CHAPTER IV AIR DISTRIBUTION AND BALANCE

Similar documents
Worksheet for Small Commercial Air System Design

Duct Design and Installation

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

CAT-SIUH-2000(3) SUPERSEDES CAT-SIUH-98(2) SARAVEL INDUSTRIAL UNIT HEATERS

Fan Selection. and Energy Savings

DESIGNING MODULAR VAV SYSTEMS

Adding More Fan Power Can Be a Good Thing

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Product Data. 40RUA/40RUS 6to15TonDirectExpansion 7.5to15TonChilledWater Packaged Air---Handling Units FEATURES/BENEFITS. Indoor air quality features

Pharmaceutical Facility Design

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

COMMERCIAL PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 20 TONS

Modular Active. Chilled. Beams

ENGINEERING LETTER 4

IBIS INTERNATIONAL, INC. DESIGN STANDARDS FOR DUCTING OF EQUIPMENT

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

STANDARD EFFICIENCY PACKAGE A/C UNIT to 216 MBtuh

Product Data FEATURES/BENEFITS 524J***H 6 TO 20 TON DIRECT EXPANSION PACKAGED HEAT PUMP AIR -HANDLING UNIT. Indoor air quality features 524J-H 07-12

Advance Release September 2009

Product Data FEATURES/BENEFITS. 524J PACKAGED AIR -HANDLING UNITS WITH PURONr REFRIGERANT SIZES 07, 08, 12, 14, 16. Indoor air quality features

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

In the past, contractors sized heating and cooling systems GETTING HVAC RIGHT

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Jim Aswegan Chief Engineer

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Company Acme HVAC Inc. Customer James Allen Preparer J White Address 3652 Shady LaneAnywhere, Earth Phone

COMMERCIAL AIR HANDLER

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Use this Construction/HVAC Glossary to answer the questions below.

Fans: Features and Analysis

Technical Development Program

CERV Fan and Duct Sizing Information

ASHRAE JOURNAL ON REHEAT

Installation, Operation, and Maintenance Information

FG7T (C and L Series)

COMMERCIAL AIR HANDLER

Air-Cooled Condensers

Problems Air and Water Distribution Systems

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

A/C Cooling Load calculation and measurement

Design Guide. Ecosmart Mini Duct Trunk and Outlet Design Guide for HVP50, HVP90 and HVP100 Air Handlers P/N 14013A

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award

ENERGY STAR Qualified Homes

ASHRAE 90.1 EFFICIENCY PACKAGE AIR CONDITIONER UNIT MBtuh

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

Residential HVAC System Design

EPH - International Journal of Science and Engineering

Air Conditioning Clinic

What is a High Velocity System?

Rittling Induction Units Catalog

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

DCG Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

Case 13 Food Storage & Processing Center

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

MECCI Engineers. Institute of Engineering Design & Research

When Duct Sealing Kills HVAC Equipment and Efficiency

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

TECHNICAL SPECIFICATIONS

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Contents INDEX. TDM Series Indirect Fired Heaters

Displacement Ventilation

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

Active Chilled Beams

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

INDOOR, SUSPENDED, STEAM OR HOT WATER HYDRONIC UNIT HEATER FOR VERTICAL OR HORIZONTAL CONFIGURATION

Product Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama ! WARNING

Series HF custom designed flange and insert heaters.

DCC Commercial. Submittal Data Form. 7½ - 12½ Ton Packaged Air Conditioners Up to 11.3 EER Cooling Capacity: 88, ,000 BTU/h

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

ELECTRICAL QUANTITY WEIGHT (LB)

Desiccant Dehumidifier

NH 3. Dual Discharge Evaporator. Ammonia Industrial Applications 1-16 Tons MDAN

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Zoning System Design Manual

Product Data. 50ZP (60Hz) Single-Package. Air Conditioners 3-5 Nominal Tons

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Unico Training. Class for R E Michel Salesmen

Product Data. Features/Benefits. 50HX High Efficiency Single-Packaged Heat Pumps. 2 to 5 Nominal Tons

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Indoor Pool Design Considerations Colorado Springs, Colorado

EXHAUST FAN SCHEDULE

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

SAFETY AND INSTALLATION MANUAL MODEL 8100

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

b.) Technical Information:

Chilled Water DOAS Fan Powered Terminal Units

A Treatise on Liquid Subcooling

SECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

Transcription:

