Construction Products Regulation (CPR) and cables. British Cables Association Guidance to Specifiers

Similar documents
Belcom Cable excellence engineered through quality. CPR Construction Products Regulation

YOUR GUIDE TO UNDERSTANDING CPR

White paper. Construction Product Regulations* by Multimedia Connect. Which cables are concerned by these new regulations?

Europacable FAQ on CPR Status: 26/01/17

1. Terms defined in the Construction Products Regulation (CPR)

CONSTRUCTION PRODUCTS REGULATION MOLEX CES COPPER AND FIBRE CABLE

Construction Products Regulation (CPR) and BS 6701

BT Cables Technical Seminar CIBSE South Wales Region. Nov 17

Construction Products Regulation (CPR)

DID YOU GET USED TO THE NEW CPR? HERE S A QUICK REVIEW!

Üntel is ready for CPR

UK Direction BS7671 BS 8492 BS /01/2018

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034

Technical Bulletin CE marking: from 1st July 2013

Hygiene & Textile Toys. Toys Safety Directive 2009/48/EC Annex II, Part V, Point 2.

CE MARKING OF WOOD-BASED PANELS

Record of Amendments. Version Date Amendment Section/page affected

Record of Amendments. Version Date Amendment Section/page affected

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Abrasion Resistance of Fluoropolymer and polyester Coatings

A Step by Step Guide to Energy Labelling of Gaseous Fuel Local Space Heaters (Part 1)

Specification for Road Works Series Introduction

Implementing the Construction Products Regulation (EU) 305/2011

Significance of the Construction Products Regulation, including for data centers WHITEPAPER

Harmonisation and equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study

The effects on the UK Fire Industry. Paul Pope Eng.Tech AIFireE

Controlled Door Closing Devices

Annex A to joint CELMA / ELC Guide on LED related standards: Photobiological safety of LED lamps and lamp systems

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

asphalt applications European Asphalt Standards and their application in the UK mpa asphalt Asphalt Information Service Mineral Products Association

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

Guidance Note No 19/1. CE Marking windows and doorsets

WORLDWIDE CABLE EXPERTS

COMMISSION DELEGATED REGULATION (EU) /... of

The products covered by the Regulation can be classified as follows:

LSOH Wiring Cables. LSOH Conduit Wire (HO7Z-R) Low Voltage (450/750 V) Cable Approvals. Key Applications. Conductor. Insulation. Core Identification

Regulation (EU) No 305/2011 laying down harmonised conditions for the marketing of construction products (EU CPR)

Mechanically operated locks and locking plates

Classification Report

CPR: EUROCLASSIFICATION & TESTS FOR CABLES

Guidance Note on the Construction Products Regulation

2.2 Factors in design

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

DNVGL-CP-0402 Edition February 2016

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

Frequently Asked Questions on the Construction Products Regulation (CPR) - Enterprise and Industry

Best practice guide. Hardware for sliding doors and folding doors to BS EN in association with. Association of Building Hardware Manufacturers

White Paper. Keeping up with compliance: Escape doors standards. The global leader in door opening solutions

Consumer unit replacement in domestic and similar premises

Standards and Standardisation. An Overview

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

CLASSIFICATION REPORT

CE marking of industrial doors under the CPR Michael Skelding, Secretary and General Manager Door and Hardware Federation

Prescription of qualifications. ARB Criteria at Part 2

Panic and Emergency Exit Devices

FINAL REPORT ON THE 4 TH JOINT CROSS-BORDER EMC MARKET SURVEILLANCE CAMPAIGN (2011) LED LIGHTING PRODUCTS

Confused by standards Standards for social alarms

New European Fire Testing Classification for Construction Products

Guidance from the Group of Notified Bodies for the Construction Products Directive 89/106/EEC

The New EMC Directive 2004/108/EC

New European Cable Testing and Classification

Best Practice Guide. Windows and Doors. Single-axis hinges to BS EN

Your Key to achieving C.E Marking Compliance

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

Guidelines accompanying:

