Diesel Fuel System Report

Similar documents
2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805)

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

Carbon Dioxide Enrichment Systems

Fire Protection Coffee Break Training May 2016

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Agency for Health Care Administration

Plant Processing and Extraction Facilities

For additional information regarding R-3.1 residential care facilities please contact (951)

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry.

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s

Tents and Temporary Membrane Structures Permit Procedure

Tents and Temporary Membrane Structures Packet

FIRE SAFETY INSPECTION REPORT

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

CHAPTER 7 ALTERATIONS LEVEL

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

16620 EMERGENCY POWER SYSTEMS

SEMICONDUCTOR FABRICATION FACILITIES

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

MEP Basis of Design Report

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

Winnipeg Fire Department Fire Prevention Branch

SECTION INSPECTION AND TESTING OF WORK

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

Port of St Helens SIA Aircraft Hanger Scappoose, OR

HIGH-RISE RETROFIT ORDINANCES - NO and NO

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

NFPA Changes

Are You Prepared? The impending impact of Code on Servicing Security Systems

(h) Pesticide Application.

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

SECTION 915 CARBON MONOXIDE DETECTION

Residential-based Care Facility R-4 Guideline

Laboratories and Hazardous Materials. Company Overview

FIRE SAFETY INSPECTION REPORT

Flammable Liquid Storage

Orange County EMERGENCY POWER PLAN (EPP) CRITERIA FOR ASSISTED LIVING FACILITIES & NURSING HOMES

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

American Fire Sprinkler Association. An Introduction to the IBC and IFC

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

SEMICONDUCTOR FABRICATION FACILITIES

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

FIRE SAFETY INSPECTION REPORT

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

NFPA 45 NFPA 211 NFPA 1600

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14

SEMICONDUCTOR FABRICATION FACILITIES

First Revision No NFPA [ Section No ]

Above Ground Fuel Tank Requirements

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY

The Residences at Christina Landing Wilmington, DE

By: Russell Bainbridge March 18th, 2016 FPE 596

SEMICONDUCTOR FABRICATION FACILITIES

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

GENERAL AREAS OF INSPECTION

EMERGENCY POWER SYSTEMS

INITIAL FIRE SAFETY ASSESSMENT

PRESENTERS OVERVIEW COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS

2. Closed circuit television, design and installation.

INITIAL FIRE SAFETY ASSESSMENT

2008 NYC Fire Code. New Laboratory Standards. Operational & Maintenance Provisions effective July 2008

INITIAL FIRE SAFETY ASSESSMENT

PLAN REVIEW SUBMITTAL GUIDE

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

FIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS

January 1, 2014 Mandatory Effective Date

Life Safety - Means of Egress/Exits NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101

Large Family Daycare Guideline

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

Are there any policies regarding outlets that contain USB ports?

BUILDING/FIRE CODE REFERENCES 2006 EDITION

PERFORMANCE COMPLIANCE METHODS

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Agency for Health Care Administration

WEST VIRGINIA UNIVERSITY

IFE-NFPA WORKSHOPS. Jointly organized by The Institution - of Fire Engineers, Singapore Branch & National Fire Protection Association, USA

Plan Submittal Checklist

Transcription:

Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical Design Studi 1801 Oakland Blvd., Suite 110 Walnut Creek, CA 94596 MEP Issue for Bid

I. SUMMARY A. This report is intended to supplement the San Francisco Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps. The permit checklist has been included in the 100% Construction Documents for permit review on Plumbing/Fire Protection Sheet P1-5062. B. This report also documents the applicable code references that affect the minimum size requirements for the onsite fuel system supply. C. In addition to the code required durations and the related capacity of diesel fuel storage onsite, the TJPA has requested that additional fuel be provided to extend the time of operation during a utility power outage to support the facility emergency, legally required standby and optional systems for the building. The limited physical building site for the Transit Center prevents installation of underground fuel storage tanks within the property, and the current design is constrained by the applicable codes and regulations for fuel storage within the building. D. To address the request for increased capacity, a proposed design modification that is described in this report includes provisions for additional fuel storage capacity to support the Transit Center, and is included for review and consideration. II. CODE REQUIREMENTS FOR GENERATOR FUEL CAPACITY A. For the purpose of determining the amount of fuel required by the applicable codes to be stored on site for the Transbay Transit Center, the following requirements are summarized: 1. The 2007 California Building Code (CBC) and California Fire Code (CFC) as adopted and amended by the City of San Francisco are the governing fire and life safety codes for the base building design. The Trainbox and the Bus Deck Level are also governed by NFPA 130 as agreed by the Authority Having Jurisdiction (AHJ). The 2007 California Electrical Code with San Francisco amendments is also a required code. 2. The suite of NFPA standards, including NFPA 110 (Standard for Emergency Power Supply and Standby Power Systems), provides design guidance for the various building provisions that are required by the CBC or CFC for this building. In San Francisco, NFPA 110 is not adopted as code in its entirety. NFPA 72 (2010 version, Fire Alarm Signaling) is adopted as clarified in the RFLE#5 documentation. 3. The secondary power supply for the transit center is provided by diesel generators. For fire life safety purposes, secondary power supply is not required to be more than 8 hours in duration for any of the fire life safety provisions (e.g. emergency exiting lighting, exit signs, fire command center equipment, emergency ventilation systems (train platform, lower concourse, selected pressurized stairs), fire pump, elevators, accessible means of egress, protective signaling systems, fire alarm etc.) as indicated in the CBC and CFC. 4. San Francisco Fire Department publication states that the Emergency Power Supply System for the life safety systems in a building shall be operational at all times while the building is occupied. This requires the generators and fuel WSP Ref. No.: S08.14200.00 1

