Installation Manual. Truck Edition SPECTRUM TM TS Multi-Temperature Systems. TK IM (Rev. 11, 05/15)

Similar documents
Installation Manual. SB Domestic Refrigerated Container (DRC) Unit Single Temperature System. TK IM (Rev.

Trailer Edition Precedent S-600M, C-600M and S-600DE with S-2 and S-3 Remote Evaporator Systems TK IM (Rev. 4, 12/15)

V-220 / V-320 Heater Kits Installation Instructions TK IM (Rev. 0, 06/17)

Installation Manual. Truck Edition SPECTRUM Multi-Temperature Systems T-800R, T-1000R and T-1200R (ESA ONLY) T-1000 (TSA)

SB Domestic Refrigerated Container (DRC) Unit Single Temperature System TK IM (Rev. 2, 02/13)

Installation Manual. Truck Edition UT-1280 Undermount Systems. TK IM (Rev 0, 01/17)

Installation Manual. Truck Edition V-520 RT Series Model 10, 20, 30 and 50 Single Temperature Systems. TK IM (Rev.

Truck Edition V-520 RT Series Models 10, 20, 30 and 50 Single Temperature Systems TK IM (Rev. 8, 1/16)

Installation Manual. Truck Edition V-500 Series. TK IM (Rev. 3, 01/05) Copyright 2004 Thermo King Corp., Minneapolis, MN, U.S.A.

Truck Edition V-220 / V-320 Series Single Temperature Systems TK IM (Rev. 0, 06/17)

Truck Edition V-520 Series Single Temperature and SPECTRUM Multi-Temperature Systems TK IM (Rev. 4, 01/12)

Installation Manual. NAD Truck Edition V-200 and V-300 Series. TK IM (Rev. 7, 02/12)

Truck Edition V-520 Series Single Temperature and SPECTRUM Multi-Temperature Systems TK IM (Rev. 11, 03/18)

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

Installation Manual. TriPac. Auxiliary Heating and Cooling Temperature Management System. TK IM (Rev. 13, 01/12)

1998 Expedition/Navigator Workshop Manual

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

PRELIMINARY INSTALLATION. Operation & Service Manual. Carrier Transicold Europe 03/09/07 Viento - Installation/Rev- #1/56

Climate Control System

Heavy Duty Heater / Air Conditioner Model R-8545

an ISO 9001:2015 Registered Company

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

INSTALLATION, OPERATION, SERVICE & PARTS SUPPLEMENT for

HEATING AND AIR CONDITIONING

BlueHeat AirTop 2000 Heater

Component. Maintenance. Manual Z SERIES. Evaporator Assembly

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

Sleeper Heater and Air Conditioner, Blend Air System 83.05

PME. Series Enclosures. Battery Enclosure (BE) Field Upgrade Installation Instructions. Effective: January, Alpha Technologies

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

1. General Description

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Installation Instructions

INSTALLATION INSTRUCTIONS

IMAGE V. Parts and Service Manual

Installation Instructions

HEATING AND AIR CONDITIONING

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

Heater for BRP Commander. Caution: Before using this product, read this manual and follow all safety instructions. Owner s Manual

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30)

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Installation Instructions

Installation Instructions

Installation Instructions

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

DUAL VOLTAGE ICE BOX CONVERSION SYSTEM 120 VOLTS A.C. & 12/24 VOLTS D.C. MODELS: SCQT-4408F-U1-L SCQT-4408F-U1-I OWNER'S GUIDE

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

SEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL TO THE SEA FROST R-12 ENGINE DRIVE MANUAL INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Camaro A/C Install Instructions

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be

INSTALLATION INSTRUCTIONS

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

Installation Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

WATER PUMP REQUESTED INFORMATION STANDARD PROCEDURE RAM Pickup 6.7L Eng 2500 STANDARD PROCEDURE - COOLANT AIR EVACUATION

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

Engine Block Heater Service Kits (Tank Type) 30RZ/33RZ/45RZ (CSG 649 Ford Powered) Standby Generator Sets

SAN JUAN FRESH WATER COOLING SYSTEMS

Heater with Air Conditioning. E-Series Ford Aeromaster

SEA FROST BD 12 OR 24-VOLT D.C. AIR-COOLED SYSTEM

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

Installation Instructions

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

INSTALLATION INSTRUCTIONS

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

SAVE THESE INSTRUCTIONS

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

Enspeco RMS. The Enspeco Refrigerant Management. The following instructions will INSTRUCTIONS

Installation Instructions

Installation Instructions

Page 1 of 18. Part# /5/2013

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

OPERATION & MAINTENANCE MANUAL TX600

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Installation Instructions Built-In Dishwasher

Installation Instructions

Transcription:

Installation Manual Truck Edition SPECTRUM TM TS Multi-Temperature Systems TK 51580-1-IM (Rev. 11, 05/15)

Installation Manual Truck Edition SPECTRUM TS Multi-Temperature Systems TK 51580-1-IM (Rev. 11, 05/15) Copyright 2002 Thermo King Corp., Minneapolis, MN, U.S.A.

Release History Original (05/02) Rev. 1 (06/02) Revised art and text on pgs. 36, 70, and 88. Rev. 2 (03/03) Revised art on pg. 73 Rev. 3 (06/04) Added new art and text for 3 temp systems Rev. 4 (08/04) Revised selection guide art and text Rev. 5 (02/05) Changed art to show new skin, added printing history Rev. 6 (03/05) Revised SPECTRUM dimensions, ORS fittings locations and terminal strip wire connections. Rev. 7 (08/05) Added new door switch information. Rev. 8 (03/06) Revised S-2 dimensions (art on pgs. 29, 31, 33, 35). Rev. 9 (10/06) Added new fuel pump and bracket and note that the Hose Management Adapter must be installed on every unit. Rev. 10 (02/13) Pages 11, 24, 25, 39 and 41 - Changed art to show revised lifting bar with forged clevis and pins, forged connecting links and forged locking hooks used for lifting the unit. Rev. 11 (05/15) Pages 94-98: Updated door switch installation information and added setup procedures. 2

Installation Manual for SPECTRUM TS Multi-Temperature Systems 3

Introduction This manual was written to assist with the installation of Thermo King SPECTRUM TS Multi-Temperature truck condensing units and SPECTRUM remote evaporators onto truck bodies specifically designed and built for these applications. Due to its complexity, you should not attempt this installation unless you: Are an experienced mechanic. Can safely lift 34 kilos (75 lbs.). Are certified or trained in the repair and maintenance of diesel powered refrigeration systems. Have a basic understanding of electricity and electrical wiring. Have the necessary tools and equipment to complete the installation. This manual is published for informational purposes only. Thermo King makes no representations warranties express or implied, with respect to the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering all contingencies. If further information is required, Thermo King Corporation Service Department should be consulted. Thermo King s warranty shall not apply to any equipment which has been so installed, maintained, repaired or altered as, in the manufacturer s judgment, to affect its integrity. Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect, special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or descriptions contained herein. 4

