MPU Cooler for Pentium 4, SAN ACE MC Michinori Watanabe Toshiki Ogawara Haruhisa Maruyama Masayuki Iijima

Similar documents
"SAN ACE MC" for Pentium & Pentium 4

"SAN ACE MC" for Pentium *

High Performance Liquid Cooling System SAN ACE MC Liquid Tomoaki Ikeda Toshiki Ogawara Masashi Miyazawa Kouji Ueno

Cooling Fans Contributing to Effective Use of Power

High-Performance, High-Reliability Gas Heat Pump

Development of a Compact High Efficiency Cooling Device for the PA8000 Processor*

15. Heat Pipes in Electronics (1)

The Basics of Package/Device Cooling

Heat sinks for electronic cooling applications

(12) United States Patent

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Development of the San Ace Airflow Tester - A Measuring Device for System Impedance and Operating Airflow of Equipment

Cooling Solutions for High Heat Flux in Dense Packed Servers. Dr. Walter Angelis R&D Manager Aerodynamics Helmut Sebisch Key Account Manager

Development of Large Size Hybrid Fan

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Figure 1: Overview of CO 2 evaporator types

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

FABRICATING A HEAT PIPE STRUCTURE WITHIN A RADIATING PLATE FOR ELECTRONICS FAN-LESS COOLING

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

A NEW BEGINNING IN FAN COIL HISTORY

An Introduction of Below-Freezing and Humidity Environment Controlling Technology Equipped on Brake Test Equipment

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

COOLING OF DESKTOP COMPUTER USING HEAT PIPES

High-efficiency Turbo Chiller (NART Series)

Low Noise Type Hydraulically Driven Engine Cooling Fan System

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

(12) United States Patent (10) Patent No.: US 6,639,797 B2

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Compact design & easy maintenance

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

WHITE PAPER: Cooling Industrial Enclosures with Filter Fans

(51) Int Cl.: F03D 11/00 ( )

A new method for preventing air-source heat pumps and refrigerators from frosting

Fike set out to develop a better understanding of the power density trends in data centers around the world.

Thermal management architectures for rack based electronics systems. Sukhvinder Kang, David Miller Aavid Thermalloy, Concord NH, USA

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

Research on Waste Heat Recovery System for Residential Gas Engine-Driven Heat Pump

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

ZERO Heating Power Vending Machine Hybrid ZERO

Momentum in Greenhouse Air Movement

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

PERFORMANCE EVALUATION OF THE MINIATRIZED CATALYTIC COMBUSTION TYPE HYDROGEN SENSOR

Ultrasonic Reflective Sensor

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

- 1 - Corona - Treatment

NOREN Products. Compact Cabinet Coolers

Application Note Heat Transfer Design Team 7 Compact Inverter Jack Grundemann

42CW/CH. Fan Coil Unit (High Static Pressure) 42CW/CH. Welcome to Carrier Website w w w. c a r r i e r. c o m. c n

Heat Dissipation in Control Panel using Heat Pipe

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Delta Electronics Corp. APPROVAL SHEET PLEASE SEND ONE COPY OF THIS SPECIFICATION BACK AFTER YOU SIGNED APPROVAL FOR PRODUCTION PRE-ARRANGMENT.

ACT-HSC Series Heat Sink Coolers Sealed Enclosure Cooling Installation Guide

Environmental Radiation Monitoring System

Solar Still - Improved Distillation

METHOD OF TEST FOR PREPARATION OF MARSHALL SPECIMENS 3. APPARATUS. Canadian Council of Independent Laboratories June 2016 LS-261 R27 ASTM D

DESIGN CONSIDERATIONS WHEN USING HEAT PIPES

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

OPTIMISATION OF NOZZLE ARRANGEMENTS ON DESCALING HEADERS. Jürgen W. Frick Lechler GmbH D Metzingen / Germany

0Effect of Fin on the Performance Characteristics of Close and Open Loop Pulsating Heat Pipe

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

2.2. General view of Microchannel Heat Exchangers

Pump technology: Improved energy efficiency in refrigeration plants. Dr. R. Krämer

FHS-A9025S20. Picture:

Rotary type Oil-free Air Compressor General Catalogue. Oil-free Scroll Air Compressor Oil-free Claw Air Compressor

POWERENERGY

EP A2 (19) (11) EP A2 (12) EUROPEAN PATENT APPLICATION. (51) Int Cl.: G08B 17/06 ( ) G08B 17/103 (2006.

Cylinders for Domestic Purposes Heat Pumps

GEA Ultra-Denco. GEA Heat Exchangers / HVAC Systems. Close Climate Control for IT Environments. Reliability with low power consumpstion

(12) United States Patent (10) Patent No.: US 7,654,310 B2. Li (45) Date of Patent: Feb. 2, 2010

Impact of TXV and Compressor in the Stability of a High-End Computer Refrigeration System

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

Finned Heat Sinks for Cooling Outdoor Electronics under Natural Convection

Cooling System Technology for Cube-Based Display Walls

Homework 8: Patent Liability Analysis Due: Thursday, March 24, at Classtime

Variable Refrigerant Flow (VRF) Systems

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit

Granulator. Features. Soundproof customer engineered products. (A User and Environment Friendly product)

ICE THERMAL STORAGE SYSTEM USING DYNAMIC ICE IN HERBIS OSAKA PHASE I AND II PROJECTS

Environmental Design The tank has separating devices at the exhaust port to prevent oil-spraying and to reduce pollution.

