Daikin Direct Expansion (DX) Cooling Coils

Similar documents
Daikin Water Cooling, Heating, and High Capacity Booster Coils

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

FLUID COIL INSTALLATION OPERATION AND MAINTENANCE

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Installation Instructions

Installation Instructions

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

COOLING / HEATING COILS

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation Instructions

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation Instructions

Condensing Unit Installation and Operating Instructions

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Condensing Unit Installation and Operating Instructions

Installation Owner Diagnostics

INSTALLATION INSTRUCTIONS FOR RCQD COILS

Series 6, Vertical Floor-Mount Units

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Greenheck Coils. A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

Installation Instructions

PL Series Premier Indoor Plenum Coils

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

Greenheck Coils A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

Installation, Start-Up and Service Instructions

Evaporator Coil. Installation Instructions GENERAL

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

Installation Instructions

Installation Instructions

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

Service Step by Step Trouble-Shooting Check-List

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS

R Series Cooling Modules

Greenheck Coils A Complete Line of Custom Coils to Meet Your Needs. 5/16, 3/8, 1/2, 5/8 and 1 inch OD Tubing

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

METHOD STATEMENT INFORMATION REQUIRED

RCM Refrigerant Module

Installation Instructions

INSTALLATION INSTRUCTIONS

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

Evaporator Coil. Installation Instructions GENERAL

Owner s Manual Therma-Stor II Heat Recovery System

R Series Cooling Modules

Installation, Start-Up and Service Instructions

Air Cooled Condenser Installation and Operating Instructions

Refrigerant Recovery Machine. Model No Operating Manual

INSTALLATION INSTRUCTIONS

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

Horizontal/Side Discharge Condensing Units

INSTALLATION INSTRUCTIONS

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

C7 Series Split System Uncased Indoor Coils

Installation, Operation, and Maintenance Information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

SECTION AIR COILS

Series 1140 and 1141 Temperature Regulators

Refrigerant Recovery Unit, Model RRU134

Series 6, Vertical Floor-Mount Units

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

R100 Oil-Less Refrigerant Recovery Unit

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

Room Air Conditioner Service and Parts Manual

MODELS K2EU060A, K4EU090A, & K3EU120A

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FAS/FHS Series, Package Air Handling Units 6 to 25 Ton Air Conditioners 6to20TonHeatPump

WineZone Ceiling Mount Ductless Split 15

DESIGN STANDARDS SECTION 15600

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SuperKlean Washdown Products

Installation and Maintenance Manual IM 1102

Transcription:

Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied

Contents Introduction... 3 General Information... 3 Hazard Identification Information... 3 Receiving Instructions... 3 Coil Types... 3 Model EN... 3 Model EF... 3 Model ER... 3 Model EJ... 3 Model EK... 3 Nomenclature... 4 Installation... 5 Mounting... 5 Installation... 5 Operation and Maintenance... 7 Operation... 7 General... 7 Maintenance... 7 General... 7

Introduction Introduction General Information Guidelines for the installation, operation and maintenance of Daikin direct expansion (DX) cooling coils have been provided to help insure proper performance of the coils and their longevity. These are general guidelines that may have to be tailored to meet the specific requirements of any one job. As always, an experienced installation company or fully trained individual should perform the installation and maintenance of any coil. Protective equipment such as safety glasses, steel toe boots and gloves are recommended during the installation and routine maintenance of the coil. Hazard Identification Information DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided. WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided. CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided. Receiving Instructions 1 All Daikin coils are factory tested at 315 psig minimum air pressure while submersed in water, inspected, and carefully packaged. 2 Damage to the coils can occur after they have left the factory. Therefore, the coils should be inspected for shipping damage upon receipt. The freight bill should also be checked against items received for complete delivery. 3 Damaged and/or missing items should be noted on the carrier's freight bill and signed by the driver. 4 For additional assistance, contact your local Daikin sales representative. Coil Types Model EN This evaporator coil is used for applications where capacity control is not required. Single or multiple distributors are available depending on the number of circuits required. Model EN (Figure 1) evaporators utilize dual suction connections when multiple distributors are used. Model EF Face control (model EF - Figure 1) is another evaporator coil option offered. Face control is the simplest form of capacity control. These coils are normally furnished with two distributors and two suction connections offering 50% capacity reduction capabilities. Model ER Daikin offers a row control option (model ER - Figure 1) for six row evaporator coils. These coils are split into two rows and four rows that offer approximately a 50% capacity reduction. Model EJ These evaporator coils (model EJ - Figure 1) come with interlaced circuiting. This form of capacity control utilizes two distributors with each feeding every other tube in the first row of the coil. Each distributor has a separate suction connection. Model EK For applications that require face control and interlaced circuits, we offer evaporator model EK (Figure 1). Interlaced face control utilizes four distributors and four suction connections. Figure 1: Evaporator Coil Types EN Normal Rows 2, 3, 4, 5 6, 8, 10, 12 EF Face Control Rows 2, 3, 4, 5 6, 8, 10, 12 ER Row Control Rows 6 2 Distributors EJ Interlaced Rows 3, 4, 6, 8 2 Distributors EK Interlaced Face Control Rows 4, 8 4 Distributors Daikin IM 902 3