Table of Contents Safety Precautions.............................................. 6 SPECTRUM TS Multi-Temperature System Selection Guide............ 9 Required Tools................................................ 10 Condensing Unit Installation Components.......................... 12 Evaporator Installation Components............................... 14 Truck Body Opening Dimensions................................. 16 Condensing Unit Dimensions.................................... 18 Service Area Dimensions........................................ 19 Receptacle Box Dimensions..................................... 20 Battery Box Dimensions......................................... 21 HMI (Human Machine Interface) Dimensions........................ 22 Lifting Bar Details............................................... 23 Lifting Bar Dimensions.......................................... 25 S-2 Dimensions................................................ 26 S-2 + S-2 Dimensions........................................... 28 S-3 Dimensions................................................ 30 Important Installation Notes...................................... 32 Uncrating the Condensing Unit................................... 38 Installing the Condensing Unit.................................... 40 Installing the Hose Management Adapter........................... 42 Installing the Fuel Pickup Tube Steel Tank......................... 44 Installing the Fuel Pickup Tube Plastic Tank........................ 46 Installing the Fuel Tank.......................................... 48 Installing the Fuel Pump......................................... 50 Installing the Power Receptacle Box International Models............ 52 Installing the Power Receptacle Box North American Models......... 54 Installing the HMI.............................................. 56 Installing the Battery Box........................................ 58 Battery Connections............................................ 60 Installing Covers and Screens.................................... 62 Removing Holding Charge....................................... 66 Installation S-2 or S-3........................................... 68 Condensing Unit Tube Connections S-2 or S-3...................... 70 Evaporator Tube Connections S-2 or S-3........................... 72 Wire Connections S-2........................................... 74 Wire Connections S-3........................................... 76 Condensing Unit Tube Connections (2) S-2 + S-2.................... 78 Evaporator Tube Connections (2) S-2 + S-2......................... 80 Wiring Connections S-2 + S-2.................................... 82 Condensing Unit Tube Connections 3 Temperature Systems.......... 84 Evaporator Tube Connections 3 Temperature Systems............... 86 Wiring Connections 3 Temperature Systems....................... 88 Drain Hose Installation.......................................... 90 Drain Hose Resistance Wire Installation Guide...................... 92 Installing the Door Switch (OPTION)............................... 94 Door Switch Setup Procedures (OPTION).......................... 98 Sensor Calibration Procedures.................................. 100 System Leak Check........................................... 102 System Evacuation............................................ 104 System Charging............................................. 106 Installing Covers.............................................. 108 System Check List............................................ 110 5

Safety Precautions Caution Thermo King Multi-Temp SPECTRUM TS condensing units are shipped with a 35-69 kpa (5-10 psi) holding charge of nitrogen. This holding charge may be safely vented into the atmosphere. IMPORTANT: Do not release the holding charge until necessary to prevent moisture from entering the system. SPECTRUM S-2 and S-3 remote evaporators are shipped with a 35-69 kpa (5-10 psi) holding charge of nitrogen. This holding charge may be safely vented into the atmosphere. SEVERE COMPRESSOR DAMAGE will result from operating the engine/motor before completing the system installation which includes: installing the components, releasing the condensing unit holding charge, releasing the remote unit holding charge, soldering the refrigeration lines, leak testing the system, evacuation and clean-up, and charging the system. Recover Refrigerant At Thermo King, we recognize the need to preserve the environment and limit the potential harm to the ozone layer that can result from allowing refrigerant to escape into the atmosphere. We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the atmosphere. 6

Safety Precautions The symbol appears next to a point that is particularly important: DANGER: Addresses a circumstance that, if encountered, will lead to death or serious injury. WARNING: Addresses a circumstance that, if encountered, might lead to death or serious injury. CAUTION: Addresses a circumstance that, if encountered, may cause damage to equipment or minor injury. DANGER: Never operate the unit with the discharge valve closed because it could cause the compressor to explode, causing death or serious injury. DANGER: Never apply heat to a sealed refrigeration system or container because it could explode, causing death or serious injury. DANGER: Fluorocarbon refrigerants, in the presence of an open flame or electrical short, produce toxic gases that are severe respiratory irritants capable of causing death. DANGER: Be careful when working with a refrigerant or refrigeration system in any enclosed or confined area with a limited air supply (i.e., a trailer, container or the hold of a ship). Refrigerant tends to displace air and can cause oxygen depletion which may result in death by suffocation. WARNING: Always wear goggles or safety glasses. Refrigerant liquid, refrigeration oil, and battery acid can permanently damage the eyes (see First Aid under Refrigeration Oil). WARNING: Keep your hands away from fans and belts when the unit is running. This should also be considered when opening and closing the compressor service valves. WARNING: Make sure gauge manifold hoses are in good condition. Never let them come in contact with a belt, fan motor pulley, or any hot surface. WARNING: Make sure all mounting bolts are tight and are of correct length for their particular application. WARNING: When using ladders to install or service refrigeration systems, always observe the ladder manufacturer s safety labels and warnings. A work platform is the recommended method for installations. 7

Safety Precautions WARNING: Never drill holes in the unit unless absolutely necessary. Holes drilled into the unit may weaken structural components. Holes drilled into electrical wiring can cause fire or explosion. WARNING: Exposed coil fins are very sharp and can cause painful lacerations. WARNING: Regulators used on bottles of nitrogen gas must be equipped with relief valves. The pressure in a bottle of nitrogen gas is extremely high. It is high enough to cause components of the refrigeration system to explode if the regulator malfunctions or is set wrong. The relief valve provides a safe outlet in case the regulated pressure exceeds the relief valve limit. CAUTION: Remove the nitrogen holding charge from the condensing unit and remote evaporators prior to making any refrigeration tubing connections to prevent personal injury! Refrigerant WARNING: Although fluorocarbon refrigerants are classified as safe refrigerants, certain precautions must be observed when handling them or servicing a unit in which they are used. When released to the atmosphere in the liquid state, fluorocarbon refrigerants evaporate rapidly, freezing anything they contact. First Aid FROSTBITE: In the event of frost bite, the objectives of First Aid are to protect the frozen area from further injury, to warm the affected area rapidly and to maintain respiration. EYES: For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical attention. SKIN: Flush area with large amounts of lukewarm water. Do not apply heat. Remove contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from infection/injury. Get medical attention. Wash contaminated clothing before reuse. INHALATION: Move victim to fresh air and use CPR or mouth-to-mouth ventilation, if necessary. Stay with victim until arrival of emergency medical personnel. Refrigeration Oil WARNING: Avoid refrigeration oil contact with the eyes. Avoid prolonged or repeated contact of refrigeration oil with skin or clothing. Wash thoroughly after handling refrigeration oil to prevent irritation. First Aid In case of eye contact, immediately flush with plenty of water for at least 15 minutes. CALL A PHYSICIAN. Wash skin with soap and water. 8

