Technical Manual for the Manual Alarm Call Point BG

Similar documents
Technical Manual for the Horn - DB1PUL DB1HP UL

Technical Manual for the Strobe - SM87 HXB

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit

Technical Manual for the Fire Alarm Call Point - SM87 PBL

Technical Manual for the Alarm Pull Station PH1

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

100 & 120 Series Pressure and Temperature Switches Safety Manual

PPA Michaël GROSSI - FSCE PR electronics

FUNCTIONAL SAFETY CERTIFICATE

Soliphant M with electronic insert FEM52

Liquiphant S, Nivotester FDL60/61, FTL670

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

United Electric Controls One Series Safety Transmitter Safety Manual

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Digital EPIC 2 Safety manual

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P

Safety in the process industry

Failure Modes, Effects and Diagnostic Analysis

Mobrey Magnetic Level Switches

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Failure Modes, Effects and Diagnostic Analysis

FUNCTIONAL SAFETY MANUAL

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Certification Report of the ST3000 Pressure Transmitter

Functional Safety Solutions

Certification Report of the ST 3000 Pressure Transmitter with HART 6

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

Rosemount 2140:SIS Level Detector

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

Manual Alarm Call Points

Failure Modes, Effects and Diagnostic Analysis

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS

IEC Functional Safety Assessment

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure

Failure Modes, Effects and Diagnostic Analysis

Proservo NMS5- / NMS7-

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual

Session Ten Achieving Compliance in Hardware Fault Tolerance

Technical Report Proven In Use SITRANS P500

Proof Testing Level Instruments

SAFETY INTEGRITY LEVEL MANUAL. IEC and IEC XP95 and Discovery SIL Approved Product Range

Functional Safety Manual Oil Leak Detector NAR300 System

Failure Modes, Effects and Diagnostic Analysis

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

Failure Modes, Effects and Diagnostic Analysis

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Failure Modes, Effects and Diagnostic Analysis

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

Failure Modes, Effects and Diagnostic Analysis

GMA200-MW4. User Manual. Gas detection controller for wall mounting

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Failure Modes, Effects and Diagnostic Analysis

Functional Safety SIL Safety Integrity Level

Functional Safety Manual June pointek CLS500/LC500

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 Electromagnetic Flowmeter

Operating Manual MS220DA

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Simply reliable: Process safety from Endress+Hauser

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

Hazardous Area Communications

Failure Modes, Effects and Diagnostic Analysis

Measurement of Safety Integrity of E/E/PES according to IEC61508

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

Technical Manual for the Horn DB1P UL DB1HP UL

IEC Functional Safety Assessment

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

New Developments in the IEC61511 Edition 2

Hazardous Area Communications

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions

FUNCTIONAL SAFETY MANUAL

Operating Manual MS220KA and MSR220KA

DB1 Range - HORNS - Up to 103 db(a)

Failure Modes, Effects and Diagnostic Analysis


PRODUCT ATEX IECEx UL ULC CSA Inmetro CUTR CQST ABS SIL IP Rating Page DB7 66 / DB12 66 / DB15 66 / DB1 DB3 DB3V DB3B

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

Cerabar S PMC71, PMP71, PMP75

2015 Functional Safety Training & Workshops

Functional Safety: the Next Edition of IEC 61511

Transcription:

Technical Manual for the Manual Alarm Call Point BG Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or expense resulting from any error or omission. We reserve the right to make alterations in line with technical advances and industry standards. Cooper MEDC 2013 06/13

06/13 Cooper MEDC 2013

Cooper MEDC 2013 06/13

7. Functional Safety Introduction The BG Call Point has been designed for use in potentially explosive atmospheres and harsh environmental conditions. The glass reinforced polyester enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The function of the BG is to raise an alarm manually once verification of a fire or emergency condition exists, by breaking the Glass. The BG Break glass Unit is configured with either a single series Resistor (R1) or an R1 and end of line resistor known as R2. No Current passes through R1 in either configuration until the glass has been broken and the switch contacts have closed. Upon closure of the switch the current is then sent through R1 and hence changes the resistive value in the circuit which triggers the alarm. The R2 resistor always has a current flowing through which provides the reference resistive value for the circuit. The circuit can diagnose an open circuit failure in R1 without having to trigger the system via a continuity check which is a form of diagnostics for determining if an R1 resistor has failed Open Circuit. This form of diagnostics does however require a proof test to be conducted in order to identify the failure and depending on the set up of the system the defective Resistor may not be easily traceable if there are several BG break glass Units in the system. The end of line resistor R2 is used for the purpose of detecting an open or short circuit in the supply conductors. 06/13 Cooper MEDC 2013

The safety function of the Call Point is to raise the alarm when the Glass is Broken Under No fault (Normal) Operating conditions the BG Break Glass Unit will raise the alarm upon operating the switch via breaking the glass. Under fault conditions the failure mode of the Break Glass is a failure to raise the alarm. For the failure rate associated with this failure mode please refer to the table below. Assessment of Functional Safety The BG Call Point is intended for use in a safety system conforming to the requirements of IEC61508. Sira Test & certification Ltd has conducted a Failure Modes Effect and Diagnostic Analysis (FMEDA) of the BG Break Glass unit against the requirements of IEC61508-2 using a proof test interval of 8760hrs. The Call Point is classed as a Type A device. BGI BREAKGLASS UNIT Safety Function of BG Break Glass Unit: To raise the alarm arm upon breaking the glass Type A Proof of Test Interval Architectural constraints: HFT=0 =8760Hrs SFF= 97% MTTR TR = 8 Hrs Random hardware failures: Probability of failure on demand: Probability of Dangerous failure on safety function: Hardware safety integrity [1] compliance Systematic safety integrity compliance Systematic Capability Overall SIL-capability achieved DD = 0 DU = 5.72E-07 DU PFD AVG =2.51E-03 (Low Demand Mode) PFH = 5.72E-07 (High Demand Mode) SD = 0 SU = 2.04E-05 SIL2 SIL2 Route 1 H Route 1 S SC2 SIL 2 (Low Demand) SIL 2 (High Demand) SIL3 Cooper MEDC 2013 06/13

Conditions of Safe use The following conditions apply to the installation, operation and maintenance of the assessed equipment. Failure to observe these may compromise the safety integrity of the assessed equipment: 1. The user shall comply with the requirements given in the manufacturer s user documentation (This Safety Manual and Technical manual) in regard to all relevant functional safety aspects such as application of use, installation, operation, maintenance, proof tests, maximum ratings, environmental conditions, repair, etc; 2. Selection of this equipment for use in safety functions and the installation, configuration, overall validation, maintenance and repair shall only be carried out by competent personnel, observing all the manufacturer s conditions and recommendations in the user documentation. 3. All information associated with any field failures of this product should be collected under a dependability management process (e.g., IEC 60300-3-2) and reported to the manufacturer. 4. The unit should be tested at regular intervals to identify any malfunctions; in accordance with this safety manual. 06/13 Cooper MEDC 2013

Cooper MEDC 2013 06/13

Cooper MEDC Ltd, Unit B, Sutton Parkway, Oddicroft Lane, Sutton in Ashfield NG17 5FB Tel: +44 (0)1623 444444 Fax: +44 (0)1623 444531 Email: medc.sales@cooperindustries.com medc.orders@cooperindustries.com MEDC Stock No: Web: www.coopermedc.com TM110-ISS.D 06/13 Cooper MEDC 2013