Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Similar documents
Performance Measurement of R32 Vapor Injection Heat Pump System

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Low GWP Refrigerants for Air Conditioning Applications

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

ABSTRACT. Heat pumps provide cooling in summers and heating in winters. It is inevitable

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Purdue e-pubs. Purdue University

R32 Compressor for Air conditioning and Refrigeration applications in China

Performance of CO2 Cycles with a Two-Stage Compressor

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Study of R161 Refrigerant for Residential Airconditioning

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Low Global Warming Refrigerants For Commercial Refrigeration Systems

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Efficiency of Non-Azeotropic Refrigerant Cycle

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

System Modeling of Gas Engine Driven Heat Pump

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Air-Cooled Heat Exchanger Performance for R410A

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Refrigerant Mass and Oil Migration During Start-up Transient

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Evaluation of an Economised Indirect Multi-Temperature Transport Refrigeration System

Scroll Compressor for Mobile HVAC/R Application

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

A study of Transient Performance of A Cascade Heat Pump System

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Evaluation of Mechanical Dehumidification Concepts (Part 2)

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Xudong Wang University of Maryland Yunho Hwang University of Maryland Reinhard Radermacher University of Maryland Follow this and additional works at: http://docs.lib.purdue.edu/iracc Wang, Xudong; Hwang, Yunho; and Radermacher, Reinhard, "Performance Investigation of Refrigerant Vapor-Injection Technique for Residential Heat Pump Systems" (2008). International Refrigeration and Air Conditioning Conference. Paper 901. http://docs.lib.purdue.edu/iracc/901 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2119, Page 1 Performance Investigation of Refrigerant Vapor-Injection Technique for Residential Heat Pump Systems Xudong WANG, Yunho HWANG*, Reinhard RADERMACHER Center for Environmental Energy Engineering Department of Mechanical Engineering, University of Maryland 3163 Glenn Martin Hall Bldg., College Park, MD 2072, USA Hung M. PHAM Emerson Climate Technologies Inc. 1675 West Campbell Road, P.O. Box, Sidney, OH 5365 * Corresponding Author: Tel. (301) 05-527, E-mail: yhhwang@umd.edu ABSTRACT An 11 kw R10A heat pump system with a two-stage vapor-injected scroll compressor has been developed and tested. A conventional heat pump system with a scroll compressor having the same displacement volume to the vapor-injected scroll compressor has been tested under the same conditions to serve as a baseline. The vaporinjected scroll compressor has been tested with the cycle options of both flash tank and internal heat exchanger configurations. The results show that the vapor-injection technique can effectively increase the system performance for both high ambient cooling application and low ambient heating application. A cooling capacity gain of around 1% with % COP improvement at ambient 6.1 C, about 30% heating capacity improvement with 20% COP gain at -17.8 C and about 7% HSPF improvement in U.S. Department of Energy s northern Region IV climate have been found for the vapor-injected R10A heat pump system as compared to the conventional system. 1 INTRODUCTION Although the refrigerant vapor-injection technique has been well justified to improve system performance in refrigeration applications, it has not received much attention for air conditioning applications, particularly with heat pumps for cold climates until recently. The previous experimental studies for the vapor-injection systems were mainly focused on the refrigerant R22 systems. Winandy and Lebrun (2002), Ma et al. (2003) and Wang et al. (2006 and 2007) conducted a series of testing the R22 vapor-injection system in laboratories. Those systems included supplementary heat exchangers serving as subcoolers to subcool main stream refrigerants. He et al. (2006) conducted a field-testing of a R22 vapor-injection heat pump. Heo et al. (2007) tested a twin rotary type compressor with the vapor injection which was applied to a R22 heat pump system. Huang et al. (2007) conducted a field-testing of a R07C vapor-injection heat pump. Nguyen et al. (2007) addressed the control issue of the vapor-injection system. An internal heat exchanger cycle and a flash tank cycle were tested in the heating applications in their study. Nowadays, R10A has been wildly recognized as a leading HFC for air-conditioners and heat pumps for replacing R22 (Beeton et al., 2002 and 2003). However, it was reported that approximately 10% performance loss was expected for R10A systems at high ambient temperatures as compared to R22 systems (Chin et al., 1999, Meurer et al., 1999 and Yana-Motta et al., 2000). The performance degradation of R10A conventional residential equipment at very high pressure-ratio operating conditions warrants further investigation of the vapor injection technique, which generally performs better with HFCs than R22. The objective of this study is to determine the performance improvement potential of a R10A heat pump system with a vapor-injected compressor. 2 EXPERIMENTAL SETUP For this study, a commercially available residential heat pump system was used. The heat pump was originally equipped with a conventional scroll compressor, having a displacement volume of 30.69cc per revolution. Indoor air enthalpy method along with refrigerant enthalpy method was applied to measure the capacity and the COP of the heat pump system based on ASHRAE Standard 116 (1995). The original heat pump was tested to establish a