SPECTRUM TS Multi-Temperature System Selection Guide Truck S-2 evaporators 919975 included mounting hardware kits 819951 Truck S-3 evaporators 919976 included mounting hardware kits 819951 Installation Configurations Fig. Zone 1 Zone 2 Zone 3 Evap Hardware Kit Tubes Kit OPTION Drain Kit OPTION Electric Hardware Kit Jumper Kit OPTION Evap Harness Zone 3 Install Kit Door Switch 2 Temp Door Switch 3 Temp DAS NAD DAS EEC DAS EEC Zone 3 919975 919976 919975 919976 919975 STD 720201 880041 STD 880040 STD 088089 700533 700534 088781 088782 088082 A S-3 S-3 --- STD 1 2 STD --- STD --- 1 --- 1 1 --- B S-2 S-3 --- STD 1 2 STD --- STD --- 1 --- 1 1 --- C S-2 + S-2 S-2 --- STD 1 2 STD 1 STD --- 1 --- 1 1 --- D* S-3 S-2 --- STD --- 2 STD --- STD --- 1 --- 1 1 --- E* S-3 S-3-* --- STD --- 4 STD --- STD --- 1 --- 1 1 --- F* S-2 S-2 S-2 STD --- 2 STD --- STD 1 --- 1 1 1 1 G S-2 S-2 S-2 STD 1 4 STD --- STD 1 --- 1 1 1 1 H S-2 S-2 S-2 STD 1 4 STD --- STD 1 --- 1 1 1 1 NOTES: 1. STD = Parts are being supplied with either the condensing unit or evaporator kits. 2. Drain kit 880041 is needed to drain on one side toward the front or back of the truck. 3. Tubes kit 720201 will be supplied per customer request only - No kit will be supplied. 4. Quantities specified are for entire truck. 5. Evaporators can be placed at the back of each zone, however this may require different refrigerant and drain tube routing. * = Configurations that will need at least 1 Tube Kit if the evaporators are mounted in the back of the zone. 9

Required Tools 1. Safety Glasses 2. Drill 3. Drill Bits 4. Tape Measure 5. Wire Crimpers 6. Tube Benders 7. Hole Saw 8. 15% Solder & Flux (copper to copper) 9. 35% Solder & Flux (copper to brass) 10. Swage 11. Tubing Cutter 12. Refrigerant Oil 13. Torch Set 14. Mechanics Tools 15. Manifold Set 16. Evacuation Station 17. Reclaiming Station 18. Refrigerant & Scale 19. Dry Nitrogen 20. Tap and Die Set 21. Battery Charger 22. Electronic Leak Detector 23. Tubing Brushes 24. Scotch Brite Pads 25. 3 Point Lifting Fixture with forged clevis and pins, forged connecting links and forged locking hooks. 26. Work Platform (Recommended) 27. Torque Wrench 28. Mechanical Lift 10

Required Tools 11

Condensing Unit Installation Components 1. T-Bolts (International Models Only) 2. Unit Washer 1.250 x 0.188 THK 3. Locking Nuts 4. Clamps 5. Self Tapping Screws 6. Exhaust Tube 7. Terminal Rings 8. Cable Ties 9. Fuel Pump Bracket 10. Screws 11. Washers 12. Locking Nuts 13. Fuel Pump Pickup Tube 14. Fuel Line Fittings 15. Fuel Pump Elbows 16. Blind Nut 17. Fuel Pump 18. Battery Cable Lug 19. Hold Down Clamps 20. HMI (Human Machine Interface) 21. DIN Mount (ISO 7736) 22. Fuse Holder 23. Hose Management Adapter 24. Adapter Hold Down Clamps 12

Condensing Unit Installation Components 13

Evaporator Installation Components 1. Clamps 2. Screws 3. Pre-Bent Tubes 4. Copper Tees 5. Copper Couplings 6. Tube Insulation 7. Refrigerant Tubing (U. S. Only) 8. Drain Hose 9. Copper Elbows 10. Drain Hose Tee 11. Mounting Spacer 12. Terminal Fork 13. Terminal Ring 14. Cable Ties 15. Jumper Strip 16. Check Valve 17. Electrical Harnesses 18. Reducing Tee 14

Evaporator Installation Components 15

Truck Body Opening Dimensions CAUTION: The truck wall must be structurally strong enough to support the weight of the refrigeration unit. SPECTRUM TS 30 = 387 kg (853 lbs.) SPECTRUM TS 50 = 446 kg (984 lbs.) 1. All unit electrical connections are to be made from the condensing unit through this access area. NOTE: Unit mounting location must allow for adequate tilt clearance (see Condensing Unit Dimensions). 2. Gasket sealing surface of 64 mm (2.50 in.) wide is required around both openings. The surface must be flat within 6.4 mm (0.25 in.) for proper gasket sealing and free of all rivets or bolt heads. 16

Truck Body Opening Dimensions 17

Condensing Unit Dimensions 18

Service Area Dimensions 19

Receptacle Box Dimensions 20

Battery Box Dimensions 21

HMI (Human Machine Interface) Dimensions 22

Lifting Bar Details WARNING: Thermo King requires a 3 point lifting bar to safely lift and install units. A lifting bar can be made from the drawings provided. WARNING: All hardware used to assemble the lifting bar must be DIN 931 class 10.9 (SAE Grade 8). The use of hardware other than specified may cause personal injury, severe damage to the equipment and void the warranty. WARNING: Use forged clevis and pins, forged chain links and forged locking hooks with strength equal to total lift capacity of hoist mechanism and that meet all safety standards. 23

