REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

Similar documents
[Mali*, 4.(12): December, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Modelling the Performance of a Diffusion Absorption Refrigeration System

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

EXPERIMENTAL PERFORMANCE ANALYSIS OF AN AMMONIA-WATER DIFFUSION ABSORPTION REFRIGERATION CYCLE

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

DESIGN AND FABRICATION OF SOLAR DRYER WITH REFRIGERATION

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Thermodynamic Analysis of Single-Effect Lithium Bromide Water Vapour Absorption Refrigeraion System

Design of solar powered vapour absorption refrigeration system

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system

Performance Optimization of the Evaporative Condenser Design

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Chapter 10. Refrigeration and Heat Pump Systems

HVAC Fundamentals & Refrigeration Cycle


Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

ISSN Vol.08,Issue.21, November-2016, Pages:

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Enhancement of COP in Vapour Compression Refrigeration System

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Adsorption refrigeration system using waste heat

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Thermodynamic Analysis of Lithium Bromide-Water(LiBr-H2O) Vapor Absorption Refrigeration System Based on Solar Energy

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

PRODUCING COOLING FROM SOLAR ENERGY BY USING ADSORPTION CYCLE WITH ACTIVATED CARBON AND METHANOL PAIR

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Design and development of vapor absorption refrigeration system for rural dwellers. Adekeye, T. Oyedepo, S.O and Oyebanji, J.A

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Chapter 9. Refrigeration and Liquefaction

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Design & Fabrication of Hybrid Cooler

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Recent Advances in Energy, Environment and Economic Development

INSTITUTE OF AERONAUTICAL ENGINEERING

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Thermodynamic Analysis of Ammonia-Water Absorption Refrigeration System with Ejector

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Carnot. 2. (a) Discuss the advantages of the dense air refrigeration system over an open air refrigeration system?

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

A Comparison Between Refrigerants Used In Air Conditioning

II. OBJECTIVE OF RESEARCH

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

LECTURE-18 Vapour Absorption Refrigeration System

Energy efficient vacuum freezing ice slurry generation using a R718 compressor

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT

DEPARTMENT OF MECHANICAL ENGINEERING REFRIGERATION & AIR CONDITIONING LAB TRIPLE FLUID VAPOR ABSORPTION SYSTEM

THE USE of DIRECT SOLAR ENERGY in ABSORPTION REFREGERATION EMPLOYING NH 3 H 2 O SYSTEM

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

K.F. Fong *, C.K. Lee, T.T. Chow

Pressure Enthalpy Charts

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Refrigeration and Air Conditioning

Design Analysis Of 3 TR Aqua Ammoniavapour Absorption Refrigeration System

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

RAC. Unit 1. Previous year Questions

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Transcription:

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM Mr. S. S. Mali 1, Prof.M.M.Wagh3 Prof. N. N. Shinde 2 1 M. Tech Scholar, Department Of Energy Technology, Shivaji University Kolhapur(INDIA). 2 H.O.D. Department Of Energy Technology, Shivaji University, Kolhapur(INDIA). 3 Prof. Department Of Energy Technology, Shivaji University, Kolhapur(INDIA) Abstract The solar powered absorption refrigeration technologies are attractive alternatives that not only can serve the needs for air-conditioning, refrigeration, ice making and coagulation purposes, but also can meet demand for energy conservation and environment protection. However, a lot of research work still needs to be done for large-scale applications in industry and for the replacement of conventional refrigeration machines. An air-conditioning system utilizing solar energy would generally be more efficient, cost wise, if it was used to provide both heating and cooling requirements in the building it serves. This research work is a review of the research state of art of the solar absorption refrigeration technologies. After an introduction of basic principles, the development history and recent progress in solar absorption refrigeration technologies are reported. The application areas of these technologies are categorized by cooling temperature demand, and are further elaborated with fundamental knowledge on absorption systems, and a detailed review on the past efforts in the field of solar absorption cooling systems with the absorption pair of Ammonia and water. This knowledge will help them to start the parametric study in order to investigate the influence of key parameters on the overall system performance. Keywords Solar absorption refrigeration, energy conservation, economical, Ammonia & Water. I INTRDUCTION Refrigeration technologies play a vital role in many industrial applications. Notably in the food field where reduction of post-harvest losses, improved food safety and hygiene, promotion of international trade and improved food supply to the cities are considered as top-priority objectives. Air-conditioning is the dominant energy consuming service in buildings in many countries. Conventional cooling technologies used for refrigeration and air-conditioning cause high electricity peak loads because of their concurrent operation during periods of high ambient temperature. Not only that but also the refrigerants generally used in conventional cooling systems are adding significantly to climatic change and ozone depletion. II SINGLE EFFECT SOLAR VAPOR ABSORPTION AIR-CONDITIONING SYSTEM Fig. Shows the schematic diagram of a single-effect solar absorption system;[2] this system has been the basis of most of the experience to date with solar air- conditioning. The main processes taking place are as follows - 1 The weak solution from the absorber at point is pumped through the heat exchanger to the generator. During this process, the concentration of the weak solution is held constant. 2 The sensible heating of the weak solution in the generator takes place. In this process the boiling of ammonia vapor from the solution at the constant condensing pressure. During this process, the weak solution becomes strong solution. 3 Tthe strong solution passing to the absorber through the heat exchanger, in which it preheats the weak solution owing from the absorber to the generator. During this process, the concentration of the strong solution is constant. 4 The absorption of ammonia vapor from the evaporator by the strong solution in the absorber. The condensation of ammonia vapor in the condenser by the cooling water from the cooling tower, at constant condensing pressure. 5 Tthe condensed ammonia flows from the condenser to the evaporator. 6 Tthe evaporation of the aq. ammonia in the evaporator takes place due to the prevailing low pressure. Also the ammonia absorbs the heat from the space to be cooled. The ammonia vapor from the evaporator is in turn absorbed by the strong solution in the absorber, thus completing the cycle of refrigeration. Page 10

Review of Solar Technologies - In the solar powered absorption air-conditioning system, it is very much essential to have hot water storage [3]. It serves as a buffer reservoir to have nearly constant heat input. Also, it has been suggested that the nominal storage amounts for cooling purposes range from 80 kg/m2 of collector area to 200 kg/m2. A critical problem with the hot water storage tank is its heat loss to the surrounding area. Sometimes, the heat loss from the hot water storage tank could be equivalent to 2 h of operation per day of the solar air-conditioning system [4]. Similar to the hot water storage tank, a chilled water storage tank is often used in the solar powered air-conditioning system. While the hot water storage tank experiences considerable heat loss, the chilled water storage tank has a lower rate of heat gain because of the small temperature difference between the chilled water tank and its surroundings. Furthermore, if the chilled water storage tank is installed near the air-conditioned area, its heat gain could assist in cooling. Generally, a parallel auxiliary-heater arrangement is preferred to the series one. Since the chiller has the best performance at high temperatures, it is better to use the auxiliary heater directly to drive the chiller when the temperature in the hot water storage tank is lower than the required level. If the auxiliary heater is connected in series between the hot water storage tank and the chiller, water is often returned to storage hotter than it is taken out, which raises the storage temperature and decreases the collector efficiency. However, if the storage temperature is below the needed energizing temperature but above the return temperature from the generator, then, a series connection can be considered, since only a portion of energy need be supplied by the auxiliary heater to reach the energizing temperature.[5] This method may be suitable in installations needing auxiliary energy only during short periods. In the heating season, the hot water is directly provided from the hot water storage to the fan-coil of the air-conditioned space, or/and to places where the heat is used for bathing or other domestic applications. The main parameter that governs the performance of the chiller is the chilled Water temperature. This is because, as the chilled water temperature decreases, the evaporator temperature decreases, thereby decreasing the pressure in the evaporator, all of which finally results in an increased concentration of the solution. This results in the possibility of crystallization of the solution. Also, with the decrease in evaporating temperature, the coefficient of performance (COP) of the chiller would decrease. [6] III MATHEMETICAL MODELING The operating pressures at which the system is working needs to be determined to carry on further calculations, using an enthalpy concentration chart. Once the pressure of the condenser (Pc) and the pressure of the evaporator (Pe) are determined the corresponding points can be fixed on the chart. The various other points and condition lines for components like absorber, generator, heat exchangers etc can be subsequently fixed. A. Condenser Pressure (Pc) The pressure to be maintained in the condenser for changing the phase of ammonia vapors into ammonia liquid depends on type of condensing medium used and its temperature. In this system, water is used as a condensing medium. Water is available at a temperature of 25 O C. i.e. condensing temperature is Tc= 25 O C. For condensing ammonia vapors at 25 O C.the corresponding pressure required can be noted from the refrigeration table of ammonia (R-717). In this way, the condenser pressure is fixed at Pc=10 bar. Page 11