2119, Page 2 baseline. The conventional scroll compressor was replaced by a vapor-injected scroll compressor having the same displacement volume after the baseline tests. The system was modified correspondingly to a two-stage vaporinjection system to conduct the vapor-injection tests. The vapor-injection cycle options of both flash tank (FTC) and internal heat exchanger (IHXC) configurations were investigated. All systems were tested under the same ambient conditions. The schematic of the experimental setup for the IHXC is illustrated in Figure 1. The heat pump system was comprised of an indoor unit and an outdoor unit. The indoor unit was mounted to a closed air loop, and the outdoor unit was installed in an environmental chamber. Both the closed loop and the environment chamber were equipped with an air handling unit and a humidifier to condition the air. A plate type heat exchanger, used as an internal heat exchanger, was installed in the environmental chamber. A manually controlled regulating valve was installed in the vapor injection line serving as an expansion valve to control the mass flow rate of the injected vapor. Two three-way valves were installed at the main stream to switch the flow direction between the cooling and heating tests, in order to secure a counter-flow heat transfer between the main stream and the injected stream at the internal heat exchanger. The schematic of the experimental setup for the FTC is illustrated in Figure 2. A manually controlled regulating valve was installed at the outlet of the outdoor heat exchanger to serve as the first stage expansion valve, and to control the mass flow rate of the injected vapor. The refrigerant liquid coming from the outdoor heat exchanger was throttled to two-phase state, and entered a vertically mounted flash tank, a 2.2 liter stainless steel cylinder, in which the two-phase refrigerant is separated to saturated vapor phase and saturated liquid phase due to gravity effect. The saturated vapor refrigerant from the top of the tank is supplied to the intermediate stage of the compressor through the injection line. The saturated liquid from the bottom of the tank is sent to the indoor unit. Figure 1: Schematic of the internal heat exchanger vapor-injection system Figure 2: Schematic of the flash tank vapor-injection system

2119, Page 3 To measure the capacity and the coefficient of performance (COP) of the heat pump system, pressures, temperatures and mass flow rates were measured in both the refrigerant-side and the air-side of the system. Additionally, humidity sensors and differential pressure transducers were applied to the air side to measure the properties and the flow rate of the air circulating in the closed loop. The volume flow rate of the air in the closed loop was 0.57 m 3 /s. The test conditions were determined based on the steady state test conditions of the ASHRAE Standard 116 (1995). In addition, one high ambient temperature of 6.1 C and one low ambient temperature of -17.8 C were added to the test matrix for the cooling and heating tests, respectively in order to investigate the performance improvement potential of the vapor-injection system at severe weather conditions. The mass flow rate of the injected vapor was varied from 0 g/s to the maximum value, resulting in an injection of saturated vapor. 3 EXPERIMENTAL RESULTS AND DISCUSSIONS In total, 288 tests were conducted. The energy balance error between the air-side and the refrigerant-side capacity was evaluated for all tests. The comparison of the air-side and the refrigerant-side capacities is shown in Figure 3. The energy balance error of all the tests was less than 6%, which is in compliance with the ASHRAE standard 116 (1995). Refrigerant-side Capacity [kw] 20 18 16 1 12 10 8 6 Cooling-Baseline Heating-Baseline Cooling-IHXC Heating-IHXC Cooling-FTC Heating-FTC +6% -6% 6 8 10 12 1 16 18 20 Air-side Capacity [kw] Figure 3: Comparison of air-side and refrigerant-side capacities for all performance tests Cooling Capacity [kw] 13 12 11 10 9 Ambient 6.1 C-IHXC Ambient 6.1 C-FTC 100 1600 1800 2000 2200 Figure : VI cooling capacity vs. intermediate pressure Power Consumption [kw] 5 3 Ambient 6.1 C-IHXC Ambient 6.1 C-FTC Cooling COP 5 3 Ambient 6.1 C-IHXC Ambient 6.1 C-FTC 2 100 1600 1800 2000 2200 Figure 5: VI cooling power consumption vs. intermediate pressure 2 100 1600 1800 2000 2200 Figure 6: VI cooling COP vs. intermediate pressure