Introduction Nomenclature 5 E N 14 06 C 24.00 x 144.00 Tube O.D. 3=3/8" 4=1/2" 5=5/8" Coil Type E = Evaporator Circuiting N = Normal F = Face Control R = Row Control J = Interlaced K = Interlaced Face Control Finned Length (inches) Finned Height (inches) Fin Design A - flat (AI, Cu) B - corrugated (AI, Cu) C - sine wave (AI, Cu) F - flat (SS, CS) Rows Deep Fins Per Inch 4 Daikin IM 902

Installation Installation Mounting Position the coil such that the suction header is at the entering airside of the coil and the distributor tubes are at the leaving airside of the coil. This orientation provides counter flow heat exchange that is required for proper coil performance. The suction connection is located at the bottom of the coil when properly installed (see Figure 1 on page 3). (Figure 2). If a hot gas bypass kit was ordered with the coil, the nozzle that is in the distributor will need to be relocated into the hot gas bypass assembly (Figure 3). 4 All field brazing and welding should be performed using high quality materials and an inert gas purge (such as nitrogen) to reduce oxidation of the internal surface of the coil. Figure 2: Distributor Installation CAUTION Sharp edges on sheet metal and fasteners can cause personal injury. This equipment must be installed, operated, and serviced only by an experienced installation company and fully trained personnel. Protective equipment such as safety glasses, steel toe boots and gloves are recommended during the installation and routine maintenance of the coil. CAUTION Failure to properly install the coil can result in irreparable damage to the coil as well as other components in the system. Retainer Ring Nozzle Figure 3: Hot Gas Bypass Kit Distributor If you are unsure about any portion of the installation, contact your local steam specialist for assistance. 1 Carefully remove the coil from the shipping package to avoid damage to the finned area. Damaged fins can be straightened using an appropriate fin comb. 2 Proper clearance should be maintained between the coil and other structures such as the fan, filter racks, transition areas, etc. 3 Inspect the refrigerant distributor and verify that the nozzle is in place. The nozzle is generally held in place by a retaining ring or it is an integral part of the distributor itself 5 If a hot gas bypass kit was ordered with the coil, install it now (refer to Figure 4 for a general installation diagram). Complete installation instructions are in the box that contains the hot gas bypass kit. Align the side port with the hot gas line prior to brazing into place (Figure 4). Figure 4: Hot Gas Bypass Kit Installed Suction Header Distributor Equalizer Line Liquid Line Nozzle Coil Expansion Valve Hot Gas By-Pass Hot Gas Side Port Suction Line Remote Sensing Bulb Straps Suction Connection Daikin IM 902 5