B. Evaporator pressure (Pe) The evaporator pressure can be fixed according to the minimum temperature required to be maintained in the evaporator chamber. The pressure maintained in the evaporator should be as close to the atmospheric pressure as possible, because maintaining a higher pressure is a difficult and costly affair. Moreover it also has leakage problems and the unit needs to be hermetically sealed. The evaporator pressure is kept equal to the atmospheric pressure(1 bar), to ensure design economy. The corresponding saturation temperature in the evaporator (ammonia vapors) becomes -33 0 C. Point 1 represents pure NH 3 saturated vapor at condenser pressure Pc and concentration C=1 Point 2 represents pure NH 3 saturated liquid at Pc and C=1. This point is marked in liquid region. Point 3 represents the condition of pure NH 3 (wet) but at pressure Pe and C=1. Point 2 coincides with point 3 as 2-3 is a throttling process in which enthalpy remains constant. Point 4 represents the condition of pure NH 3 at pressure Pe these are saturated vapors which absorbs heat in evaporator and converts from wet vapor to saturated vapor. This point is marked in vapor region. The enthalpies at points 1, 2, 3 and 4 can be noted from the chart. h1= 1630 KJ/Kg h2= h3= 460 KJ/Kg h4= 1530 KJ/Kg The literature values for the design of the Aqua Ammonia vapour absorption system are Temperature of the evaporator, Te = 10 Generator or condenser pressure, Pc = 10 bar Evaporator pressure, Pe = 1 bar Temperature of the Condenser, Tc = 25 Temperature of the Absorber, Ta = 25 Temperature of the Generator, Tg = 80 IV DESIGNS OF GENERATOR, CONDENSER, EVAPORATOR, AND ABSORBER 1 DESIGN OF GENERATOR The generator acts like the discharge of the compressor it delivers the refrigerant vapor to the rest of the system. Heat supplied in the generator Now using equation Qg Qd = (h1 - ha) We can find the Qg Page 12

Length = 1M. Tube dia. = 0.01M" Q gen = U G x A G x T G From above equation we can find out A G Area of tube = πdl Area of generator No. of tubes = -------------------- Area of tube Cross-sectional area of tube = π /4 d 2 Total cross-sectional area = n a Total cross-sectional area including space between the tubes = 2 Total cross sectional area ie,cross-sectional area of generator = Now, π/4 D 2 From above we can find out diameter of generator 2 DESIGN OF CONDENSER The function of the condenser is to remove the heat of the hot vapour refrigerant. Heat removed in condenser Heat removed in the condenser by the circulated cooling water is given by the equation: Qc = Mr (h2 h1) The cooling medium used is water Inlet temperature of water is (tc1) Exit temperature of cooling water (tc2) θ1 = Tg- tc1 θ2 = Tg- tc2 LMTDθm = θ1 - θ2/ ln (θ1/θ2) Qc= FUA θm From above we can find out Area of the Condenser Ac Length of each tube (L) = 100 cm =1m Diameter of Condenser tube (D) = to be calculated The effective area of Condenser (Ac) = n π D L Page 13