III. systems supplying all building life safety systems to be available for use during occupancy in the event that utility power is interrupted. CODE REFERENCES FOR FUEL STORAGE CAPACITY A. Fuel Supply Requirements for Fire Pump: Reference NFPA 20.9.6.2.2 (2003). The fuel supply capacity shall be sufficient to provide 8 hours of fire pump operation at 100% of the rated pump capacity in addition to the supply required for other demands. B. Fuel Supply requirements for Emergency Systems (emergency lighting, fire alarm and elevator cab lights/fans) San Francisco Electric Code (California Electric Code 2007) (NFPA 700-2005). NFPA 700.12.2 requires diesel generators to have on-premise fuel supply sufficient for not less than 2 hours full demand operation of the system. C. Fuel Requirements for NFPA 130 Stations: Reference NFPA 130. 5.4.11: Enclosed stations shall be provided with Type 1 Class 60 emergency power for fire alarm, emergency communication, emergency lighting and fire command center. Class 60 designates 60 minutes (1 hour) operation. IV. DESCRIPTION OF CURRENT FUEL SYSTEM DESIGN A. Refer to the Generator Fuel Use Projection Table at the end of this report for the calculation of the generator run time estimates for the fuel storage system capacity. The calculation accounts for maintaining reserve fuel supply for the code required fire pump and smoke ventilation systems, and it identifies the remaining fuel available for operation of the facility during a utility power outage. Based on the current design that provides separate fuel tanks for each generator, the reserve fuel capacity provides approximately twenty four hours of supply for the center generator, and longer fuel storage time provided for the west generator and the east (Phase 2) generator. B. The diesel fuel system supplying emergency generators includes fuel storage for the generator s running at full load for minimum 8 hours. The west and center generators are both 2,000kW (2,500kVA) in capacity and their fuel oil consumption at full load is 139 gallons per hour (gph) each. 139 gph x 8 x 1.33 = 1,479 gallons C. The West emergency generator is supplied by a 2,000 gallon storage tank located in a dedicated room on the Train Platform Level (B2) and a 400 gallon day tank located in the emergency generator room on Level 2. The center emergency generator is supplied by a 4000 gallon storage tank located in a dedicated room in the Lower Concourse Level (B1) and a 400 gallon day tank located in the emergency generator room on Level 2. The aggregate volume of diesel fuel in the building (for Phase 1) is 6,800 gallons. D. The diesel fuel storage rooms are less than 1,000 sq. ft. (2007 CBC, Section 415.3, exception 2). E. The diesel fuel storage rooms are located in a fully sprinklered building per NFPA 13. The rooms are classified as Extra Hazard Group 2 (2002 NPA 13, Section 5.42) and the sprinkler density coverage is 0.40 gal/sq.ft. F. The diesel fuel storage rooms are classified as H-3 occupancy (2007 CBC, Table 508.3.3) with minimum 3 hours rated walls, exhaust enclosure (2007 CFC, Sections WSP Ref. No.: S08.14200.00 2