CHAPTER IV AIR DISTRIBUTION AND BALANCE 4.1. INTRODUCTION When projecting an air-conditioning system, the following steps should be followed: 1) Determine the heat gain or loss 2) Establish the air requirements (cfm) to remove or add air. 3) Design a duct system capable of distributing the required cfm. 4) Select a fan to move the quantified cfm against the calculated resistance of the system. This chapter is devoted to steps 3 and 4. 4.2. AIR DISTRIBUTION SYSTEM Cooling and heating systems use air to carry heat through all the facility. The quantity of heat to move and the temperature difference between room air and conditioned air determines the air that circulates through the ducts and other parts that compose the air distribution system. The air distribution system is composed of air handler, ducts and registers. 4.2.1 AIR HANDLER In compressive refrigeration cycles, the air handler is composed of the warm air input, that permits the return air to flow through the device; the filter that cleans the air; the evaporator coil that conveys the cool gas, which cools the circulating air; the fan that blows the air again inside the facility; the outdoors air intake (where it exists); and the output to the distribution ducts. Figure 4.1 shows an squematic view of an air handler.

Figure 4.1. Air handler

4.2.2 REGISTERS Registers are outlets that distribute and control conditioned air. They are composed of a diffuser that spreads out the air and a damper to control the air quantity. A good register selection permits to distribute the conditioned air without causing uncomfortable drafts. When distributing cool air, the registers should be located near to the ceiling, because the more dense cool air will tend to move down. When distributing warm air, the registers should be located near the floor because the warm air tends to move up. Figure 4.2 Shows a register Figure 4.2. Register Different registers have different air distribution patterns. The patterns for wall registers are straight, medium and maximum depending on the way the air will be spread out in the room. Other factors in the wall register selection are the number of cubic feet per minute (cfm) and the horizontal distance the air stream travels from a register before it slows to a velocity comfortable for people (throw). Ceiling registers provide throw distances for one, three and four directions. Floor registers should be selected for throw distances from the floor to the ceiling. The information for the register selection can be found in manufactures' catalogs or any other specialized catalogs. 4.2.3. DUCTS The ducts serve as a carrier to convey the air used for heating or cooling. Most rectangular ducts are constructed using galvanized steel or fiberglass. Flexible round ducts are frequently used in residential installations. The factors that affect the quantity of air that circulates per unit time (cfm) through the duct and its velocity (fpm) are the duct size and the fan power. The quantity of air that circulates per minute in a duct system is determined be the quantity of heating or cooling required and by the temperature difference between conditioned air and room air. The quantity in cubic feet per minute (cfm) can be calculated using formula (2.14), which is reproduced below: where SH is the amount of sensible heat that must be added or removed to maintain the specified room temperature in BTUh and TD is the temperature difference in degrees Fahrenheit between the conditioned air and

the room air. Example 4.1. A room has a summer peak sensible heat gain of 20000 BTUh. How much 55 ºF air is required to maintain 75 ºF in the room? cfm = 20000 / ( 1.08 x ( 75-55) ) = 925.9 Having calculated the heat gain in a building, the total quantity of cfm can be calculated multiplying the total tons by 400. This is due to the assumption that air handlers typically circulate about 400 cfm for each ton of capacity. The cfm for each room in the building is calculated in proportion to floor area. 4.3 DUCT CALCULATIONS The simplest way of calculating the duct size is using the duct friction chart. On this chart the cubic feet per minute, the velocity, the duct diameter and the friction loss in the duct are represented. Knowing two of this parameters, it is possible to find out the other two. A simplified version of the chart is shown in figure 4.3. Figure 4.3. Duct Friction Chart, Range 1000 to 30000 cfm. The recommended main ducts velocities are shown on Table 4.1.

