DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

Similar documents
A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

ARCHITECTURAL SPECIFICATIONS

Architectural Specification Sheet

Single Door 39.5 Right Hand Push AL. Double Door (Twin) 75.5 Push AL Simultaneous 92 Push 11 + reveal BZ Independent Max reveal on a pull 2.

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Temperature Rise Door Framing

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING GPX Builders Series Fire Protective

SECTION DOOR HARDWARE

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

A. Section Masonry Assemblies: Anchor placement in masonry.

PART 1 GENERAL 1.01 SUMMARY

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION COMMERCIAL-KITCHEN HOODS

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION AIR DOORS

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

ARCHITECTURAL SPECIFICATIONS

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.

PART 1 GENERAL 1.01 SUMMARY

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

SECTION Overhead Coiling Doors

Engineering Specifications

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperClear 45-HS (patent pending)

University of Rochester October 17, 2008 Brooks Landing Business Center

Design & Construction Standards, Revised January

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION AUTOMATIC TRANSFER SWITCHES

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

MacroAir AirElite HVLS Fans

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

National Reach. Local Service.

SECTION FIRE EXTINGUISHER CABINETS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION AUTOMATIC TRANSFER SWITCHES

A. Product Data: Include rated capacities, furnished specialties and accessories.

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

Automatic swing door solutions. We make access in life smart and secure.

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION AIR CURTAINS

D. Reference Standards (Utilize latest editions available):

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u

SECTION ISOLATED POWER SYSTEMS

5600 series. Low Energy Power Operator

15900 HVAC INSTRUMENTATION AND CONTROLS

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

2409/2900. Fire Guard

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

SECTION ENCLOSED CONTROLLERS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

5900 SERIES Low Energy Power Operator

SECTION DOOR HARDWARE

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION AIR DUCT ACCESSORIES

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY

2408/2900. Fire Guard

SECTION OVERHEAD COILING FIRE DOORS

SECTION GENERATOR PARALLELING CONTROLS

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

XRRS Specification Fire Ready Hood

csw-200 intro d u c t i o n

DONALD H. BERG, ARCHITECT

MacroAir AirSpan HVLS Fans

FIRE & LIFE SAFTEY STANDARD

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved

MacroAir AirVolution HVLS Fans

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u

c. Oko-Tex (European environmental health standard)

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

7200 Series. Electromechanical Closer/Holder Releasing Devices

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

BLG77 Rising Fenced Barrier

ARBOR SERIES WOOD WALLCOVERINGS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

NFPA 80 Overview January 21, 2016

Electrical Specifications

1 P a g e w w w. s m o k e c o n t r o l. c o. nz

CONTENTS AUTOMATIC TRANSFER SWITCHES

.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

Electrified door control products. Accessibility and fire life safety solutions

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

SECTION AUTOMATIC TRANSFER SWITCHES

Architectural 3-Part Specifications

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

EcoAisle Thermal Containment System

16028 September 23, 2016

Transcription:

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and titles per CSI Master Format and specifier s practice. Consult with manufacturer regarding performance requirements for units applicable to project, as well as, related equipment and accessories required. PART I GENERAL 1.01 SUMMARY A. SECTION INCLUDES: Automatic Heavy Duty Low Energy Operators as specified. B. RELATED SECTIONS: 1. Division 26: Applicable Electrical Sections 2. Section 08 40 00: Entrances, Storefronts, & Curtain Walls 3. Section 08 71 00: Door Hardware. 1.02 REFERENCES A. AMERICAN ASSOCIATION OF AUTOMATIC DOOR MANUFACTURERS (AAADM) B. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI): 1. ANSI/BHMA A156.19: Power Assist and Low Energy Power Operated Doors 2. ICC/ANSI 117.1: Standard for Accessible and Usable Buildings and Facilities C. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 1. NFPA 101: Life Safety Code 2. NFPA 80: Standard for Fire Doors and Other opening Protectives. D. THE ALUMINUM ASSOCIATION (AA) 1. Aluminum Finishes Manual. E. UNDERWRITERS LABORATORY, INC. (USA & CANADA) 1. UL 325: Standard for Electrical Door, Drapery, Gate, Louver, and Window Operators and Systems. 2. UL 228: Standard for Door Closers-Holders, With or without Integral Smoke Detectors. F. BUILDER S HARDWARE MANUFACTURERS ASSOCIATION (BHMA). 1.03 SUBMITTALS A. PRODUCT DATA: Detex Low Power Door Operators Page 1

