Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Similar documents
Aspirating Gas Detection CFD Modelling Predicts Application Performance

Safety research of A2L/A3 refrigerants and risk assessment in Japan. Eiji Hihara The University of Tokyo

ACTIVITIES OF THE MEASURING GROUP

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

Compressor Explosion Accident at Pump-Down of Air Conditioners

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

IMO Resolution MSC 61(67): Annex 1: Part 2

An experimental study of the impact of tunnel suppression on tunnel ventilation

Review Fire Test Report

Tunnel Fire Dynamics and Evacuation Simulations

Heat pump supplemental heating system for motor vehicles

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

ASHRAE Safety Standards. Mechanical Rooms and Gas Detection in Commercial Applications

Smoke Layer Height and Heat Flow through a Door

Sprinklers Modeling for Tunnel Road Fire Fighting

Flammability and the Low GWP Refrigerant Challenge

MINISTERIO DE FOMENTO

EC24. Operation Manual. (Type MWG 2411, MWG 2412, MWG 2413 and MWG 2414)

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

Trials of Vexo inhibitor in domestic central. heating systems

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

Fire and Extinguishing Tests on Computer Equipment

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Retrofitting Existing Systems

Micro III (Models G203, G203S, and G213) Operation Manual

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Economic and Social Council

SHOULD SMOKE MANAGEMENT SYSTEM BE PROVIDED IN KARAOKE ESTABLISHMENTS?

The first tunnel fire. Benefits of fire

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

portable gas analyser

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

PRODUCT SAFETY DATA SHEET

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Health and Safety Documents in connection with offshore oil and gas operations

Certificate: _02 / 9 September 2014

Mist eliminators for Flue Gas Desulphurization

Large-scale fire test for interior materials of the Korean high speed train

Impact of quick incident detection on safety in terms of ventilation response

Legislation & Standards

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

NEXT GENERATION OF ELECTRICAL LADLE HEATERS: A CASE STORY. Marcus Andersson. Sandvik Heating Technology, Hallstahammar, Sweden ABSTRACT

Characterising the smoke produced from modern materials and evaluating smoke detectors

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Test Unit GTL 100 for Fire Detectors

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

TR-1 single separator for MQL and dry processes. Explosive dusts from dry processes or MQL extracted directly at the machine and separated safely

Technical Specifications and User Guide for the GDCO Detector

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning

Opening up the Gas Market (OGM) Project Oban - Laboratory and Field Testing Results

Laboratory exercise 3: Condensing water heater

Overview of the PRISME project Technical Description and Main Outcomes

J. LINES, Graham Corp., Batavia, New York

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

Gas Temperature Measurements with High Temporal Resolution

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Fire is No Accident Fire is No Accident It can be prevented.

Material Safety Data Sheet. acc. to ISO/DIS Printing date 01/26/2001 Reviewed on 03/28/2000

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

ecodry Figure 1 - Process Diagram ecodry B General Process Description

Requirements for ships carrying hydrogen and compressed natural gas vehicles

AIRAH Victoria Refrigerants Update

ARGE Guideline - Part 3 "System functionality fire detection and fire fighting systems in rolling stock"

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

( )

BST-MG08/09 Multi-gas Detecting Alarm. Manual Instruction

Transitioning to Alternatives and Challenges in Japan

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

43 May cause sensitisation by skin contact. 67 Vapours may cause drowsiness and dizziness.

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels.