The PPE Directive and the PPE Regulation

COMMISSION DELEGATED REGULATION (EU) /... of XXX

Construction Products Directive

DECLARATION OF PERFORMANCE

The New EMC Directive 2004/108/EC

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

SELF PRESERVATION SOCIETY By Jim Creak

Department of the Environment Transport and the Regions Building Regulations Division

Additional reaction to fire classification report No H

Best practice guide. Door coordinator devices to BS EN in association with. Association of Building Hardware Manufacturers

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

7.3 Design and Development Design and development planning Design and development inputs Design and development outputs 7.3.

ETICS and the EU Internal Market The European framework. G. Katsarakis European Commission, DG GROWTH Unit C-1: Clean technologies and products

DIRECTIVES. DIRECTIVE 2009/142/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 30 November 2009 relating to appliances burning gaseous fuels

Maximum Dimensions: Approved for spans unlimited in width, heights up to 10.5 m ( in), minimum panel overlap 400 mm (15.

Co-ordination of the Group of Notified Bodies for the Construction Products /Regulation 305/2011/EU

Mandate M/118 WASTE WATER ENGINEERING PRODUCTS

Electrical Equipment (implementing the Low Voltage Directive)

Eligibility criteria

New Approach vs Standards and Regulation: how it all works

PEOPLE SAFETY IS A MUST NOT AN OPTION

European Technical Assessment

DECLARATION OF PERFORMANCE

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

Both regulations are due to be reviewed by Key topics to be assessed during the reviews include:

Window and Door Standards for Performance and Security. Russell Day Senior Technical Officer Glass and Glazing Federation

Reaction to fire classification report No C

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Council Directive 93/68/EEC of 22 July 1993 amending Directives

Actions for local government

The Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock

BUSINESS PLAN CEN/TC 250 STRUCTURAL EUROCODES EXECUTIVE SUMMARY

RADAR REFLECTOR STANDARD FOR CERTIFICATION. DET NORSKE VERITAS Veritasveien 1, N-1322 Høvik, Norway Tel.: Fax:

Transcription:

Construction Products Regulation (CPR) and cables British Cables Association Guidance to Specifiers 1

Outline In January 2017 BCA issued its Guidance to Specifiers. A key consideration at the time was that with effect from 1 st July 2017 it would become obligatory for cables, having an intended use for permanent installation in buildings and construction works, to be accompanied by a Declaration of Performance (DoP) and to have CE marking under the CPR. This requirement related only to the Reaction to Fire performance of the cables, and excluded those cables which have Resistance to Fire, meaning that the intended use is retention of functionality during a fire. NOTE: Cables having Resistance to Fire, remain under review, and may be covered at an, as yet, unknown date in the future. Such cables cannot be given a DoP or have CE marking in respect of Reaction to Fire unless and until relevant EU legislation, and accompanying standardization, is completed. Apart from this specific exclusion, all cables, be they energy, metallic data or optical fibre types, are covered. It is the responsibility of the manufacturer to provide the DoP and to apply CE marking, but the main purpose of this paper is to offer advice and guidance to those who have the responsibility to specify the use of cables within construction works. Such groups of specifiers may be local authorities, architects, designers and the like. In particular, the paper acknowledges that, unlike many other EU countries, the UK has no legislation that determines the level of performance required for the cables with respect to reaction to fire, nor is it likely to in the near future. The paper therefore explains the nature of the choices available via voluntary guidance such as British Standards, and the performance that can be expected, including by relation to existing parameters and requirements. Background The essential origins of bringing cables within the Construction Products Regulation and the associated timetable for implementation were explained in BCA s statement of July 2016 see http://www.bcauk.org/application/files/9615/1525/2498/bca-cpr-public-statement.pdf NOTE: The statement and this paper exclude any complications or changes arising from BREXIT, as any effects are at present unknown. The CPR covers the way in which the product is placed on the market. It does not say how and where a particular product should be used. Crucially it does not say what class of product should be used in any given circumstance. In many EU countries the national authorities are in the process of introducing, or have introduced, legislation to say that certain applications/installations must have certain CPR classes of cable. In some countries this will be via the national wiring regulations which, unlike BS 7671 in UK, can have a statutory position. In UK there is a long history of developing low fire hazard cables with low smoke, halogen-free performance (variously LSHF, LSOH, OHLS, LSNH etc), but no statutory requirements exist for their use. This is well understood by specifiers and designers of buildings and there is some provision written into BS 7671, though it is as well to recall that, by comparison with statutory requirements, 2