Application Main Ducts Residences 1000 Hotels and motels bedrooms 1400 Theatres and auditoriums 1300 General offices, quiet restaurants 1900 Industrial buildings 2400 Table 4.1. Recommended Duct Velocities, fpm Example 4.2 The sensible heat gain in a residence is calculated as 36000 BTUh. The conditioned air has a temperature of 55º F and the residence temperature is 75º F. Calculate the size of the main duct to be connected to the air handler. The necessary cfm through the main duct are: cfm = 36000/1.08(75-55) = 1667 The recommended velocity is 1000 fpm as per Table 4.1. from Figure 4.3, the duct size is approximately 18". Frequently it is not convenient or desirable to use round ducts. In this case it is necessary to convert from round to rectangular ducts. For making the conversion, it is necessary to utilize a chart that gives the rectangular equivalents of round ducts. This chart may be found, for example in [1] or in some specialized manual. 4.4. EQUIVALENT LENGTHS OF ELBOW When calculating the friction loss in a duct system, it result convenient to find the equivalent length of elbows in order to simplify the calculations. Figure 4.4 shows an elbow, where the different participating parameters are presented. Figure 4.4. Standard Radius Elbow

Figure 4.4. Standard Radius Elbow The procedure to find out the elbow equivalent length is as follows: a) Find R/W b) Find H/W c) Go to the elbow friction-loss chart shown on Figure 4.5 to find L/W d) Multiply the L/W by the width of the elbow and divide by 12". Figure 4.5. Elbow Friction-Loss Chart. Example 4.3 Given an elbow 36" wide by 24" deep, and 20" radius, find the equivalent length of the elbow.

4.5. DUCT SYSTEM AND FAN CALCULATION When sizing the ducts and the fan, the following steps should be followed: 1) Find the cfm in the main duct 2) Find the round duct diameter for each part of the system 3) If necessary, convert the round ducts to rectangular ducts 4) Solve for the elbow equivalent length 5) Calculate the total equivalent length 6) Determine the actual duct friction loss 7) Calculate the actual friction 8) Calculate the fan hp applying the formula hp = (cfm x Fan Pressure) / 4000 Example 4.4 The air conditioning system shown on Figure 4.6 is installed in an small auditorium. For architectural and structural reasons, the ductwork must be held at 18" height throughout. The run outs are 10' each. Pressure loss through the outlet is 0.07" wc. Pressure loss through the return, outside air duct and filter bank is 1.2" wc. The main duct will be rectangular, and the run outs will be round flexible ducts.

Figure 4.6 Duct System. Solution: 1) Main Duct cfm = 1400 + 600 + 1000 = 3000 2) & 3) Round Ducts Diameter The maximum duct velocity is found from Table 4.1 as 1300 fpm. From Figure 4.3 (Duct Friction Chart), is obtained the friction loss as 0.1 inches of water per 100 feet. This will be the System design point for creating the following Table: CFM RUN Length Round Rectangular Duct Equivalent 3000 AB 60 21 18 x 18 1600 BC 40 17 18 x 13 1000 CD 30 14 18 x 9 1400 B1 10 16 600 B2 10 11 1000 B3 10 14 4) Solve for the loss at elbow Elbow at D --- (H/18) (W/9) Radius Ratio: (R/W) = 1.5 (datum) Aspect Ratio: (H/W) = (18/9) = 2 Length Ratio: (L/H) --- Chart --- (L/H) = 5 Equivalent Length: L eq = (5 x 9 ) / 12 = 3.75 ft 5) Total Equivalent Length If the run outs are in parallel only the run out with the greatest pressure drop or longest equivalent length is entered. CFM RUN SIZE Equivalent Length 3000 AB 18 x 18 60

1600 BC 18 x 13 40 1000 CD 18 x 9 30 1000 Elbowed 18 x 9 3.75 1000 B3 18 x 9 10 Total -- 143.75 ft. 6) Actual Friction Loss 7) Total Friction 8) Fan horsepower hp = (3000 x 1.413) / 4000 = 1.06 4.6 REVIEW QUESTIONS 4.1. The air volume moving through a duct is 100 cfm. The duct has a diameter of 6. Find: a. velocity in fmp b. pressure drop 4.2. In the figure below A = 80 ft; B = 100 ft; C = 50 ft; D = 80 ft

For architectural and structural reasons, the ductwork must be held to a 15 inch height throughout. The runouts are each 40 ft. The fan outlet is 1500 fpm. Pressure loss through the last outlet is 0.07 in WG. Pressure loss through the return, outside air duct and filter bank is 1 in. WG. a. size the ducts for: A, B, C, D, E, F, G, H b. Find the horsepower of the fan motor. 4.3. A system has a duct run handling 300 cfm of air inside a room. The total effective length is 170 ft. Let s assume that the fan is capable of moving the correct air flow in the supply duct with a friction loss of 0.36 in. WG. Cooling coil loss = 0.24. Supply register loss = 0.03. Find the duct diameter.