Installation 6 Connect the suction line and suction connection (Figure 4 on page 5). 7 Install the expansion valve (Figure 4 on page 5). Follow the expansion valve manufacturer s recommendations for installation to avoid damaging the valve. If the valve is externally equalized, use a tubing cutter to cut off the plugged end of the factory installed equalizer line. Next, use a de-burring tool to remove any loose metal from the equalizer line (Figure 4 on page 5) and attach it to the expansion valve. If the valve is internally equalized, the factory installed equalizer line can be left as is or it can be cut back and sealed. 8 The expansion valve s remote sensing bulb (Figure 4 on page 5) should be securely strapped to the horizontal run of the suction line at the 3 or 9 o clock position and insulated. 9 Connect the liquid line (Figure 4 on page 5) to the expansion valve. Pressurize the coil, expansion valve assembly and suction connection to 100 psig with dry nitrogen or other suitable gas. The coil should be left pressurized for a minimum of 10 minutes. 10 If the coil holds pressure, the hook-up can be considered leak free. If the pressure drops by 5 psi or less, repressurize the coil and wait another 10 minutes. If the pressure drops again, there are more than likely one or more small leaks, which should be located and repaired. Pressure losses greater than 5 psi would indicate a larger leak, which should be isolated and repaired. Be sure to check valves and fittings as potential sites for leakage or bleed. If the coil is found to be leaking, contact your local Daikin coil representative. Note: Unauthorized repair of the coil may void the coil s warranty (see the Daikin warranty policy on back cover). 11 Use a vacuum pump to evacuate the coil and any interconnecting piping that has been open to atmosphere. Measure the vacuum in the piping using a micron gauge located as far from the pump as possible (the vacuum at the pump will be greater than the rest of the system). Evacuate the coil to 500 microns or less then close the valve between the pump and the system. If the vacuum holds to 500 microns or less for one minute, the system is ready to be charged or refrigerant pumped down in another portion of the system can be opened to the coil. A steady rise in microns would indicate that moisture is still present and that the coil should be further vacuumed until the moisture has been removed. 12 Failure to obtain a high vacuum is indicative of a great deal of moisture or a small leak. Break the vacuum with a charge of dry nitrogen or other suitable gas and recheck for leaks (soapy water works well). If no leaks are found, continue vacuuming the coil until the desired vacuum is reached. 13 All field piping must be self-supporting. 6 Daikin IM 902

Operation and Maintenance and Maintenance Operation General 1 Proper air distribution is vital to coil performance. Airflow anywhere on the coil face should not vary by more than 20%. 2 The drain pan and associated piping (drain line and trap) should be installed so that there is no standing water in the drain pan and that no blow-through occurs. 3 Air velocities should be maintained between 200-550 feet per minute. Maintenance General DANGER Follow the manufacturer s guidelines for lockout/tagout and disconnect all power to the unit before performing maintenance. Contact with high voltage power will cause electrical shock, resulting in severe personal injury or death. WARNING Moving parts, high pressure, and/or high temperature fluids can cause serious personal injury. 1 Filters should be inspected on a regular basis and changed as needed. Maintaining clean filters is a cost effective way to help maintain maximum coil performance and service life. 2 Periodic inspection of the coil for signs of corrosion and/or leaks is recommended. Repair and replacement of the coil and the connecting piping, valves, etc., should be performed as needed by a qualified individual(s). 3 Should the coil surface need cleaning, caution should be exercised in selecting the cleaning solution as well as the cleaning equipment. Improper selection can result in damage to the coil and/or health hazards. 4 Suggested cleaning instructions: a When handling strong chemicals, be sure to wear chemical impervious gloves, apron, and splash goggles. b Acti-Brite (AB-1) is the recommended cleaning solution. Contact your local Daikin Parts Distributor. c Determine required dilution for the specific application. It is recommended to start with a dilution ratio of 10:1 and increase concentration until the desired results are achieved. d As with mixing all acids, place the desired amount of water into the tank and then add the chemicals. e Turn off fans and allow hot coils to cool before applying. f Using plain water, wet both the coil as well as the area surrounding the equipment. Wetting the coil with water aids in product penetration and performance. g Apply properly diluted product to coil surface. Whenever possible, apply solution from the outlet side of the coil. Allow solution to remain on surface, normally 5-10 minutes. Do not allow solution to dry on the coil. CAUTION Carefully read and follow the manufacturer's recommendations before using any cleaning fluid. Note: In extreme cases, application may have to be repeated to achieve desired results. h If foaming does not occur, check for extreme grease buildup which will slow cleaning process. Foaming may not occur if coil is coated or painted. i Rinse coils, tools, and surrounding area thoroughly after the coil cleaning. 5 Clean the coil from the leaving airside so that foreign material will be washed out of the coil rather than pushed further in. 6 Periodic inspection of the coil for signs of corrosion and for leaks is recommended. Small leaks can be detected using a Halide torch. Repair and replacement of the coil and the connecting piping, valves, etc., should be performed as needed by a qualified individual. 7 The use of filter-dryers in the system piping is recommended along with a sight glass that has a moisture indicator. Replace the filter dryer(s) as needed. Note: Refrigerant conversions are beyond the scope of this manual and should only be performed by qualified parties. Daikin IM 902 7

Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.daikinapplied.com and click on training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-43285Y. To find your local Daikin Representative, go to www.daikinapplied.com. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.daikinapplied.com. 2008 Daikin Applied www.daikinapplied.com 800-432-1342