(12) United States Patent

Microchannel REMOTE AIR COOLED CONDENSER. Technical Bulletin: MXCC_004_ Products that provide lasting solutions.

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

DEVELOPMENT AND APPLICATION OF HIGH-EFFICIENCY INDIRECT HEATING BURNER USED IN METAL HEAT TREATMENT FIELD

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

AC Backward Curved Motorized Impellers

LG Commercial Air Conditioners. Wide Range Free Combination with Various Indoor Types 24/7.0 18/5.3 12/3.5 9/2.6 7/2.1 5/

Circuit balancing: A key to improving HVAC system operation and control

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

AC-046 Peltier-Thermoelectric Air Cooler

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

BLUE GALAXY DEPYROGENATION TUNNELS. Solid Dose Sol

SKYPAK II, 3 Ton Series, gives you a

The Way We Were and Are Going on Cooling High Power Processors in the Industries

HEAT PIPES

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

Transcription:

New Products Introduction MPU Cooler for Pentium 4, SAN ACE MC Michinori Watanabe Toshiki Ogawara Haruhisa Maruyama Masayuki Iijima 1. Introduction In recent years, technical progress of the microprocessor (MPU), which is the brain of a computer, has been remarkable, and its high speed, advanced features, and high integration are being enhanced. In connection with this, the heating value from a microprocessor has been also increasing quickly. The product with a heating value (Thermal Design Power) exceeding 80W has appeared in the Pentium 4 processor from Intel Corp. In order to maintain stability while operating a microprocessor with a high heating value, a cooling device which has high cooling performance and high reliability compared with the conventional product is been needed. In our company, in order to meet such a demand, the MPU cooler for Pentium 4, SAN ACE MC, was developed and produced commercially. Its product outline and its feature are introduced in this document. 3. Outline of the Product The MPU cooler SAN ACE MC for Pentium 4 produced commercially is shown in Fig. 1, and its size specifications are shown in Fig. 2. Also, the performance overview of the product is shown in Table 1. 2. Background of the Development Until now, in our company, the MPU cooler SAN ACE MC series has been produced commercially as a cooling device for Pentium 4 microprocessors from Intel Corporation. (1)(2)(3) However, in the conventional product series, the performance was insufficient for cooling the microprocessor of the heating value of 80W class. Then, the development of SAN ACE MC, which has much higher cooling performance than before, was started. Diffusing heat efficiently by using copper, which has high heat conductivity, in addition to the conventional aluminum was examined. Moreover, the surface area of a cooling fin of a heat sink was examined to expand as much as possible, satisfying the conventional size and mass spec, in order to raise a cooling performance. The form of a fan motor was also designed in consideration of cooling performance and noise. In this way, the MPU cooler was developed. SAN ACE MC for Pentium 4. Fig. 1 MPU Cooler SAN ACE MC for Pentium 4 This product is the cooling device developed for Pentium 4 processors, which unified a cooling fan and a heat sink. The feature of the product are indicated below: (1) Sanyo original structure for the fan and the heat sink (2) Heat sink inserting copper pillar in the aluminum extruded hollow fin (3) High cooling performance (4) Low noise (5) High reliability and long life Table 1 Rated Voltage [V] Performance Overview of the MPU Cooler for Pentium R 4, SAN ACE MC Operating Voltage Range [V] Rated Current [A] Rated Rotation Speed [min -1 ] Thermal Resistance Sound Pressure Level [db[a]] 109X9912S0016 12 9~13.8 0.48 5400 0.295 45 109X9912T0S016 *Note1 12 9~13.8 0.48 5400 0.295 45 2610 0.420 28 * Note1.This model is a thermally speed control type. It operates slow for intake air of a fan being 32 or lower and faster for 40 or higher. Mass [g] 450 9 SANYO DENKI Technical Report No.15 May 2003

Fig. 2 Dimensional Overview of the MPU Cooler for Pentium R 4, SAN ACE MC Ball bearing Frame Motor Blade (3) Even if mounted in comparatively thin equipment, the frame shape is improved so that even if an obstruction stands close to the fan intake side, there is still sufficient intake area. This reduces the loss of cooling performance. Wire 3.2 Performance (Copper pillar) Heat Sink (Aluminum) (1) Heat Sink The heat sink consists of two parts and has put the creativity for realizing a high cooling performance. Copper, excellent in heat conduction, was adopted as the base, and the form was made into a pillar shape. In addition, the structure, which uses an aluminum extrusion material for a hollow cylinder and extends a fin to the four quarters, was used for the fin. It increases the surface area, while suppressing an increase in mass. The copper pillar is inserted into the hollow of the aluminum structure, creating the heat sink shown in Fig. 4. Fig. 3 Structure Drawing of SAN ACE MC for Pentium R 4 3.1 Structure The features of the structure of for Pentium 4 are listed below. The structure drawing is shown in Fig. 3. (1) The fan is located on the intake side, and the heat sink is located on the exhaust side. This structure contributes to the improved life of the fan and to increased cooling performance. (2) It adopts a unique form for the heat sink by inserting a copper pillar into the aluminum extruded hollow fin. A high cooling performance is realized by this structure, while suppressing an increase in mass. Fig. 4 Heat Sink SANYO DENKI Technical Report No.15 May 2003 10