2119, Page 3.1 Steady-State Cooling Performance The system capacity, the power consumption and the COP at different ambient conditions, are plotted with different intermediate pressures at the injection port, and illustrated in Figure through 6. As shown in Figure, the cooling capacity of the IHXC increases with the intermediate pressure, but the increment is saturated at higher intermediate pressure. This is because the temperature difference between the injected vapor and the main stream refrigerant decreases as increasing the intermediate pressure, which affects the subcooling effect at the internal heat exchanger. On the other hand, the cooling capacity of the FTC decreases with increasing the intermediate pressure. This is because the refrigerant enthalpy at the evaporator inlet increases with increasing the intermediate pressure. This reduces the enthalpy span across the evaporator, which has a negative effect on the FTC capacity. As shown in Figure 5, the power consumption of the IHXC increases with the intermediate pressure for all cases. This is because the injection mass flow rate increases with the intermediate pressure. The compressor compresses extra amounts of refrigerant coming from the injection line at its higher stage. Contrary to the IHXC, the power consumption of the FTC has little change with increasing the intermediate pressure. The power consumption even gradually decreases about 1.3% with increasing the intermediate pressure at the ambient condition of 6 C. This effect can be explained by the following reasons. One reason is that the compressor compresses more refrigerant at its higher stage with increasing the intermediate pressure. This contributes to the increased power consumption. On the other hand, increasing the intermediate pressure reduces the liquid refrigerant in the condenser so that the compressor head pressure is reduced. This effect contributes to the reduced power consumption. The combination of the two effects makes the change of the compressor power consumption not obvious. Figure 6 shows that the vapor injection has a negative impact to the COPs of the IHXC and the FTC at the low ambient cooling application (ambient temperature of 27.8 C). The COPs of the IHXC and the FTC decrease about 3% and 1%, respectively, with increasing the intermediate pressure. The COPs of the IHXC at the ambient conditions of 35 C and 6.1 C do not show obvious improvement with increasing the intermediate pressure. The maximum COP change within the test points is 2%. The COP of the FTC at such condition is almost constant. This is because the increase of the power consumption somewhat diminishes the benefit of the capacity improvement. The system performance of the IHXC and the FTC in the cooling mode has been compared to the baseline system. The changes of the system capacity and the COP at different injection ratios are illustrated in Figure 7. Overall, the IHXC and the FTC show a comparable performance improvement. However, the IHXC has a wider operating range of the intermediate pressure than the FTC does. This is because the superheat of the injected vapor can be adjusted in the IHXC, but the injected vapor in the FTC is saturated. Both systems indeed improve the system cooling capacity. The higher the ambient condition is, the more capacity improvement is observed. The maximum capacity gain is 15%, associated with a 2% COP gain, at the ambient condition of 6.1 C. The COP improvement of the vapor-injection system having the same compressor displacement volume to the baseline is not very obvious. Overall, the maximum improvement is around 2~% depending on the ambient conditions, which means that the vapor injection almost equally affects the capacity and the power consumption. The results show that this technique is more favorable for the high ambient cooling application. Change of Capacity 20% 15% 10% 5% Ambient 6.1 C-IHXC Ambient 6.1 C-FTC Change of COP 10% 5% 0% Ambient 6.1 C-IHXC Ambient 6.1 C-FTC 0% 0% 5% 10% 15% 20% 25% 30% 35% Injection Ratio (a) (b) Figure 7: Comparisons of VI cooling performance to the baseline system: (a) Capacity, (b) COP -5% 0% 5% 10% 15% 20% 25% 30% 35% Injection Ratio

