TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Similar documents
TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

January 16 th, 2014 New York City

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Low GWP Refrigerants for Air Conditioning Applications

R32 Compressor for Air conditioning and Refrigeration applications in China

Low Global Warming Refrigerants For Commercial Refrigeration Systems

R-404A Alternative with Low Compressor Discharge Temperature

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Call us today! (800)

Midea VFD Centrifugal Chiller Technology

Call us today! (800)

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Air Cooled Packaged Systems AIRAH Back to Basics

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Application Engineering

Call us today! (800)

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Steady and Cyclic Performance Testing of Packaged R-410A Units

Evaluation of HCFC Alternative Refrigerants

*Corresponding author;

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Pressure Enthalpy Charts

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

GWP Alternative Refrigerants

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

A/C Cooling Load calculation and measurement

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Chillers. Technical Data. EWYD-BZ 250~580 kw

R4H4. Product Specifications

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

MAC-120HE-03 Air-Cooled Chiller

Study of R161 Refrigerant for Residential Airconditioning

Commercial High-Efficiency Condensing Units

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

R4H4. Product Specifications

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

A Treatise on Liquid Subcooling

MAC N-407 Air-Cooled Chiller

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Sabroe MatchMaster Program COMP1

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Performance Measurement of R32 Vapor Injection Heat Pump System

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Thermodynamics: Homework A Set 7 Jennifer West (2004)

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Transcritical CO2 Bottle Cooler Development

2016 Annual Conference

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Kelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

*20D082-05NN* 20D082-05NN

2. CURRICULUM. Sl. No.

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Energy Use in Refrigeration Systems

MODULAR CHILLER. R410a R22

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Liebert CSU3000 Chiller

Presented By: John Dolan, P.E.

REFRIGERATION TUTOR. OBJECTIVE: To perform test on the refrigeration tutor to determine different COPs and other performance parameters.

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Chiller Satheesh Kulankara William McQuade Johnson Controls Inc 631 S.Richland Avenue York, PA 17403 May 1, 2013 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

List of Tested Refrigerant s Compositions (Mass%) ARM-42a R-134a/R-152a/R-1234yf (7/11/82)

1. Introduction: This report documents the results from the testing of ARM-42a refrigerant as a drop-in alternate for R-134a in a variable speed, air-cooled screw chiller. The tests were conducted in the air-cooled chiller test facilities of Johnson Controls located in York, Pennsylvania. Baseline tests were first conducted with R-134a. These were followed by drop-in tests with ARM-42a at the same conditions. After the drop-in tests with ARM- 42a, the equipment was charged with R-134a and a limited set of tests were repeated to verify the data. All the tests were conducted using the same equipment and test facility without any modifications to the equipment, test facility or instrumentation used for measurements. The test conditions and instrumentation follows the requirements for aircooled chiller testing specified in AHRI 550/590. 2. Details of Test Setup: a. Description of System The equipment that was used for this testing is a variable speed, air-cooled, screw compressor based chiller. The test chiller has 2 independent refrigerant circuits with economizers and was configured for a nominal capacity of 175 Tons at standard AHRI 550/590 full load conditions. The chiller is designed for R-134a and uses POE oil for compressor lubrication. The evaporator of the chiller is a 2-circuit, shell and tube, hybrid falling film design with the refrigerant on the shell side. The air-cooled condenser on the chiller is made up of micro-channel modules. b. Description of Modifications to System There were no modifications to the chiller between R-134a and ARM-42a testing. The chiller was first tested with R-134a to establish baseline performance. After the baseline tests. R-134a was removed from the chiller and tests were conducted with ARM-42a. The lubricating oil for both R-134a and ARM-42a tests was the same POE oil. c. Description of Tests Conducted Due to test lab constraints at the time of this testing, the chiller was tested in an air-cooled chiller test facility capable of testing chillers with a nominal capacity of 150 Tons. As a result, only one of the two refrigerant circuits of the chiller was operated in this testing. Both refrigerants were tested on the same independent refrigerant circuit, in the same test facility back to back. Figure 1 is a schematic of the test set-up showing the refrigerant circuit that was tested including the locations of key measurements. Test chiller flows, temperatures, pressures and power consumption were measured with instruments calibrated in place against NIST standards. The evaporator 2

