T4398A,B Precision Electric Heating Thermostat

Similar documents
T4398A,B High Performance Electric Heat Thermostats

T4098A,B Deluxe Electric Heat Thermostats

T834C Heating-Cooling Thermostat

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

The T6140A,B Remote Bulb Temperature Controller

IS Series Pressure Sensing Switches

T874 Multistage Thermostat and Q674 Subbase

C554A Cadmium Sulfide Flame Detector

L8005A,B; LS8005A,C,D Electronic Pool and Spa Controllers

T7079A,B Solid State Remote Temperature Controllers

Commercial/Industrial Combustion Control Level Three Announcement

T8411R Electronic Heat Pump Thermostat

Powers TM Controls ET 134 Line Voltage Room Thermostats

CT500 Electronic Thermostat

CT1500, CT1501, CT1502, CT1503

T8034C Heating/Cooling Thermostats

TC-5231 Series, TC-5232, & TC-5241 Series

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

HE360 Humidifier Installation Kit

Heating/Cooling Thermostat and Subbase Package T8196A/Q682A

T7200D,E Series 2000 Commercial Microelectronic Thermostats

Technical Instructions Document No P25 ET September 28, ET 141 Electric Surface Mounted Thermostat.

Home and Building Control Home and Building Control Helping You Control Your World

TP970 Series CONVERTASTAT Kits

UV100E Ultraviolet Air Treatment System

T6984F,G Electronic Floating Control Thermostats

HE120, HE160 Humidifier Installation Kit

T874A-F Multistage Thermostats; Q674A-G Subbases by Honeywell

T4700 Chronotherm Electronic Programmable Line Voltage Thermostat OWNER S GUIDE

T8600D Chronotherm IV Deluxe Programmable Thermostats

CR7075 Two-Stage Lighting Controller

T8602C Chronotherm IV Deluxe Programmable Thermostats

W43A Humidistat. Features and Benefits

T8090A/Q682B Heating, Cooling, and Heating-Cooling Thermostat, Wallplate and Subbase

T8611M Deluxe Programmable Heat Pump Thermostats

Deluxe Programmable Heat Pump Thermostat T8611M

CT2700 An Electronic Round Programmable Thermostat

HE220, HE260 Humidifier Installation Kit

HE365A,B Powered Flow-Through Humidifier

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

UV100A Ultraviolet System

Deluxe Programmable Thermostats

HE360A,B Powered Flow-Through Humidifier

T8624D Chronotherm IV Deluxe Programmable Multistage Thermostats

Q382A,B Pilot Burners

F150E Media Air Cleaner

HE360 Powered Flow-Through Humidifier

Must be installed by a trained, experienced technician

Electronic Thermostat

T7984 A,B,C Electronic Modulating Control Thermostats

RA889A Switching Relay

TK-1001, 1101, 1201, 1301, 1601

Retrostat Kits for Johnson Controls D/N or H/C Thermostats

Q7800H Integrated Burner Control Subpanel

IMPORTANT INSTRUCTIONS FOR FAN-FORCED HEATER USE

CT2800 Programmable Thermostat

Schneider Electric Erie T155 Series

HE420A Steam Power Humidifier

T8611G Chronotherm Deluxe Zoning Heat Pump Thermostat

HE365A,B Powered Flow-Through Humidifier with

Line Voltage Non- Programmable Thermostat Installation Instructions & User Guide

INSTALLATION GUIDE Dual Fuel Ranges

MagicStat CT3300 Programmable Thermostat

C6097A,B Pressure Switches

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents

F200E Charged-Media Air Cleaner

Installation Instructions

HE420A,B and HE460A,B Steam Power Humidifiers OWNER S GUIDE

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz

Solid Core and Split Core Fixed Current Status Switches CSS-O,C; CSP-O,C -F (FIXED) SERIES

L8151A Triple Aquastat Relay

T8401C Electronic Thermostats

TK-1801, TK-1811 TK-1801, TKR-1811

INSTALLATION MANUAL. Need Help? This manual covers TopTech models: TT-N-721 and T721. Power Type. Thermostat Applications Guide.