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Annex B Plenum Spaces

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

LET S PLAY IT SAFE. robecco secure center (RSC) G.A.S. inert control (RIC) dust control (RDC) silo automation (RSA)

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Warranty Registration

Residential ventilation concepts based on the idea of displacement airflow distribution

Cone Calorimeter. (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test THE BENCHMARK IN FIRE TESTING

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Modeling a real backdraft incident fire

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

Fire Safety in a Laser Lab

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Effects of Smoke on Evacuation Martin Lopušniak 1, a

BASIC BOILERS NAME :- DATE :-

MICRO IV. Operation Manual. Single Gas Detector

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

Natural Gas & Propane Burners

Transcription:

D M T G m b H & C o. K G B u i l d i n g S a f e t y Expert Body for Fire Protection Tremoniastraße 13 44137 Dortmund GERMANY Phone +49 231-5333-0 Fax +49 231-5333-299 Emaill: gs@dmt.de http://www.dmt.de Survey of the Burning Behaviour of the Refrigerant HFO-1234yf - - - - - - - - - - Brief Report Document number: Order number: 206 40227 Customer: Deutsche Umwelthilfe e.v. Hackescher Markt 4 10178 Berlin Order from: 31 October 2013 Order contents: Part: Survey of the burning behaviour of the refrigerant HFO-1234yf Execution of the "fire loss" fire tests in the burning gallery for the study of inflammation of the refrigerant HFO-1234yf as well as for the formation of hydrogen fluoride Test date: 13 & 14 January 2014 Valid until: unlimited This brief report comprises 6 pages. It may only be redistributed in its entirety and without changes. Any publication requires our approval.

TABLE OF CONTENTS PAGE 1 CUSTOMER... 3 2 BACKGROUND TO THE ASSIGNMENT... 3 3 DESCRIPTION OF THE PERFORMANCE OF THE FIRE TEST AND MEASUREMENT PROCEDURE... 3 4 RESULTS OF THE FIRE TEST... 4 5 SUMMARY... 6 Page 2 of 6

1 Customer Deutsche Umwelthilfe e.v. Hackescher Markt 4 10178 Berlin 2 Background to the Assignment The reason for the survey is to determine respectively to estimate the hazard potential of the refrigerant 2,3,3,3-tetrafluoroprop-1-en (R1234yf). The refrigerant is currently preferred by many car manufacturers as a replacement for the previously used R134a. According to the Honeywell safety data sheet, the ignition temperature of the refrigerant R1234yf is 405 C and reference is made to the possibility of the formation of hydrogen fluoride (HF) in the case of fire. It is assumed that for humans an exposure level of 42 mg/m³ (50 ppm HF) over 30 to 60 minutes can be lethal. The IDLH value ("immediately dangerous to life or health") has been set at 25 mg/m³ (30 ppm) [ NIOSH IDLHs "Documentation for Immediately Dangerous to Life or Health Concentrations (IDLHs)" U.S. Department of Health and Human Service, Cincinnati May 1994]. The Expert Body for Fire Protection at the Centre for Fire and Explosion Protection at the company DMT GmbH & Co. KG has been commissioned by the Deutsche Umwelthilfe e.v. (German Environmental Aid Association) with carrying out targeted fire tests in order to clarify the following question: During the (partial) combustion of a current car model, does the refrigerant HFO-1234yf ignite and is any hydrogen fluoride (HF) formed? 3 Description of the Performance of the Fire Test and Measurement Procedure The targeted combustion of the vehicle in the burning gallery for the simulation of a tunnel fire was performed on the fire test site at DMT in Dortmund. The combustion gases were passed via an exhaust pipe to the flue gas cleaning system, where they were cleaned. Within the context of this brief report, only the important results obtained with respect to this accident scenario are reproduced. A final report includes all test results. Page 3 of 6