was instrumented with two resistance temperature detectors (RTDs) to measure the inlet water temperature, two RTDs to measure the exiting water temperature and two turbine flow meters in series to measure chilled water flow rate at evaporator inlet. The condenser was instrumented with five thermocouples (TCs) to measure the incoming air temperature. Single pressure transducers were used to measure the pressure at compressor suction, discharge and condenser outlet. A TC was used to measure the temperature of refrigerant at condenser outlet. The compressor power consumption was measured with a power analyzer designed for use with s. The condenser fan power was measured separately using a second power analyzer. Redundant measurements were averaged before use in data reduction and analysis. The instrument measurement uncertainties are listed in Table 1. Both R-134a and ARM-42a were tested with the same instruments without any adjustments between the tests. Table 1: Measurement Uncertainties Parameter Uncertainty, RTD ±0.1 F, TC ±0.2 F Volume ±0.20% Electrical Power ±0.15% Data for each of the tests were recorded over a 15 minute span after the test chiller reached steady state. The speed of the variable speed compressor was held constant during each of the tests once the chiller reached steady state. Instrument data recorded over the 15 minute span was averaged for data reduction and analysis. Measurements were checked for consistency by comparing the redundant instrumentation on the evaporator water side. During testing, the readings of the two evaporator water flow meters differed by an average of 1.3 GPM. The average difference between the two RTDs reading the evaporator water inlet temperature and evaporator water outlet temperature was 0.02 F. Only one of the two refrigerant circuits on the chiller was tested during this work. For the full load test, the evaporator water inlet and outlet temperatures were set at 50.5 F and 45.5 F, respectively and the evaporator water flow rate was adjusted to get these temperatures. The evaporator water side conditions were selected based on prior testing of this same chiller with R134a in a larger test facility. During this prior testing, both circuits of the chiller were tested simultaneously at standard AHRI 550/590 full load conditions (54 F evaporator water inlet temperature/44 F evaporator water outlet temperature adjusted for 0.0001 hr-ft²- F/Btu fouling factor as described in AHRI 550/590, 95 F condenser air inlet temperature). The evaporator test conditions for the single circuit testing in this study were selected to result in a suction pressure within 1 psi of the suction pressure from the prior two circuit testing at AHRI 550/590 conditions in the larger test facility while maintaining the same tube side water velocity. For part load tests, the evaporator water flow rate from the full load test and the evaporator water outlet temperature of 45.5 F were maintained. The same test procedure was used for both R- 134a and ARM-42a testing. 3

3. Results The test cooling capacity was calculated from the measurements using: Q e V.c (T - T ) (1) chw chw p chw chw,in chw, out The test cooling COP was calculated using: COP (2) (W W ) c. Q e fans Table 2 below lists the results from this study including the associated uncertainties in capacity and efficiency ratios. The capacity and efficiency of the chiller with ARM-42a are normalized by the values for R-134a at the same test condition. Test # % Capacity Table 2: Test Results Capacity Ratio Q. e, ARM 42a Q e,r-134a COP Ratio COP. COP ARM 42a R-134a 1 100 1.008 ± 0.039 0.967 ± 0.039 2 75 1.005 ± 0.054 0.994 ± 0.054 3* 50 0.986 ± 0.074 0.929 ± 0.075 4 25 1.063 ± 0.158 1.002 ± 0.159 5 100 0.991 ± 0.040 0.959 ± 0.040 *for Test 3, the chiller controls had different number of fans operating for R-134a and ARM-42a. As mentioned previously, the baseline tests 1, 2 and 5 in Table 2 with R-134a were repeated after ARM-42a tests to verify data. The change in measured performance for R-134a before and after ARM-42a tests for these three tests were less than 0.8% in capacity and less than 1.5% in efficiency. The average value of the two tests with R-134a is used as the basis of comparison in Table 2 for these 3 tests. From Table 2, it can be seen that the capacity of ARM-42a is 0.8% higher than that of R- 134a near standard AHRI 550/590 chiller design conditions. However, the efficiency of the chiller with ARM-42a is 3.3% lower than that of R-134a at the same conditions. At high ambient air temperature conditions in Test 5, the capacity of the chiller with ARM-42a was 0.9% lower than that with R-134a. At the high ambient air temperature conditions, the efficiency of the chiller was 4.1% lower than that of R-134a. It should be noted that the chiller operating conditions for Test 3 was different in terms of the number of fans that were operating. The controls on the chiller are designed to turn fans on and off depending on operating conditions. The fan control logic was optimized for R-134a and 4