the British Standard counts as voluntary guidance. It can of course be called up in a legally-binding contract. This is explained in more detail in the recently released BCA statement see: http://www.bcauk.org/application/files/4215/2292/1826/cpr_and_cables_-_uk_position_march_2018.pdf The UK government had said a long time ago it will not amend the Building Regulations as far as Reaction to Fire for cables is concerned, though it is possible that this may change in the wake of the enquiries relating to Grenfell Tower. If there is a change, then it is likely that specific guidance would be given via Approved Document B Fire safety. Therefore, for now, there may be some benefit in offering advice and guidance to specifiers, especially in respect of any relationship between existing requirements and those derived from the CPR. What is available already? A major pre-existing document of relevance is BS 7671 (IET Wiring Regulations). It specifies reaction to fire characteristics for cables in a number of places, most but not all of which are for installations in buildings and construction works and therefore fall under CPR. NOTE: The existing version of BS 7671 is the 17th edition of the IET Wiring Regulations. An 18th edition is in preparation with publication scheduled for 1st July 2018, and a coming into effect of 1st January 2019. The final text has had its technical content approved. It makes no significant change in respect of the requirements for cables in respect of Reaction to Fire. The existing requirements of BS 7671 can be used to illustrate the most important determinant for cables and reaction to fire under CPR namely the classification. The classification splits cables into 7 classes in respect of their reaction to fire. They range from Class A ca, being essentially non-combustible, as for instance bare MICC, through to class F ca, which is for cables having no measurable resistance to the spread of flames. All classes are summarised in Annex A. For the vast majority of practical purposes it will be the classes from E ca up to B2 ca that are most likely to be applicable. By reference to existing requirements in BS 7671 the significant comparisons are: Existing requirement in BS 7671 BS EN 60332-1-2 (Bunsen burner test) BS EN 60332-1-2 and BS EN 60332-3 BS EN 60332-1-2, BS EN 60332-3 and BS CPR class and equivalence Class E ca is an exact equivalent to the requirement of BS EN 60332-1-2 No direct equivalence, but classes above class E ca should be used. No direct equivalence, but classes above class E ca should be used, and must include at least the additional classification for smoke (see Annex A) Comments Minimum requirement for any application within buildings and construction works The choice of class is a matter for the user, bearing in mind that a better performance is given by a higher class The choice of class is a matter for the user, bearing in mind that a better performance is given by a higher class. A minimum additional classification for smoke of s2 is required 3