Combustion of the Vehicle in the Burning Gallery The test vehicle equipped with thermocouples with the refrigerant R1234yf in the air conditioning system was set up in the burning gallery at DMT Dortmund. The vehicle was placed with the engine compartment facing the direction of flow. It was fitted with thermocouples in various positions in order to record the temperature profiles, with the thermocouples being connected by cables to a data collector. The flow velocity in the fire gallery was adjusted to 1.5 m/s for adaptation to the conditions in a road tunnel. With an open cross-section of 10 m² this corresponds to a flow rate of 54,000 m³/h. The simulation of an ignition process, which often comes into play in cases of vandalism and results in the fire being transferred from the ignited tyre to the rest of the body, was carried out as follows. A tray filled with approximately 1 litre of diesel was placed near to the tyre (front tyre on the left when seen from the driver's perspective). Ignition of the diesel, and subsequently the tyre and then the vehicle itself, was performed by means of a grill lighter which was immersed in the tray of diesel. The gas measurement technology (FT-IR) and temperature data acquisition system were located in the side corridor of the burning gallery. By means of a steel capillary (6 mm OD, 4 mm ID), combustion gas was extracted by suction out of the gallery 20 m downstream of the back of the vehicle via a heated sampling line (180 C) through the measuring cell of the Fourier transform infra-red spectrometer (FT-IR). Infra-red spectra of the gases were recorded at regular intervals. The quantitative amounts of the resulting combustion gases were determined using the substance-specific bands. Main focus was the determination of HF. After approximately 45 minutes the vehicle, which was still burning, was extinguished. 4 Results of the Fire Test Before the middle-class car was burnt the air conditioning system contained 372 g of refrigerant R1234yf. The curves for the combustion gases shown in Figure 1, i.e. carbon monoxide (CO), carbon dioxide (CO 2 ) and hydrogen fluoride (HF), show that in comparison to the rise in carbon monoxide as an indicator of the development of the fire, the increase in hydrogen fluoride in the combustion gases occurs after a delay of 4 minutes. Figure 2 shows the temperature profiles at various measurement positions on the vehicle (engine section) in the burning gallery, as well as the temperature of the air in front of and behind the vehicle. Page 4 of 6

conzentration HF [ppm] & CO2 [%] conzentration CO [ppm] DMT GmbH & Co. KG Automotive fire test "Tunnel" - Generation of Hydrogen Fluoride (HF) (volume rate 54,000 m³/h) 50 2000 45 HF 1800 40 35 CO2-vol% CO MAK HF: 1 ppm MAK CO: 30 ppm 1600 1400 30 1200 25 1000 20 800 15 600 10 400 5 200 0 0 0 5 10 15 20 25 30 35 40 45 50 time [min] Fig. 1) Change over time of the combustion gases carbon monoxide (CO), carbon dioxide (CO 2 ) and hydrogen fluoride (HF) Fig. 2) Change over time of the temperatures at the various measurement points in the engine section, as well as in front of (input) and behind (output) the vehicle Page 5 of 6

Figure 1 shows that under the combustion conditions in the fire gallery, up to almost 43 ppm v hydrogen fluoride was present in the exhaust air behind the vehicle. Within the period of 5 to 15 minutes after the start of the vehicle fire, an average of 17 ppm v HF was recorded in the exhaust air behind the burning vehicle. The integration of the HF mass flow in the burning gallery during the fire results in a quantity of 126 g of pure hydrogen fluoride that was formed. 5 Summary The Deutsche Umwelthilfe e.v. (German Environmental Aid Association) has commissioned the Expert Body for Fire Protection at the firm DMT GmbH & Co. KG to carry out a fire safety test involving a vehicle fire in the burning gallery in order to simulate a tunnel fire. The aim of the test was the determination or assessment of the hazard potential caused by the formation of hydrogen fluoride in case of fire. The selected medium class vehicle has an air conditioning system which is filled with the new refrigerant R1234yf. The result of the fire test is as follows: As a result of a vehicle fire with an air conditioning system filled with the new refrigerant R1234yf, considerable quantities of hydrogen fluoride can be formed in a tunnel and expelled into the tunnel air as combustion gas. Under the selected fire test conditions the limit value for workplaces (AGW) and the maximum workplace concentration (MAK) of 1 ppm v were significantly exceeded by a HF concentration of up to 43 ppm v which was registered in the exhaust air. Dortmund, January 24 th 2014 Note: This official opinion on fire test only applies to the aforementioned fire test of a medium-class car equipped with R1234yf under the described test conditions. It is not possible to transfer the above results to other test scenarios or tunnel geometries, etc. Page 6 of 6