2119, Page 5 3.2 Steady-State Heating Performance The vapor-injection effects on the system performance in the heating application are illustrated in Figure 8 through 10. For the case of the IHXC, the heating capacity and the power consumption, shown in Figure 8 and 9, respectively, increase almost the same trend when the intermediate pressure increases, which overall results in a fairly constant COP for the high ambient heating applications (T amb =16.7 C and T amb =8.3 C) as shown in Figure 10. However, for the low ambient temperature heating applications (T amb =-8.3 C and T amb =-17.7 C) in the same charts, the increase of the heating capacity has a greater extent than the increase of the power consumption when the intermediate pressure increases, so that the COP increases almost linearly when the intermediate pressure increases. The rises of both the heating capacity and the power consumption come from the increase of the mass flow rate of the injected vapor refrigerant with increasing the intermediate pressure. The compressor needs more power to overcome the increased mass flow rate at its higher stage. Meanwhile, the heating capacity increases with more refrigerant flowing through the condenser. Heating Capacity [kw]. 20 16 12 8 Ambient 16.7 C-IHXC Ambient 8.3 C-IHXC Ambient -8.3 C-IHXC Ambient -17.8 C-IHXC Ambient 16.7 C-FTC Ambient 8.3 C-FTC Ambient -8.3 C-FTC Ambient -17.8 C-FTC Power Consumption [kw] 3 Ambient 16.7 C-IHXC Ambient 8.3 C-IHXC Ambient -8.3 C-IHXC Ambient -17.8 C-IHXC Ambient 16.7 C-FTC Ambient 8.3 C-FTC Ambient -8.3 C-FTC Ambient -17.8 C-FTC 500 700 900 1100 1300 1500 1700 1900 Figure 8: VI heating capacity vs. intermediate pressure Heating COP 6 5 3 Ambient 16.7 C-IHXC Ambient 8.3 C-IHXC Ambient -8.3 C-IHXC Ambient -17.8 C-IHXC 2 500 700 900 1100 1300 1500 1700 1900 Figure 9: VI heating power consumption vs. intermediate pressure Ambient 16.7 C-FTC Ambient 8.3 C-FTC Ambient -8.3 C-FTC Ambient -17.8 C-FTC 2 1 500 700 900 1100 1300 1500 1700 1900 Figure 10: VI heating COP vs. intermediate pressure The heating performance of the vapor-injection system has been compared to the baseline system. The changes of the system capacity and COP at different injection ratios are illustrated in Figure 11. The results show that the vapor-injection technique indeed improves the heating capacity significantly, and it is more favorable for the low ambient heating applications. The lower the ambient temperature is, the more capacity improvement is found. The maximum heating capacity gain varies from 13% to 33% as the ambient temperature decreases from 16.7 C to - 17.8 C. The improvement of the heating COP is more significant at the low ambient conditions than that at the high ambient conditions. The maximum COP improvement is 23% for the FTC at the ambient temperature of -17.8 C. As compared to the IHXC, the FTC has very limited range of the intermediate pressure since the injected vapor is