Area of tube = πdl Cross-sectional area of tube = π /4 d 2 Total cross-sectional area = n a Total cross-sectional area including space between the tubes = 2 Total cross-sectional area ie,cross-sectional area of condenser = Now, π/4 D 2 From above we can find out diameter of the condenser 3 DESIGN OF EVAPORATOR Evaporator is an equipment in which refrigerant vaporizes to generate the desired refrigeration. It is also known as chiller. Considering the evaporator made of tubes and air cooled. Let air inlet temperature to evaporator Th1. Air outlet temp; Th2 θ1= Th1-Te θ2 =Th1-Te = = Heat removed in the evaporator Qe = FUA θm From above equation we can find out Area of the evaporator. Considering the number of evaporator tubes (n) Length of each tube (L) = 1m. Diameter of evaporator tube (D) = to be calculated. The effective area of evaporator (Ae)=n π D L Area of tube = πdl From above we can find out diameter of the evaporator Page 14

4 DESIGN OF ABSORBER Considering the absorber to be direct contact heat exchanger in which the weak solution from the generator mixes with the ammonia gas from the evaporator and due to the direct mixing the heat is rejected. Air is used as cooling medium. Heat removed from absorber. Q A = U A x A A x T A From above equation we can find out Area of the absorber Area of tube = πdl Area of generator No. of tubes = -------------------- Area of tube Cross-sectional area of tube = π /4 d 2 Total cross-sectional area = n a = Total cross-sectional area including space between the tubes = 2 Total cross-sectional area ie,cross-sectional area of generator = Now, π/4 D 2 Calculations of solar water heater. Energy absorbed by the collector plate is given by Qu= K S A Where, K=efficiency of collector plate (assume k=0.70) S=average solar heat falling on earth s surface=6 kwhr/ m2/day= 250 W/m2 A=Area of collector plates COP of the system (For flat plate collector system) The cop of the refrigerating unit can be calculated by using the equation: COP = Refrigerant Effect / Heat input in the generater Now the COP of the system as a whole (system including solar water heater) can be calculated as COP = Net refergerent effct produced / Heat input at the solar Page 15

collecter IV: CONCLUSION From the discussion, one may conclude that solar-powered absorption refrigeration technologies could be used for producing a wide range of temperatures of cold. They are attractive technologies that not only can serve the needs for refrigeration, airconditioning applications and ice making, but also can meet demand for energy conservation and environment protection. Comparatively, absorption systems are more suitable for air-conditioning while adsorption systems are more employed for low temperature purpose. In light of the above results, the feasibility of the solar powered vapour refrigeration system has been reasonably proved. V REFRENCES 1. Pongsid Srikhirin, Satha Aphornratana, Supachart Chungpaibulpatana, A review of absorption refrigeration technologies Renewable and Sustainable Energy Reviews 5 (2001) 343 372 2. R.Z. Wang,1, T.S. Ge, C.J. Chen, Q. Ma, Z.Q. Xiong, Solar absorption cooling systems for residential applications: Options and guidelines International journal of refrigeration 32 (2009) 638-660 3. Wilbur PJ, Mitchell CE. Solar absorption air-conditioning alternatives. Solar Energy 1975; 17:193-99. 4. Ward DS, Lof GOG. Design, construction and testing of a residential solar heating and cooling system. Report to the Committee on the Challenges of Modern Society (CCMS) Solar Energy Pilot Study, July 1976. 5. Rupesh V. Ramani, Dr. Bharat M. Ramani, Anjana D. Saparia, Solar Refrigeration Technologies: A Key review on Current Status and Recent Developments International Journal of Emerging Technology and Advanced Engineering. 6. V Mittal, KS Kasana, NS Thakur, The study of solar absorption air-conditioning systems 7. V.D.Patel, A.J.Chaudhari, R.D.Jilte Theoretical and Experimental Evaluation of Vapour Absorption Refrigeration System 8. V.K.Bajpai, Design of Solar Powered Vapour Absorption System Page 16