped with output relays the frequent switching has a significant effect on the life of the regulator. If regulators with triac output are used, this form of operation does not load the regulator in the same way. Auto tuning From the above explanation of the effect of regulating parameters on temperature regulation it can be seen that there is a contradiction between the settings that improve stability and those that reduce deviations. Smaller regulation deviations require a smaller Xp setting. This increases the risk of hunting, and hunting during no-load operation becomes amplified. A larger Xp setting gives rise to greater deviations in the domestic hot water temperature during load changes. In contrast, the domestic hot water temperature during no-load operation becomes more stable. The conclusion must be that there ought to be different regulator settings, depending on whether the system operates while hot water is being consumed or whether it is operating under no load. Experience with the operation of domestic hot water systems, tests in laboratories and dynamic computer simulations have led to the development of an automatic setting function that is able to satisfy both conditions: a setting function (auto tuning) for automatically setting Xp and the motor constant in a consumption situation and a function (motor protection) that changes setting parameters during no-load operation. In this way stable operation is ensured. Patents have been applied for both functions. VF.BB.V1.02 09/2002 5

T 11 T 12 T 21 T 22 m 1 m 2 Fig. 3. Example of auto tuning of a domestic hot water system where the regulator setting parameters are changed to ensure stable temperature. The setting of the regulator for a domestic hot water system with auto tuning is now limited to just the following: 1. Loading the system with a constant tapping flow corresponding to the simultaneous opening of several taps. 2. Activation of auto tuning on the regulator. 3. Waiting 7-15 minutes until auto tuning has been completed. Fig. 3 shows a test in which auto tuning has been initiated. The test shows where the regulation of domestic hot water goes from an unstable to a stable situation when the regulator setting parameters are being changed. In this light, the settings thus arrived at will be the optimum. The setting of motor protection occurs automatically during system operation. 6 VF.BB.V1.02 09/2002

T 11 T 12 T 21 T 22 m 1 m 2 Fig. 4. Test of a motor protector. Regulation becomes stable after a short time. Figure 4 shows a test result from a noload operation situation. Regulation becomes stable after a relatively short time, which is what happens when regulator settings are changed automatically. In addition, after about 19 minutes of operation a further tapping period of approximately 6 minutes takes place and the regulator settings are changed automatically to the values set for auto tuning. After final tapping, the regulator again performs a parameter change so that once again the temperature becomes stable during no-load operation. Conclusion The introduction of automatic setting of regulation parameters on the regulator itself, i.e. auto tuning and motor protection, gives optimum regulation of the domestic hot water system. This ensures a high degree of comfort, stable regulation during no-load operation and, subsequently, longer motor life. The setting of regulator parameters can thus be reduced to one simple and reliable procedure. Auto tuning is especially necessary in domestic hot water systems. Parameter setting for heating systems is not as critical, although in such systems motor protection in the regulator can be relevant. References 1. Finnish District Heating Society: District Heating in Buildings, Requirements and Instructions, K1/1992. 2. Benonysson, A., Boysen H.: Optimum Control of Heat Exchangers. 5th International Symposium on Automation of District Heating Systems, Finland, August 1995. 3. Benonysson A., Boysen H.: Valve characteristics for motorised valves in district heating substations, Euroheat & Power Fernwärme International 7-8/99. 4. Boysen H.: District heating house substation and selection of regulating valves, Danish Board of District Heating News from DBDH Journal number 2/1999. VF.BB.V1.02 09/2002 7

More articles on the same subject Valve characteristics for motorized valves in district heating substations by Atli Benonysson and Herman Boysen Optimum control of heat exchangers by Atli Benonysson and Herman Boysen Differential pressure controllers as a tool for optimization of heating systems by Herman Boysen District heating house substations and selection of regulating valves by Herman Boysen kv: What, Why, How, Whence? By Herman Boysen Pilot controlled valve without auxiliary energy for heating and cooling system by Martin Hochmuth Pressure oscillation in district heating installation by Bjarne Stræde Dynamic simulation of DH House Stations by Jan Eric Thorsen District Heating Academy VF.BB.V1.02 09/2002