2119, Page 6 saturated. Overall, the FTC shows better performance improvement in terms of the capacity and the COP gains at the low ambient heating than the IHXC does. This is because the intermediate pressure of the FTC is slightly higher than the IHXC, so that it injects more refrigerant into the second stage of the compressor than the IHXC does. This effect makes more refrigerant flow through the FTC s condenser, and delivers higher heating capacity than the IHXC. Change of Capacity 50% 5% Ambient 16.7 C-IHXC Ambient 16.7 C-FTC Ambient 8.3 C-IHXC Ambient 8.3 C-FTC 0% Ambient -8.3 C-IHXC Ambient -8.3 C-FTC 35% Ambient -17.8 C-IHXC Ambient -17.8 C-FTC 30% 25% 20% 15% 10% 5% 0% -5% 0% 5% 10% 15% 20% 25% 30% 35% 0% Injection Ratio (a) (b) Figure 11: Comparisons of VI heating performance to the baseline system: (a) Capacity, (b) COP Change of COP 35% 30% 25% 20% 15% 10% 5% 0% -5% Ambient 16.7 C-IHXC Ambient 8.3 C-IHXC Ambient -8.3 C-IHXC Ambient -17.8 C-IHXC Ambient 16.7 C-FTC Ambient 8.3 C-FTC Ambient -8.3 C-FTC Ambient -17.8 C-FTC 0% 5% 10% 15% 20% 25% 30% 35% 0% Injection Ratio 3.3 Cooling and Heating Seasonal Efficiency In this study, the seasonal energy efficiency ratio (SEER) and the heating seasonal performance factor (HSPF) of the baseline, the IHXC, and the FTC are carried out. The results of the SEER and HSPF are summarized in Table 1 and 2. The inputs for evaluating the SEER are the system cooling capacity and the power consumption at the ambient temperatures of 27.8 C and 35 C. The inputs for calculating the HSPF are the system heating capacity and the power consumption at the ambient conditions of 8.3 C, 1.7 C and -8.3 C. Those capacities and the power consumptions are evaluated from the experimental study; the capacities are converted from SI units to the required units. Table 1: Summary of SEER results Ambient ( C) Capacity (kw) Power (kw) Degradation Coefficient* SEER (Btu/W-h) Baseline 27.8 10. 3.310 35.0 11.1 2.910 IHXC + 27.8 11.0 3.583 35.0 11. 2.867 27.8 11.0 3.583 IHXC 35.0 11.5 2.992 0.08 FTC 27.8 11.2 3.58 35.0 11.8 3.018 *A typical OEM value for cooling degradation coefficient is used in this study. + Injection port is turned on at the ambient of 35 C, and turned off at the 27.8 C. SEER Improvement 12.50 0.0% 13.03.2% 12.62 1.0% 12.82 2.6% In Table 1, it is observed that the IHXC and the FTC have little effect on improving the system SEER when the compressor injection port is open. If the baseline SEER is regarded as a base, the maximum SEER improvement is 2.6%, which is achieved by the FTC. The IHXC shows only 1% improvement. This is because the system COP at the low ambient condition (27.8 C) has to be enhanced in order to improve the SEER. However, the vapor-injection cycles have little benefit or even negative effect on the system COP at such an ambient condition. This diminishes the fact that the system performance is indeed improved at 35 C by the vapor injection. To eliminate the negative effect, another operating option is examined in the IHXC, in which the injection port is shut off at the ambient temperature of 27.8 C. In this case, the SEER of the IHXC shows.2% improvement as compared to the baseline.