From the above it can be seen that, with the exception of Class E ca, the European classification for reaction to fire of cables does not directly correlate with the existing fire performance requirements for cables in British Standards. On the basis that the UK Government was not planning to introduce the classes, and in order to allow time to assess market needs, no changes have yet been made to cable product standards, be they British Standards or BS implementations of CENELEC standards. For some specific telecommunication installations, requirements for fire performance of cables are now given in BS 6701 (as amended in 2017). The new amendment has two specific classes of performance, Class C ca for what are defined as installation cables in specified high risk areas, and Class E ca for all other telecommunication cables. From a regulatory point of view, as with BS 7671, the standard is classed as voluntary guidance. Cautionary notes Bearing in mind that the legalistic position is that any class automatically satisfies the requirements of the classes below, and hence for instance class C ca is automatically better than class D ca, it may be tempting to play safe and specify the highest possible class. This should not be done without being sure that every family of cable to be used in a particular construction works is available, with the necessary authentication, i.e. DoP and CE marking derived from certification via a Notified Body. It is also advisable to ask whether every type of cable for every kind of installation needs to have the same class of performance. Cables installed singly, or in small numbers, in protected situations may not need such a high class as for large bunches in areas of high risk. Furthermore, risk assessments, such as those described in BS 9999, may point to alternative means of ensuring fire safety other than vis prescriptive requirements for materials and products, such as cables, in buildings. In addition, it should be recalled that the position of cables under CPR at present relates only to two Essential Requirements, or as they are properly called Basic Requirements of Construction Works (BRCW). These are: Reaction to fire Dangerous substances A cable that satisfies only these BRCWs is almost certainly not fit for purpose. Electrical and mechanical performance are covered via existing standards and users should ensure that the relevant performances for these requirements, are also satisfied, for instance in UK via a 3 rd party certification and approval system, such as BASEC. 4

BCA recommendations Taking account of all the above factors, and recognising that a very wide range of buildings and construction works are embraced by CPR, BCA recommends that specifiers should adopt the following guidance for the use of cables under the regulation: 1. Always specify that cables must have the CE marking according to CPR, accompanied by a Declaration of Performance (DoP); NOTE: It is the responsibility of the specifier/purchaser/user to be satisfied that the information on the DoP is accurate and authentic. Some examples of incorrect and misleading DoPs have already been seen, including those where the declared class is higher than may be expected, and cannot be verified. 2. Take due note of the relationship between the statutory regulation, and relevant documents that are classed as guidance, such as BS 7671; 3. Specify cables of class E ca or higher; 4. Preferably use cables described as low fire hazard or equivalent, in particular where fire safety requirements are high or very high; 5. Ensure that low fire hazard cables above class E ca include the additional classifications for smoke and acidity (LSHF, LSOH, OHLS, LSNH etc) and, for particular applications, flaming droplets; 6. Avoid cables classified as F ca, as they are likely to burn uncontrollably in a fire; 7. In case of doubt, consult the manufacturer. 5

Annex A: Reaction to fire classes for cables Class 1 Classification criteria 2 Test method(s) Approximate performances of different classes according to EN13501-6 Additional classification 3 Test method(s) A ca Gross heat of combustion (PCS) EN ISO 1716 Level of highest performance corresponding to products that practically cannot burn B1 ca Vertical flame spread (FS) 30 kw flame source (very high intensity) Products that are combustible but show no or very little burning B2 ca Vertical flame spread (FS) 20.5 kw flame source (high intensity) Products that are combustible but show very little burning C ca Vertical flame spread (FS) 20.5 kw flame source (high intensity) Products that do not give a continuous flame spread, show a limited fire growth rate and show a limited heat release rate D ca 20.5 kw flame source (high intensity; NO flame spread measured) Products that show a continuous flame spread, a moderate fire growth rate, and a moderate heat release rate. E ca Products where a small flame attack is not causing large flame spread F ca Flammable 1 The level of reaction to fire performance decreases in going from Class A ca to Class F ca 2 The full description of the classification criteria, the symbols used and the numerical values of reaction to fire performance are given in the Commission delegated regulation (EU) 2016/364 of 1 July 2015 (L 68/4-15 March 2016). These will eventually be taken into an updated version of EN 13501-6 Fire classification of construction products and building elements - Part 6: Classification using data from reaction to fire tests on electric cables 3 The additional classifications apply only to Classes B1, B2, C and D. They are optional, but should be regarded as essential for use with cables described as low smoke and/or halogen-free. Their full description can be found in the same documents as for footnote 2 above 6

For further information please contact: Peter Smeeth: secgen@bcauk.org Mike Hagger: mike.hagger@btconnect.com British Cables Association (BCA): Flat 7, 11 The Grange Wimbledon Village London SW19 4PT Tel: 07973 636688 Or visit www.bcauk.org 7