In this product development, one of the goals was to attain a high cooling performance within the mass restrictions of 450g. Generally, as cooling performance increases, mass tends to become heavy, due to designs that increase the number of fins in an attempt to make the heat dissipation area of a heat sink expand, or that thickens the base of a heat sink in order to raise the thermal conductivity, etc. Moreover, if copper, which excels in heat conductivity, is used for a material of a heat sink, performance will improve, but mass will increase similarly. Therefore, not all heat sinks are constituted from copper material, but copper is used only for the heat sink s central part, and it was determined to use aluminum for a fin part. However, a target cooling performance is unrealizable only by embedding copper material in the central part of the conventional aluminum extruded heat simply. The performance of a heat sink is determined by the heat dissipation area and amount of exhausted air, which passes over the heat dissipation. Therefore, it is necessary to reconcile the opposite conditions of securing the opening area for the air sent by the fan passing and increasing the heat dissipation area of a fin. Therefore, it was not made to extrude and arrange a fin part perpendicularly to a fan s axis of rotation like the conventional extruded heat sink, but it was made to extrude a fin to a fan s direction of the axis of rotation. And it was considered as the composition, which spreads a fin from a center to the four quarters. Thereby, the surface area of a fin was increased about 16% to the conventional extruded heat sink, and the opening area for ventilation could be secured. Moreover, heat is quickly diffused in the height direction of the heat sink central part, and it enabled it to conduct heat to each fin by inserting heat conductive high copper pillar in this fin hollow part. By these, the high cooling performance of heat resistance of about 0.3 K/W was attained, suppressing the increase in heat sink mass to about 20% of the conventional product. (2) Fan The fan that carried in the product was designed to exclusive use in consideration of a cooling performance and noise. The fan is shown in Fig. 5. Since larger air volume was needed in comparison with the former to attain high cooling performance, the size rise of fan size and the motor size was carried out. In addition, the venturi part was designed to be lowered one step from the motor part so that performance is demonstrated when fan is actually put in apparatus. It secures a path of air even if the obstruction approaches the upper part of the fan. Furthermore, the shape of a blade, the distance of a blade and a fin, and the direction of a spoke to blade etc., were optimized, and large air volume and low noise levels were attained. (3) Comparison With the Conventional Product The result of comparing the size, the cooling performance, and the mass of this product and the conventional product is shown in Table 2. Even though the size of this product is equivalent and the mass is increased approx. 80g (approx. 22%) compared with the conventional product, heat resistance has been improved sharply by 0.125 K/W (about 30%) as a result of an exclusive design so that the performance of a fan and a heat sink can be pulled out to the maximum extent as mentioned. This degree of improvement shows that temperature rise reduction of 10K can be attained as compared with the conventional product, when the heating value for cooling is 80W. Table 2 Size of Exterior [mm] Comparison Table Mass [g] Thermal Resistance 109X9912S0016 95 74 62 450 0.295 109X9812H0016 95 71.3 62.5 370 0.420 Moreover, the noise in the same cooling performance was compared in Table 3. Consequently, about 10dB[A] of noise reduction was attained compared to the conventional product, and equipment noise can be reduced by using this product. Table 3 Comparison Table of Noise at the Same Cooling Performance Thermal Resistance Rotating Speed [min -1 ] Sound Pressure Level [db[a]] *Note2 109X9912T0S016 0.420 2610 28 109X9812H0016 0.420 3900 39 *Note 2. Sound pressure level is the value at1 m from fan intake side Fig. 5 Fan 11 SANYO DENKI Technical Report No.15 May 2003

4. Conclusion A part of the structure and performance of the MPU cooler for Pentium 4, SAN ACE MC were introduced. Heating value increases with performance improvement, and speed increases of microprocessors continue to be expected. In such a situation, it is thought that smaller size and greater cooling performance of a cooling device will be demanded. * Pentium in the text is the registered trademark of Intel Corporation Reference (1) Ogawara and others : SAN ACE MC for Pentium R Ⅲ& Pentium R 4 SANYO DENKI Technical Report, No.11 pp5-8 (2001-5). (2) Watanabe and others : MPU Cooler SAN ACE MC-HX SANYO DENKI Technical Report, No.12 pp25-28 (2001-11). (3) Ikeda and others: SAN ACE MC for Pentium 4 1U Server SANYO DENKI Technical Report, No.14 pp20-23 (2002-11). Michinori Watanabe Joined company in 1989 Toshiki Ogawara Joined company in 1984 Haruhisa Maruyama Joined company in 1997 Masayuki Iijima Joined company in 1999 SANYO DENKI Technical Report No.15 May 2003 12