Lifting Bar Details D 8 7 6 5 4 3 2 1 UNIT TYPE FRONT CHAIN LIFT HOLE LOCATION ENTIRE UNIT CLEVIS LIFTING HOLE LOCATION TS 200/300/500/600-30 LEFT HOLE 1 TS 200/300/500/600-50 LEFT HOLE 2 SPECTRUM TS LEFT HOLE 4 MD II, MD 200, MD 300-30 RIGHT HOLE 1 MD II, MD 200, MD 300-50 RIGHT HOLE 2 KD II - 30 RIGHT HOLE 1 KD II - 50 RIGHT HOLE 2 RD II - 30 RIGHT HOLE 1 RD II - 50 RIGHT HOLE 2 T SERIES - 30/50 LEFT HOLE 3 T SERIES SPECTRUM LEFT HOLE 5 RELEASED 14/Jan/2013 REVISIONS CHANGE ORDER REV DESCRIPTION DATE APPROVED MOVED LIFTING HOLES ALONG REAR BAR, ADDED BRIDGING BAR FOR SPECTRUM TS 529536 F 18-Jun-08 M GILMAN LIFTING POINT. ADDED WELD SYMBOLS, RE-LABLED ALL LIFTING POINTS ADDED LIFTING HOLES FOR NEW UNITS, 532334 G 25-Mar-09 M GILMAN ADDED BRIDGING BAR FOR MULTI-TEMPS. DIM 17.22 WAS 16.42. DIM 11.12 WAS 539147 H 20-Jan-10 E KIRBY 10.42. ADDED TSERIES SPECTRUM VIEW CHG DRAWING AND VIEWS, MOVED HOLES 1-6, 543699 I 14-Jun-10 M GILMAN ADDED TABLE FOR ALL TRUCK UNITS. REMOVED CHAINS, BOLTS FROM VIEW SHT 1, 665985 J 27-NOV-12 J.DAVIES DEL NOTE 2. D C ENTIRE UNIT CLEVIS LIFTING HOLES (1-5) C 4 1 2 3 5 B B A NOTES: 2. USE TWO CHAIN LINKS WITH A CHAIN LINK MASTER AS SHOWN. 3. USE THREE FORGED CLEVIS AND PINS TO ATTACH LIFTING CHAINS. 4. EACH ASSEMBLY MUST HAVE STRENGTH EQUAL TO MINIMUM OF 1.5 TIMES THE WEIGHT OF THE HOIST AND MEET ALL SAFETY STANDARDS. CAD GENERATED DRAWING, INGERSOLL-RAND IS THE SOLE OWNER OF THIS UNLESS OTHERWISE SPECIFIED DO NOT MANUALLY UPDATE DRAWING AND ALL INFORMATION IN IT, WHICH ARE DIMENSIONS ARE IN INCHES. UNLESS OTHERWISE SPECIFIED TOLERANCES PROTECTED BY COPYRIGHT AND OTHER LAWS AND MAY INTERPRET DIM AND TOL PER ON DIMENSIONS PER TKS09109 BE SUBJECT TO LAWS REGARDING EXPORTING ASME Y14.5M - 1994 INFORMATION OUTSIDE OF THE U.S. THIS DRAWING DRAWN DATE MAY BE USED ONLY BY ITS RECIPIENTS FOR THE PURPOSE FOR WHICH IT IS PROVIDED AND ONLY BY THIRD ANGLE PROJECTION JO 1/20/88 THE RECIPIENT, WHO AGREES THAT IT WILL NOT, CHECKED WITHOUT INGERSOLL-RAND'S PRIOR WRITTEN PERMISSION: 1) DISCLOSE NOR USE THIS DRAWING TB 6/15/90 OR THE INFORMATION IN IT EXCEPT AS SPECIFIED ABOVE; OR 2) MAKE ANY COPIES OF OR EXTRACTS, APPROVED REVISIONS, OR UPDATES FROM THE DRAWING. ALL COPIES MUST BE RETURNED TO INGERSOLL-RAND RL 6/15/90 UPON COMPLETION OF THE WORK FOR WHICH THEY HAVE BEEN PROVIDED OR UPON ANY EARLIER FINISH ENG APPVL REQUEST. - - - CODE IDENT NO SIZE DWG NO REV D J SCALE 0.250 SHEET 1 OF 2 8 7 6 5 4 3 2 1 TITLE Thermo King DIAGRAM-LIFTING BAR ASS'Y FOR SELF-POWERED LARGE TRUCK 9127C30 A 24

Lifting Bar Dimensions 8 7 6 5 4 3 2 1 54.2 27.1 D 2X 58 3.5 25.1 3.5 D.50 THICK 7.9 2X 58 4.0.534 4.0 1.75 2.1 2.1.534.50 THICK 2X 3.4 C I I I 50.20 28.70 26.60 23.50 2X 58 (30.3) 2X.8 4X.534 C R1.25 11.2 I 3.5 1.75 17.2 I 31.7 4.0 1.75 (1.6) 2X.75 2X.75 I 3X.875 SCALE 0.250 REAR MEMBER 3.5 1.75 1.75 1.75 (1.4) B 1.0 1.0 SCALE 0.250 CENTER MEMBER B 5.0 21.1 5.0 8.85 21.1 (2X 122 ) 8.85 FRONT MEMBER 11.45 11.45 CENTER MEMBER REAR MEMBER 2X 4X.534 23.6 4X.534 2X 7.5 2.4 A SCALE 0.150 WELDING DETAIL A 2X.75 1.75 SCALE 0.250 FRONT MEMBER SIZE CODE IDENT NO DWG NO REV 8 7 6 5 4 3 2 1 D SCALE 0.250 9127C30 J SHEET 2 OF 2 25

S-2 Dimensions All mounting locations must be correct to properly install evaporators. IMPORTANT: Mount all evaporators as close to one side wall as possible to minimize drain tube length and reduce exposure to damage. The minimum distance 600 mm (24.00 in.) from the bulkhead to the front of the evaporator must be maintained for proper operation. A, B, C, D, E, and F indicate locations of ORS fittings measured from trailer ceiling and from edge of Spectrum evaporator. NOTE: A). 50 mm (2.00 in.) is approximate spacing between evaporator and truck side wall for 2590.8 mm (102.00 in.) wide truck with 376.2 mm (3.00 in.) walls. A narrow 2438 mm (96.00 in.) wide truck will allow only 25.4 mm (1.00 in.) spacing depending upon wall thickness. B). Allow 50.8-101.6 mm (2.00-4.00 in.) space between the back of the evaporator to the truck wall. The information above is only relevant to an application where an S-2 is used in one lane and an S-2 + S-2 is used in the adjacent lane. 26

S-2 Dimensions WEIGHT = 43 kg (95 lb.) Reference: 1E02132 Sheet 1 27

S-2 + S-2 Dimensions All mounting locations must be correct to properly install evaporators. IMPORTANT: Mount all evaporators as close to one side wall as possible to minimize drain tube length and reduce exposure to damage. The minimum distance 609.6 mm (24.00 in.) from the bulkhead to the front of the evaporator must be maintained for proper operation. A, B, C, D, E, and F indicate locations of ORS fittings measured from trailer ceiling and from edge of Spectrum evaporator. NOTE: A). 50 mm (2.00 in.) is approximate spacing between evaporator and truck side wall for 2590.8 mm (102.00 in.) wide truck with 376.2 mm (3.00 in.) walls. A narrow 2438 mm (96.00 in.) wide truck will allow only 25.4 mm (1.00 in.) spacing depending upon wall thickness. B). Allow 50.8-101.6 mm (2.00-4.00 in.) space between the back of the evaporator to the truck wall. The information above is only relevant to an application where an S-2 is used in one lane and an S-2 + S-2 is used in the adjacent lane. 28

S-2 + S-2 Dimensions Reference: 1E02132 Sheet 3 29

S-3 Dimensions All mounting locations must be correct to properly install evaporators. IMPORTANT: Mount all evaporators as close to one side wall as possible to minimize drain tube length and reduce exposure to damage. The minimum distance 600 mm (24.00 in.) from the bulkhead to the front of the evaporator must be maintained for proper operation. A, B, C, D, E, and F indicate locations of ORS fittings measured from trailer ceiling and from edge of Spectrum evaporator. NOTE: A). 50 mm (2.00 in.) is approximate spacing between evaporator and truck side wall for 2590.8 mm (102.00 in.) wide truck with 376.2 mm (3.00 in.) walls. A narrow 2438 mm (96.00 in.) wide truck will allow only 25.4 mm (1.00 in.) spacing depending upon wall thickness. B). Allow 50.8-101.6 mm (2.00-4.00 in.) space between the back of the evaporator to the truck wall. The information above is only relevant to an application where an S-3 is used in one lane and another S-3 is used in the adjacent lane. 30