T7300F Series 2000 Commercial Microelectronic Conventional or Heat Pump Thermostat

C7232A,B Sensor and Controller

Installation Instructions for Models: HES232U, HES236UHES246U, HES247U, HES245U, HES242U, HES256U, HES255U, HES252U

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

A19, A28 Series Thermostats for Agricultural Buildings

INSTALLATION MANUAL. Need Help? This manual covers the following models: T755. Power Type. Thermostat Applications Guide. Page.

Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

1. SAFETY RULES. 8. Avoid placing objects in the path of the blades.

UVIOOAUltravioletSystem

7800 SERIES 22-Terminal Universal Subbase

TG509, TG510, TG511, TG512 Versaguard Universal Thermostat Guards

IMPORTANT SAFETY INFORMATION:

Solid Core and Split Core 4-20 ma Output Current Sensors CTS-20; CTP-20

TP970 SERIES ASPIRATING WALL BOX ASSEMBLIES BEFORE INSTALLATION

INSTALLATION MANUAL. Need Help? This manual covers the following models: T725. Power Type. Thermostat Applications Guide. Page.

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents

Eldex Column Heater. Operator s Manual

HE225A,B and HE265A,B Bypass Flow-Through Humidifier

Two-Position Electric Duplex Room Thermostats

T8011R Programmable Heat Pump Thermostat

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

HE365A,B Powered Flow-ThroughHumidifier with JI

Ceiling Fan Installation Instructions

TK-5001, Pneumatic Room Thermostats General Instructions GENERAL INFORMATION INSTALLATION

Install Guide 8046 ENGLISH. Customer Support: or: visit our website Printed in China ON.

Transcription:

T398A,B Precision Electric Heating Thermostat FEATURES PRODUCT DATA APPLICATION The T398 Electric Heating Thermostat provides precise, accurate line voltage control of electric heating equipment. A snap action switch makes the heating circuit on temperature fall. B models feature double-line break in the Off position. Controls both fan-forced and baseboard electric heaters. Vapor-filled dual diaphragm sensing element provides high-temperature sensitivity with minimum droop. Canadian Standards Association (CSA) Performance Certified up to 0A. CSA Certified, UL Listed up to 5 kw at 77 Vac. Long-life, industrial-grade Micro Switch mechanism. Rugged-engineered, plastic mounting base with captive mounting screw. Color-coded flyleads compatible with aluminum wire for quick installation. Replaces any standard wall-mounted electric heat thermostat. Contemporary white styling. Operating temperature range of 50 F to 80 F (10 C to 30 C). Celsius and fahrenheit models available. Optional thermometer. Altitude compensation feature. Frost protection setting (A models only). Optional locking cover and range stops available. U.S. Registered Trademark Copyright 00 Honeywell All Rights Reserved 69-160

SPECIFICATIONS Models: T398A: Makes heating circuit on temperature fall. With setting knob at far left (counterclockwise) position, provides calibration-free frost protection setting of 0 F ( C). See Fig.. T398B: Makes heating circuit on temperature fall. With setting knob at Off position, provides double line break for fuse-protected 0V heating circuits. (See Fig. 3.) Both models feature optional thermometer, located in the cover, to indicate the actual room temperature. Accessories (Not Included): 780A Range Stop and Cover Locking Assembly: Allows field-selection of minimum and maximum temperature settings. Includes range stop assembly, cover lockingscrews and wrench. Setting Range: Fahrenheit Models: Indicates range of 50 F to 80 F with marking indications in 5 F increments. Celsius Models: Indicates range of 10 C to 5 C with marking indications in 1 C increments. Approval Ratings: Underwriters Laboratories Inc: Listed; file no. E73, guide no. XAPX. Canadian Standards Association: File no. LR13. Mounting: Direct mounting on NEMA standard vertical in. x in. switch box, or in. x in. box using 6-3 slot Robertson screws. Sensing Element: Vapor-filled, hermetically-sealed, stainless steel, dual diaphragm. Thermometer (Optional): Coil bimetal 50 F to 90 F (10 C to 30 C). Barometric Sensitivity: 1 F/500 ft (0.3 C/kPa). Dimensions: See Fig. 1. Differential: Approximately F (1 C) mechanical and thermal, non-adjustable. FRONT VIEW SIDE VIEW Switch Type: Enclosed industrial-grade Micro Switch snap switch. T398A: Single-line break (single-pole, single-throw). T398B: Double-pole, single-throw with double-line break (double-pole, single-throw) in Off position. 80 70 60 50 1-3/ (8) 3/ (19) 1/ (13) Wiring Connections: Six-inch (150 mm) stranded copper leadwires suitable for connecting to aluminum wiring if approved special service CO/ ALR connectors are used. F -3/8 (111) -1/8 (5) 3-1/ (83) Electrical Rating: A non-inductive at 10/08/0 Vac. 19A non-inductive at 77 Vac. Canadian Standards Association Performance Rating: 0A at 10/08/0 Vac. -7/8 (73) 1-1/ (39) 1/ (13) M5795A Fig. 1. T398A,B dimensions in in. (mm). 69-160