2704.3 and 2704.3.1), two exit doors (2007 CBC, Section 1015.1) and interior wall and ceiling finish per 2007 CFC, Table 803.3. G. The diesel fuel storage tanks are Fireguard type, UL 2085, double wall. H. The diesel fuel storage rooms are provided with secondary containment per 2007 CFC, Section 2704.2.2 for spill control. The curb around the diesel fuel storage rooms are calculated to include the volume of the fuel tank plus 20 minutes of sprinkler design flow. Leak detection for the containment area is provided (2007 CBC, Sections 415.6.2.6 and 415.6.2). I. Fuel tank is filled via a closed piping system with remote fill (2007 SFFC, Section 7901.1.1.1). Remote fill inlet is located outside of building. Opening is provided with a tamper-proof, liquid-tight cap which is closed when not in use and is properly identified (2007 CFC, Sections 3402.7.5.2 and 3404.2.7.5.6). Remote fill inlet is provided in accordance with the 2007 CFC, Section 3404.2.7.5.8, 3404.2.9.6.6, 3404.2.9.6.6.1 and 3404.2.9.6.6.2. All tank openings are in accordance with 2007 CBC, Section 415.6.2.10; 2007 CFC, Section 3403.6.7; and 2003 NFPA, Section 4.3.4.7. J. Piping systems are supported and protected against physical damage and excessive stresses in accordance with MSS SP-69, Pipe Hangers & Supports-Selection and Application. Flexible connectors are provided to protect the piping system against damage caused by settlement vibration, expansion, contraction, or corrosion (2002 NFPA 37, Section 6.8.2). Fuel piping supports are protected against exposure to fire by draining liquid away from piping system at a minimum slope of not less than 1 percent and providing protection with a fire-resistive enclosure rated of not less than 2 hours (2003 NFPA 30, Sections 5.5.2; 2002 NFPA 37, 6.8; and 2007 CFC, Sections 3403.6.2 and 3403.6.8). K. The fuel tanks are provided with vents for normal venting in accordance with 2007 CFC, Section 3404.2.7.3 and emergency venting (2003 NFPA 30, Section 4.2.5.2). L. Diesel fuel storage tank supports and connection are designed to resist damage as a result of seismic activity (2007 CFC, Section 2703.2.8, 3404.2.9; and 2003 NFPA 30, 4.2.4). M. The fuel supply system is provided with a comprehensive fuel management, monitoring and alarm system (2002 NFPA 37, Section 6.5.2). N. All fuel piping is double-walled (2007 CFC, Section 2703.2.2, 2704.2.2.5, 3403.6 and 7902.1.10.8) and is provide with a leak-detection system (CBC Section 415.6.2, 414.7 and CFC 2704.2.5.5). WSP Ref. No.: S08.14200.00 3

Generator Runtime hours w/2000 gallon tanks 43 hours 24 hours 48 hours WSP Ref. No.: S08.14200.00 4 Generator Fuel Use Projection Phase 1 & Phase 2 Generator West Generator Center Generator East (PH2) Load Description kva kva kva Egress Ltg/Exit Signs (0.25W/SF incl retail SF) 64.4 191.2 66.3 Low Voltage/PA/Security Systems 188.0 285.0 58.0 HVAC Systems for Optional Loads (80% diversity) 289.5 408.4 362.7 Sewage Ejectors, Fuel Oil Pumps 77.0 236.0 0.0 Elevators (1 per bank) 127.0 232.7 164.5 Fire Alarm System 25.0 25.0 25.0 SUBTOTAL- Loads to support for outage duration 770.9 kva 1,378.3 kva 676.5 kva % of Generator full load 31 % 55 % 27 % Fuel consumption-gph @ % load 51.0 gph 93.0 gph 45.0 gph Stair Pressurization System Fans to center only 0.0 kva 320.0 kva Add Stair Press Fans (1 hour) 25.0 kva 25.0 kva 25.0 kva Add sump pumps (run 1 hour) 53.0 kva 167.0 kva Add Trainbox Fan Systems (run 1 hour) 932.0 kva 0.0 kva 804.0 kva TOTAL GEN LOAD- Run for 1 hour 1,780.9 kva 1,890.3 kva 1,505.5 kva % of Generator full load 71 % 76 % 60 % Fuel consumption- gph @% load 99.7 gallons 119.1 gallons 84.3 gallons 1 hour fuel consumption with trainbox fans 99.7 gallons 119.1 gallons 84.3 gallons Reserve 8 hr fuel for Fire Pump 307.0 kva 320.0 gallons

Notes to Fuel Use Projection *Loads include Ph1 and Ph2 Emergency, Standby and Optional Loads connected to the generators *Escalators- Not required and not included on generator power *275 gallon daytanks included *Runtime hours include all generator loads for duration except trainbox fans(1 hour), stair press fans(1hour), sump pumps(1 hour), and fire pump (8 hours) *Retail SF is based on 50% CD areas *Bus deck fans assumed at :Zone A- 100 hp; Zone B- 100; Zone C- 100; Zone D- 100 WSP Ref. No.: S08.14200.00 5