S-3 Dimensions WEIGHT = 52 kg (115 lb.) Reference: 1E02132 Sheet 2 31

Important Installation Notes Safety Precautions See Safety Precautions on pages 6-8 prior to installing and servicing this product. Evaporator Location The best airflow is achieved when the evaporator is installed an equal distance from each side wall. It is recommended that moving bulkheads not be allowed closer than 1219 mm (48.00 in.) or 1 pallet from the evaporator outlet (Detail A). The minimum clearance from the bottom of the evaporator to the top of the cargo should be 101 mm (4.00 in.) (Detail A). NOTE: This minimum clearance is required under the fan intake area only and does not refer to the LOAD LINE. The evaporator should be located a minimum of 51 mm (2.00 in.) from the truck wall (Detail B). Defrost Drains The evaporator must be properly mounted to provide a slope towards the drain. This is accomplished by adding one 3/8 in. and one 3/16 in. washers on the drain side and only one 3/8 in. washer on the other side at each mounting surface. Defrost drains must exit the evaporator at a 45 angle. Drains should be 267 mm (10.50 in.) from the evaporator to the truck ceiling (Detail C). Wall Drain Tube CPVC 1.00 in. ID (Internal Diameter) Refrigerant Tubing and Electrical Wiring It is important to minimize the amount of time the tubes are uncapped and open to ambient conditions. Always keep tubes capped until ready to connect and solder. Check tubes and copper fittings for obstructions prior to assembly. It is also required that nitrogen or another inert gas be used to purge the tubes while soldering. This prevents oxidation and formation of scale inside tubes. Use 35% silver solder for joining all remote refrigerant tubes. Insulate suction and hot gas lines. All refrigeration tubes should be secured by clamps every 600 mm (24.00 in.). All electrical harness should be secured by clamps or tie bands every 600 mm (24.00 in.). Only one trough (W = Wall and C = Ceiling) is required (Detail D & E). All dual evaporator installations require two suction tubes. Door Switches Door switches automatically turn off remote evaporators when the corresponding door is opened. This avoids the entry of warm, moist air into the load space. Door switches are recommended for all multi-temp installations. Door Curtains It is always recommended to use good quality insulated curtains on all doors to limit the amount of warm, moist air from entering the load space during door openings. 32

Important Installation Notes 33

Important Installation Notes Defrost Drain Tube Connectors IMPORTANT: Follow the instructions below to prevent defrost drain tube water leaks. All Spectrum remote evaporators are equipped with a quick disconnect fitting that connects the drain pan to the drain tubes (Detail I). To properly install the tube make sure that the tube is fully inserted past the O-ring and up to the stop inside the coupler (Detail II). NOTE: The fitting will grip the tube before it seals with the o-ring. When the tube is in the correct position the O-ring will seal and the teeth will grip the tube keeping it in place. Check the fit by pulling on the tube(s) to insure that it will not pull out of the fitting (Detail III). To disconnect the tube from the fitting: press the collet into the fitting. Hold the collect in place and pull the tube out. The fitting can be re-used. Clean any burrs off the tube before re-inserting it into the fitting (Detail IV). 34

Important Installation Notes 35

Important Installation Notes 36

Important Installation Notes 37

Uncrating the Condensing Unit WARNING: Thermo King requires a 3 point lifting bar to safely lift and install units. A lifting bar can be made from the drawings provided WARNING: Use forged clevis and pins, forged chain links and forged locking hooks with strength equal to total lift capacity of hoist mechanism and that meet all safety standards. WARNING: Eyebolts must be forged steel and minimum M12 (1/2 in.) diameter. WARNING: Use only locking lifting hooks to attach to the lifting eyebolts (Detail A). The point shown in Detail B, below, is not a major lifting point. It is used only to level the unit during installation (Detail B). 1. Remove the top cover and top screen (if equipped) 2. Install two lifting eyebolts into the lifting holes at the rear frame rails, install nuts, and tighten securely. 3. Attach the 3 point lifting bar securely to the eyebolts and balance point and slightly raise the unit. 4. Remove the base of the crate by removing the eight skid bracket screws (Detail C). 5. Remove the two rear members of the crate and lift unit up from base approximately 304.8 mm (12.0 in.) (Detail C). 6. Remove the two bottom access panels from the unit. 7. Remove the four mounting bolts securing the two upright members to the unit (Detail C). Unit is now ready to install. 38

Uncrating the Condensing Unit 39

Installing the Condensing Unit WARNING: Thermo King requires a 3 point lifting bar to safely lift and install units. A lifting bar can be made from the drawings provided (See Lifting Bar Dimensions). WARNING: Use forged clevis and pins, forged chain links and forged locking hooks with strength equal to total lift capacity of hoist mechanism and that meet all safety standards. WARNING: Use only locking lifting hooks to attach to the lifting eyebolts (Detail A). 3. The four 4.8 mm (0.188 in.) mounting washers provided must be used between the frame of the unit and the locking nut holding the unit to the front wall of the truck. 4. Torque mounting hardware to 81.4 N m (60 ft-lb.) IMPORTANT: After completing the installation of the unit, be sure to add insulating foam around the opening where the Suction, Liquid and Hot Gas tubes run through the truck box wall and into the cargo area. This must be done to prevent water, heat, or debris from entering into the truck box and to allow the unit to function properly. WARNING: The use of a safe working platform for truck unit installations is recommended. 1. Use a 3 point lifting bar to carefully lift the unit up to the truck opening. 2. Install four M12 (1/2-13 in. Grade 5) mounting bolts through the wall of the truck box. NOTE: The mounting bolts should protrude 63.5 mm (2.50 in.) full thread from the front wall (Detail B). IMPORTANT: Do not install any compressible washers or other materials between the unit and the truck! 40

Installing the Condensing Unit 41

Installing the Hose Management Adapter IMPORTANT: The Hose Management Adapter must be installed to help prevent moisture from entering the control box. 1. The hose management adapter provides a exit point under the unit for the fuel lines, battery cables and drain hoses while also helping prevent moisture from entering the control box. Locate the small square holes (two each side) in the rear frame channel under the unit. Slide the hose management adapter onto the rear frame channel. The two end tabs should grip the frame channel while the two center tabs lock into the matching square holes of the frame. 2. Secure the hose management adapter to the truck cargo box with the two hold down clamps and screws. NOTE: If Hose Management Kit (719180 or 719184) is used, follow installation instructions supplied with kit. 42