2119, Page 7 Table 2 shows that the IHXC and the FTC can significantly improve the system HSPF. In average, about 8% improvement in the HSPF can be achieved as compared to the baseline. Overall, the SEER and the HSPF for the IHXC and the FTC are really close to each other. The difference is less than 1.6%, which is within the measurement uncertainties. Therefore, it is hard to conclude which one is particularly better than another. Baseline IHXC FTC Table 2: Summary of HSPF results Ambient ( C) Capacity (kw) Power (kw) Degradation Coefficient* 8.3 10. 3.110 1.7 8.0 2.930-8.3 6.5 2.790 8.3 12.0 3.395 1.7 9.3 3.183 0.20-8.3 7.8 3.018 8.3 12.0 3.53 1.7 9.2 3.225-8.3 8.0 3.08 HSPF** HSPF Improvement 8.22 0.0% 8.90 8.3% 8.85 7.7% *A typical OEM value for heating degradation coefficient is used in this study. **HSPF is evaluated under the following conditions: The climate region is Region IV defined by U.S. Department of Energy; the demand-defrost credit is 1.03; the compressor is turned on/off at -3. C/-37.2 C. CONCLUSIONS In this study, the performance potential of the two-stage heat pump system with a vapor-injected scroll compressor was experimentally investigated. The FTC and the IHXC options of the two-stage vapor-injection system were explored. The experimental results show that the IHXC has a wider operating range of the intermediate pressure than the FTC due to its freedom of setting for a certain amount of superheat at the injection port. Overall, the IHXC and the FTC show a comparable performance improvement as compared to the baseline system. A cooling capacity gain of around 1% with % COP improvement at ambient 6.1 C and about 30% heating capacity improvement with 20% COP gain at -17.8 C and about 7% HSPF improvement in U.S. Department of Energy s northern Region IV climate were found for the vapor-injected R10A heat pump system as compared to the conventional system. It is concluded that the vapor-injection system is more favorable in the high ambient temperatures for the cooling mode and the low ambient temperatures for the heating mode. NOMENCLATURE COP FTC HSPF IHXC SEER Coefficient of Performance Flash Tank Cycle Heating Seasonal Performance Factor Internal Heat Exchanger Cycle Seasonal Energy Efficiency Ratio REFERENCES ASHRAE, 1995, Methods of testing for rating seasonal efficiency of unitary air conditioners and heat pumps, ANSI/ASHRAE Standard 116, Atlanta, GA. Beeton, W. L., Pham, H. M., 2002, Performance improvements in commercial refrigeration with vapor injected scroll compressors, Proc. Int. Conference: New technologies in commercial refrigeration, Urbana, IL, pp. 85~92. Beeton, W. L., Pham, H. M., 2003, Vapor-injected scroll compressor, ASHRAE Journal, vol. 5, no., pp. 22~27. Chin, L., Spatz, M. W., 1999, Issues relating to the adoption of R10A in air conditioning systems, Proc. 20th International Congress of Refrigeration, Sydney, Australia.

2119, Page 8 He, S., Guo, W., Wu, M., 2006, Northern china heat pump application with the digital heating scroll compressor, Proc. International Compressor Engineering Conference, West Lafayette, IN., R116. Heo, J., Lee, Y., Lee, S., Kim, Y., 2007, Improvement of the heating performance in a variable speed heat pump by applying the gas injection technique into a twin rotary compressor, Proc. 21th International Congress of Refrigeration, Beijing, China, ICR07-E2-911. Huang, M., Hewitt, N., Nugyen, M., 2007, Field testing of an economized vapor injection heat pump, Proc. 21th International Congress of Refrigeration, Beijing, China, ICR07-E2-1108. Ma, G., Chai, Q., Jiang, Y., 2003, Experimental investigation of air-source heat pump for cold regions, International Journal of Refrigeration, vol. 26, pp. 12~18. Meurer, C., Buyle, O., Paulus-Lanckriet, M., 1999, Comparison of R22 and R10A at elevated condensing temperatures, Proc. 20th International Congress of Refrigeration, Sydney, Australia. Nguyen, M., Hewitt, N., Huang, M., 2007, Performance evaluation of an air source heat pump using economized vapor injection compressor and flash tank coupled with capillary tubes, Proc. 21th International Congress of Refrigeration, Beijing, China, ICR07-E2-1110. Winandy, E. L., Lebrun, J., 2002, Scroll compressor using gas and liquid injection: Experimental analysis and modeling, International Journal of Refrigeration, vol. 25, pp. 113~1156. Wang, B., Li, X., Shi, W., Yan, Q., 2006, Effects of refrigerant injection on the scroll compressor, Proc. International Compressor Engineering Conference, West Lafayette, IN., C091. Wang, B., Li, X., Shi, W., Yan, Q., 2007, Design of experimental bench and internal pressure measurement of scroll compressor with refrigerant injection, International Journal of Refrigeration, vol. 30, no. 1, pp. 179~186. Yana Motta, S., Domanski, P.A., 2000, Performance of R22 and its alternatives working at high outdoor temperatures, International Refrigeration Conference, West Lafayette, IN., pp. 7-5. ACKNOWLEDGMENT The support of this research through the Alternative Cooling Technologies and Applications Consortium of the Center for Environmental Energy Engineering at the University of Maryland is gratefully acknowledged.