1. Submit manufacturer s complete product and installation documents. 2. Submit Shop drawings showing layout, profiles, elevations and product components including anchorage, accessories, and electrical access locations. 3. Manufacturer s Operation and Maintenance documents. 4. Warranty document as specified herein. 5. Inspection compliance certification. Include certification that installation conforms to the requirements of ANSI/BHMA A156.19 unless specifically shown otherwise. Certification shall be completed and signed by an individual knowledgeable about the requirements of the standard and its application to the installation. Include a statement showing the qualifications of the inspector. 1.04 QUALITY ASSURANCE A. INSTALLERS QUALIFICATIONS: Installer shall be experienced to perform work of this section. B. MANUFACTURER S QUALIFICATIONS: Manufacturer capable of providing field service representation during installation, reviewing installer qualifications, and reviewing application method. C. Equipment supplied shall comply with ANSI A156.19 and UL 325. 1.05 WARRANTIES A. MANUFACTURER S WARRANTY: 1. Operators shall be warranted against defect in material and workmanship for a period of three (3) years for mechanical components and one (1) year for electrical components. 2. Other products shall be warranted against defects in material and workmanship for a period of one (1) year. 3. Warranty shall start from the date of Substantial Completion. 4. Manufacturer s warranty is in addition to, and not a limitation of, other rights Owner may have under Contract Documents. 1.06 PROJECT CONDITIONS A. MEASUREMENTS: Verify actual dimensions/openings by field measurements before fabrication and record on shop drawings. Coordinate production, shipping and construction schedule to avoid construction delays. 1.07 DELIVERY, STORAGE AND HANDLING A. ORDERING AND DELIVERY: Comply with factory s ordering instructions and lead time requirements. Delivery shall be in factory s original unopened, undamaged containers with identification labels intact. B. STORAGE AND PROTECTION: Provide protection from exposure to harmful environmental conditions and vandalism. Detex Low Power Door Operators Page 2

PART II PRODUCTS 2.01 APPROVED MANUFACTURER. Low energy automatic door operator shall be manufactured by: DETEX CORPORATION 302 Detex Drive New Braunfels, Texas 78130 Phone 800-729-3839 Fax 830-620-6711 2.02 EQUIPMENT A Operator Series AO19 1. Header Assembly a. Surface Mounted b. Extruded aluminum case 7 x 4.5 x required length determined by door/frame size. Include hangar plate for quick installation 2. Operating Mechanism a. Maximum current draw shall not exceed 3.15 amps per operator b. Concealed in aluminum case c. Smooth, quiet operation d. Opening Action: accomplished by a 1/8 HP D.C. permanent magnet motor working through reduction gears to the output shaft. Gear train bearings shall be sealed ball bearing types e. Closing action: accomplished by an enclosed clock spring. Close speed control shall be supplied by dynamic braking of the motor and shall be fully adjustable. Operator shall act as a manual closer when power is off. f. Provide 3-way On/Off/Hold switch 3. OPERATOR CONTROL: Shall incorporate the following features a. Adjustable hold open time delay of 2 to 30 seconds (ANSI A156.19 requirements 5 second minimum time delay). b. Finite adjustment to opening and open check speeds including adjusting the opening force without affecting the opening speed. c. Field selectable immediate reverse on obstruction during the closing and opening cycles. d. Motor Current Limit: An adjustable current limit shall shut off current to the motor when the door is inadvertently locked or otherwise prevented from opening, protecting motor and control from damage. e. Power Assist Close: Field selectable on/off. When on, power shall be applied to reverse motor when the door stalls in the latch position. Power level shall be field adjustable. f. Door Seal: Field selectable on/off. The control shall provide a small current to the motor to hold door closed after Power Assist Close has fully closed the door. g. Delayed Activation: A signal will start the delayed activation timer. When the timer expires, door activation is generated. This signal is used to do door sequencing. h. Lockout (Safety A): For use with an overhead presence detection sensor, the lock-out function is incorporated into the door control without the need Detex Low Power Door Operators Page 3