Installing the Hose Management Adapter 43

Installing the Fuel Pickup Tube Steel Tank 1. Tape the paper template (supplied with pickup tube) to the desired location on the diesel fuel tank and center punch the three holes. NOTE: Use a magnet, grease or special hole saws/drills that will minimize steel chips from entering the fuel tank. Thoroughly clean and flush the tank to remove any chips. 2. Drill: DANGER: Diesel fuel vapors are potentially explosive. Use extreme caution when drilling in or around the diesel fuel tank. Sparks from an electric drill or drill bit could cause an explosion. Do not smoke while working near the diesel fuel tank. Drain all diesel fuel from the tank and use nitrogen or an inert gas to purge the diesel fuel vapors from the tank prior to drilling. Keep the diesel tank filled with inert gas while drilling. 9.5 mm (0.375 in.) diameter holes first. 31.8 mm (1.250 in.) diameter hole next. Remove the template from the tank and remove any burrs from the hole. 3. Cut the end of the pickup tube so approximately 25 mm (1.00 in.) is above the bottom of the fuel tank. 4. Loosen the nut and slide all the parts to the top of the pickup tube assembly. 5. Hold the parts in position and slide the assembly into the hole at a slight angle until the bushing is inside the hole. 6. Tip the backup washer and slide it through the hole and position it onto the bushing. Thread the nut onto the bushing, position as needed to facilitate fuel line connections and tighten to 54 Nm. (40 ft-lb.). 44

Installing the Fuel Pickup Tube Steel Tank 45

Installing the Fuel Pickup Tube Plastic Tank 1. Tape the paper template (supplied with pickup tube) to the desired location on the diesel fuel tank and center punch the three holes. NOTE: Use grease or special hole saws/drills that will minimize plastic chips from entering the fuel tank Thoroughly clean and flush the tank to remove any chips. 2. Drill: DANGER: Diesel fuel vapors are potentially explosive. Use extreme caution when drilling in or around the diesel fuel tank. Sparks from an electric drill or drill bit could cause an explosion. Do not smoke while working near the diesel fuel tank. Drain all diesel fuel from the tank and use nitrogen or an inert gas to purge the diesel fuel vapors from the tank prior to drilling. Keep the diesel tank filled with inert gas while drilling. 9.5 mm (0.375 in.) diameter holes first. 31.8 mm (1.250 in.) diameter hole next. Remove the template from the tank and remove any burrs from the hole. 3. Cut the end of the pickup tube so approximately 25 mm (1.00 in.) is above the bottom of the fuel tank. 4. Loosen the nut and slide all the parts to the top of the pickup tube assembly. 5. Hold the parts in position and slide the assembly into the hole at a slight angle until the bushing is inside the hole. 6. Tip the backup washer and slide it through the hole and position it onto the bushing. Thread the nut onto the bushing, position as needed to facilitate fuel line connections and tighten to 54 Nm. (40 ft-lb.). 46

Installing the Fuel Pickup Tube Plastic Tank 47

Installing the Fuel Tank DANGER: An improperly installed fuel tank could lead to serious injury or death! Consult your chassis manufacturer for specific details on proper fuel tank installation and recommendations. 48

Installing the Fuel Tank 49

Installing the Fuel Pump DANGER: Leaking fuel lines could cause a fire resulting in death or serious injury! All fuel line fittings must be tight and leak free! DANGER: Do not route fuel lines with battery cables or electrical wires, as this could cause a fire! S=Supply R=Return 1. The fuel pump must be installed as close to the fuel tank as possible and not more than 762 mm (30.0 in.) above the fuel in the fuel tank. 2. Fuel lines should be routed in a protective housing with no kinks or sharp bends. NOTE: Do not connect unit fuel lines into truck/trailer fuel lines. 3. Rubber grommets must be used when routing fuel lines through metal. 4. Secure all fuel lines with provided clamps. 5. Route fuel line from fuel pump INLET fitting to fuel tank pickup SUPPLY fitting. 6. Route fuel line from fuel pump OUTLET fitting to diesel engine SUPPLY fitting. 7. Route fuel RETURN line from diesel engine to fuel tank pickup RETURN fitting. 50

Installing the Fuel Pump 51

Installing the Power Receptacle Box International Models DANGER: To prevent serious injury or death, the electric standby power cord must not be connected to the unit during installation! Choose an appropriate location for the Power Receptacle Box. Front Mount 1. Remove cover. 2. Measure and drill four appropriate size holes into truck body. 3. Insert rubber blind nuts into hole in truck body. 4. Install base and fasten with appropriate hardware. Reinstall cover. 5. Route and secure harness with supplied clamps. 52

Installing the Power Receptacle Box International Models 53

Installing the Power Receptacle Box North American Models DANGER: To prevent serious injury or death, the electric standby power cord must not be connected to the unit during installation! Choose an appropriate location for the Power Receptacle Box. Front Mount (Detail A) 1. Remove cover. 2. Measure and drill two appropriate size holes into truck body. 3. Insert rubber blind nuts into hole in truck body. 4. Install base and fasten with appropriate hardware. Reinstall cover. 5. Route and secure harness with supplied clamps. Side Mount (Detail B) 6. Remove cover. 7. Remove two hole plugs from base. Measure and drill two appropriate size holes into truck body. 8. Insert rubber blind nuts into hole in truck body. 9. Install base and fasten with appropriate hardware. Install hole plugs into unused mounting holes and reinstall cover. 10. Route and secure harness with supplied clamps. 54

Installing the Power Receptacle Box North American Models 55

Installing the HMI NOTE: Route and secure harness to prevent rubbing, chafing or making contact with sharp, moving or hot components. Allow excess harness for tilt cab applications. Rubber grommets must be used when routing harness through sheet metal holes. Driver Panel DIN Mounting Choose an appropriate location for the HMI inside the truck cab. 1. Install DIN (ISO 7736) mounting sleeve into driver panel DIN opening. 2. Bend tabs to secure in position. 3. Connect harness and install HMI into DIN sleeve. 56

Installing the HMI 57

Installing the Battery Box CAUTION: Battery boxes must be installed securely with proper hardware to prevent them from falling off. CAUTION: Battery cables must be properly routed and secure to prevent rubbing, chafing or making contact with sharp, moving or hot components. 1. Secure battery in place with hold down bracket and rod. 2. Rubber grommets must be used where cables exit box. 3. Protective cover will be installed at a later step. 58

Installing the Battery Box 59

Battery Connections CAUTION: All battery connections and electrical wires must be properly routed and secured to prevent rubbing, chafing or making contact with sharp, moving or hot components. Do not route battery cables together with fuel lines. CAUTION: All electrical connections must be clean and tightly secured. CAUTION: Set all electrical controls to the OFF position to prevent the unit from starting. Although the unit comes pre-wired from the factory, wire connections at the battery are required (Detail A). Unroll the harness bundle from the unit. Positive Cable 1. At the unit, locate the large black cable marked POS+. Route this cable to the battery, cut to the proper length and add battery cable lug from installation kit. Connect to POSITIVE terminal of battery (Detail B). Unit Control Power Wire 2. At the unit, locate the large 8 AWG (#2) wire. Route this wire to the battery, cut to the proper length and add fuse holder assembly. Use battery cable crimper to securely crimp 8 AWG (#2) wire and fuse holder together and heat shrink the connection. Apply a liberal amount of Superlube to the 60 amp fuse and fuse holder and then install fuse. Connect the fuse holder terminal to the POSITIVE terminal of battery (Detail B). Fuel Pump Harness 3. Locate and route the Fuel Pump harness to the fuel pump and connect to matching connector at the pump. Negative Cable 4. At the unit, locate the large black battery cable marked NEG -. Route this cable to the battery, cut to the proper length and add battery lug from installation kit. Connect to the NEGATIVE terminal of battery (Detail C). 5. Route and secure all harnesses and battery cables with provided clamps. 60