INSTALLATION WARNING 10-77 Volt Line Voltage Hazard. Can cause serious injury or death. Do not install thermostat unless you are a trained, experienced electrical service technician. CAUTION Electrical Shock Hazard. Can cause personal injury and equipment damage. Disconnect power supply before connecting wiring. Use a limit control when wiring the thermostat. MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly. Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control. When Installing This Product... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.. Check the rating given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician.. After installation is complete, check out product operation as provided in these instructions. 5. Follow local codes for installation and application. Selecting Location Mount the thermostat on an approved electrical junction box. Locate the thermostat to 5 ft (1.5m) above the floor on an inside wall where the thermostat can be exposed to average room temperature. Locate the thermostat away from concealed warm or cold water pipes, light switches and dimmers, and refrigerators. Locate the thermostat away from drafts of hallways, fireplaces, stairways, and fans. Mounting When replacing an old line voltage thermostat: Carefully remove the old thermostat to avoid damaging the wiring insulation. Check the old insulation for cracks, chips, or fraying and apply approved electrical tape, where necessary, to ensure adequate insulation. NOTE: Make line voltage wiring connections directly to the leadwires installed on the thermostat, using wire connectors approved for the number and size of conductors. IMPORTANT When using aluminum conductors, all wiring connections to the thermostat must be made to the factoryinstalled lead wire, using approved CO/ALR solderless connectors. 1. Connect all wires with the thermostat cover in place. Be sure that all wire connectors are tight. Install any security features. See Fig. and 3.. Pre-bend the solid conductors and push them into the electrical box. 3. Remove the thermostat cover by grasping both the top and bottom of the cover and pulling out.. IMPORTANT Carefully handle the thermostat. Excessive pressure can damage the control knob or sensing element.. Turn the dial so the setpoint indicator is at the 1 o clock position. (This prevents accidental damage to the dialstop during mounting.) 5. Using the screwdriver, secure the thermostat to the electrical box by tightening the two mounting screws. See Fig.. 6. Level the thermostat only for appearance. 7. Tighten the screws and replace the cover. 1 3 1 L1 (HOT) L T398A L1 T1 SOLDERLESS CONNECTORS POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE HAZARD MAY RESULT. USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE. BREAKS AND REMAKES BELOW -31 F (-35 C); NORMALLY THERMAL ACTIVATED. BREAKS ON TEMPERATURE RISE; MAKES ON TEMPERATURE FALL. M5791B Fig.. T398A typical hookup. ELECTRIC HEATER 3 3 69-160

L1 T398B L RED WIRE 6 WALL 3 5 T1 T THERMOSTAT BASE ELECTRIC HEATER L 1 L1 (HOT) SOLDERLESS CONNECTORS OUTLET BOX SETTING DIAL INDICATOR 80 75 70 65 60 55 50 1 3 5 6 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE HAZARD MAY RESULT. BREAKS AT POSITIVE OFF AND REMAKES UNDER 31 F ( 35 C); NORMALLY THERMALLY ACTIVATED. BREAKS ON TEMPERATURE RISE; MAKES ON TEMPERATURE FALL. USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE. BREAKS AT POSITIVE OFF ONLY; NOT THERMALLY ACTIVATED. DO NOT CONNECT GROUNDED CONDUCTOR (NEUTRAL) ON 10 OR 7V CIRCUITS. INSULATE AND TAPE OR CUT OFF RED WIRES IF UNUSED. M579B MOUNTING SCREWS () M5797 Fig.. Mounting thermostat to outlet box. Fig. 3. T398B typical hookup. 69-160