was not changed for ARM-42a. It is likely that the efficiency for Test 3 can be improved significantly by optimizing the fan logic for ARM-42a. This change in control logic is outside the scope of this drop-in test. Due to limitations of the test facility at the time of this testing, the ambient air temperature for Test 4 could not be maintained at the target value of 55 F specified in AHRI 550/590 standard for 25% load for air-cooled chillers. The tests with R-134a and ARM-42a were conducted at the closest possible air temperature which allowed stable operation. The refrigerant charge quantity for the tests with R-134a and ARM-42a were determined based on refrigerant level in the evaporator. During testing the sub-cooling exiting the condenser coil was controlled to a constant set point. The saturation temperature of ARM-42a for a given pressure is within approximately 2 F (ranges from about 2 F lower at the lower ambient air temperature to 2 F higher at the higher ambient air temperature) of that of R-134a at the condenser outlet conditions in this study. Due to the relatively small difference, the sub-cooling set point calculations at the condenser outlet for control purposes for both R-134a and ARM-42a were calculated using R-134a properties. With the sub-cooling controlled, refrigerant was added until the evaporator had sufficient charge as indicated by level in a sight glass for Test 1 in Table 2. This resulted in the chiller requiring 4.5% lower refrigerant quantity (by mass) for tests with ARM-42a. 5

NOMENCLATURE COP: Coefficient of Performance (ratio of heat transfer rate at the evaporator and the total power consumed by the compressors and condenser fans) c : Specific heat capacity of chilled water through the evaporator at average of evaporator p chw water inlet and outlet temperatures (kj/kg) P d : Pressure of refrigerant at compressor discharge (kpa) P l : Pressure of refrigerant at condenser outlet (kpa) P s : Pressure of refrigerant at compressor suction (kpa) Q e : Evaporator heat transfer rate (kw) T : Air temperature at inlet of condenser (K) air,in T chw,in : Chiller water temperature at evaporator inlet (K) T chw,out: Chiller water temperature at evaporator outlet (K) T l : of refrigerant at condenser outlet (K) V chw : Volumetric flow rate of chilled water entering the evaporator (m 3 /s) W : Electrical power input to compressor motor (kw) c W : Electrical power input to condenser fan motors (kw) fans chw : Density of chilled water entering the evaporator (kg/m 3 ) 6

Compressor T air,out T air,in W fans P l, T l Condenser P d Economizer W c P s T chw,out Evaporator V chw, T chw,in Figure 1 Schematic of the Test Chiller With Key Measurement Locations 7

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #1 Manufacturer: Johnson Controls Manufacturer s Notation: YVAA Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System ARM-42a POE, ISO-120 R-134a, POE (ISO-120) YVAA Test Chiller 175 Tons, Air-cooled screw chiller Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Cooling Cooling Cooling Compressor Type Compressor Displacement 7.985 7.985 m^3/min 282 282 Ft ^3/min 1.0 Nominal Motor Size 240 240 hp Nominal Motor Speed 5100 5100 rpm 1.0 Expansion Device Type EEV EEV EEV EEV Lubricant Charge 9.39 9.39 kg 20.7 20.7 lb 1.0 Refrigerant Charge 90.7 86.6 kg 200 191 lb 0.955 Refrigerant Mass Flow kg/min lb/min N/A Rate Composition, at compr. if applicable % wt Ambient In - db N/A N/A C N/A N/A F Temps. door wb N/A N/A C N/A N/A F Out db N/A N/A C N/A N/A F - door wb N/A N/A C N/A N/A F Total Capacity 293.3 295.8 kw 83.4 84.1 Tons 1.008 Sensible Capacity N/A N/A kw N/A N/A Btu/hr Total System Power Input 104.0 108.4 kw 104.0 108.4 kw 1.042 Compressor Power Input 91.3 95.7 kw 91.3 95.7 kw 1.048 Energy Efficiency Ratio 9.6 9.3 W/W Btuh/W 0.967 (EER) Coeff. Of Performance (COP) 2.82 2.73 0.967 Other System Changes 8