Battery Connections 61

Installing Covers and Screens CAUTION: All covers, guards and screens must be securely in place to prevent personal injury or damage to equipment. Condensing Unit 1. Reinstall top cover and top screen (if equipped). 2. Confirm Hose Management Adapter is installed. 3. Reinstall bottom panels. 4. Install exhaust pipe. 5. Install battery cover. 62

Installing Covers and Screens 63

BLANK PAGE 64

STOP! Caution SEVERE COMPRESSOR DAMAGE will result from operating the engine/motor before completing the system installation which includes: installing the components, releasing the condensing unit holding charge, releasing the remote evaporator holding charge, soldering the refrigeration lines, leak testing the system, evacuation and clean-up, and charging the system. 65

Removing Holding Charge CAUTION: Thermo King Multi-Temp SPECTRUM TS condensing units are shipped with a 35 kpa (5 psi) holding charge of nitrogen. This holding charge may be vented into the atmosphere. CAUTION: Thermo King SPECTRUM evaporators are shipped with a 35 kpa (5 psi) holding charge of nitrogen. This holding charge may be vented into the atmosphere. CAUTION: Holding charges must be removed before opening system to avoid serious injury. HG = Hot Gas S = Suction L = Liquid SPECTRUM Condensing Unit To release nitrogen holding charge, slowly remove ORS caps from hot gas, liquid and suction lines. SPECTRUM Evaporator To release nitrogen holding charge, slowly remove ORS caps from hot gas, liquid and suction lines. 66

Removing Holding Charge 67

Installation S-2 or S-3 Ceiling Preparation IMPORTANT: The ceiling must be flat and the mounting locations correct for proper SPECTRUM evaporator installation. The foam insulation in the ceiling must be removed from the evaporator mounting area and aluminium spacers must be installed between the evaporator mounting plate and trailer ceiling. For ceiling mounting stud applications, weld a nut (same thread as stud) onto a 44.45 mm (1.75 in.) hole saw and turn the nut onto the mounting stud using a socket wrench (Detail A). For ceiling mounting bolt applications, weld a bolt (same thread as tapped hole) onto a 44.45 mm (1.75 in.) hole saw and turn into the tapped mounting hole using a socket wrench (Detail A). Alternative method is to remove the mounting studs or bolts and use a hole saw with a standard pilot drill small enough to run up into the threaded hole without damaging the threads. Reinstall mounting studs or bolts. Mounting Stud or Bolt Requirements The mounting studs or bolts used to attach the evaporator(s) to the ceiling must be 10.0 mm, (0.50 in., Grade 5, U.S. applications only), Medium Carbon Steel, 120000 PSI Tensile Strength, Zinc Plate and Dichromate finish. Studs to extend below ceiling 38.0 mm (1.50 in.) to 50.1 mm (2.00 in.) Evaporator Installation 1. Remove evaporator cover to access mounting holes. NOTE: The installation kit provides both metric and imperial nuts and washers. Be sure to use the correct ones for your application. Mounting Stud Installations 2. Install the aluminum spacers onto the ceiling mounting studs and raise the evaporator into position. Secure the evaporator onto the mounting studs with flat washers and locking nuts. (Detail B). Torque to 81.3 N m (60 ft-lb). Mounting Bolt Installations 3. Install the mounting bolts, lock washers and flat washers onto the evaporator and raise into position. Install the aluminium spacers and secure the evaporator to the ceiling. (Detail C). Torque to 81.3 N m (60 ft-lb). 4. A properly installed evaporator will slope slightly toward the drain tubes to allow for water drainage (Detail D). Two additional washers are included in the kit to help assist sloping the evaporator towards the drain. 68

Installation S-2 or S-3 69

Condensing Unit Tube Connections S-2 or S-3 CAUTION: Remove holding charge from condensing unit before proceeding to avoid personal injury. NOTE: Thermo King requires the use of bulk rolled refrigeration tubing and tube benders to reduce fittings and solder joints where applicable (Detail A). It is also required that the use of nitrogen or another inert gas be used to purge the tubes before soldering. This prevents oxidation and formation of scale inside tubes. NOTE: Discard O-rings that come with the condensing unit. Oil and install new O-rings supplied in kit. HG = Hot Gas S = Suction L = Liquid Item Description Part Number #2 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968 #3 7/8 in. x 7/8 in. Elbow 553326 #7 3/8 in. x 3/8 in. x 3/8 in. Tee 553251 #8 3/8 in. x 3/8 in. Elbow 552876 #11 1/2 in. x 1/2 in. x 1/2 in. Tee 552296 #12 1/2 in. x 1/2 in. Elbow 558812 1. Oil O-ring and install pre-bent 90 1-1/8 in. tube onto suction fitting of condensing unit (Detail B). 2. Install 1-1/8 in. x 7/8 in. x 7/8 in. tee onto suction tube (Detail B). 3. Install 7/8 in. x 7/8 in. elbow onto suction tube tee (Detail B). 4. Install check valves onto suction tubes as close as possible to condensing unit (Detail B). NOTE: Remove internal components of valves before soldering and use 35% silver solder. 5. Fabricate 7/8 in. tubes and install onto check valves (Detail B). 6. Oil O-ring and install pre-bent 90 3/8 in. tube onto liquid fitting of condensing unit (Detail B). 7. Install 3/8 in. x 3/8 in. x 3/8 in. tee onto liquid tube (Detail B). 8. Install 3/8 in. x 3/8 in. elbow onto liquid tube tee (Detail B). 9. Fabricate 3/8 in. tubes and install onto liquid tubes (Detail B). 10. Oil O-ring and install pre-bent 90 1/2 in. tube onto hot gas fitting of condensing unit (Detail B). 11. Install 1/2 in. x 1/2 in. x 1/2 in. tee onto hot gas tube (Detail B). 12. Install 1/2 in. x 1/2 in. elbow onto hot gas tee (Detail B). 13. Fabricate 1/2 in. tubes and install onto hot gas tubes (Detail B). 14. Add insulation to suction and hot gas tubes only (Detail B). 15. Secure all tubing with provided clamps (Detail C). 70