OPERATION AND CHECKOUT After the thermostat is installed and wired, check out normal operation as follows: 1. Turn setting dial fully clockwise until the switch clicks and the electric heater starts to heat.. Turn the dial fully counterclockwise; the power circuit breaks and the electric heater starts to cool. 3. The T398 is a more accurate thermostat, allowing users to be more comfortable at lower setpoint settings (saving energy and lowering heating costs). To determine final setting: a. Begin with setting the dial indicator at 68 F (0 C). b. After two operating hours, if not comfortable, adjust setpoint to raise or lower the temperature, adjusting temperature only a few degrees each time. Calibration BAROMETRIC PRESSURE KPa 0. 101 99 95 93 89 (SEA LEVEL) WINNIPEG REGINA EDMONTON CALGARY ELEVATION 1..0.8 3.6. 5. 6.0 ELEVATION IN METERS 0 0M 57M 677M 1079M INCREASING CITIES WITH TEMPERATURE CORRECTIONS ( C CORRECTIONS TO BE ADDED) (FOR EXAMPLE, A CORRECTION OF APPROXIMATELY 3.5 C WOULD BE INDICATED FOR INSTALLATION IN CALGARY.) M035 IMPORTANT Do not assume the thermostat is out of calibration until it is installed and allowed to operate for several hours. The T398 is accurately calibrated at the factory under controlled conditions. The snap switch turns on heat when the setpoint is raised to room temperature. The vapor-filled diaphragm sensor is affected by barometric pressure and altitude. Deviations up to 1 F (±1/ C) are within normal operation. The control point drops F every 1000 ft (1 C/300m) above sea level. See Fig. 5 and 6. 10 8 DENVER Fig. 6. T398 altitude correction in (m). To calibrate (see Fig. 7): 1. Remove cover and place it in a location that allows it to sense the room temperature. NOTE: Allow several minutes for the thermometer to stop being affected by the heat from your hand.. Rotate the setpoint knob counterclockwise until you hear the switch click. 3. Hold the setpoint knob firmly and rotate the setpoint scale ring counterclockwise until 1 o clock on the ring is aligned with the thermometer cover.. The heat from your hand will affect the diaphragm sensor so wait five minutes and verify the calibration. F 6 LAS VEGAS ATLANTA LOS ANGELES 0 0 1000 000 3000 000 5000 6000 SEA ELEVATION IN FEET LEVEL M0353 Fig. 5. T398 altitude correction in (ft). 5 69-160

50 75 T398A,B PRECISION ELECTRIC HEATING THERMOSTAT BASE THERMOSTAT BASE 80 75 70 65 60 55 SETTING KNOB AT 1 O'CLOCK POSITION SCALE RING THERMOSTAT COVER LOCKING COVER CLIP SETTING KNOB LOCKING COVER SCREW Fig. 7. Calibrating the thermostat. Security Features To install the locking cover (select models (Fig. 8): 1. Remove cover by swinging up from the bottom.. Insert the Tinnerman Speed Nut (supplied) into the slot at the lower rear thermostat base. 3. Drive Allen screw into Speed Nut until head is flush with lower edge of thermostat base.. Reinstall cover and lock by backing out Allen screw until screw body protrudes through cover hole. 5. To unlock cover, drive Allen screw into thermostat base until screw body clears cover. Fig. 8. Installing locking cover. ALLEN WRENCH M5798 To install the range stops (select models) (Fig. 9): 1. Set thermostat to desired setpoint and remove the cover.. Install plastic dowels (supplied) into minimum and/or maximum range stop holes on the back of the cover. 3. Reinstall the cover and check range stop operation. BACK OF THERMOSTAT COVER 70 0 C 65 16 60 55 1 INSERT RANGE STOP PINS IN SLOTS. M5801 Fig. 9. Installing range stops. 69-160 6

Frost Protection (T398A) When the ambient temperature falls to 0 F ( C), the vapor in the diaphragm changes into liquid. The diaphragm collapse to a fraction its original thickness, turning on the heat, regardless of setpoint. This feature guarantees minimum, yet reliable, operation of heaters in spaces near freezing. NOTE: To prevent heat from turning on below 0 F ( C), turn off the circuit at the breaker panel, or install a T398B. 7 69-160

Automation and Control Solutions Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55 Scarborough, Ontario M1V Z9 69-160 G.H. 3-0 www.honeywell.com/yourhome