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #1 Type of System: Air-Cooled Chiller (e.g., SSHP, window RAC, chiller, etc.) Alternate Refrigerant: ARM-42a (and composition as charged, % weight, if not proprietary) Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Water Water (gas) m ^ 3/min ft 3/min 25.2 25.6 l/s 399 405 gal/min 1.015 10.28 10.33 C 50.5 50.6 F 7.50 7.56 C 45.5 45.6 F Condenser Heat Exchange Air Air (gas), 1580 1580 m ^ 3/min 55800 55800 ft 3/min 1.0 nominal l/s gal/min 35.0 35.2 C 95.0 95.4 F C F Refrigerant Side Data Baseline Alternative Baseline Alternative s & Pressures T (C) P [kpa] T (C) P [kpa] T [F] P T [F] P Compressor Suction 344.7 374.4 50.0 54.3 Compressor Discharge 1435.5 1487.2 208.2 215.7 Condenser Condenser 39.83 1156.9 39.44 1170.0 103.7 167.8 103.0 169.7 Expansion Device Subcooling, at expan. device 5.1 6.1 9.1 11.0 Evaporator Evaporator Evaporator Superheat Data Source(s) for Refrigerant Properties NIST REFPROP for R-134a ARKEMA for ARM-42a Additional Notes 9

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #2 Manufacturer: Johnson Controls Manufacturer s Notation: YVAA Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System ARM-42a POE, ISO-120 R-134a, POE (ISO-120) YVAA Test Chiller 175 Tons, Air-cooled screw chiller Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Cooling Cooling Cooling Compressor Type Compressor Displacement 5.635 5.635 m^3/min 199 199 ft ^3min 1.0 Nominal Motor Size 240 240 hp Nominal Motor Speed 3600 3600 rpm 1.0 Expansion Device Type EEV EEV EEV EEV Lubricant Charge 9.39 9.39 kg 20.7 20.7 lb 1.0 Refrigerant Charge 90.7 86.6 kg 200 191 lb 0.955 Refrigerant Mass Flow kg/min lb/min N/A Rate Composition, at compr. if applicable % wt Ambient In - db N/A N/A C N/A N/A F Temps. door wb N/A N/A C N/A N/A F Out db N/A N/A C N/A N/A F - door wb N/A N/A C N/A N/A F Total Capacity 220.5 221.6 kw 62.7 63.0 Tons 1.005 Sensible Capacity N/A N/A kw N/A N/A Btu/hr N/A Total System Power Input 62.5 63.1 kw 62.5 63.1 kw 1.010 Compressor Power Input 49.4 50.0 kw 49.4 50.0 kw 1.012 Energy Efficiency Ratio 12.1 12.0 W/W Btuh/W 0.994 (EER) Coeff. Of Performance (COP) 3.55 3.52 0.994 Other System Changes 10

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #2 Type of System: Air-Cooled Chiller (e.g., SSHP, window RAC, chiller, etc.) Alternate Refrigerant: ARM-42a (and composition as charged, % weight, if not proprietary) Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Water Water (gas) m ^ 3/min ft 3/min 25.2 25.6 l/s 399 406 gal/min 1.015 9.56 9.72 C 49.2 49.5 F 7.50 7.67 C 45.5 45.8 F Condenser Heat Exchange Air Air (gas), 1580 1580 m ^ 3/min 55800 55800 ft 3/min 1.0 nominal L/min gal/min 26.7 26.7 C 80.0 80.0 F C F Refrigerant Side Data Baseline Alternative Baseline Alternative s & Pressures T (C) P [kpa] T (C) P [kpa] T [F] P T [F] P Compressor Suction 353.0 387.5 51.2 56.2 Compressor Discharge 1023.2 1061.1 148.4 153.9 Condenser Condenser 28.6 871.5 28.3 879.8 83.5 126.4 83.0 127.6 Expansion Device Subcooling, at expan. device 5.8 5.9 10.4 10.6 Evaporator Evaporator Evaporator Superheat Data Source(s) for Refrigerant Properties NIST REFPROP for R-134a ARKEMA for ARM-42a Additional Notes 11