for additional modules. When door is fully closed or fully open, door operation is inhibited when an obstruction is detected. i. Lockout (Safety B): For use with door mounted presence detection sensors. The lock-out function is incorporated into the door control without the need for additional modules. When this option is selected: 1) The sensor shall be inhibited from stalling the door when the door reaches back-check during the opening cycle. 2) If an obstruction is detected while the door is closed, door activation will be prevented 3) If an obstruction is detected during the opening cycle or closing cycle, the door will go to a safety speed. 4) If an obstruction is detected when the door is fully open, the door will be prevented from entering the closing cycle. j. Electric Lock form C Contacts 1) Normally Open: To control a non-fail safe electric locking device. 2) Normally Close: To control a fail-safe electric locking device. k. Secondary activation: Automatically reopens door upon closing, when secondary traffic approaches. Activation is inactive when door reaches latch-check in accordance with ANSI/BHMA A156.19. l. Power output for sensing devices 1) 24 volt AC and DC. 2) Maximum current draw: 300 ma. 3) May be used to power electric lock provided total current draw of lock and sensors does not exceed 300 ma. 4. OPERATION: Automatic and/or Manual: a. Automatic: Push button switch actuates door open; door closes after time delay expires. b. Push-N-Go: When selected, manually pushing door activates automatic opening cycle; door closes after time delay expires. c. Operator to include the following variable adjustments for compliance with ANSI Standard A156.19: Opening speed - 4 to 8 seconds; Closing speed 4 to 20 seconds d. Manual: Opening and closing force, measured 1 (25.4 mm) out from the lock stile of the door, not to exceed 15 pounds (67 N). Force to stop the door when operating in either direction, not to exceed 15 pounds.. B. ACTIVATION DEVICES: 1. Shall be located on each side of door in accordance with ANSI Standard A-117. 2. Push Plate: 4/12 x 41/2 a. Surface or flush mounted b. Hard Wired or Radio Control with Clearpath tm Transmission system. c. Push Plate shall have International Symbol for wheelchair accessibility logo and Press to open or PUSH TO OPEN legend. d. Stainless Steel or Blue powder coat Detex Low Power Door Operators Page 4

2.03 RELATED WORK REQUIREMENTS A. ELECTRICAL: 120 VAC, 60 cycle, 1 phase, 15 amp. 2.05 MATERIALS, FINISHES AND FABRICATION A. FINISHES (for all exposed aluminum surfaces): 1. 204-Ri Clear: Arch. Class II Clear Anodized Coating, AA-M12C22A31. 2. 313-Ri Dark Bronze: Arch. Class II Anodized Coating, AA-M12C22. PART III - EXECUTION 3.01 EXAMINATION A. SITE VERIFICATION OF CONDITIONS: 1. Have Installer verify that base conditions previously installed under other sections are acceptable for product installation according to manufacturer s instructions. 2. Have Installer make notification in writing of conditions detrimental to the proper and timely completion of work. 3. Do not allow Installer to start work until negative conditions are corrected in a manner acceptable to the installer and manufacturer. 3.02 INSTALLATION A. GENERAL: 1. Install door operator unit(s) plumb and level. Provide support and anchor in place. 2. Install activation and safety devices as required. 3. Make low voltage connections of related devices. 4. Make operator control adjustments in accordance with ANSI A156.19 and AAADM guidelines. B. ELECTRICAL (Provided under Division 26 sections): Electrical wiring for each operator shall be on a separate circuit breaker and shall be routed into the operator header. C. LOW VOLTAGE ELECTRICAL (Provided under Division 26 sections): Provide low voltage wiring for actuators to activate door operators. 3.03 CLEANING, ADJUSTMENT AND PROTECTION A. CLEANING: After installation: 1. Repair or provide new product where installed products are damaged. Detex Low Power Door Operators Page 5

2. Clean product surfaces and remove debris from immediate area of operating equipment for optimum condition and safety. B. ADJUSTMENT: Arrange for a qualified technician to inspect and adjust installation to assure compliance with ANSI A156.19. C. PROTECTION: Provide protection against damage to door operators and assemblies until time of substantial completion.. END OF SECTION Detex Low Power Door Operators Page 6