Condensing Unit Tube Connections S-2 or S-3 71

Evaporator Tube Connections S-2 or S-3 CAUTION: Remove holding charge from the evaporator(s) before proceeding to avoid personal injury. NOTE: Thermo King requires the use of bulk rolled refrigeration tubing and tube benders to reduce fittings and solder joints where applicable. It is also required that the use of nitrogen or another inert gas be used to purge the tubes before soldering. This prevents oxidation and formation of scale inside tubes. IMPORTANT: Discard O-rings that come with the evaporator and install the new ones that come in the kit. Clean all threads on ORS fittings prior to installation. Apply refrigerant oil to the O-rings only. DO NOT APPLY OIL TO THE ORS FITTING THREADS. When tightening ORS tubing connections, always use a backup wrench to hold the backside of the ORS fitting to prevent the refrigeration tube from twisting. Torque all ORS connections as shown in the table. HG = Hot Gas S = Suction L = Liquid 1. Fabricate a 7/8 in. suction tube from the condensing unit and route in the trough, install 7/8 in. x 7/8 in. elbow, attach 7/8 in. preformed tube, oil new O-ring and connect to the evaporator 7/8 in. ORS fitting. 2. Fabricate a 1/2 in. hot gas tube from the condensing unit and route in the trough, install 1/2 in. x 1/2 in. elbow, attach 1/2 in. preformed tube, oil O-ring and connect to the evaporator 1/2 in. ORS fitting. 3. Fabricate a 3/8 in. liquid tube from the condensing unit and route in the trough, install 3/8 in. x 3/8 in. elbow, attach 3/8 in. preformed tube, oil new O-ring and connect to the evaporator 3/8 in. ORS fitting. 4. Insulation should be added to all segments of suction and hot gas tubes. 5. Secure all tubing with provided clamps. Item Description P/N A 7/8 in. x 7/8 in. Elbow 553326 B 1/2 in. x 1/2 in. Elbow 551483 C 3/8 in. x 3/8 in. Elbow 556359 Specifications for Evaporator ORS Fittings Tube Size Thread Torque O-ring Gaskets Liquid 3/8 in. 11/16-16 30 ft-lb 331222 Hot Gas 1/2 in. 13/16-16 40 ft-lb 331015 Suction 7/8 in. 1-3/16-16 60 ft-lb 330566 72

Evaporator Tube Connections S-2 or S-3 73

Wire Connections S-2 S-2 Evaporator NOTE: Trim all harnesses to appropriate length before installing terminals. NOTE: Superlube (203-524 or equivalent) must be applied to all electrical connections. 1. Connect Zone Harness (2C42230-24 pin connector) to appropriate mating connector at the back of condensing unit (Detail A), route harness to evaporator, cut harness to length and connect to terminal block (Detail B). NOTE: If Zone Harness is cut to length, use wire CHE-06 from discarded harness length to connect SOL terminal to the ground stud (Detail B). 2. Connect Coil Temperature Sensor (CTN-01, CTP-01), Discharge Air Temperature Sensor (DTN-01, DTP-01) and Return Air Temperature Sensor (RTN-01, RTP-01) to matching connectors in evaporator (Detail C). 3. Connect Fan Harness (2C42229 - CHE-01, FMA-01, CHE-02, FMB-01) to appropriate mating connectors at the back of the condensing unit (Detail A), route harness to evaporator, cut harness to length and connect to terminal block (Detail B). 4. Move jumper to connect DH to LLS on S-2 terminal board (Detail B). 5. Secure all harnesses with adequate clamps or ties. 74

Wire Connections S-2 75

Wire Connections S-3 S-3 Evaporator NOTE: Trim all harnesses to appropriate length before installing terminals. NOTE: Superlube (203-524 or equivalent) must be applied to all electrical connections. 1. Connect Zone Harness (2C42230-24 pin connector) to appropriate mating connector at the back of condensing unit (Detail A), route harness to evaporator, cut harness to length and connect to terminal block (Detail B). NOTE: If Zone Harness is cut to length, use wire CHE-06 from discarded harness length to connect SOL terminal to the ground stud (Detail B). 2. Connect Coil Temperature Sensor (CTN-01, CTP-01), Discharge Air Temperature Sensor (DTN-01, DTP-01) and Return Air Temperature Sensor (RTN-01, RTP-01) to matching connectors in evaporator (Detail C). 3. Connect Fan Harness (2C42229 - CHE-01, FMA-01, CHE-02, FMB-01) to appropriate mating connectors at the back of the condensing unit (Detail A), route harness to evaporator, cut harness to length and connect to terminal block (Detail B). 4. Move jumper to connect DH to LLS on S-3 terminal board (Detail B). 5. Add jumper to connect FM2 to FM3 on S-3 terminal board (Detail B). 6. Secure all harnesses with adequate clamps or ties. 76

Wire Connections S-3 77

Condensing Unit Tube Connections (2) S-2 + S-2 CAUTION: Remove holding charge from condensing unit before proceeding to avoid personal injury. NOTE: Thermo King requires the use of bulk rolled refrigeration tubing and tube benders to reduce fittings and solder joints where applicable (Detail A). It is also required that the use of nitrogen or another inert gas be used to purge the tubes before soldering. This prevents oxidation and formation of scale inside tubes. NOTE: Discard O-rings that come with the condensing unit. Oil and install new O-rings supplied in kit. HG = Hot Gas S = Suction L = Liquid Item Description Part Number #2 1-1/8 in. x 1-1/8 in. x 7/8 in. Tee 559517 #3 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968 #4 7/8 in. x 7/8 in. Elbow 553326 #8 3/8 in. x 3/8 in. x 3/8 in. Tee 553251 #9 3/8 in. x 3/8 in. Elbow 552876 #12 1/2 in. x 1/2 in. x 1/2 in. Tee 552296 #13 1/2 in. x 1/2 in. Elbow 558812 1. Oil new O-ring and install pre-bent 90 1-1/8 in. tube onto suction ORS fitting of condensing unit (Detail B). 2. Install 1-1/8 in. x 1-1/8 in. x 7/8in. tee into suction tube. 3. Install 1-1/8 in. x 7/8 in. x 7/8 in. tee onto suction tube (Detail B). 4. Install 7/8 in. x 7/8 in. elbows onto suction tube tees (Detail B). 5. Install check valves onto suction tubes as close as possible to condensing unit (Detail B). NOTE: Remove internal components of valves before soldering and use 35% silver solder. 6. Fabricate 7/8 in. tubes and install onto check valves (Detail B). 7. Oil new O-ring and install pre-bent 90 3/8 in. tube onto liquid ORS fitting of condensing unit (Detail B). 8. Install 3/8 in. x 3/8 in. x 3/8 in. tee onto liquid tube (Detail B). 9. Install 3/8 in. x 3/8 in. elbow onto liquid tube tee (Detail B). 10. Fabricate 3/8 in. tubes and install onto liquid tubes (Detail B). 11. Oil new O-ring and install pre-bent 90 1/2 in. tube onto hot gas ORS fitting of condensing unit (Detail B). 12. Install 1/2 in. x 1/2 in. x 1/2 in. tee onto hot gas tube (Detail B). 13. Install 1/2 in. x 1/2 in. elbow onto hot gas tee (Detail B). 14. Fabricate 1/2 in. tubes and install onto hot gas tubes (Detail B). 15. Add insulation to suction and hot gas tubes only (Detail B). 16. Secure all tubing with provided clamps (Detail C). 78