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #3 Manufacturer: Johnson Controls Manufacturer s Notation: YVAA Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System ARM-42a POE, ISO-120 R-134a, POE (ISO-120) YVAA Test Chiller 175 Tons, Air-cooled screw chiller Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Cooling Cooling Cooling Compressor Type Compressor Displacement 3.766 3.511 m^3/min 133 124 ft ^3min 0.938 Nominal Motor Size 240 240 hp Nominal Motor Speed 2400 2250 rpm 0.938 Expansion Device Type EEV EEV EEV EEV Lubricant Charge 9.39 9.39 kg 20.7 20.7 lb 1.0 Refrigerant Charge 90.7 86.6 kg 200 191 lb 0.955 Refrigerant Mass Flow kg/min lb/min N/A Rate Composition, at compr. if applicable % wt Ambient In - db N/A N/A C N/A N/A F Temps. door wb N/A N/A C N/A N/A F Out db N/A N/A C N/A N/A F - door wb N/A N/A C N/A N/A F Total Capacity 148.1 146.0 kw 42.1 41.5 Tons 0.986 Sensible Capacity N/A N/A kw N/A N/A Btu/hr Total System Power Input 37.7 40.0 kw 37.7 40.0 kw 1.061 Compressor Power Input 30.7 26.6 kw 30.7 26.6 kw 0.866 Energy Efficiency Ratio 13.4 12.4 W/W Btuh/W 0.929 (EER) Coeff. Of Performance (COP) 3.93 3.65 0.929 Other System Changes 12

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #3 Type of System: Air-Cooled Chiller (e.g., SSHP, window RAC, chiller, etc.) Alternate Refrigerant: ARM-42a (and composition as charged, % weight, if not proprietary) Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Water Water (gas) m ^ 3/min ft 3/min 25.2 25.5 l/s 399 404 gal/min 1.013 8.94 9.00 C 48.1 48.2 F 7.56 7.67 C 45.6 45.8 F Condenser Heat Exchange Air Air (gas), 790 1580 m ^ 3/min 27900 55800 ft 3/min 2.0 nominal L/min gal/min 18.3 18. C 65.0 65.3 F C F Refrigerant Side Data Baseline Alternative Baseline Alternative s & Pressures T (C) P [kpa] T (C) P [kpa] T [F] P T [F] P Compressor Suction 357.8 391.6 51.9 56.8 Compressor Discharge 858.4 766.0 124.5 111.1 Condenser Condenser 24.0 775.7 19.4 688.1 75.2 112.5 67.0 99.8 Expansion Device Subcooling, at expan. device 6.2 5.7 11.2 10.2 Evaporator Evaporator Evaporator Superheat Data Source(s) for Refrigerant Properties NIST REFPROP for R-134a ARKEMA for ARM-42a Additional Notes The chiller was tested with the chiller controls in automatic mode. Chiller controls turned off some of the fans for the baseline R-134a testing. All the fans were operating for ARM-42a testing. There is room to optimize the performance of the chiller with ARM-42a by adjusting the fan controls. 13

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #4 Manufacturer: Johnson Controls Manufacturer s Notation: YVAA Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System ARM-42a POE, ISO-120 R-134a, POE (ISO-120) YVAA Test Chiller 175 Tons, Air-cooled screw chiller Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Cooling Cooling Cooling Compressor Type Compressor Displacement 2.350 2.492 M^3/min 83 88 ft ^3min 1.060 Nominal Motor Size 240 240 hp Nominal Motor Speed 1500 1590 rpm 1.060 Expansion Device Type EEV EEV EEV EEV Lubricant Charge 9.39 9.39 kg 20.7 20.7 lb 1.0 Refrigerant Charge 90.7 86.6 kg 200 191 lb 0.955 Refrigerant Mass Flow kg/min lb/min N/A Rate Composition, at compr. if applicable % wt Ambient In - db N/A N/A C N/A N/A F Temps. door wb N/A N/A C N/A N/A F Out db N/A N/A C N/A N/A F - door wb N/A N/A C N/A N/A F Total Capacity kw 20.6 21.9 Tons 1.063 Sensible Capacity N/A N/A kw N/A N/A Btu/hr Total System Power Input kw 25.5 27.0 kw 1.059 Compressor Power Input kw 21.4 22.9 kw 1.070 Energy Efficiency Ratio 9.69 9.71 W/W Btuh/W 1.002 (EER) Coeff. Of Performance (COP) Other System Changes 14

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #4 Type of System: Air-Cooled Chiller (e.g., SSHP, window RAC, chiller, etc.) Alternate Refrigerant: ARM-42a (and composition as charged, % weight, if not proprietary) Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Water Water (gas) m ^ 3/min ft 3/min 25.0 25.6 l/s 396 405 gal/min 1.023 8.17 8.22 C 46.7 46.8 F 7.50 7.50 C 45.5 45.5 F Condenser Heat Exchange Air Air (gas), 395 395 m ^ 3/min 13950 13950 ft 3/min 1.0 nominal L/min gal/min 15.4 14.7 C 59.8 58.5 F C F Refrigerant Side Data Baseline Alternative Baseline Alternative s & Pressures T (C) P [kpa] T (C) P [kpa] T [F] P T [F] P Compressor Suction 366.1 395.8 53.1 57.4 Compressor Discharge 930.1 980.4 134.9 142.2 Condenser Condenser 28.2 893.6 29.4 929.4 82.7 129.6 85.0 134.8 Expansion Device Subcooling, at expan. device 7.1 6.9 12.8 12.4 Evaporator Evaporator Evaporator Superheat Data Source(s) for Refrigerant Properties NIST REFPROP for R-134a ARKEMA for ARM-42a Additional Notes The chiller was tested with the controls in automatic mode. Chiller controls turned off some of the fans for this test. Both R-134a and ARM-42a tests had the same number of fans operating for this test condition. Please note that the air inlet temperature during R-134a testing was 1.3 F higher than that during ARM-42a testing Due to limitations of the test facility at the time of these tests, the target air inlet temperature of 55 F corresponding to the 25% load conditions in AHRI 550/590 could not be achieved. 15

Low_GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #5 Manufacturer: Johnson Controls Manufacturer s Notation: YVAA Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System ARM-42a POE, ISO-120 R-134a, POE (ISO-120) YVAA Test Chiller 175 Tons, Air-cooled screw chiller Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Cooling Cooling Cooling Compressor Type Compressor Displacement 7.985 7.985 m^3/min 282 282 ft ^3min 1.0 Nominal Motor Size 240 240 hp Nominal Motor Speed 5100 5100 rpm 1.0 Expansion Device Type EEV EEV EEV EEV Lubricant Charge 9.39 9.39 kg 20.7 20.7 lb 1.0 Refrigerant Charge 90.7 86.6 kg 200 191 lb 0.955 Refrigerant Mass Flow kg/min lb/min N/A Rate Composition, at compr. if applicable % wt Ambient In - db N/A N/A C N/A N/A F Temps. door wb N/A N/A C N/A N/A F Out db N/A N/A C N/A N/A F - door wb N/A N/A C N/A N/A F Total Capacity 247.2 245.1 kw 70.3 69.7 Tons 0.991 Sensible Capacity N/A N/A kw N/A N/A Btu/hr Total System Power Input 127.7 132.1 kw 127.7 132.1 kw 1.034 Compressor Power Input 115.4 119.8 kw 115.4 119.8 kw 1.038 Energy Efficiency Ratio 6.6 6.3 W/W Btuh/W 0.959 (EER) Coeff. Of Performance (COP) 1.94 1.86 Other System Changes 16

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM TEST #5 Type of System: Air-Cooled Chiller (e.g., SSHP, window RAC, chiller, etc.) Alternate Refrigerant: ARM-42a (and composition as charged, % weight, if not proprietary) Air/Water Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Water Water (gas) m ^ 3/min ft 3/min 21.5 21.1 l/s 340 334 gal/min 1.015 10.22 10.22 C 50.4 50.4 F 7.44 7.44 C 45.4 45.4 F Condenser Heat Exchange Air Air (gas), 1580 1580 m ^ 3/min 55800 55800 ft 3/min 1.0 nominal L/min gal/min 48.0 47.8 C 118.4 118.1 F C F Refrigerant Side Data Baseline Alternative Baseline Alternative s & Pressures T (C) P [kpa] T (C) P [kpa] T [F] P T [F] P Compressor Suction 341.3 370.9 49.5 53.8 Compressor Discharge 1858.1 1906.4 269.5 276.5 Condenser Condenser 53.8 1603.7 53.3 1621.6 128.8 232.6 127.9 235.2 Expansion Device Subcooling, at expan. device 4.2 6.2 7.6 11.2 Evaporator Evaporator Evaporator Superheat Data Source(s) for Refrigerant Properties NIST REFPROP for R-134a ARKEMA for ARM-42a Additional Notes 17